BATTERY SIZE CALCULATION

Document No.: SK‐B‐001
Document Name: FACP BATTERY SIZE CALCULATION
Project: EXTENSION OF NEW SIH BUILDING
Location:   YANBU
Battery Size (AH) = [Derating Factor] x [{Standby Current x standby time (H)} + {Alarm Current x Alarm time (min)/60}]

Equipment Tag No. = V22‐FACP‐002 Choose nearest battery size available from the following:
Minimum battery size, Amp/hrs              25.4 5AH, 7AH, 12AH, 18AH, 26AH, 55AH, 100AH
Total standby current, Amp.                          0.86 If battery size is bigger then 100AH, split into 2 or 3
Total alarm current, Amp. 4.62 and add  FCPS‐24S6E (6A)or FCPS‐24S8E (8A) as required.

No. of hours standby, hours  24 Hours
Alarm condition, minutes         5 Minutes
Battery Derating Factor 1.2

Standby  Alarm Module Standby  Alarm


Qty
(mA) (mA) Model No. (mA) (mA)
350 350 CPU2‐640 ( E) 1 350 350
100 100 KDM‐R2 1 100 100
100 100 LEM‐320 ( 1 loop) 4 400 400
0.3 6.5 FSP‐851 Addressable Photoelectric Smoke Detector 19 5.7 123.5
0.33 6.5 FSL‐751 Very Intellegent Smoke Detector (HSSD) 20 6.6 130
0.375 0.375 NBG‐12LX Addressable Manual Pull Station 6 2.25 2.25
0 900 XB15 Xenon beacons, 15 Joule 3 0 2700
0 146 P2R Horn and Strobes (15cd) 5 0 730
0 75 HR Horn, Red, Outdoor 1 0 75
0.3 6.5 Innovair Flex Duct Detector (Requires FSP‐851) 1 0.3 6.5

Note: Current ratings stated above should be validated with latest installation sheets

Total Battery Requirements = 1x 25.4 AH
Existing Battery size = 1x 55.0 AH

Therefore, exisitng FACP battery is sufficient to handle the additional fire alarm devices.