4.2.

8 PRESET VALUE SW

• Preset value SW (Terminal 08, ITEM 52)


The control output is fixed at a preset value when the switch is turned on. Use the terminal 08 to control it from a sequential
control block.

• Preset value (ITEM 53)


Used to specify the preset value. The preset value lies downstream of the output high/low limits and thus not is limited by
them.

4.2.9 OUTPUT HOLD SW (Advanced PID)

• Output hold SW (Terminal 09, ITEM 55)


The control output is held when the switch is turned on. Use the terminal 09 to control it from a sequential control block.

4.2.10 EXTERNAL FEEDBACK (OUTPUT TRACKING) (Advanced PID)


External feedback signal is routed to the PID control output (output tracking) when the switch is turned on. When the function
is reset, the output transitions smoothly to that by PID control.

• External feedback connection terminal (ITEM 56)


Used to specify Group and Terminal No. of the external feedback signal.

• Output hold SW (Terminal 10, ITEM 58)


The control output tracks the external feedback signal when the switch is turned on. Use the terminal 10 to control it from a
sequential control block.

4.2.11 AUTO/MAN SW

• A/M SW (Terminal 11, ITEM 59)


Automatic or manual control is selected by the switch. Use the terminal 11 to control it from a sequential control block.

SC100/200 Series Function Block Application Manual EM-6460-C 20