Sie sind auf Seite 1von 1

Tie to

top line post


Insulators
Insula

5 7/8"
2 7/8"
R 1"

R 1"

9 3/16"

6 5/16"
2 7/8"
6 1/8" R 1"
2 7/8"
3/4"-10 UF
R 1" R 1"
9325X-70
R 1"

15"
12 7/16"

3/4"/10 UF 3/4"-10 UF

9335X-70 9345X-70

CATALOG NUMBER 9325X-70 9335X-70 9345X-70


ANSI CLASS (C29.7-1996 rev. 2002) 57-1 57-2 57-3
CRITICAL DISTANCES, inches
Dry arcing distance 6.5 9.5 12.2
Leakage distance 14 22.5 29.5
MECHANICAL VALUES, pounds
Cantilever strength 2800 2800 2800
ELECTRICAL VALUES, kV
Typical application voltage 25 35 46
Low-frequency dry ßashover 90 115 135
Low-frequency wet ßashover 60 70 100
Critical impulse ßashover, positive 130 179 214

RADIO INFLUENCE DATA


15 22 30
Low-frequency test voltage, RMS to ground, kV
100 100 200
Maximum RIV at 1000 kHz, ðV
Note 1: ANSI 70 gray is standard, Brown or white available by request
Note 2: Insulators can be requested with M20 thread size
Note 3: Available with short or long stud, sold separately