Sie sind auf Seite 1von 4

EQUIPMENT DATA SHEET

INSERT SPU LOGO HERE


NO. BY DATE REVISION
1 MC 1/1/07

Project: Example Pump Selection


Spec Section:: 11306 Location/Building: Influent P
TAG/EQUIP NO: PS-WPS -001 Loop Wiring Diagram: Manufacturer: Fairbanks M
Asset No: - P&ID Sheet: P-2 Rep/Phone: -
Name/Type: wet pit submersible pump Model: D5731
Service: Wastewater Manufacturer: -
Spec Sht 1: Spec Sht 3: Rep/Phone: -
Spec Sht 2: Spec Sht 4: Model: -

Capacity: 8,000 Units: GPM Pressure: Max


Connection Size: 14 Units: Inches Amb Temperature: 95 Max 32

ENVIRONMENTAL
MECHANICAL

Connection Type: Flanged Location Occupancy Code:


Size (LxWxH): 72" X 39" X 116.5" Units: Inches Elevation: 224 Units: ft
Operating Weight: 5750 Units: LB Inside Building: Confined Space
Speed (Min/Max RPM): 440/1200 Subject to Flooding: ✘ Direct Sunlight:
Mat'ls of Construction: Cast Iron and Stainless Steel Dusty Area: Corrosive Area:
Accessories Damp W/D Area: ✘ Freezing:
and Spare Parts: Classified Area: ✘ Class: I

Electrical Pwr: ✘ Standby Pwr: ✘ UPS: Type: Induction - Standard


Voltage: 480 VAC Phase: 3 Wire: 3 Speed(s) (RPM): 440 to 1200
NEMA Enclosure Type: 4X IP Enclosure Type: 54 Enclosure: SUBMERSIBLE
Continuous Amps: AIC (kAmps): NEMA Torque Design Code:
ELECTRICAL

UL Service Entrance: ✘ Main Breaker (AT/AF): Estimated Starts/Hour: 6 Efficiency:


MOTOR

Rear Access Required: Powered From: EP and genrator Svc Fctr (Full Speed): Svc Fctr (VFD):
Two Exits Required: Est. Heat Release (kW): ACCESSORIES AND FEATURES
Design Operating Temp: Units: Deg F HVAC Req'd Space Heater: ✘ Chem Duty:
Variable Speed Drive: ✘ Pulses: AFE: T'Stat: Severe Duty:
Harmonic Mitigation: RTD: Inverter Duty:
Special Controls/Relays: Thermistors: Tropical Duty:
Accessories Mtr Vib Sw: Bearing Vib Sw:
and Spare Parts: Mtr Vib Xmtr: Bearing Vib Xmtr:

Seal Water: Air Supply: Drain: Process Var: Sensor Type:


Painting/Coating: Coating suitable for wastewater service (epoxy) Accuracy: Ops Range:
SPECIAL REQUIREMENTS

Special O&M, Environmental, or Equipment Specific Information, etc. Repeatability: Calib Range:
INSTRUMENTATION

Owner Furnished: GC Furnished: ✘ Setting:


Output (mA): 4 to 20 mA Voltage:
Pneumatic Hydraulic:
Fieldbus Type: Monitored From:
Wetted Parts Materials:
Int Safe: Packgd by Mfgr:
NEMA Enclosure Type: 4X
ALARMS SETPOINTS
SPECI

IN
Hi-Hi: 244 Hi: 240 Lo:

Also need to monitor motor and pump run time, speed, and temperature and vibration.
NOTES
w
N

w
S

&

sS
e
n
o
o
d
o
e
cn
e
o
h

sd

h
e
c

s
t
t

t
i
il

ei
i

(ATTACH CATALOG CUTS AS NECESSARY)

A
e

u
a

o
c

c
r

r
t

t
l

l
PM ✘ DNDF I&C ✘ SPEC
DIST

PE ✘ ELECTRICAL MECHANICAL STRUCT ✘


ARCH ESTIMATOR PLUMBING CLIENT 1
CIVIL ✘ HVAC PROCESS ✘ CLIENT 2
E:\Ch11_v.2_FinaltoSPU\AppxD_EquipData\[AppDequipmentdatasheettemplate.xls]CDM Template
DATA SHEET NO. REV.
001
SHEET OF DATE
1 1 1/1/07
BY CHK'D PROC. APPR.

P.O.
REQ.
Influent Pump Station
Fairbanks Morse
-
D5731
-
-
-

Min Units: PSI


32 Min Units: Deg F
Site Specific Accel:
Seismic Zone: 3
nfined Space Humidity: >80%
ect Sunlight:
rrosive Area: ✘
eezing:
Div: 2 Group: IIC

Induction - Standard
HP: 250
kW: 187
Hertz: 60
80 Pwr. Fct. 1.15
Svc Fctr (VFD):
ORIES AND FEATURES
Cntrl T Box:
LR Code:
Insl Code:
Mounting: Vertical

Sensor Type:
Units: PERCENT
Units: PERCENT
Units: PSI
Voltage: 480 VAC
Input to DCS:
Monitored From:

Dia. Seal:
IP Enclosure Type: 54
RMS SETPOINTS
Lo: 232 Lo-Lo: 228

###