Spirax Sarco Valves & Instruments Product Handbook
Thirteenth Edition
2
Spirax Sarco has a broad range of products tailored to meet the vast needs of
steam and process fluid users everywhere. For years, Spirax Sarco has fulfilled
these needs and today strives to improve this technology as we are in the 21st
Century.
Today, the Spirax Sarco companies employ more than 3,700 people around the
world giving total customer support through 105 Spirax Sarco sales offices and
offices in 37 countries – all of these in close contact with engineers and
designers of plants.
Spirax Sarco is committed to quality and excellence now and into the future.
The best choice for reliable equipment to fulfill the needs of steam
and process fluid users with the right price, at the right place and time.
3
How To Use This Book
Accepted international designations for limiting conditions are used throughout this catalog.
An explanation of Pressure Shell Design Conditions and Limiting Operating Conditions follows:
These are the maximum pressures and temperatures to which the pressure shell (body, cover, bolt-
ing, etc.) of the product may be safely and permanently exposed. The product may or may not operate
properly at these maximum conditions; the internal parts may be damaged or destroyed, but the pres-
sure-retaining components will not break or become permanently distorted. It is sometimes permissible
to exceed the maximum allowable conditions temporarily. For example, a cold hydraulic test at 1-1/2
times the cold PMA is usually permitted.
Because the maximum allowable pressure depends on the temperature, there is no one value for
PMA. Quoting only the cold PMA without mentioning the corresponding temperature could be mislead-
ing. PMA is usually given at three temperatures:
• Cold
• Maximum Allowable Saturated Steam Temperature
• Maximum Allowable Temperature
There is only one value for maximum allowable temperature (TMA); the corresponding pressure
range is given in this literature.
PMA and TMA are strictly safety related. They have very little to do with the actual operation of the
product.
PMO is the maximum fluid (steam, gas or liquid) pressure at which the product will operate properly.
Depending on the type of product, PMO may or may not be related to temperature. Unless otherwise
indicated, the downstream pressure is assumed to be O psig.
Maximum operating temperature may depend on superheat tolerance, internal materials (e.g. neo-
prene o-rings), pressure shell design conditions, or any combination of these factors. Depending on the
type of product, it usually varies with the actual operating pressure.
4
Example of Limiting Conditions
TMA
752°F / 0-188 psig
800 PMA (at TMA)
188 psig / 752°F
600
400
90°F
Pressure Shell Design
Conditions
Saturated Steam
200
PMA (cold)
362 psig / 0-248°F
5
6
VALVES & INSTRUMENTS
Product Handbook
7
Control Valves
Control Valves
INDEX
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
8
Control Valves
INDEX
Control Valves Table of Contents
Tech. Illus. Model / Description Page No.
e
TI-1-618-US Steam Sizing Chart
Glob l 12
tro
TI-1-622-US PM Series Pneumatic Actuators for B Series Control Valves Con s 14
e
TI-1-620-US B Series 1/2" to 2" 2-Way and 3-Way Bronze Control Valves Valv 16
TI-S24-70-US SPIRA-TROL 1/2" to 4" ASME Two-port LEA, LFA and LLA Control Valves 18
TI-S24-71-US SPIRA-TROL 1/2" to 4" ASME Two-port KEA, KFA and KLA Control Valves 30
TI-P378-02-US SPIRA-TROL 6" and 8" KEA, KFA, and KLA Two-port Control Valves 50
TI-P183-02-US Steri-Trol Clean Service ‘S’ Series Control Valves 1/2" (DN15) to 4" (DN100) 59
TI-F12-21-US CE43 1" (DN25) to 4" (DN100) Carbon Steel Cage Design, Two Port Control Valves 76
TI-F12-24-US CE43 5" (DN125) to 8" (DN200) Carbon Steel Cage Design, Two Port Control Valves 78
TI-F12-20-US CE83 1" (DN25) to 4" (DN100) Alloy Steel Cage Design, Two Port Control Valves 80
TI-F12-25-US CE83 5" (DN125) to 8" (DN200) Alloy Steel Cage Design, Two Port Control Valves 82
TI-F12-34-US CE63 1" (DN125) to 4" (DN200) Stainless Steel Cage Design, Two Port Control Valves 84
TI-F12-33-US CE63 5" (DN125) to 8" (DN200) Stainless Steel Cage Design, Two Port Control Valves 86
TI-F12-22-US C Series Valve Spares 89
TI-F12-23-US C Series Valve Options 90
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
9
Control Valves
INDEX
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
10
Control Valves
INDEX
Control Valves Table of Contents
itters
TI-P320-47-US PN600 Series Pneumatic Controllers 174
sm
TI-P323-28-US SX80 Process Controller
r s , Tran 176
trolle Sensors
TI-P323-30-US SX90 Process Controller Con &
180
TI-P322-06-US EL2270 & EL2271 Temperature Probes 186
TI-P322-02-US EL2600 Pressure Transmitter and ‘U’ Syphons 188
TI-P373-13-US PF6 Series Stainless Steel Piston Actuated On/Off Valves 190
n
TI-P373-14-US PF51G Bronze Piston Actuated On/Off Valves Pisto d 198
ate
TI-P373-04-US Type DM Solenoid Valves for use with Piston Actuated Valves Actu es 207
TI-8-500-US Typed MDM Banked Pilot Valves for use with Piston Actuated Valves Valv 208
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
11
Control
Valves
Globe Control
Valves
Cv = Valve Coefficient
P1 = Upstream Pressure, psia
P2 = Downstream Pressure, psia
∆ P = Pressure drop P1 - P2, psia
w = Flow Rate, lb/h
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-618-US 3.03
12
Steam Capacity Chart
Control
Valves
Globe Control
Valves
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-618-US 3.03
© Spirax Sarco, Inc. 2003
13
Control
Valves
Globe Control
Technical Data
Ambient temperature range -4F to 230°F
Maximum air pressure 60 psig
Stem travel ¾”
Air supply connection ¼” NPT
Materials
Diaphragm housing Carbon Steel Selection Guide
Yoke Ductile Iron
Diaphragm Reinforced Nitrile Type PM
PM
Gaskets Neoprene PMS
Springs Steel (50CR4V2)
Bolts and nuts Carbon/alloy steel Actuator size 2 = 36 sq.in
3 = 60 sq.in
3
7 = 109 sq.in
Available Spares
Diaphragm kit
Spring Kit Spindle travel 2 = ¾” 2
Spindle seal kit
Spring range 0 = 3-15 psig
1 = 3-9 psig 0
2 = 9-15 psig
Example:
1 x PM320E pneumatic actuator.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-622-US 11.13
14
PM Series Pneumatic Actuators for
Control
Valves
B Series Control Valves
Maximum differential pressures for ANSI/FCI 70-2 Class IV and VI shut-off
Note: The actuator must be fully vented to achieve the differential pressures shown below. If the control system does not allow the actuator to be
vented, please contact Spirax Sarco for assistance.
Globe Control
Spring Retract
Valves
Closes B Series 2-way valve and closes top seat of B Series 3-way valve on loss of air.
Model Net Spring Min. Air 1/2” 3/4” 1” 1-1/4” 1-1/2” 2”
Range (psig) Pressure Cv Cv Cv Cv Cv 13 Cv Cv 20 Cv 13 Cv 28 Cv 20 Cv 50 Cv 28
(psig) 6 3.5 8 6 8
PM220R 3 - 15 20 250 250 149 250 83 130 44 75 26 37 13 21
6 - 18 23 250 250 250 250 205 250 114 197 76 107 45 71
PM221R 3-9 20 250 250 149 250 83 130 44 75 26 37 13 21
PM222R 9 - 15 20 250 250 250 250 250 250 184 250 126 177 77 121
PM320R 3 - 15 20 165 250 91 157 60 84 35 54
6 - 18 23 250 250 209 250 144 202 88 138
PM321R 3-9 20 165 250 91 157 60 84 35 54
PM322R 9 - 15 20 250 250 250 250 228 250 141 222
PM720R 3 - 15 20 187 250 128 180 78 123
6 - 18 23 250 250 250 250 175 250
PM721R 3-9 20 187 250 128 180 78 123
Spring Extend
Opens B Series 2-way valve and closes bottom seat of B Series 3-way valve on loss of air.
Model Net Spring Air 1/2” 3/4” 1” 1-1/4” 1-1/2” 2”
Range (psig) Pressure Cv Cv Cv Cv Cv 13 Cv Cv 20 Cv 13 Cv 28 Cv 20 Cv 50 Cv 28
(psig) 6 3.5 8 6 8
PM220E 18 3 - 15 44 75 26 37 250
13 21 250 149 250 83 130
20 91 157 60 84 250
34 54 250 250 250 164 250
25 208 250 143 201 250
87 137 250 250 250 250 250
30 250 250 226 250 140 221
PM320E 3 - 15 18 250 250 165 250 91 157 60 84 35 54
20 250 250 250 250 170 250 116 163 70 110
25 250 250 250 250 159 250
Approximate dimensions and weights
(inches and pounds)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-622-US 11.13
15
Control
Valves
Globe Control
Technical Specifications
Body sizes 1/2", 3/4", 1", 1-1/4", 1-1/2", 2"
Body material ASTM B62
Connection Screwed NPT
Body rating 400 psig @150°F / 250 psig @ 400°F (ASME B16. 15 Class 250)
Characteristic 2-Way: Equal Percentage or Linear 3-Way: Linear
Rangeability 50:1
Temperature range -20° to 400°F
Metal Seating
ANSI/FCI 70-2, Class IV
(2 Way and 3 Way Valves)
Leakage Rate
PTFE Soft seating
ANSI/FCI 70-2, Class VI
(2 Way Valves only)
Operating Range
1
3
2
8
Materials
No. Part Material
1 Locknut Stainless Steel
2 Bonnet Nut Steel
3 Gland Nut Brass ASTM B16
4* Stem Seal PTFE/EPDM
5 Body Cast Bronze ASTM B62
6 Seat Stainless Steel ASTM A561 303
7* Head and Stem Stainless Steel ASTM A561 303
8 Plug Cast Bronze ASTM B62
16
B Series 1/2" to 2"
Control
Valves
2-Way and 3-Way Bronze Control Valves
Dimensions and Weights (inches and pounds)
A B C D
Globe Control
Size End to Bottom to Centerline to Actuator Shoulder Weight
Valves
End Centerline Actuator Shoulder to end of steam
(closed position)
2" B E A 5 1 Cv 50 NPT
How To Order A
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-620-US 11.11
17
Control
Valves
Globe Control
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification.
TI-S24-70-US 2.14
18
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard LEA, LFA and LLA ½" to 4"
SPIRA-TROL valve characteristic - options:
LEA Equal percentage (E) - Suitable for most modulating process control applications providing good control at all flowrates.
Globe Control
LFA Fast opening (F) - For on / off applications only.
Valves
LLA Linear (L) - Primarily for liquid flow control where the differential pressures across the valve are constant.
Important note: Throughout this document, reference has been made to the standard LEA control valve. With the exception of trim type,
the LEA, LFA, and LLA control valves are identical.
Certification
This product is available with certification to EN 10204 3.1. Note:
All certification / inspection requirements must be stated at the
Flow %
Linear
time of order placement.
50
Equal percentage
0
0 50 100
Valve opening %
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
© Spirax Sarco, Inc. 2003
19
SPIRA-TROL Two-port Control Valves
Control
Valves
Graphite packing
9
Lower and upper stem guide All versions Stellite 6
High 16
temperature 14 Grafoil packing All versions Graphite rings
packing
10, 11, 12, 15, 17, 19 Not used
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
TI-S24-70-US 2.14
20
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard LEA, LFA and LLA ½" to 4"
3 3
Globe Control
Valves
18 18
19
20 8
17 9
15 16
14
14 27
28
13 2 27
12
16
11
10 4
9
1 6 7 5
LEA valve 14
with PTFE packing
2a
2b
LEA valve
with
bellows seal (D)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
© Spirax Sarco, Inc. 2003
21
SPIRA-TROL Two-port Control Valves
Control
Valves
Equal % 5.0 7.5 12.0 16.0 30.0 45.0 75.0 120.0 190.0
Valves
Full port Linear 5.0 7.5 12.0 16.0 30.0 45.0 75.0 120.0 190.0
Fast 5.0 7.5 12.0 16.0 32.0 50.0 88.0 136.0 210.0
opening
Reduced Equal % 2.5 5.5 8.5 18.0 16.0 33.0 48.0 85.0 130.0
Standard trim 1 Linear 2.5 5.5 8.5 12.0 18.0 33.0 48.0 85.0 130.0
trim
Reduced Equal % 1.8 2.5 6.0 8.5 13.0 18.0 36.0 50.0 90.0
trim 2 Linear 1.8 2.5 6.0 8.5 13.0 18.0 36.0 50.0 90.0
Reduced Equal % 1.0 1.88 3.0 6.0 9.0 14.0 18.0 38.0 53.0
trim 3 Linear 1.0 1.8 3.0 6.0 9.0 14.0 18.0 38.0 53.0
0.5 0.5 0.5
0.2 0.2 0.2
Microflute 0.1 0.1 0.1
0.07 0.07 0.07
0.01 0.01 0.01
Notes: - Special Cv on request
- For low noise and anticavitation Cv please see TI-S24-59
Pressure / temperature limits - LEA31 and LEA33 cast iron valve body
Pressure psi g
Note:
When the process fluid temperature
is sub-zero and the ambient
Temperature °F
Temperature °C
Screwed NPT
temperature is below 41°F,
Steam the external moving parts of the
Flanged saturation valve and actuator must be heat
curve traced to maintain normal operation.
ASME class 125
Pressure bar g
PTFE soft seated valves are limited to a maximum operating temperature of 392°F.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
TI-S24-70-US 2.14
22
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard LEA, LFA and LLA ½" to 4"
Pressure / temperature limits - LEA43 carbon steel valve body
Globe Control
Valves
Pressure psi g
Please note - Bellows sealed valves
(Option D) are limited to A - A.
Temperature °C
Temperature °F
A
Note:
Flanged When the process fluid temperature
ASME class 150 Steam
is sub-zero and the ambient
temperature is below 41°F,
saturation
curve A the external moving parts of the
valve and actuator must be heat
traced to maintain normal operation.
Pressure bar g
High temperature graphite packing is required for use in this region. Note: Soft seated valves cannot be used in this region.
PTFE soft seated valves are limited to a maximum operating temperature of 482°F.
For valve operating above 572°F extended bonnet is recommended for actuator suitability.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
23
SPIRA-TROL Two-port Control Valves
Control
Valves
Pressure psi g
Valves
Please note - Bellows sealed valves
(Option D) are limited to A - A.
Temperature °C
Temperature °F
A Note:
Flanged When the process fluid temperature
ASME class 150 Steam
is sub-zero and the ambient
temperature is below 41°F,
saturation
curve the external moving parts of the
A
valve and actuator must be heat
traced to maintain normal operation.
Pressure bar g
High temperature graphite packing is required for use in this region. Note: Soft seated valves cannot be used in this region.
PTFE soft seated valves are limited to a maximum operating temperature of 482°F.
For valve operating above 572°F extended bonnet is recommended for actuator suitability.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
TI-S24-70-US 2.14
24
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard LEA, LFA and LLA ½" to 4"
Dimensions for the SPIRA-TROL two-port control valve
approximate in inches
Globe Control
Screwed Flanged
Valves
Valve NPT LEA valves
size A B C C1 A1 C1 D E F
Thread Bellows Extended
seals bonnet
E E
D D
C C1
A A1
Bellows sealed or
Screwed version Flanged version extended bonnet version
Additional
Valve
LEA31 LEA33 LEA43 LEA63 bellows and
size
Extended bonnet
½ 16 16 16 16
¾ 16 18 18 18 10
1 22 30 30 30
1¼ 25 29 31 31
1½ 31 31 36 36 12
2 33 38 38 38
2½ 84 78 78
21
3 91 89 89
4 132 124 124 28
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
25
SPIRA-TROL Two-port Control Valves
Control
Valves
F
F G H J Weight
Valves
AEL51, AEL52,
AEL53, 7" 18" 11.0
AEL62 and AEL63
AEL54 and AEL64 7" 19" 15.5
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
26
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard LEA, LFA and LLA ½" to 4"
Spare parts A
Globe Control
SPIRA-TROL - L series
Valves
The spare parts available are shown in solid outline. Parts drawn
in broken line are not supplied as spares.
Note: When placing an order for spare parts please specify clearly
the full product description as found on the label of the valve
body, as this will ensure that the correct spare parts are supplied.
C1 C
Available spares C2
Actuator clamping nut A
Gasket set (Non-bellows sealed) B, G
PTFE chevrons C
Stem
seal kits PTFE to Graphite conversion kit C1
Graphite packing C2
Plug stem and seat kit (No gaskets supplied) D, E
PTFE soft seat seal H
B, G, C1
Stem packing and gasket B, G, C
B, G, C2
Soft seat set H1
D
How to order spares
Always order spares by using the description given in the column
headed 'Available spares', and state the size and type of valve
Soft seat B
including the full product description of the product.
arrangement
How to fit spares
Full fitting instructions are given in the Installation and H1
Maintenance Instructions supplied with the spare. H
E
G
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
27
SPIRA-TROL Two-port Control Valves
Control
Valves
The spare parts available are shown in solid outline. Parts drawn
in broken line are not supplied as spares. C
Note: When placing an order for spare parts please specify clearly
the full product description as found on the label of the valve
body, as this will ensure that the correct spare parts are supplied.
A
Available spares
Actuator clamping nut A
Gasket set (Non-bellows sealed) B, G
Stem seal kit Graphite packing and gasket set C2
Plug stem and seat kit (No gaskets supplied) D, E
Bellows seal assembly F
PTFE soft seat seal H
Soft seat set H1
D3
B
Soft seat
arrangement
H
E
G
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
28
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard LEA, LFA and LLA ½" to 4"
SPIRA-TROL selection guide:
Valve size ASME standard = ½", ¾", 1", 1¼", 1½", 2", 2½", 3" and 4"
Globe Control
Valve series L = L series 2-port control valve L
Valves
E = Equal percentage
Valve characteristic F = Fast opening E
L = Linear
Flange type A = ASME A
Blank = under
Flow Blank
T = over
3 = Cast iron
Connections 4 = Carbon steel 4
6 = Stainless steel
1 = Screwed
Connections 3
3 = Flanged
P = PTFE
H = Graphite
Stem sealing P
N = PTFE / Nitronic bush (½" to 2" only)
D = Bellows
T = 431 stainless steel
G = PTFE soft seat
Seating T
S = 316L stainless steel
W = 316L with stellite 6 facing
S = Standard trim
A1 = 1 stage anticavitation
A2 = 2 stage anticavitation
Type of trim S
P1 = 1 stage low noise cage
P2 = 2 stage low noise cage
P3 = 3 stage low noise cage
U = Unbalanced
Trim balancing U
B = Balanced (only available LEA series)
S = Standard
Bonnet type S
E = Extended
Bolting S = Standard bolting S
Blank = Standard finish
Finish Blank
N = Nickel plated
Series 2 = .2 0.2
Cvs To be specified Cvs 12
Flanged ASME
Connection type To be specified Class 150
Selection example:
Flanged ASME
1" - L E A 4 3 P T S U S S .2 - Cvs 12 -
Class 150
How to order
Example: 1 off Spirax Sarco SPIRA-TROL 1" LEA43PTSUSS.2 Cvs 12 two-port control valve having flanged connections.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-70-US 2.14
29
Control
Valves
Globe Control
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-S24-71-US 2.14
30
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
SPIRA-TROL valve characteristic - options:
KEA Equal percentage (E) - Suitable for most modulating process control applications providing good control at all flowrates.
Globe Control
Valves
KFA Fast opening (F) - For on / off applications only.
KLA Linear (L) - Primarily for liquid flow control where the differential pressures across the valve are constant.
Important note: Throughout this document, reference has been made to the standard KE or KEA control valve. With the exception of trim
type, the KEA, KFA, and KLA control valves are identical.
Bellows / graphite secondary seals (D) Zero emissions and high temperature applications
Hard facing 316L stainless steel with Stellite 6 facing - for more arduous applications
Standard trim
Trim
Low noise and anti-cavitation trim (see TI-S24-59)
SPIRA-TROL valves are compatible with the following actuators and positioners:
Electric EL7200, AEL5 and AEL6 series
Note: Reference the product specific Technical Information sheet for further details.
Standards
Designed in accordance with EN 60534. This product fully complies with the requirements of the European Pressure Equipment
Directive 97 / 23 / EC and carries the mark when so required.
Certification
This product is available with certification to EN 10204 3.1. Note: All certification / inspection requirements must be stated at the
time of order placement.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
31
SPIRA-TROL Two-port Control Valves
Control
Valves
Equal 50:1
Fast 10:1
(½"- 2") (¾")
Travel (1½"- 4") (1 ")
(5"- 8") (2¾")
100
Fast opening
Linear
Flow %
50
Equal percentage
0
0 50 100
Valve opening %
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
32
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Materials - ½" to 4"
Globe Control
Body Type No. Part Material
material
Valves
1 Body Cast steel ASTM A216 WCB
KEA41 ½" to 2" Forged steel ASTM A105N
2 Bonnet
Carbon steel KEA42 2½" to 4" Cast steel ASTM A216 WCB
KEA43 2a Bonnet extension Cast steel ASTM A216 WCB
2c Extended bonnet Cast steel ASTM A216 WCB
1 Body
KEA61
Stainless 2 Bonnet Stainless steel ASTM A351 CF8M
steel KEA62 2a Bonnet extension
KEA63 2c Extended bonnet Stainless steel ASTM A351 CF8M
1 Body
SG iron ASTM A395
SG iron
KEA71 2 Bonnet
KEA73 2a Bonnet extension
Cast steel ASTM A216 WCB
2c Extended bonnet
2b Bellows Stainless steel
3 Stem lock-nut Stainless steel
4 Bonnet gasket Reinforced exfoliated graphite
5 Seat retainer Stainless steel
6 Valve seat ring Stainless steel
7 Seat gasket Reinforced exfoliated graphite
8 Valve plug and stem Stainless steel
9 * Lower stem guide Glass filled PTFE
10 Lower stem wiper PTFE
11 * Packing guard washer Stainless steel
12 * Spring Stainless steel
13 Packing spacer Stainless steel
14 * Chevron packing set PTFE
All versions 15 * Outer 'O' ring Viton
16 * Upper stem guide Glass filled PTFE
17 * Inner 'O' ring Viton
18 Gland nut Stainless steel
19 Scraper ring PTFE
KEA6_ Stainless steel
20 Actuator clamp nut
Others Plated carbon steel
21 Bellows assembly Stainless steel
22 Bonnet extension gasket Reinforced exfoliated graphite
23 Top plate (used on bonnet extension only) Stainless steel
24 Lower spindle bearing housing Stainless steel
25 Lower spindle bearing Stellite 6 or stainless steel for KE43, KE71 and KE73
26 Spindle lock and anti-rotation nut Stainless steel
27 and 28 For nuts and studs, see page 8
* Graphite packing
9
Lower and upper stem guide Stelite 6
16
High temperature
packing 14 Grafoil packing Graphite rings
10, 11, 12, 15, 17 and 19 Not used
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
33
SPIRA-TROL Two-port Control Valves
Control
Valves
18
14 2c Extended
bonnet (E)
16
18
19
14
20 8
17
15 16
28
14
27
13 2
12
11
10 4 ½" - 4" KEA with
9 2a bellows seal (B) and (C)
2b
22
1 6 7 5
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
34
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Globe Control
Body
Valves
Type No. Part Material
material
1 Body Cast steel ASTM A216 WCB
Carbon steel KEA43 2 Bonnet Cast steel ASTM A216 WCB
Stainless 1 Body
steel KEA63 2 Bonnet
Stainless steel ASTM A351 CF8M
1 Body
SG iron KEA73 2 Bonnet
SG iron ASTM A395
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
35
SPIRA-TROL Two-port Control Valves
Control
Valves
20
Valves
17 11
18
12 14
2
8
9 15
10
16 6
21
31
3a
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
36
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Globe Control
Valves
Body material No. Part Material
KEA4_
27 Standard bonnet studs KEA6 _ Steel ASTM A194 Gr.2H
KEA7 _
All versions KEA4_ Steel ASTM A193 Gr.B7
28
27
KE valve
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
37
SPIRA-TROL Two-port Control Valves
Control
Valves
Cv values
Globe Control
Valves
Valve size (½" ) (¾") (1") (1¼") (1½") (2") (2½") (3") (4") (5") (6") (8")
Full port Linear 5.0 7.5 12.0 16.0 30 45 75 120 190 456 749
Fast
5.0 7.5 12.0 16.0 32 50 88 136 210 456 749
opening
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
38
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Pressure / temperature limits - KEA41, KEA42 and KEA43 (Carbon steel)
Pressure psi g
Globe Control
A - B Flanged ASME 300 and screwed NPT and SW.
A
Valves
A - D Flanged ASME 150.
Temperature °C
Temperature °F
E
The product must not be used in this region.
Steam
saturation Graphite stem sealing is required for use in this region.
curve
E D C B
Pressure bar g
Notes:
1. Where the process fluid temperature is sub-zero and the ambient temperature is below 41°F, the external moving parts of the valve and
actuator must be heat traced to maintain normal operation.
2. When selecting a valve with a bellows sealed bonnet, the pressure / temperature limits of the bellows must be read in conjunction
with the valve pressure / temperature limits shown above.
3. As standard the KEA, KFA, KLA series two-port control valves are supplied with the PTFE stem sealing option.
Temperature °F
above.
Steam
The product must not be used in this region. saturation
curve
Pressure bar g
Bellows C Bellows D
Pressure psi g Pressure psi g
Temperature °C
Temperature °F
Temperature °C
Temperature °F
Steam
Steam saturation
saturation curve
curve
Pressure bar g Pressure bar g
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
39
SPIRA-TROL Two-port Control Valves
Control
Valves
Temperature °C
Temperature °F
screwed NPT and SW.
D
Valves
Temperature °F
above.
Steam
saturation
curve
Pressure bar g
Bellows C Pressure psi g Bellows D Pressure psi g
Temperature °C
Temperature °C
Temperature °F
Temperature °F
Steam
saturation
curve
Steam
saturation
curve
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
40
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Pressure / temperature limits - KEA71 and KEA73 (SG iron)
Pressure psi g
Globe Control
A
Temperature °C
Temperature °F
A - F Flanged ASME 250 and screwed NPT and SW.
Valves
A - G Flanged ASME 125.
Steam
saturation The product must not be used in this region.
curve
G E F
Pressure bar g
Notes:
1. Where the process fluid temperature is sub-zero and the ambient temperature is below +41°F, the external moving parts of the valve
and actuator must be heat traced to maintain normal operation.
2. When selecting a valve with a bellows sealed bonnet, the pressure / temperature limits of the bellows must be read in conjunction
with the valve pressure / temperature limits shown above.
3. As standard the KEA, KFA, KLA series two-port control valves are supplied with the PTFE stem sealing option.
Temperature °F
above. Steam
saturation
curve
Pressure bar g
Bellows C Pressure psi g Bellows D Pressure psi g
Temperature °C
Temperature °F
Temperature °C
Temperature °F
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
41
SPIRA-TROL Two-port Control Valves
Control
Valves
Screwed Flanged
Valve NPT KEA valves
size
A B C A1 C1 D E F
ASME ASME Thread Bellows Extended
125 250 seals bonnet
and and
150 300
½" 6½" 1¾" 4" 7½" 4"
¾" 6½" 1¾" 4" 7½" 4" 9" 13.25"
1" 7¾" 2¼" 4" 7¼" 7¾" 4"
2¾" M8
1¼" 8½" 2¼" 5" 5"
1½" 9¼" 2½" 5" 8¾ 9¼" 5" 10½" 19.94
2" 10½" 3" 5" 10" 10½" 5"
2½" 10½ 11½" 7 " 14½"
19.38"
3" 11¾ 12½" 7 " 3" M12 14½"
4" 13¾ 14½" 8½" 15" 17"
5" 21 1/5"
4 7/8" M30
6" 17¾" 185/8" 11" 21 7/8"
Bellows sealed or E
extended bonnet version
D
Screwed version Flanged version
E E
D D
C C1
A A1
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
42
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Weights for the SPIRA-TROL two-port control valve approximate in lbs
Globe Control
KEA valves Additional Additional
Valves
Valve KEA43 KEA63 KEA73 KEA41
bellows balanced
size and
KEA42
Extended
KEA61 bonnet
KEA62
KEA71
½" 16 16 16 16
¾" 18 18 18 16 10
1" 20 20 20 22
1¼" 31 31 29 25
1½" 36 36 31 31 12
2" 38 40 38 33
2½" 78 78 84
21
3" 86 89 91
5" 35 4.4
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
43
SPIRA-TROL Two-port Control Valves
Control
Valves
Dimensions / weights for the EL and AEL actuator ranges approximate in inches and lbs
F
Actuator range F G Weight
inches inches lbs
H J
EL3500 5¼" x 6¼" 9½" 3.0
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
44
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Spare parts A
Globe Control
SPIRA-TROL
Valves
two-port control valve
½" to 4"
The spare parts available are shown in solid outline. Parts
drawn in broken line are not supplied as spares.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
45
SPIRA-TROL Two-port Control Valves
Control
Valves
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
46
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
Spare parts
Globe Control
SPIRA-TROL two-port control valve with
bellows seal - Type D
Valves
½" to 4"
C3
The spare parts available are shown in solid outline. Parts
drawn in broken line are not supplied as spares.
D6
B
Soft seat
arrangement
H
E
G
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
47
SPIRA-TROL Two-port Control Valves
Control
Valves
Example: 1 - PTFE stem seal kit for a Spirax Sarco 1" SPIRA-
TROL two-port KEA43B TSUSS.2 Cvs12 control valve.
Soft seat
arrangement D9
E
G
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
48
SPIRA-TROL Two-port Control Valves
Control
Valves
ASME Standard KEA, KFA and KLA ½" to 8"
SPIRA-TROL selection guide:
Globe Control
Valve size ASME standard = ½", ¾", 1", 1¼", 1½", 2", 2½", 3", 4", 5", 6", 8", 10" and 12" 1"
Valve series K
Valves
K = K series 2-port control valve
E = Equal percentage
Valve characteristic F = Fast opening E
L = Linear
Flange type A = ASME A
Blank = under
Flow Blank
T = over
4 = Carbon steel
Body material 6 = Stainless steel 4
7 = SG iron
1 = Screwed
Connections 2 = Socket weld 3
3 = Flanged
B = Bellows / PTFE secondary seals
C = Bellows / graphite secondary seals
Stem sealing D = Bellows / graphite secondary seals P
H = Graphite
P = PTFE
G = PTFE soft seat
S = 316L stainless steel
Seating T
T = 431 stainless steel
W = 316L with stellite 6 facing
A1 = 1 stage anti-cavitation
A2 = 2 stage anti-cavitation
P1 = 1 stage low noise cage
Type of trim S
P2 = 2 stage low noise cage
P3 = 3 stage low noise cage
S = Standard trim
B = Balanced (available for 6" and 8" valves only)
Trim balancing U
U = Unbalanced
E = Extended
Bonnet type S
S = Standard
H = High temperature
Bolting S
S = Standard
Blank = Standard
Finish N = ENP coating
Series 2 = .2 .2
Cvs To be specified Cvs 16
Flanged
Connection type To be specified Class 300
Selection example:
Flanged
1½" - K E A 4 3 P T S U S S .2 - Cvs 16 -
Class 300
How to order
Example: 1 off Spirax Sarco SPIRA-TROL 1½" KEA43PTSUSS.2 Cvs 16 two-port control valve having flanged ASME Class.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-S24-71-US 2.14
49
Control
Valves
Globe Control
Sizes and pipe connections
Type Body material Connections Size range
Flanged
KEA43 Cast steel ASME 150 6" and 8"
and ASME 300
Flanged
KEA73 SG iron ASME 125 6" and 8"
Valve opening %
and ASME 250
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P378-02-US 08.13
50
SPIRA-TROL 6" and 8"
Control
Valves
KEA, KFA and KLA Two-port Control Valves
Globe Control
Valves
Type No. Part Material
High temperature
26 Gland packing Graphite
gland versions
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P378-02-US 08.13
© Spirax Sarco, Inc. 2003
51
SPIRA-TROL 6" and 8"
Control
Valves
17
Valves
11
18
12 14
8 2
10 15
16 6
22
21
31
3a
52
SPIRA-TROL 6" and 8"
Control
Valves
KEA, KFA and KLA Two-port Control Valves
Pressure / temperature limits
KEA43 (Cast steel) KEA73 (SG iron)
Globe Control
A A E
Valves
Temperature °F
Temperature °F
E
Steam Steam
saturation saturation
curve curve
D
E B C C E
* *
Pressure psi g Pressure psi g
A - B Flanged ASME (ANSI) 150. A - C Flanged ASME (ANSI) 125.
A - C Flanged ASME (ANSI) 300 and screwed NPT and SW. A - D Flanged ASME (ANSI) 250 and screwed NPT.
E - E Valves fitted with bellows are limited to a E - E Valves fitted with bellows are limited to a
maximum bellows rating of 230 psi @ 572°F. maximum bellows rating of 230 psi.
The product must not be used in this region. * If fluid temperature is below 0°F then the ambient conditions
must be at or above 41°F.
Graphite stem sealing is required for use in this region.
Note: As standard the KEA, KFA, KLA series two-port control valves are supplied with the PTFE stem sealing option.
Cvs values
Size 6" 8"
Travel 2¾"
Equal % 433 679
Full port Linear 456 749
Fast opening 456 749
Equal % 336 433
Trim 1
Trim Linear 336 433
Equal % 154 271
Reductions Trim 2
Linear 154 271
Equal % 120 191
Trim 3
Linear 120 191
Full port Linear 351 604
Low noise trim Trim 1 Linear 298 535
Reductions
Trim 2 Linear 234 410
Trim 3 Linear 178 310
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P378-02-US 08.13
© Spirax Sarco, Inc. 2003
53
SPIRA-TROL 6" and 8"
Control
Valves
Balanced Unbalanced
and 150 and 300
Valves
Flanged version
Dimensions / weights for the actuator range (approximate) in inches and lbs
Weight
Actuator range F G H J
Actuator With handwheel
PN1600 and PN2600 18 " 46" - - 339 + 103
PN9400 and variants 20½" - 28¼" - 583 + 116
TN2277E and variants 21" 34" 13" 13" 561 + 103
TN2277NDA and variants 21" 34" - - 475 -
EL565 8¾" 31 /8"
3
- - - 97
F
J
Actuator F
H J
G
Actuator
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P378-02-US 08.13
54
SPIRA-TROL 6" and 8"
Control
Valves
KEA, KFA and KLA Two-port Control Valves
Spare parts - SPIRA-TROL
(unbalanced valve)
Globe Control
The spare parts available are shown in solid outline. Parts
drawn in broken line are not supplied as spares.
Valves
Note: When placing an order for spare parts please specify
clearly the full product description as found on the label of
the valve body, as this will ensure that the correct spare C2
parts are supplied. C1
C
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P378-02-US 08.13
© Spirax Sarco, Inc. 2005
55
SPIRA-TROL 6" and 8"
Control
Valves
H J
E
G Exploded view of
soft seat arrangement
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P378-02-US 08.13
56
SPIRA-TROL 6" and 8"
Control
Valves
KEA, KFA and KLA Two-port Control Valves
SPIRA-TROL selection guide:
6"
Globe Control
Valve size 6" and 8"
Valves
Valve series K = K series 2-port control valve K
Valve characteristic F = Fast opening (not available for low noise option) E
L = Linear
T = Flow over
Flow direction
Blank = Flow under
4 = Carbon steel
Body material 4
7 = SG iron
3
Connections 3 = Flanged
P = PTFE
Stem sealing P
H = Graphite
S = Standard trim
Type of trim S
P = Low noise cage (Linear balanced trim only)
B = Balanced
Trim balancing U
U = Unbalanced
S = Standard
Bolting S
H = High temperature
Series 2 = .2 .2
ASME
Connection type To be specified 150
Selection example:
6" - K E A 4 3 P T S U S S .2 - Cvs 433 - ASME 150
How to order
Example: 1 off Spirax Sarco 6" SPIRA-TROL KEA 43PTSUSS.2 Cvs 433 two-port control valve having flanged ASME 150 connections.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P378-02-US 08.13
57
Control
Valves
Globe Control
Valves
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
58
Control
Valves
STERI-TROL Clean Service
Globe Control
Valves
'S' series Two-port and Three-Port
Control Valves - DN15 (½") to DN100 (4")
Description
STERI-TROL 'S' series are 316L stainless steel, two-port and
three-port control valves. They are designed for mixing / diverting
fluids (three-port only), and for on /
off and modulating control
of clean steam, pure steam and process fluids. The valve is
operated by a pneumatic actuator and may be interfaced with a
control system using any of the Spirax Sarco range of positioners.
Available types
SA Two-port angle pattern design
SH Two-port horizontal pattern design
SQ Three-port design
59
Materials
23
Control
Valves
4 1
16 2
Globe Control
PNS3000 series
Valves
3 6
7 8
10
15
14 12
11
8
10
3 1
7 9
4 2
PNS4000 series
16
24
15
14
11
12
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
60
PN 9000 series actuators
Control
Valves
No. Part Material
1 Yoke SG iron
2 Upper diaphragm housing Carbon steel (plated)
3 Diaphragm plate Aluminium
4 Diaphragm Reinforced NBR
Globe Control
5 Spring Spring steel
Valves
6 Spindle Stainless steel
7 Washer Carbon steel (plated)
8 Spacer Carbon steel (plated)
9 'O' ring Viton
10 Connector Carbon steel (plated)
11 Adaptor Carbon steel (plated)
12 Collar Carbon steel (plated)
13 Clamp front Stainless steel
14 Clamp rear Stainless steel
15 Scale Stainless steel
16 Vent plug Brass
17 Bearing PTFE / steel composite
18 Seal Polyurethane
19 Pan head screw Carbon steel (plated)
20 Nyloc nut Carbon steel (plated)
21 Bolt Carbon steel (plated) Gr. 8.8
22 Hex. head screw (short) Carbon steel (plated) Gr. 8.8
23 Hex. head screw (long) Carbon steel (plated) Gr. 8.8
24 Nut Carbon steel (plated) Gr. 8.8
25 Lock-nut Carbon steel (plated)
26 Socket head screw Carbon steel (plated) Gr. 8.8
27 Nut Carbon steel (plated) Gr. 8.8
28 Washer Carbon steel (plated)
29 Screw Carbon steel (plated) Gr. 8.8
30 Gasket Reinforced graphite
31 Lower diaphragm housing Carbon steel (plated)
32 Lifting eye Cast steel
16
2
5
21
28
32
22
and
23
24
8
3 9
4
7 29
31 17
30
PN9000 18
6
15 25
10
19 and 20
12
26 and 27 13 and 14
1 11
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
61
Control
Valves
26
31
30
31
30
27
27
30
30 32
32
29 28
29 28
26
25
25
32 32
28
28
26
25
25
26
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
62
Pressure / temperature limits
Control
Valves
338
302
Temperature °F
212
Steam
Globe Control
122 saturation
curve
Valves
14
24 58 87 116 145 174 203 232
Pressure psig
Micro-flow trim for all valves < = 1" (DN25) (SA and SH only)
Travel ¾" (20 mm)
Micro-flow trim
Trim size 1
/8" 3
/16" ¼" ¼" 3/8"
Linear characteristic Cv (Kvs) .47 (0.4) .74 (0.63) 1.17 (1.0) 1.9 (1.6) 2.9 (2.5)
Notes:
1. Lower Cv (Kv) values are available to special order.
2. Micro-filter and Equal percentage trim not available for the SQ 3-port control valve.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
63
Maximum differential pressures for Class IV shut-off SA and SH valves
Control
Valves
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Globe Control
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring range Positioner Maximum differential pressure Class IV (psi)
required
PN9120E 6 - 18 Optional 203 116 58 29 15 - - - -
PN9126E 15 - 30 Yes 232 232 218 131 87 44 - - -
PN9123E 30 - 60 Yes 232 232 232 232 218 116 - - -
PN9220E 3 - 15 Optional 232 232 145 87 44 15 - - -
6 - 18 Optional 232 232 232 218 145 73 - - -
PN9226E 15 - 30 Yes 232 232 232 232 232 232 - - -
PN9223E 30 - 60 Yes 232 232 232 232 232 232 - - -
PN9320E 3 - 15 Optional 232 232 232 203 145 73 - - -
6 - 18 Optional 232 232 232 232 232 174 - - -
PN9330E 6 - 18 Yes - - - - - - 87 58 44
PN9336E 15 - 30 Yes - - - - - - 232 174 116
PN9337E 36 - 50 Yes - - - - - - 232 232 232
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
64
Maximum differential pressures for Class IV shut-off SA and SH valves
Control
Valves
PNS4000 spring-to-retract actuators
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Globe Control
Cv 4.7 7.4 12 19 29 42 74 117 187
Valves
Travel (inches) 3/4" 1 3/16"
Actuator Spring Positioner Air Maximum differential pressure Class IV (psi)
range required pressure
required
PNS4220 3 - 15 Optional 20 232 203 103 58 35 - - - -
3 - 15 Yes 30 232 232 232 219 148 77 - - -
3 - 15 Yes 45 232 232 232 232 232 184 - - -
3 - 15 Yes 60 232 232 232 232 232 232 - - -
PNS4320 3 - 15 Optional 20 232 232 232 165 110 55 - - -
3 - 15 Yes 30 232 232 232 232 232 184 - - -
3 - 15 Yes 45 232 232 232 232 232 232 - - -
PNS4420 3 - 15 Optional 20 - - 232 232 186 99 - - -
3 - 15 Yes 30 - - 232 232 232 232 - - -
3 - 15 Yes 45 - - 232 232 232 232 - - -
PNS4430 3 - 15 Optional 20 - - - - - - 49 29 17
3 - 15 Yes 30 - - - - - - 155 100 67
3 - 15 Yes 45 - - - - - - 232 218 148
3 - 15 Yes 60 - - - - - - 232 232 229
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring Positioner Maximum differential pressure Class IV (psi)
range required
PN9120R 3 - 15 Optional 232 232 232 232 232 232 - - -
6 - 18 Optional 232 232 232 232 232 232 - - -
PN9126R 15 - 30 Yes 232 232 232 232 232 232 - - -
PN9123R 30 - 60 Yes 232 232 232 232 232 116 - - -
PN9220R 3 - 15 Optional 232 232 232 232 232 232 - - -
6 - 18 Optional 232 232 232 232 232 232 - - -
PN9226R 15 - 30 Yes 232 232 232 232 232 232 - - -
PN9223R 30 - 60 Yes 232 232 232 232 232 232 - - -
PN9320R 3 - 15 Optional 232 232 232 232 232 232 - - -
6 - 18 Optional 232 232 232 232 232 232 - - -
PN9330R 6 - 18 Yes - - - - - - 232 232 232
PN9336R 15 - 30 Yes - - - - - - 232 232 232
PN9337R 36 - 50 Yes - - - - - - 116 73 44
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
65
Maximum differential pressures for Class VI shut-off (soft seat seal only) SA and SH valves
Control
Valves
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Globe Control
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring range Positioner Maximum differential pressure Class VI (psi)
required
PN9120E 6 - 18 Optional 102 58 15 15 - - - - -
PN9126E 15 - 30 Yes 232 232 102 87 58 29 - - -
PN9123E 30 - 60 Yes 232 232 232 218 145 73 - - -
PN9220E 3 - 15 Optional 232 160 58 44 29 15 - - -
6 - 18 Optional 232 232 174 145 102 44 - - -
PN9226E 15 - 30 Yes 232 232 232 232 232 160 - - -
PN9223E 30 - 60 Yes 232 232 232 232 232 232 - - -
PN9320E 3 - 15 Optional 232 232 160 131 102 44 - - -
6 - 18 Optional 232 232 232 232 218 116 - - -
PN9330E 6 - 18 Yes - - - - - - 58 44 29
PN9336E 15 - 30 Yes - - - - - - 189 145 87
PN9337E 36 - 50 Yes - - - - - - 232 232 232
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
66
Maximum differential pressures for Class VI shut-off (soft seat seal only) SA and SH valves
Control
Valves
PNS4000 spring-to-retract actuators
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Globe Control
Cv 4.7 7.4 12 19 29 42 74 117 187
Valves
Travel (inches) 3/4" 1 3/16"
Actuator Spring Positioner Air pressure Maximum differential pressure Class VI (psi)
range required required
PNS4220 3 - 15 Optional 20 175 122 44 33 19 - - - -
3 - 15 Yes 30 232 232 175 144 100 48 - - -
3 - 15 Yes 45 232 232 232 232 232 122 - - -
3 - 15 Yes 60 232 232 232 232 232 196 - - -
PNS4320 3 - 15 Optional 20 232 232 132 107 74 33 - - -
3 - 15 Yes 30 232 232 232 232 232 122 - - -
3 - 15 Yes 45 232 232 232 232 232 232 - - -
PNS4420 3 - 15 Optional 20 - - 219 180 128 64 - - -
3 - 15 Yes 30 - - 232 232 232 196 - - -
3 - 15 Yes 45 - - 232 232 232 232 - - -
PNS4430 3 - 15 Optional 20 - - - - - - 32 25 -
3 - 15 Yes 30 - - - - - - 107 86 54
3 - 15 Yes 45 - - - - - - 232 190 122
3 - 15 Yes 60 - - - - - - 232 232 190
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring Positioner Maximum differential pressure Class VI (psi)
range required
PN9120R 3 - 15 Optional 232 232 232 232 232 232 - - -
6 - 18 Optional 232 232 232 232 232 218 - - -
PN9126R 15 - 30 Yes 232 232 232 232 232 174 - - -
PN9123R 30 - 60 Yes 232 232 232 232 232 73 - - -
PN9220R 3 - 15 Optional 232 232 232 232 232 232 - - -
6 - 18 Optional 232 232 232 232 232 232 - - -
PN9226R 15 - 30 Yes 232 232 232 232 232 232 - - -
PN9223R 30 - 60 Yes 232 232 232 232 232 232 - - -
PN9320R 3 - 15 Optional 232 232 232 232 232 232 - - -
6 - 18 Optional 232 232 232 232 232 232 - - -
PN9330R 6 - 18 Yes - - - - - - 232 232 232
PN9336R 15 - 30 Yes - - - - - - 232 232 203
PN9337R 36 - 50 Yes - - - - - - 87 58 44
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
© Spirax Sarco, Inc. 2006
67
Maximum differential pressures for Class IV metal seated SQ valves
Control
Valves
For pure control applications providing control across the full valve opening range but not guaranteeing shut-off to a greater level than the
minimum flowrate based on the valves 30:1 turndown.
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Valves
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring range Positioner Maximum differential pressure Class IV (psi)
required
PN9120E 3 - 15 Optional 160 29 15 - - - - - -
6 - 18 Optional 232 131 58 29 15 - - - -
PN9126E 15 - 30 Yes 232 232 232 145 102 44 - - -
PN9123E 30 - 60 Yes 232 232 232 232 218 116 - - -
PN9220E 3 - 15 Optional 232 232 232 87 58 29 - - -
6 - 18 Optional 232 232 232 218 145 87 - - -
PN9226E 15 - 30 Yes 232 232 232 232 232 232 - - -
PN9223E 30 - 60 Yes 232 232 232 232 232 232 - - -
PN9320E 3 - 15 Optional 232 232 232 232 145 73 - - -
6 - 18 Optional 232 232 232 232 232 189 - - -
PN9330E 6 - 18 Yes - - - - - - 102 58 44
PN9336E 15 - 30 Yes - - - - - - 232 174 116
PN9337E 36 - 50 Yes - - - - - - 116 73 44
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
68
Maximum differential pressures for Class IV metal seated SQ valves
Control
Valves
For pure control applications providing control across the full valve opening range but not guaranteeing shut-off to a greater level than the mini-
mum flowrate based on the valves 30:1 turndown.
Globe Control
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Valves
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring range Positioner Maximum differential pressure Class IV (psi)
required
PNS4320 0.2 – 1.0 Optional 232 203 103 58 35 - - - -
0.4 – 1.2 Optional 232 232 232 165 110 55 - - -
PNS4326 1.0 – 3.0 Yes 232 232 232 232 232 184 - - -
PNS4420 0.2 – 1.0 Optional 232 232 186 112 73 33 - - -
0.4 – 1.2 Optional 232 232 232 232 186 99 - - -
PNS4426 1.0 – 3.0 Yes - - 232 232 232 232 - - -
PNS4430 0.4 – 1.2 Optional - - - - - - 49 29 17
PNS4436 1.0 – 3.0 Yes - - - - - - 155 100 67
PNS4534 0.8 – 1.5 Yes - - - - - - 197 128 86
PNS4634 0.8 – 1.5 Yes - - - - - - 232 193 131
Valve size 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Kv 4 6 10 16 25 36 63 100 160
Cv 4.7 7.4 12 19 29 42 74 117 187
Travel (inches) 3/4" 1 3/16"
Actuator Spring range Positioner Maximum differential pressure Class IV (psi)
required
PN9120R 0.4 – 1.2 Optional 102 58 15 15 - - - - -
PN9126R 1.0 – 2.0 Yes 232 232 102 87 58 29 - - -
PN9123R 2.0 – 4.0 Yes 232 232 232 218 145 73 - - -
PN9220R 0.2 – 1.0 Optional 232 160 58 44 29 145 - - -
0.4 – 1.2 Optional 232 232 174 145 102 44 - - -
PN9226R 1.0 – 2.0 Yes 232 232 232 232 232 160 - - -
PN9223R 2.0 – 4.0 Yes 232 232 232 232 232 232 - - -
PN9320R 0.2 – 1.0 Optional 232 232 160 131 102 44 - - -
0.4 – 1.2 Optional 232 232 232 232 218 116 - - -
PN9330R 0.4 – 1.2 Yes - - - - - - 58 44 29
PN9336R 1.0 – 2.0 Yes - - - - - - 189 145 87
PN9337R 2.5 – 3.5 Yes - - - - - - 87 58 44
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
69
Valve dimensions (approximate in inches)
Control
Valves
1" 2.86 1.63 2.24 2.46 4.08 0.82 2.98 2.33 3.27
1 1/4" 2.86 1.76 2.69 2.63 4.29 0.94 3.06 2.33 3.43
1 1/2" 2.86 2.00 2.86 2.85 4.69 1.10 3.27 2.33 3.84
2" 3.47 2.20 3.35 3.63 5.10 1.31 3.71 2.65 4.73
2 1/2" 4.29 2.78 4.29 3.63 5.92 1.76 3.88 3.47 4.65
3" 4.29 3.39 4.49 3.89 6.33 2.12 4.94 3.47 6.78
4" 5.31 3.92 6.12 4.67 7.14 2.45 5.43 3.96 7.35
PNS3000/4000 actuator dimensions and weights PN9000 actuator dimensions and weights
(approximate) in inches and lb. (approximate) in inches and lb.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
70
F
J
Control
Valves
H
Globe Control
Valves
G
A D
SH valve SQ valve
C
C
E E
B
B1
A D A D
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
71
Connection codes
The codes specified below represent a small selection of pipe end connections that are available. If the connection required is not specified
Control
Valves
BS 4825 (Pt 1) OC
ASME BPE OD
BS 4825 (Pt 3) BO
Sanitary clamp
ISO 2852 CO
DIN 32676 SO
EN 1092 PN6 FE
With smooth
EN 1092 PN10 FF
sealing face
EN 1092 PN16 FG
SMS 3008 GV
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
72
How to order
Control
Valves
Ordering a control valve
Valve size ½", ¾", 1", 1¼", 1½", 2", 2½", 3" and 4" ½"
Globe Control
SA = Two-port angle pattern design
Valves
Valve series SH = Two-port horizontal design SA
SQ = Three-port valve design
Ordering
a: PNS pneumatic actuator PN or PNP pneumatic actuator
2 1
Diaphragm size 3 2 3
4 3
Ordering example:
1 off Spirax Sarco STERI-TROL type ½" SAE6SOSV0004 and 1 pneumatic actuator type PNS3320. Having a spring range of 6 to 18 psig.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
73
Spare parts
Control
Valves
The available spares are identified by the part numbers listed below. When placing an order for spare parts, always specify the actuator or
the valve model (shown on the data plate) and the name of the part as described below.
Available spares for the SA, SH and SQ control valves and the PNS3000 and PNS4000 series actuators
Description Part number
Globe Control
16 2
12
30 31
18
22
17
20 30
21
19
29
28
31
30
26
30
28
29
28
26
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
74
Control
Valves
Available spares for the PN9000 series actuators
Description Part number
Stem seal kit 'O' ring and 'V' ring 17, 18 and 30
Diaphragm kit Diaphragm 'O' ring and 'V' ring 4 and 9
Actuator Travel indicator 15, 19 and 20
Globe Control
Spring kit Set of springs, included 3 off longer hex, head bolts and nut on some spring range 5
Valves
Linkage kit Lock-nut, top adaptor connectors, bolts and nuts 10, 13, 14, 26 and 27
30
9 17
18
15, 19 and 20
10
26 and 27 13 and 14
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P183-02-US 1.14
75
Control
Valves
76
CE43 1" (DN25) to 4" (DN100)
Control
Valves
97 Carbon Steel Cage Design, Two Port Control Valves
Operating range for body material and flange type only. Valve flow coefficients at 100% lift
Note: See limiting conditions for stem and plug limitations. Cv (US) for single stage trims (Kvs shown in brackets).
Globe Control
Size Equal % Cv (Kvs) FL
Pressure barg 1" (DN25) 19 (16) 0.94
Valves
0 B 10 20 30 40 50 60 70 80 90 1-1/2" (DN40) 35 (30) 0.94
797 425 2" (DN50) 63 (54) 0.94
A
Temperature ° C
2-1/2" (DN65) 95 (81) 0.94
Temperature ° F
2" C E 4 3 P T C 1 U S 1 Cv 35
Weights (approximate) in lbs and (kg)
Valve size 1" 1-1/2" 2" 2-1/2" 3" 4"
DN25 DN40 DN50 DN65 DN80 DN100 How to order
Weights 29 48 59 92 130 213 Example: 1 of 2" CE43 PTC1US1 Cv35 flanged to ANSI 300.
(13) (22) (27) (42) (59) (97)
Spare parts See TI-F12-22-US
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-F12-21-US 08.11
© Spirax Sarco, Inc. 2004
77
Control
Valves
Limiting conditions
Body design conditions ANSI 300 and ANSI 600
Standard PTFE chevron stem seals 14°F to +482°F (-10°C to +250°C)
Standard bonnet 14°F to +572°F (-10°C to +300°C)
Graphite packing stem seals
Design
temperature Extended bonnet 14°F to +797°F (-10°C to +425°C)
Graphite sealed balanced plug (Class IV) 797°F (425°C)
PTFE sealed balanced plug (Class VI) 356°F (180°C)
(ANSI 300) 1110 psi g (76.6 bar g)
Designed for a maximum cold hydraulic test pressure of:
(ANSI 600) 2220 psi g (153 bar g)
Maximum differential pressure See relevant actuator TI
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-F12-24-US 08.11
78
CE43 5" (DN125) to 8" (DN200)
Control
Valves
Carbon Steel Cage Design, Two Port Control Valves
Operating range for body material and flange type only. Valve flow coefficients at 100% lift
Note: See limiting conditions for stem and plug limitations. Cv (US) for single stage trims (Kvs shown in brackets).
Size Equal % Cv (Kvs) FL
Globe Control
Pressure bar g
0 10 20 30 40 50 60 70 80 90 103 5"
Valves
B 293 (250) 0.85
1004 (DN125)
Temperature ° C
Steam 300 6"
800 A 386 (330) 0.85
Temperature ° F
saturation (DN150)
curve 200
600 8"
100 560 (480) 0.85
400 (DN200)
0 Three reduced Cv are available for equal percentage and linear
200
C H D E J F G K trims, for further details see TI-F12-23-US ‘C’ series valve options.
0
0 200 400 600 800 1000 1200 1400 For conversion Cv (UK) = Cv (US) x 0.833 Kvs = Cv (US) x 0.855
Pressure psi g
Sizing
The product must not be used in this region. Please consult Spirax Sarco, Inc.
A-C PN16 A-D PN25 A-E PN40 A-F PN63 A-G PN100 Installation
B-H ANSI 150 B-J ANSI 300 B-K ANSI 600 The valve should be installed in a horizontal pipeline with the
direction of flow as indicated by the arrow on the valve name-
plate. The actuator position will depend on the type fitted to the
valve. Full instructions are supplied with the product.
Dimensions (approximate) in inches and (mm)
‘C’ series valve selection guide
Valve size 5" 6" 8"
DN125 DN150 DN200 5", 6" and 8" 5"
Valve size
ANSI 300 16-3/4" 18-5/8" 22-3/8" DN125, 150, 200
PN25 - PN40 (425) (473) (568) C
A Valve series C = Cage trim
ANSI 600 18" 20" 24"
PN63 - PN100 (457) (508) (610) E = Equal percentage
F = Fast opening
Valve E
B 6-1/2" 7" 8-1/4"
characteristic L = Linear
(165) (178) (210)
M = Modified equal percentage
C 11-3/8" 13-6/16" 14-5/8"
4
(290) (339) (370) Body material 4 = Carbon steel
Extended 16-11/16" 18-11/16" 19-14/16" 2 = Butt weld (5" to 8") 3
Connections
C1 bonnet (425) (474) (505) 3 = Flanged
Bellows sealed 27" 29" 30-1/4" P = PTFE chevron
Stem
sealing H = Graphite P
bonnet (690) (739) (770) options
B = Bellows
T = AISI 431 hardened
Seating options G = PTFE soft seat T
W = Hard face AISI 316
C1 C = Standard cage
Type of trim P = Noise reducing perforated cage C
A = Anti-cavitation cage
1 = One
Number of 2 = Two 1
stages 3 = Three
Other = To be specified
B = Balanced B
Trim balancing
C U = Unbalanced
S = Standard
Bonnet type H = Extended for high temperature S
L = Extended for low temperature
0 = No reduction
1 = 1 reduction 0
Reduced trim
2 = 2 reductions
B 3 = 3 reductions
Cv To be specified Cv 293
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-F12-24-US 08.11
© Spirax Sarco, Inc. 2004
79
Control
Valves
80
CE83 1" (DN25) to 4" (DN100)
Control
Valves
Alloy Steel Cage Design, Two Port Control Valves
Operating range for body material and flange type only. Valve flow coefficients at 100% lift
Note: See limiting conditions for stem and plug limitations. Cv (US) for single stage trims (Kvs shown in brackets).
Globe Control
Size Equal % Cv (Kvs) FL
Pressure bar g
Valves
1" (DN125) 19 (16) 0.94
0
10
20 30 40
50 60
70
80 90 1-1/2" (DN125) 35 (30) 0.94
1004 2" (DN150) 63 (54) 0.94
540
Temperature ° C
2-1/2" (DN125) 95 (81) 0.92
Temperature ° F
800
400
600 3" (DN200) 130 (111) 0.90
300
4" (DN200) 216 (185) 0.89
400
200
Three reduced Cv are available for equal percentage and linear
200
100 trims, for further details see TI-F12-23-US ‘C’ series valve options.
0
0
For conversion Cv (UK) = Cv (US) x 0.833 Kvs = Cv (US) x 0.855
0
200
400
600
800 1000 1200 1400
Pressure psi g Sizing
Please consult Spirax Sarco, Inc.
The product must not be used in this region. Installation
A-C PN16 A-D PN25 A-E PN40 A-F PN63 A-G PN100 The valve should be installed in a horizontal pipeline with the
B-H ANSI 150 B-J ANSI 300 B-K ANSI 600 direction of flow as indicated by the arrow on the valve name-
plate. The actuator position will depend on the type fitted to the
valve. Full instructions are supplied with the product.
Dimensions (approximate) in inches and (mm)
‘C’ series valve selection guide
Valve size 1" 1-1/2" 2" 2-1/4" 3" 4"
DN25 DN40 DN50 DN65 DN80 DN100 1", 1-1/2", 2", 2-1/2", 3" and 4"
2"
ANSI 300 7-3/4" 9-1/4" 10-1/2" 11-1/2" 12-1/2" Valve size
DN25, 40, 50, 65, 80 & 100
14-1/2" PN25 - PN40 (197) (235) (267) (292) C
A Valve series C = Cage trim
(317) (368) ANSI 600 8-1/4" 9-7/8"
11-1/4" 12-1/4" 13-1/4" 15-1/2" PN63 - PN100 E = Equal percentage
(210) (251) (268) (311) (337) (394)
Valve F = Fast opening E
characteristic L = Linear
B 2-1/2" 3" 3" 4-3/4" 4-1/8" 5"
M = Modified equal percentage
(62) (80) (80) (95) (105) (128)
Body material 8 = Alloy steel 8
C 5-1/2" 7" 7-3/16" 8-1/4" 8-1/4" 9-3/4"
(141) (179) (183) (209) (209) (247) 3 = Flanged
Connections 3
Extended 10" 11-1/2" 11-5/8" 13-1/2" 13-1/2" 15" 4 = Socket weld (1", 1-1/2", 2")
bonnet (255) (293) (296) (344) (344) (382) P = PTFE chevron
C1 Stem sealing
Bellows sealed 15" 16-1/2" 18-14/16" 20" 20" 25" H = Graphite P
options
bonnet (380) (419) (480) (506) (506) (634) B = Bellows
T = AISI 431 hardened
Seating options G = PTFE soft seat T
W = Hard face AISI 316
C1
C = Standard cage
Type of trim P = Noise reducing perforated cage C
A = Anti-cavitation cage
1 = One
Number of 2 = Two
stages 3 = Three 1
Other = To be specified
B = Balanced
C Trim balancing U
U = Unbalanced
S = Standard
Bonnet type H = Extended for high temperature S
L = Extended for low temperature
0 = No reduction
1 = 1 reduction
Reduced trim 1
B 2 = 2 reductions
3 = 3 reductions
Cv To be specified Cv 35
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-F12-20-US 08.11
© Spirax Sarco, Inc. 2004
81
Control
Valves
Limiting conditions
Body design conditions ANSI 300 and ANSI 600
Standard PTFE chevron stem seals 14°F to +482°F (-10°C to +250°C)
Standard bonnet 14°F to +572°F (-10°C to +300°C)
Graphite packing stem seals
Design
temperature Extended bonnet 14°F to +1004°F (-10°C to +540°C)
Graphite sealed balanced plug (Class IV) 1004°F (540°C)
PTFE sealed balanced plug (Class VI) 356°F (180°C)
(ANSI 300) 1125 psi g (77.6 bar g)
Designed for a maximum cold hydraulic test pressure of:
(ANSI 600) 2250 psi g (155 bar g)
Maximum differential pressure See relevant actuator TI
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-F12-25-US 6.07
82
CE83 5" (DN125) to 8" (DN200)
Control
Valves
Alloy Steel Cage Design, Two Port Control Valves
Operating range for body material and flange type only. Valve flow coefficients at 100% lift
Note: See limiting conditions for stem and plug limitations. Cv (US) for single stage trims (Kvs shown in brackets).
Pressure bar g Size Equal % Cv (Kvs) FL
Globe Control
0 10 20 30 40 50 60 70 80 90 103 5"
Valves
B 293 (250) 0.85
1004 (DN125)
540
6"
Temperature ° C
Temperature ° F
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
© Spirax Sarco, Inc. 2004
83
Control
Valves
Globe Control
Limiting conditions
Body design conditions ANSI 300 and ANSI 600
Standard PTFE chevron stem seals -20°F to +482°F (-29°C to +250°C)
Standard bonnet -20°F to +572°F (-29°C to +300°C)
Graphite packing stem seals
Design temperature
Extended bonnet -20°F to +1004°F (-29°C to +540°C)
Graphite sealed balanced plug (Class IV) 1004°F (540°C)
PTFE sealed balanced plug (Class VI) 356°F (180°C)
(ANSI 300) 1080 psi g (74.5 bar g)
Designed for a maximum cold hydraulic test pressure of:
(ANSI 600) 2160 psi g (149 bar g)
Maximum differential pressure See relevant actuator TI
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-F12-34-US 08.11
84
CE63 1" (DN25) to 4" (DN100)
Control
Valves
Stainless Steel Cage Design, Two Port Control Valves
Operating range for body material and flange type only. Valve flow coefficients at 100% lift
Note: See limiting conditions for stem and plug limitations. Cv (US) for single stage trims (Kvs shown in brackets).
Globe Control
Size Equal % Cv (Kvs) FL
Valves
1" (DN125) 19 (16) 0.94
Pressure bar g
1-1/2" (DN125) 35 (30) 0.94
0 B 10 20 30 40 50 60 70 80 90 103
1004 2" (DN150) 63 (54) 0.94
Temperature ° C
A 540 2-1/2" (DN125) 95 (81) 0.92
Temperature ° F
800 400
Steam 3" (DN200) 130 (111) 0.90
600 saturation 300 4" (DN200) 216 (185) 0.89
A
400 curve
200 Three reduced Cv are available for equal percentage and linear
K
200 C H D E J F G 100 trims, for further details see TI-F12-23-US ‘C’ series valve options.
0 0 For conversion Cv (UK) = Cv (US) x 0.833 Kvs = Cv (US) x 0.855
0 200 400 600 800 1000 1200 1400
Pressure psi g Sizing
Please consult Spirax Sarco, Inc.
The product must not be used in this region. Installation
A-C PN16 A-D PN25 A-E PN40 A-F PN63 A-G PN100 The valve should be installed in a horizontal pipeline with the
B-H ANSI 150 B-J ANSI 300 B-K ANSI 600 direction of flow as indicated by the arrow on the valve name-
plate. The actuator position will depend on the type fitted to the
valve. Full instructions are supplied with the product.
Dimensions (approximate) in inches and (mm)
‘C’ series valve selection guide
Valve size 1" 1-1/2" 2" 2-1/4" 3" 4"
DN25 DN40 DN50 DN65 DN80 DN100 1", 1-1/2", 2", 2-1/2", 3" and 4"
2"
Valve size
ANSI 300 7-3/4" 9-1/4" 10-1/2" 11-1/2" 12-1/2" 14-1/2" DN25, 40, 50, 65, 80 & 100
A PN25 - PN40 (197) (235) (267) (292) (317) (368) Valve series C = Cage trim C
ANSI 600 8-1/4" 9-7/8" 11-1/4" 12-1/4" 13-1/4" 15-1/2"
E = Equal percentage
PN63 - PN100 (210) (251) (268) (311) (337) (394)
Valve F = Fast opening
B 2-1/2" 3" 3" 4-3/4" 4-1/8" 5" characteristic L = Linear E
(62) (80) (80) (95) (105) (128) M = Modified equal percentage
C 5-1/2" 7" 7-3/16" 8-1/4" 8-1/4" 9-3/4"
Body material 6 = Stainless steel
(141) (179) (183) (209) (209) (247) 6
Extended 10" 11-1/2" 11-5/8" 13-1/2" 13-1/2" 15" 2 = Butt weld (2" to 4")
Connections
C1 bonnet (255) (293) (296) (344) (344) (382) 3 = Flanged 3
Bellows sealed 15" 16-1/2" 18-14/16" 20" 20" 25" 4 = Socket weld (1", 1-1/2", 2")
bonnet (380) (419) (480) (506) (506) (634) P = PTFE chevron
Stem
sealing H = Graphite P
options
B = Bellows
T = AISI 431 hardened
Seating options G = PTFE soft seat T
C1 W = Hard face AISI 316
C = Standard cage
Type of trim P = Noise reducing perforated cage C
A = Anti-cavitation cage
1 = One
Number of 2 = Two
stages 3 = Three 1
Other = To be specified
C B = Balanced
Trim balancing U
U = Unbalanced
S = Standard
Bonnet type H = Extended for high temperature S
L = Extended for low temperature
0 = No reduction
1 = 1 reduction
B Reduced trim 1
2 = 2 reductions
3 = 3 reductiion
Cv To be specified Cv 35
A
Connection type To be specified ANSI 300
Weights (approximate) in lbs and (kg) Cv 35 ANSI 300
2" C E 6 3 P T C 1 U S 1
Valve size 1" 1-1/2" 2" 2-1/4" 3" 4"
DN25 DN40 DN50 DN65 DN80 DN100 How to order
Weights 29 48 59 92 130 213 Example: 1 off 2" CE63 PTC1US1 Cv 35 flanged to ANSI 300.
(13) (22) (27) (42) (59) (97)
Spare parts See TI-F12-22-US
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-F12-34-US 08.11
© Spirax Sarco, Inc. 2004
85
Control
Valves
Globe Control
Limiting conditions
Body design conditions ANSI 300 and ANSI 600
Standard PTFE chevron stem seals -20°F to +482°F (-29°C to +250°C)
Standard bonnet -20°F to +572°F (-29°C to +300°C)
Graphite packing stem seals
Design
temperature Extended bonnet -20°F to +1004°F (-29°C to +540°C)
Graphite sealed balanced plug (Class IV) 1004°F (540°C)
PTFE sealed balanced plug (Class VI) 356°F (180°C)
(ANSI 300) 1080 psi g (74.5 bar g)
Designed for a maximum cold hydraulic test pressure of:
(ANSI 600) 2160 psi g (149 bar g)
Maximum differential pressure See relevant actuator TI
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-F12-33-US 08.11
86
CE63 5" (DN125) to 8" (DN200)
Control
Valves
Stainless Steel Cage Design, Two Port Control Valves
Operating range for body material and flange type only. Valve flow coefficients at 100% lift
Note: See limiting conditions for stem and plug limitations. Cv (US) for single stage trims (Kvs shown in brackets).
Globe Control
Size Equal % Cv (Kvs) FL
Pressure bar g
Valves
5"
0
10 20
30
40 50 60
70
80
90 103 (DN125) 293 (250) 0.85
1004 B
Temperature ° C
A 6"
Temperature ° F
800
300 (DN150) 386 (330) 0.85
Steam
600 saturation
200 8"
A
400 curve (DN200) 560 (480) 0.85
100
K Three reduced Cv are available for equal percentage and linear
200 C H D E J F G
0 trims, for further details see TI-F12-23-US ‘C’ series valve options.
0 0
200
400 600
800
1000
1200
1400 For conversion Cv (UK) = Cv (US) x 0.833 Kvs = Cv (US) x 0.855
Pressure psi g
Sizing
The product must not be used in this region. Please consult Spirax Sarco, Inc.
A-C PN16 A-D PN25 A-E PN40 A-F PN63 A-G PN100 Installation
The valve should be installed in a horizontal pipeline with the
B-H ANSI 150 B-J ANSI 300 B-K ANSI 600
direction of flow as indicated by the arrow on the valve name-
plate. The actuator position will depend on the type fitted to the
valve. Full instructions are supplied with the product.
Dimensions (approximate) in inches and (mm)
‘C’ series valve selection guide
Valve size 5" 6" 8"
DN125 DN150 DN200 Valve size 5", 6" and 8" 5"
ANSI 300 16-3/4" 18-5/8" 22-3/8" DN125, 150, 200
A PN25 - PN40 (425) (473) (568) Valve series C = Cage trim C
ANSI 600 18" 20" 24"
E = Equal percentage
PN63 - PN100 (457) (508) (610)
F = Fast opening
Valve
B 6-1/2" 7" 8-1/4" characteristic L = Linear E
(165) (178) (210) M = Modified equal percentage
C 11-3/8" 13-6/16" 14-5/8"
Body material 6 = Stainless steel
(290) (339) (370) 6
Extended 16-11/16" 18-11/16" 19-14/16" Connections
2 = Butt weld (5" to 8")
3
C1 bonnet (425) (474) (505) 3 = Flanged
Bellows sealed 27" 29" 30-1/4" P = PTFE chevron
Stem
sealing H = Graphite
bonnet (690) (739) (770) options
P
B = Bellows
T = AISI 431 hardened
Seating options G = PTFE soft seat T
W = Hard face AISI 316
C = Standard cage
C1 Type of trim P = Noise reducing perforated cage C
A = Anti-cavitation cage
1 = One
Number of 2 = Two
1
stages 3 = Three
Other = To be specified
B = Balanced
Trim balancing B
U = Unbalanced
C S = Standard
Bonnet type H = Extended for high temperature S
L = Extended for low temperature
0 = No reduction
1 = 1 reduction
Reduced trim 0
2 = 2 reductions
B 3 = 3 reductions
Cv To be specified Cv 293
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-F12-33-US 08.11
© Spirax Sarco, Inc. 2004
87
Control
Valves
Globe Control
Valves
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
88
Control
Valves
Globe Control
Valves
‘C’ Series Valve Spares
1 = One
Number of 2 = Two 1
stages 3 = Three
Other = To be specified
Description
The Spirax Sarco ‘C’ series valve range has a number of available Linear
Fast
options. The options relate to valve stem sealing, trim materials, Typical valve flow opening
valve flow characteristics and Cv capacity values. They are characteristics
Flow %
described in (and may be selected from) this TI.
Equal
percentage
Valve characteristics
See typical flow characteristic curves chart opposite
The standard characteristic for the ‘C’ series valve is equal percentage
(E), however the following options are available: Valve opening %
Equal percentage E ‘C’ series valve selection guide
Linear L 1", 1-1/2", 2", 2-1/2", 3", 4", 5", 6" & 8
Valve size 2"
Fast opening F DN25, 40, 50, 65, 80, 100, 125, 150 & 200
Modified equal percentage M Valve series C = Cage trim C
Note: Modified special characteristic trims are designed upon request. L = Linear
Valve E = Equal percentage
Valve stem sealing characteristic F = Fast opening E
PTFE chevron (P) M = Modified equal percentage
Design temperature 14°F to 482°F (-10°C to +250°C) 4 = Carbon steel
Material PTFE chevron Body material 6 = Stainless Steel 4
8 = Alloy Steel
Graphite (H) 2 = Butt weld (2" to 8")
Design temperature 14°F to 572°F (-10°C to +300°C) standard bonnet Connections 3 = Flanged 3
14°F to 1004°F (-10°C to +540°C) extended bonnet 4 = Socket weld (1", 1-1/2" and 2")
P = PTHE chevron
Bellows (B) Stem sealing H = Graphite P
Design temperature 14°F to 752°F (-10°C to +400°C) options B = Bellows
Material Carbon steel housing ASTM 216 WCB T = AISI 431 hardened
Pressure rating ANSI 150 Seating options G = PTFE soft seat T
W = Hard face AISI 316
Plug and seat treatment
C = Standard cage
Hardened (T)
Type of trim P = Noise reducing perforated cage C
Design temperature 14°F to 797°F (-10°C to +425°C)
A = Anti-cavitation cage
Material Stainless steel AISI 431
Leakage ANSI Class IV 1 = One
Number of 2 = Two
stages 3 = Three 1
PTFE soft seat (G)
Other = To be specified
Design temperature 14°F to 356°F (-10°C to +180°C)
Material PTFE B = Balanced
Trim balancing U
Leakage ANSI Class VI U = Unbalanced
S = Standard
Hard face (W)
Bonnet type H = Extended for high temperature S
Design temperature 14°F to 1004°F (-10°C to +540°C) L = Extended for low temperature
Material Hard faced stellite AISI 316
Leakage ANSI Class IV or V 0 = No reduction
Reduced trim 1 = 1 reduction 1
2 = 2 reductions
Single and multiple stage cage 3 = 3 reductions
Noise reducing perforated cage (P)
Design temperature 14°F to 1004°F (-10°C to +540°C) Cv To be specified Cv 35
Material Stainless steel AISI 316 ENC
Connection type To be specified ANSI 300
Anti-cavitation cage (A)
2" C E 4 3 P T C 1 U S 1 Cv 35 ANSI 300
Design temperature 14°F to 662°F (-10°C to +350°C)
Material Stainless steel AISI 316 ENC How to order
Example: 1 of 2" CE43 PTC1US1 Cv35 flanged to ANSI 300.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-F12-23-US 6.07
90
‘C’ Series Valve Options
Control
Valves
Valve capacities Flow coefficient Cv (US) depending on the various trim options - Kvs values are shown in brackets.
Cv (Kvs) by valve size and trim reduction
Valve 1" 1-1/2" 2" 2-1/2" 3" 4" 5" 6" 8"
Type of side DN25 DN40 DN50 DN65 DN80 DN100 DN125 DN150 DN200
Globe Control
Flow
cage trim characteristic 3/4" 1-3/16" 2" 2-1/2" 3"
1-1/2"
Valves
Travel
(20mm) (30mm) (38mm) (50mm) (65mm) (75mm)
Full area 19 (16) 35 (30) 63 (54) 95 (81) 130 (111) 216 (185) 293 (250) 386 (330) 560 (480)
Fast opening
One stage Reduction 1 19 (16) 35 (30) 63 (54) 95 (81) 130 (111) 216 (185) 293 (250) 386 (330)
linear and
standard Reduction 2 19 (16) 35 (30) 63 (54) 95 (81) 130 (111) 216 (185) 293 (250)
Equal %
Reduction 3 19 (16) 35 (30) 63 (54) 95 (81) 130 (111) 216 (185)
Maximum 15 (13) 35 (30) 60 (51) 100 (86) 140 (120) 250 (214) 320 (274) 425 (364) 650 (556)
Linear Reduction 1 15 (13) 35 (30) 60 (51) 100 (86) 140 (120) 250 (214) 320 (274) 425 (364)
Reduction 2 15 (13) 35 (30) 60 (51) 100 (86) 140 (120) 250 (214) 320 (274)
Reduction 3 15 (13) 35 (30) 60 (51) 100 (86) 140 (120) 250 (214)
Maximum 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171) 250 (214) 360 (308) 530 (453)
One stage Modified Reduction 1 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171) 250 (214) 360 (308)
low noise Equal %
Reduction 2 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171) 250 (214)
Reduction 3 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171)
Maximum 15 (13) 25 (21) 45 (39) 75 (64) 95 (81) 150 (128) 210 (178) 280 (240) 425 (364)
Equal % Reduction 1 15 (13) 25 (21) 45 (39) 75 (64) 95 (81) 150 (128) 210 (178) 280 (240)
Reduction 2 15 (13) 25 (21) 45 (39) 75 (64) 95 (81) 150 (128) 210 (178)
Reduction 3 15 (13) 25 (21) 45 (39) 75 (64) 95 (81) 150 (128)
Maximum 17 (14.5) 28 (24) 46 (39) 70 (60) 125 (107) 170 (145) 250 (214) 440 (376)
Reduction 1 17 (14.5) 28 (24) 46 (39) 70 (60) 125 (107) 170 (145) 250 (214)
Linear
Reduction 2 17 (14.5) 28 (24) 46 (39) 70 (60) 125 (107) 170 (145)
Reduction 3 17 (14.5) 28 (24) 46 (39) 70 (60) 125 (107)
Two stage Maximum 15 (13) 26 (22) 43 (37) 65 (56) 115 (98) 155 (133) 230 (197) 400 (342)
low noise Modified Reduction 1 15 (13) 26 (22) 43 (37) 65 (56) 115 (98) 155 (133) 230 (197)
(Flow under) Equal %
Reduction 2 15 (13) 26 (22) 43 (37) 65 (56) 115 (98) 155 (133)
Reduction 3 15 (13) 26 (22) 43 (37) 65 (56) 115 (98)
Maximum 13 (11) 22 (19) 40 (34) 60 (52) 110 (94) 145 (125) 210 (180) 370 (317)
Reduction 1 13 (11) 22 (19) 40 (34) 60 (52) 110 (94) 145 (125) 210 (180)
Equal %
Reduction 2 13 (11) 22 (19) 40 (34) 60 (52) 110 (94) 145 (125)
Reduction 3 13 (11) 22 (19) 40 (34) 60 (52) 110 (94)
Maximum 13 (11) 20 (17) 35 (30) 50 (43) 85 (73) 105 (90) 155 (133) 280 (240)
Reduction 1 13 (11) 20 (17) 35 (30) 50 (43) 85 (73) 105 (90) 155 (133)
Linear
Reduction 2 13 (11) 20 (17) 35 (30) 50 (43) 85 (73) 105 (90)
Reduction 3 13 (11) 20 (17) 35 (30) 50 (43) 85 (73)
Maximum 10 (8.5) 15 (13) 30 (26) 45 (39) 75 (64) 95 (81) 145 (124) 250 (214)
Three stage
Modified Reduction 1 10 (8.5) 15 (13) 30 (26) 45 (39) 75 (64) 95 (81) 145 (124)
low noise
(Flow under) Equal % Reduction 2 10 (8.5) 15 (13) 30 (26) 45 (39) 75 (64) 95 (81)
Reduction 3 10 (8.5) 15 (13) 30 (26) 45 (39) 75 (64)
Maximum 7 (6) 10 (8.5) 25 (21.5) 30 (26) 55 (47) 75 (64) 115 (99) 200 (171)
Equal % Reduction 1 7 (6) 10 (8.5) 25 (21.5) 30 (26) 55 (47) 75 (64) 115 (99)
Reduction 2 7 (6) 10 (8.5) 25 (21.5) 30 (26) 55 (47) 75 (64)
Reduction 3 7 (6) 10 (8.5) 25 (21.5) 30 (26) 55 (47)
Maximum 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171) 250 (214) 360 (308) 530 (453)
One stage
anti-cavitation Linear Reduction 1 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171) 250 (214) 360 (308)
(Flow over) Reduction 2 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171) 250 (214)
Reduction 3 15 (13) 30 (26) 55 (47) 85 (73) 120 (103) 200 (171)
Maximum 15 (13) 26 (22) 43 (37) 65 (56) 115 (98) 155 (133) 230 (197) 400 (342)
Three stage
Reduction 1 15 (13) 26 (22) 43 (37) 65 (56) 115 (98) 155 (133) 230 (197)
anti-cavitation Linear
(Flow over) Reduction 2 15 (13) 26 (22) 43 (37) 65 (56) 115 (98) 155 (133)
Reduction 3 15 (13) 26 (22) 43 (37) 65 (56) 115 (98)
For conversion Cv (UK) = Cv (US) x 0.833 Kvs = Cv (US) x 0.855
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-F12-23-US 6.07
91
Control
Valves
TN2000 Series
Actuators
Linear
Available types
SE = Single-acting, spring-extend
SR = Single-acting, spring-retract
DE = Double-acting, spring assisted (extend)
DR = Double-acting, spring assisted (retract)
DA = Double-acting, no spring
Optional extra
Manual handwheel
G J
H
F
TN2277SE TN2277SRH
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P327-01-US 11.11
92
TN2000 Series
Control
Valves
Pneumatic Piston Actuators
for 6" and 8" SPIRA-TROL Series Control Valves
32 21
Materials
Actuators
Linear
15
23
3
10
16
31
19
9
29
18
8 5
6
17 30
31 10
16
2 15
26 7
22, 27, 28
24
25 14
33 11
12
13
1
93
TN2000 Series
Control
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P327-01-US 11.11
94
TN2000 Series
Control
Valves
Pneumatic Piston Actuators
for 6" and 8" SPIRA-TROL Series Control Valves
Unbalanced flow over applications
Actuators
Linear
Recommended for On-Off Applications ONLY
Caution 1: Maximum operating air pressure onto the actuator must not exceed 150 psig.
Caution 2: DE and DR versions must not exceed 120 psig.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P327-01-US 11.11
95
TN2000 Series
Control
Selection example: TN 2 2 7 7 SE
How to order
Example: 1 off Spirax Sarco TN2277SE pneumatic piston actuator.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P327-01-US 11.11
96
TN2000 Series
Control
Valves
Pneumatic Piston Actuators
for 6" and 8" SPIRA-TROL Series Control Valves
TN2000 series selection guide:
Spare parts
Actuators
Linear
The spare parts available are common across the range of actuators detailed in this document. No other parts are available as spares.
Available spares
'O' ring kit 15, 29, 30, 31
Travel indicator kit 22, 27, 28
Spring 6
Handwheel A
EH kit B
RH kit C
22, 27 and 28
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P327-01-US 11.11
97
Control
Valves
Actuators
Technical data
Temperature range - 4°F to 230°F (- 20°C to +110°C)
PN9100 87 psig (6 bar g)
Maximum operating
PN9200
inlet pressure 87 psig (6 bar g)
PN9300 58 psig (4 bar g)
J
Air supply connection ¼" NPT
PN9100 20 mm H
Actuator travel PN922_ and PN932_ 20 mm
PN923_ and PN933_ 30 mm
J
H
G
F
F
F
G G
Dimensions Weights
Actuator Range F G H J Actuator Handwheel
mm in mm in mm in mm in Kg lb Kg lb
PN9100E and variants 275 10.8 170 6.7 55 2.2 225 8.9 6 13.2 5.86 12.9
PN9100R and variants 275 10.8 170 6.7 140 5.5 225 8.9 6 13.2 2.5 5.5
PN9200E and variants 300 11.8 300 11.8 68 2.7 350 13.8 17 37.4 7.2 15.8
PN9200R and variants 300 11.8 300 11.8 152 6.0 350 13.8 17 37.4 3.77 8.3
PN9230E and variants 360 14.2 300 11.8 65 2.6 350 13.8 17 37.4 3.77 8.3
PN9230R and variants 360 14.2 300 11.8 152 6.0 350 13.8 17 37.4 3.77 8.3
PN9320E and variants 325 12.8 390 15.4 65 2.6 350 13.8 27 59.4 7.2 15.8
PN9320R and variants 325 12.8 390 15.4 152 6.0 350 13.8 27 59.4 3.77 8.3
PN9330E and variants 335 13.2 390 15.4 65 2.6 350 13.8 27 59.4 7.2 15.8
PN9330R and variants 335 13.2 390 15.4 152 6.0 350 13.8 27 59.4 3.77 8.3
PN9336E and variants 335 13.2 390 15.4 65 2.6 350 13.8 27 59.4 7.2 15.8
PN9336R and variants 335 13.2 390 15.4 152 6.0 350 13.8 27 59.4 3.77 8.3
PN9337E and variants 335 13.2 390 15.4 410 16.1 350 13.8 27 59.4 21 46.2
PN9337R and variants 335 13.2 390 15.4 410 16.1 350 13.8 27 59.4 21 46.2
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P357-30-US 7.12
98
PN9000 Series Pneumatic Actuators
Control
Valves
for SPIRA-TROL K and L Series Control Valves
16
Materials 32
2
5
Actuators
21
Linear
28
22
and
23 24
8
3 9
4
7 29
31 17
30
18
6
15 25
10
19 and 20
12
26 and 27 13 and 14
1 11
99
PN9000 Series Pneumatic Actuators
Control
Valves
Spare parts
Actuators
The only spares available are clearly indicated below and are common for both spring-extend and spring-retract versions.
Linear
Available spares
Stem seal kit 17, 18, 30
Diaphragm kit 4, 9
Travel indicator kit 15, 19, 20
Spring kit 5
Linkage kit (suitable for Mk1 and SPIRA-TROL valves) 10, 13, 14, 26, 27
30
9 17
18
15, 19 and 20
10
26 and 27 13 and 14
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-30-US 7.12
100
PN9000 Series Pneumatic Actuators
Control
Valves
for SPIRA-TROL K and L Series Control Valves
Actuators
The following tables supply guidance as to the sizing of the PN9000 when it is used on the SPIRA-TROL K and L series valves.
Linear
Two conditions are illustrated in tabular form:
Class IV shut-off - Providing shut-off of the valve to the requirements of BS 5793-4 (IEC 60534-4) class IV.
Class VI shut-off - Providing shut-off of the valve to the requirements of BS 5793-4 (IEC 60534-4) class VI.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-30-US 7.12
101
PN9000 Series Pneumatic Actuators
Control
Valves
Linear
PN9226E 15 - 30 360 360 360 360 360 360 360 360 228 189 162 135
PN9236E 16 - 30 58 31 37 20 23 12
PN9223E 30 - 60 360 360 360 360 360 360 360 360 360 360 360 360
PN9320E 6 - 18 360 360 360 360 360 294 316 227 136 97 97 69
PN9322E 9 - 15 360 360 360 360 360 360 360 360 324 286 231 204
PN9330E 6 - 18 21 13
PN9332E 9 - 15 96 70 61 45 38 28
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-30-US 7.12
102
PN9000 Series Pneumatic Actuators
Control
Valves
for SPIRA-TROL K and L Series Control Valves
Actuators
Linear
PTFE or Graphite stem seal
Maximum Differential Pressure (psi)
Spring Air 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"
Actuator
Range Pressure PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
30 450 234 334 163 195 81 158 69 42 20
40 740 712 712 541 448 333 353 265 127 88 80 53
50 740 740 740 740 700 586 549 460 211 173 141 113
PN9120R 3 - 15
60 740 740 740 740 740 740 740 656 296 258 201 174
70 740 740 740 740 740 740 740 740 381 342 261 234
90 740 740 740 740 740 740 740 740 550 512 382 355
20 640 424 485 314 296 181 235 147 76 37 44 17
30 740 740 740 740 740 740 740 740 376 337 258 230
40 740 740 740 740 740 740 740 740 675 637 472 444
PN9220R 3 - 15 50 740 740 740 740 740 740 740 740 740 740 685 658
60 740 740 740 740 740 740 740 740 740 740 740 740
70 740 740 740 740 740 740 740 740 740 740 740 740
90 740 740 740 740 740 740 740 740 740 740 740 740
30 130 104 76 59 41 30
40 251 224 153 136 89 78
50 371 345 230 213 137 126
PN9230R 3 - 15
60 491 465 307 290 185 174
70 611 585 384 367 233 222
90 740 740 537 521 329 318
20 740 740 740 740 740 659 605 517 236 197 158 131
30 740 740 740 740 740 740 740 740 740 740 579 552
PN9320R 3 - 15 40 740 740 740 740 740 740 740 740 740 740 740 740
50 740 740 740 740 740 740 740 740 740 740 740 740
60 740 740 740 740 740 740 740 740 740 740 740 740
20
30 243 216 147 131 86 75
PN9330R 6 - 18 40 480 453 299 282 180 170
50 716 690 451 434 275 264
60 740 740 602 586 369 359
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-30-US 7.12
103
PN9000 Series Pneumatic Actuators
Control
Valves
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-30-US 7.12
104
PN9000 Series Pneumatic Actuators
Control
Valves
for SPIRA-TROL K and L Series Control Valves
Actuators
Linear
PN = Polyester powder coated (standard)
PNP
Type PNP = Electroless nickle plated
1 = 100 cm2
3 = 670 cm2
2 = 20 mm
Valve travel 3
3 = 30 mm
E = Spring-extend
Spring action E
R = Spring-retract
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-30-US 7.12
105
Control
Valves
Actuators
Description
A range of single spring linear actuators having 2 diaphragm
sizes for matching the requirements of different valves at
various differential pressures. Each actuator is fitted with
a combined mechanical stroke indicator and anti-rotation
guard. The actuators are designed for easy conversion from
spring extend to spring retract, and vice versa, without the
need for special tools.
Available types
Spring extend spindle actuators:
PN1500 and PN1600 series.
Technical data
Temperature range -20°C to +110°C (-4°F to +230°F) 6
Maximum operating pressure 4.5 bar (65 psi)
Air supply connection PN1500 and PN1600 1/4" NPT
4
Materials
No. Part Material
1 Diaphragm housing Carbon steel
2 Diaphragm Reinforced nitrile rubber
3 Diaphragm plate Stainless steel
4 Spring Spring steel
5 Spindle guide Bronze 15 1
6 Bearing Hardened steel
7 Yoke Cast steel
8 Housing securing nuts Zinc plated steel 8
and bolts
9 Spindle Stainless steel 16
2
10 Connector Zinc plated steel
11 Travel indicator Stainless steel 3
12 Lock plate Zinc plated steel 5
13 ‘O’ ring Nitrile rubber 13
14 Lock-nut Zinc plated steel
15 Cap with vent hole Nickel plated brass
9
16 Spring location washer Zinc plated steel
17 Valve spindle adapter Stainless steel 7
14
10
11 12
17
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P320-57-US 6.07
106
PN1000 Series Spring Extend Pneumatic Actuators
Control
Valves
Differential pressures for LE/LEA and KE/KEA series valves and PN1000 series actuators (spring extend)
Note: The differential pressures stated in the tables below are limited by the maximum operating pressures of the selected control valve.
In certain circumstances with a reduced Cv value, or where reduced valve stroke is acceptable, it may be possible to increase the maximum
differential pressure above that shown in the table by special setting of the actuator. Please consult Spirax Sarco.
Actuators
Travel mm 30 20 30 20 30 20
Linear
Full Cv Reduced Cv Full Cv Reduced Cv Full Cv Reduced Cv
Valve capacity*
74 42 29.3 18.7 1
17 74 42 29.3 187 117 74 42
Differential pressures shown apply to valves with standard PTFE stem seals or
bellows sealed stems with either metal-to-metal or PTFE soft seat.
Actuator Spring Positioner
Travel range Maximum differential pressure (psi)
model required
PN1523A3 20 mm 30-60 Yes - 725 725 725 - - 725 725 - - - 725
PN1533A3 30 mm 30-60 Yes 560 - - - 362 560 - - 226 362 560 -
PN1653B4 30 mm 30-60 Yes 725 - - - 535 725 - - 336 535 725 -
Differential pressures shown below apply to valves with high temperature graphite (H) stem seals and metal-to-metal seats.
Actuator Spring Positioner
Travel Maximum differential pressure (psi)
model range required
PN1523A3 20 mm 30-60 Yes - 725 725 725 - - 725 725 - - - 725
PN1533A3 30 mm 30-60 Yes 557 - - - 361 557 - - 224 361 557 -
PN1653B4 30 mm 30-60 Yes 725 - - - 533 725 - - 335 533 725 -
* For fast opening, low noise and anti-cavitation trims use Full Cv column.
Installation
Actuators should be mounted on the valve with the stem in a
vertical position. Installation and Maintenance Instructions are
supplied with the product.
Spare parts
Information regarding available spare parts is given on TI-P357-20 US.
Actuation PN = Pneumatic PN
Diaphragm size 5
5
6
PN 1 5 2 3 A
How to order
Example: 1 off Spirax Sarco PN1523A actuator, set to 30 to 60 psig.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P320-57-US 6.07
© Spirax Sarco, Inc. 2003
107
Control
Valves
Actuators
Description
A range of single spring linear actuators having 2 diaphragm
sizes for matching the requirements of different valves at
various differential pressures. Each actuator is fitted with
a combined mechanical stroke indicator and anti-rotation
guard. The actuators are designed for easy conversion from
spring extend to spring retract, and vice versa, without the
need for special tools.
Available types
Spring extend spindle actuators:
PN1600
Technical data 6
Temperature range -20°C to +110°C (-4°F to +230°F)
Maximum operating pressure 4.5 bar (65 psi)
Air supply connection 1/4" NPT
4
Materials
No. Part Material
1 Diaphragm housing Carbon steel
2 Diaphragm Reinforced nitrile rubber
3 Diaphragm plate Stainless steel
4 Spring Spring steel 15 1
5 Spindle guide Bronze
6 Bearing Hardened steel
7 Yoke Cast steel 8
8 Housing securing nuts Zinc plated steel
and bolts 16
9 Spindle Stainless steel 2
10 Connector Zinc plated steel 3
11 Travel indicator Stainless steel 5
12 Lock plate Zinc plated steel 13
13 ‘O’ ring Nitrile rubber
14 Lock-nut Zinc plated steel
15 Cap with vent hole Nickel plated brass 9
16 Spring location washer Zinc plated steel 7
17 Valve spindle adapter Stainless steel 14
10
11 12
17
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P320-56-US 08.11
108
PN1000 Series Spring Extend Pneumatic Actuators
Control
(for 6" and 8" Spira-Trol Valves)
Valves
Differential pressures for KE and KEA series valves and PN1000 series actuators
Note: The differential pressures stated in the tables below are limited by the maximum operating pressures of the selected control valve.
Differential Pressures for PN1000 actuator - Unbalanced Flow Under - Class 4 - Spring Extend
Actuators
Maximum Differential Pressure (psi)
Linear
Actuator Max air
Actuator 6" 8"
pressure
Closed Open PTFE Graph PTFE Graph
PN1670 6 18 60
PN1676 15 30 60
PN1673 30 60 60 83 79 32 30
Differential Pressures for PN1000 actuator - Unbalanced Flow Over - Class 4 - Spring Extend
Maximum Differential Pressure (psi)
Actuator Max air
Actuator 6" 8"
pressure
Closed Open PTFE Graph PTFE Graph
PN1670 6 18 65 329 333 184 187
PN1676 15 30 65 281 285 158 160
PN1673 30 60 65 202 206 113 115
Differential Pressures for PN1000 actuator - Unbalanced Flow Under - Class 6 - Spring Extend
Maximum Differential Pressure (psi)
Actuator Max air
Actuator 6" 8"
pressure
Closed Open PTFE Graph PTFE Graph
PN1670 6 18 60 28 24 43 13
PN1676 15 30 60 77 73 43 41
PN1673 30 60 60 159 155 90 87
Differential Pressures for PN1000 actuator - Unbalanced Flow Over - Class 6 - Spring Extend
Maximum Differential Pressure (psi)
Actuator Max air
Actuator 6" 8"
pressure
Closed Open PTFE Graph PTFE Graph
PN1670 6 18 65 329 333 184 187
PN1676 15 30 65 281 285 158 160
PN1673 30 60 65 202 206 113 115
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P320-56-US 08.11
© Spirax Sarco, Inc. 2003
109
PN1000 Series Spring Extend Pneumatic Actuators
(for 6" and 8" Spira-Trol Valves)
Control
Valves
Installation
Actuators should be mounted on the valve with the stem in a vertical posi-
tion. Installation and Maintenance Instructions are supplied with the product.
Actuators
Linear
Spare parts
Information regarding available spare parts is given on TI-P357-23-US.
Actuation PN = Pneumatic PN
Diaphragm size
6 6
Actuator travel 7 = 70 mm 7
PN 1 6 7 3 B
How to order
Example: 1 off Spirax Sarco PN1553B actuator, set to 30 to 60 psig.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P320-56-US 08.11
110
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
111
Control
Valves
Please note: the external profile for the PN1700 and PN2700 is different to the illustrations shown above.
Description
The range of PN1000 and PN2000 series pneumatic actuators are single spring linear actuators (with exception to the PN1700 and
PN2700 series) having 5 diaphragm sizes for matching the requirements of different valves at various differential pressures. Each
actuator is fitted with a combined mechanical stroke indicator and anti-rotation guard.
These actuators are designed to be used with the C series 2-port control valve.
Available types:
PN1300, PN1400, PN1500, PN1600 and PN1700 series Spring extend spindle actuators
PN2300, PN2400, PN2500, PN2600 and PN2700 series Spring retract spindle actuators
Technical data
Temperature range -4°F to +230°F (-20°C to +110°C)
PN1000 80 psi (5.5 bar)
Maximum operating pressure
PN2000 44 psi (3.0 bar)
PN1300, PN1400, PN1500 and PN1600 ¼" NPT
PN1700 ½" NPT
Air supply connection
PN2300, PN2400, PN2500 and PN2600 ¼" NPT
PN2700 ½" NPT
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P357-23-US 6.07
112
PN1000 series
Materials - PN1700
Control
Valves
Materials - PN1300 to PN1600
No. Part Material
1 Diaphragm housing Carbon steel
2 Diaphragm Reinforced nitrile rubber
6
3 Diaphragm plate Stainless steel 31
32
4 Spring Spring steel
Actuators
33
Linear
5 Spindle guide Bronze
6 DU bearing Hardened steel
7 Yoke Cast steel 4
23
8 Housing securing nuts and bolts Zinc plated steel
15
9 Spindle Stainless steel
10 Connector Zinc plated steel 1
11 Travel indicator Stainless steel
12 Lock plate Zinc plated steel 16 8
13 'O' ring Nitrile rubber
14 Lock-nut Zinc plated steel
15 Cap with vent hole Nickel plated brass 2 28
16 Spring location washer Zinc plated steel 3 24
27
17 Valve spindle adaptor Stainless steel
26 5
13 25
9
7 14
10
11
17
12
Materials - PN1700
No. Part Material
4 1 Diaphragm housing Carbon steel
2 Diaphragm Reinforced nitrile rubber
3 Diaphragm plate Stainless steel
4 Spring Spring steel
5 Main spindle guide Bronze
6 Auxiliary spindle guide Bronze
15 1 7 Yoke Cast steel
8 Housing securing nuts and bolts Zinc plated steel
9 Main spindle Stainless steel
8 10 Connector Zinc plated steel
16 11 Travel indicator Stainless steel
2
12 Lock plate Zinc plated steel
3
5 13 'O' ring Nitrile rubber
13 14 Lock-nut Zinc plated steel
15 Cap with vent hole Nickel plated brass
9 7 16 Lock-nut Zinc plated steel
17 Valve spindle adaptor Zinc plated steel
14 10 23 Auxiliary spindle Stainless steel
24 Spacer Zinc plated steel
11 12 25 Hex. head screws Zinc plated steel
17
26 'O' ring Nitrile rubber
27 'V' ring Nitrile rubber
© Spirax Sarco, Inc. 2007
113
PN2000 series
Materials - PN2700
Control
27 5
Linear
13
2
114
PN1000 and PN2000 pneumatic actuators
closing pressures for 1" to 8" C series valves
Control
Valves
‘C’ series valve
1" 1½" 2" 2¼" 3" 4" 5" 6" 8"
Valve size
DN25 DN40 DN50 DN65 DN80 DN100 DN125 DN150 DN200
Standard travel in inches and (mm) ¾" (20) ¾" (20) 1 3/16"(30) 1½" (38) 1½" (38) 2" (50) 2-1/2"(65) 2-1/2"(65) 3" (75)
Actuators
PN1000 and PN2000 series actuators Maximum differential pressures (psi) -
Linear
Class IV and VI shut-off with: UNBALANCED valves controlled by positioner
PTFE chevron or graphite stem seal. For extended bonnets and bellows seal read ‘PTFE’ or ‘graphite’ depending on seal chosen.
Spring Minimum air
Maximum differential pressure (bar) for standard valve trim with either graphite or PTFE stem seal
range pressure psig
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Positioner
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
Actuator extend retract extend retract
required
PN1000 PN2000 PN1000 PN2000
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Positioner
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
Actuator extend retract extend retract
required
PN1000 PN2000 PN1000 PN2000
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-23-US 6.07
115
Control
Valves
Standard travel in inches and (mm) ¾" (20) ¾" (20) 1 3/16"(30) 1½" (38) 1½" (38) 2" (50) 2-1/2"(65) 2-1/2"(65) 3" (75)
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Positioner
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
Actuator extend retract extend retract
required
PN1000 PN2000 PN1000 PN2000
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-23-US 6.07
116
Dimensions / weights
(approximately) in inches (mm) and pounds (kg)
Control
Valves
D H
Actuator Weight
Yoke Type A YokeType B YokeType C
PN1300 and PN2300 11¼" (285) 28" (716) - - - - 51 (23)
PN1400 and PN2400 13¼" (336) 30" (760) 30¾" (780) - - 73 (33)
PN1500 and PN2500 16" (405) 31" (785) 31¾" (805) 33¾" (855) 121 (55)
PN1600 and PN2600 19" (465) 34" (860) 34¾" (880) 36¾" (930) 154 (70)
Actuators
Linear
PN1700 and PN2700 23 " (589) - - - - 37¾" (1070) 242 (110)
Please note: the external profile for the PN1700 and PN2700 is different to the illustrations shown below.
PN1000 PN2000
D
Selection example: PN 1 5 2 0 A
How to order
Example: 1 off Spirax Sarco PN1520A pneumatic actuator, set to 6 to 18 psig.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-23-US 6.07
© Spirax Sarco, Inc. 2006
117
Spare parts
Control
The spare parts available are detailed below. No other parts are supplied as spares.
Valves
Available spares
Stem seal kit Spindle 'O' ring and 'V' ring and diaphragm plate 'O' ring B, C, D
Diaphragm kit Diaphragm A
Spring kit Set of spring(s) E
Actuators
Always order spares by using the description given in the column headed 'Available spares' and state the actuator type.
Example for PN1000: 1 Stem seal kit for a PN1520A pneumatic actuator.
Example for PN2000: 1 Stem seal kit for a PN2520A pneumatic actuator.
PN1000 PN2000
B
C
D
A
D
A
C
F J H
G I
J H
I G
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P357-23-US 6.07
118
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
119
Control
Valves
for
½" to 2" B Series and SPIRA-TROL L & K Series Control Valves
Description
The Belimo NV Series actuators are suitable for either two position
or modulating control. These actuators can be used with B Series or 3
SPIRA-TROL L and K Series control valves.
Multi-Function Technology (MFT)
An integrated microprocessor allows for a variety of parameters, in- 2
cluding control signal type, to be configured in the factory or the field
with a PC and Belimo software.
Manual Operation
A 3/16" or 5mm Allen wrench can be used to manually operate the ac-
tuator. Turning the wrench clockwise will extend the spindle. Spindle
position will be retained until power is applied to the actuator.
Overload Protection
The actuator is protected against short circuiting and reverse polarity. 1
The spindle stroke is adapted automatically and is overload protected.
Operational Display
The stroke is physically shown by a travel indicator on the actuator
yoke. Additionally, the operational status of the actuator is shown by
a two color LED under the cover.
Available Types
Valve action in event of power failure
Actuator Model
B Series SPIRA-TROL Specifications
NVF24-MFT-US CLOSED OPEN
Supply Voltage 24 VAC 50/60 Hz or 24 VDC
NVF24-MFT-E-US OPEN CLOSED
Transformer Sizing 10 VA (Class 2 power supply)
NVG24-MFT-US STAY-PUT STAY-PUT
Power Consumption 5.5W
Electrical Connection 3 ft., 18 GA appliance cable, 1/2" conduit fitting
Materials of Construction Runnning Time Motor NVF 74 sec, NVG 32 sec
Runnning Time Spring 30 sec. At 3/4" (20mm) stroke
No. Component Material Overload Protection Electronic throughout stroke
1 Yoke Aluminum die casting 2 to 10 VDC, 0.5mA max
2 Base Aluminum die casting Control Signal 4 to 20 mA w/ 500Ω resistor
3 Cover ABS (to be specified Pulse Width Modulation (pulse
at time of order) width to be specified by customer)
Floating Point
Ambient Limits On/Off
Storage temperature -40°F to 176°F (-40°C to 80°C) at 5 to 95% RH 100KΩ for 2 to 10VDC,
Ambient temperature 32°F to 122°F (0°C to 50°C) at 5 to 95% RH Input Impedance 500Ω for 4 to 20 mA,
Maximum valve media temperature 298°F (148°C)* 1500Ω for Pulse Width Modulation (PWM)
* Equivalent to a saturated steam pressure of 50psig (3.5barg) Feedback 2 to 10 VDC, 0.5mA max
Maximum Stroke 3/4" (20mm)
NVF24-MFT US 180lbf (800N)
Agency Listings Spindle Force NVF24-MFT-E US 180lbf (800N)
General CE, UL 873, CSA C22.2 No. 24 certified NVG-24-MFT-US 360lbf (1600N)
Housing NEMA 2, IP54 with cable entry down Position Indication Stroke indicator on yoke
Housing Material UL 94-5V (flammability rating) Manual Override 3/16" hex, 5mm hex or phillips screwdriver
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-518-US 08.07
© Spirax Sarco, Inc. 2006
120
Installation and Wiring Dimensions and Weights
Control
Valves
The valves should be installed in the horizontal line. Allow 6" for the Weight 4lb (1.8kg)
cover removal and 16" for complete actuator removal. These actua- Dimensions See below
tors should never be mounted underneath the valve as condensation
can build up and result in a failure of the actuator. Full instructions are
supplied with the product. 7.05" [179mm] 4.35" [110mm]
24 VAC Transformer
Actuators
Linear
Line Blk (1) Common -
Volts Red (2) + Hot
Wht (3) Y 1 Input, 2 to 10V
2 to 10 VDC (-)
Control Signal (+) Wht (5) U Output, 2 to 10V
11.0" [279.4mm]
2 to 10 VDC (-)
Feedback Signal (+) NVF24-MFT-US
NVF24-MFT-E-US
24 VAC Transformer
500
4 to 20 mA (-) Wht (3) Y 1 Input, 2 to 10V
Control Signal (+)
2 to 10 VDC (-) Wht (5) U Output, 2 to 10V
Feedback Signal (+)
NVF24-MFT-US
NVF24-MFT-E-US
MFT typical 2 to 10 VDC or 4 to 20 mA wiring
Spares
No spare parts are available for this actuator range
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-518-US 08.07
121
Control
Valves
for
½" to 2" B Series and SPIRA-TROL L & K Series Control Valves
Description
The Belimo AF Series actuators are suitable for either two position
or modulating control. These actuators can be used with B Series or
SPIRA-TROL L and K Series control valves.
Multi-Function Technology (MFT) 2
An integrated microprocessor allows for a variety of parameters, in-
cluding control signal type, to be configured in the factory or the field
with a PC and Belimo software.
Manual Operation
A 5mm Allen wrench can be used to manually operate the actuator.
3
Turning the wrench clockwise will extend the spindle. Spindle posi-
tion will be retained until power is applied to the actuator.
Overload Protection
The actuator is protected against short circuiting and reverse polarity.
The spindle stroke is adapted automatically and is overload protected. 1
Operational Display
The stroke is physically shown by a travel indicator on the actuator yoke.
Spares
No spare parts are available for this actuator range 1
A5"
122
Installation and Wiring 24 VAC Transformer Master
Control
Valves
The valves should be installed in the horizontal line. Allow 6" for the Blk (1) Common
Line
cover removal and 12" for complete actuator removal. These actua- Volts Red (2) + Hot
tors should never be mounted underneath the valve as condensation Ω
can build up and result in a failure of the actuator. Full instructions Control Signal (-)
are supplied with the product. The diagram below shows the wiring 2 to 10 VDC or Wht (3) Y1 Input, 2 to 10V
schematic. For AFB-MFT-US actuators, connect as shown in the (+) 4 to 20 mA Wht (5) U Output, 2 to 10V
'Master' schematic. For 2 x AFB-MFT-US actuators, one actuator CCW (L) CW (R)
Actuators
AFB24-MFT-US
motor should be connected as a 'Master' and the other as a 'Slave'
Linear
unit, as shown in the schematic.
Slave
Blk (1) Common
Note: Due to temperature capability limitations, maximum saturated Wht (3) Y1 Input, 2 to 10V
steam inlet pressure is 100 psig. For reduced capacity valves, use the Wht (5) U
differential pressures for the next valve size down.
CCW (L) CW (R)
AFB24-MFT-US
B Series 2-Way and 3-Way Control Valves
ANSI/FCI 70-2 Class IV Shut-off (metal seated trim) for 2-way valves
and Class III for 3-way (mixing) valves Note: Please contact Belimo for other wiring information.
Class VI Shut-Off
Theoretical Maximum Differential Pressure (psi)
Model Thrust (N) ½" ¾" 1" 1 - ¼" 1 - ½" 2"
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
AFB24-MFT 1383 725 703 725 555 485 371 376 287 162 123 115 88
2xAFB24-MFT 2063 725 725 725 725 725 630 576 488 249 210 177 150
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-519-US 8.13
123
Control
Valves
AEL5 Series
Actuators
Linear
Mounting flange
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P358-25-US 1.14
124
AEL5 Series
Control
Valves
Electric Linear Actuators
for ½" to 4" Control Valves
Technical data
Actuators
Linear
Actuator type AEL51_ AEL52_ AEL53_ AEL54_ AEL55_ AEL56_
Supply voltage 230 Vac (2-wire single phase), 115 Vac, 24 Vac, (24 Vdc) ±10%
Actuator thrust lbf (kN) 225 (1kN) 450 (2kN) 1,011 (4.5kN) 1,798 (8kN) 3,147 (14kN) 5,620 (25kN)
Ambient limits -4°F to 140°F (Caution: -4°F to 122°F with positioner card fitted)
Synchronous motor for 225 lbf to 3147 lbf Asynchronous motor for 5620 lbf (Alternative current) or
Motor
Brushed direct current motor (Direct current)
Terminations 1.5 mm²
Conduit entries 2 x M20 x 1.5 (for 225 to 3147 lbf) and 3 x M20 x 1.5 (for 5620 lbf)
Positioner power
1
consumption VA
For alternative speed versions please contact Spirax Sarco
Approvals
This equipment is CE marked and conforms to the following:
- EN 50081-1 and EN 50082-2 (EMC)
- EN 61010-1/A2 (Safety), following the provisions of directives 89 / 336 / EEC amended by 92 / 31 / EEC and 93 / 68 / EEC (EMC) and
72 / 73 / EEC amended by 93 / 68 / EEC (LVD).
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-25-US 1.14
125
AEL5 Series
Control
Voltage
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
AEL51211 230 580 432 507 340 333 228 261 174 115 75 81 54 44 17 28 10 17 6
AEL51212 115 580 432 507 340 333 228 261 174 115 75 81 54 44 17 28 10 17 6
AEL51213 24 580 432 507 340 333 228 261 174 115 75 81 54 44 17 28 10 17 6
AEL52211 230 580 580 580 561 471 242 203 173 145 94 68 59 44 38 26
AEL52212 115 580 580 580 561 471 242 203 173 145 94 68 59 44 38 26
AEL52213 24 580 580 580 561 471 242 203 173 145 94 68 59 44 38 26
AEL53211 230 580 580 563 522 400 373 222 196 142 125 88 78
AEL53212 115 580 580 563 522 400 373 222 196 142 125 88 78
AEL53213 24 580 580 563 522 400 373 222 196 142 125 88 78
AEL54211 230 580 580 580 402 376 257 232 160 149
AEL54212 115 580 580 580 402 376 257 232 160 149
AEL54213 24 580 580 580 402 376 257 232 160 149
AEL55311 230 580 580 454 438 283 273
AEL55312 115 580 580 454 438 283 273
AEL55313 24 580 580 454 438 283 273
AEL56411 230 580 580 508 497
AEL56412 115 580 580 508 497
AEL56413 24 580 580 508 497
Voltage
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
TI-P358-25-US 1.14
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
126
AEL5 Series
Control
Valves
Electric Linear Actuators
for ½" to 4" Control Valves
Maximum differential pressures for class IV shut-off -
KEA and LEA 2-port valves
Actuators
Linear
with PTFE or Graphite stem seal
Valve size 1/2” 3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4”
Cv 5.0 7.5 12 16 30 45 75 120 190
Valve travel ¾" 13/16"
Maximum differential pressure psi
Actuator
Voltage
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
AEL51211 230 431 215 319 145 174 69 149 61 38 17
AEL51212 115 431 215 319 145 174 69 149 61 38 17
AEL51213 24 431 215 319 145 174 69 149 61 38 17
AEL52211 230 580 580 566 461 445 348 165 128 109 81 46 20 21.8 4
AEL52212 115 580 580 566 461 445 348 165 128 109 81 46 20 21.8 4
AEL52213 24 580 580 566 461 445 348 165 128 109 81 46 20 21.8 4
AEL53211 230 580 580 580 486 447 336 309 174 148 103 87 58 48
AEL53212 115 580 580 580 486 447 336 309 174 148 103 87 58 48
AEL53213 24 580 580 580 486 447 336 309 174 148 103 87 58 48
AEL54211 230 580 580 580 354 328 218 189 129 116
AEL54212 115 580 580 580 354 328 218 189 129 116
AEL54213 24 580 580 580 354 328 218 189 129 116
AEL55311 230 580 580 580 416 399 252 242
AEL55312 115 580 580 580 416 399 252 242
AEL55313 24 580 580 580 416 399 252 242
AEL56411 230 580 580 477 464
AEL56412 115 580 580 477 464
AEL56413 24 580 580 477 464
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Actuator Voltage
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
AEL52211 230 70 33
AEL52212 115 70 33
AEL52213 24 70 33
AEL53211 230 580 580 580 580 278 241 187 160 57 31 26 10 9
AEL53212 115 580 580 580 580 278 241 187 160 57 31 26 10 9
AEL53213 24 580 580 580 580 278 241 187 160 57 31 26 10 9
AEL54211 230 580 580 506 479 236 210 142 125 80 70
AEL54212 115 580 580 506 479 236 210 142 125 80 70
AEL54213 24 580 580 506 479 236 210 142 125 80 70
AEL55311 230 580 580 545 363 339 322 204 193
AEL55312 115 580 580 545 363 339 322 204 193
AEL55313 24 580 580 545 363 339 322 204 193
AEL56411 230 580 580 428 418
AEL56412 115 580 580 428 418
AEL56413 24 580 580 428 418
TI-P358-25-US 1.14
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
127
AEL5 Series
Control
Voltage
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
AEL51211 230 580 431 508 336 334 225 261 173 112 74 80 52 42 16
AEL51212 115 580 431 508 336 334 225 261 173 112 74 80 52 42 16
AEL51213 24 580 431 508 336 334 225 261 173 112 74 80 52 42 16
AEL52211 230 580 580 580 557 468 241 202 160 144 93 67 59 42 36 26
AEL52212 115 580 580 580 557 468 241 202 160 144 93 67 59 42 36 26
AEL52213 24 580 580 580 557 468 241 202 160 144 93 67 59 42 36 26
AEL53211 230 580 580 560 521 392 371 220 194 141 125 87 77
AEL53212 115 580 580 560 521 392 371 220 194 141 125 87 77
AEL53213 24 580 580 560 521 392 371 220 194 141 125 87 77
AEL54211 230 580 580 580 400 374 255 239 160 148
AEL54212 115 580 580 580 400 374 255 239 160 148
AEL54213 24 580 580 580 400 374 255 239 160 148
AEL55311 230 580 580 454 437 283 273
AEL55312 115 580 580 454 437 283 273
AEL55313 24 580 580 454 437 283 273
AEL56411 230 580 580 580
AEL56412 115 580 580 580
AEL56413 24 580 580 580
Voltage
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
128
AEL5 Series
Control
Valves
Electric Linear Actuators
for ½" to 4" Control Valves
Maximum differential pressures for modulating duties only
QL 3-port valves
Actuators
Linear
with PTFE or Graphite stem seal
Valve size 1/2” 3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4”
Cv 4.6 7.3 11.6 18.6 29 41.8 73.1 116 185.6
Valve travel ¾" 13/16"
Maximum differential pressure psi
Actuator
Voltage
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
Graphite
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
PTFE
AEL51211 230 386 174 386 174 222 93 133 54 81 29 46 14 16 6 1.5
AEL51212 115 386 174 386 174 222 93 133 54 81 29 46 14 16 6 1.5
AEL51213 24 386 174 386 174 222 93 133 54 81 29 46 14 16 6 1.5
AEL52211 230 580 574 580 574 466 336 283 203 178 128 107 75 54 33 33 19 16 9
AEL52212 115 580 574 580 574 466 336 283 203 178 128 107 75 54 33 33 19 16 9
AEL52213 24 580 574 580 574 466 336 283 203 178 128 107 75 54 33 33 19 16 9
AEL53211 230 580 580 580 580 423 373 260 228 149 129 102 87 54 46
AEL53212 115 580 580 580 580 423 373 260 228 149 129 102 87 54 46
AEL53213 24 580 580 580 580 423 373 260 228 149 129 102 87 54 46
AEL54211 230 580 473 439 284 264 196 181 107 100
AEL54212 115 580 473 439 284 264 196 181 107 100
AEL54213 24 580 473 439 284 264 196 181 107 100
AEL55311 230 580 438 418 303 290 168 161
AEL55312 115 580 438 418 303 290 168 161
AEL55313 24 580 438 418 303 290 168 161
AEL56411 230 580 580 367 358
AEL56412 115 580 580 367 358
AEL56413 24 580 580 367 358
TI-P358-25-US 1.14
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
129
AEL5 Series
Control
Valves
Disposal
This product is recyclable. No ecological hazard is anticipated with the disposal of this product, providing due care is taken.
Selection example
Control valve ¾" LEA43 PTSUSS.2 Cv 7.5 Flanged ANSI 150
Maximum ∆P 290 psi
Electrical supply 230 Vac
Control signal 4 - 20 mA
Actuator selected AEL51211
Positioner required AEL5961
Valve adaptor AEL6911
Mounting flange EL5970
How to order
Product A = Actuator A
Type E = Electric E
Movement L = Linear L
Series 5 5
1 = 225 lbf (1kN)
2 = 450 lbf (2kN)
3 = 1,011 lbf (4kN)
Thrust lbf (kN) 1
4 = 1,798 lbf (8kN)
5 = 3,147 lbf (14kN)
6 = 5,620 lbf (25kN)
2 = 1" (50mm) (AEL51_, AEL52_, AEL53_ and AEL54_ series only)
Stroke in (mm) 3 = 2½" (65mm) (AEL55_ series only) 2
4 = 4" (100mm) (AEL56_ series only)
Maximum speed (mm/s) 1 = 0 - 0.4 in/sec 1
1 = 230 Vac (2-wire, single phase)
2 = 115 Vac
Supply voltage 1
3 = 24 Vac
4 = 24 Vdc (not available for AEL56_)
F = Integral 24 V VMD (only for actuators with 24 V supply voltage)
Control signal* G = Integral 115 V VMD (only for actuators with 115 V supply voltage) J
J = Integral 230 V VMD (only for actuators with 230 V supply voltage)
Failure mode X = No mechanical / electrical fail safe device X
A = With 1 k Ω potentiometer
Potentiometer A
S = Without
* For 0 / 2 - 10 Vdc and 0 / 4 - 20 mA modulating control signal the appropriate positioner card must be ordered at time of order.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-25-US 1.14
130
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
131
Control
Valves
Accessories
Actuators
Linear
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P358-28-US 1.14
132
Accessories
Control
Valves
for the AEL5 Series
of Electric Linear Actuators
Wiring diagrams (Note: X0, X4, X5, X6, X8 and X9 refer to termination board location)
Actuators
Linear
AEL5951 auxiliary switches AEL5952 feedback ptentiometer and
AEL5953 1st output from tandem potentiometer
X6
1 2 3 4 5 6 X4 16 14 15
X11 1 2 3
Extend position
Retract Extend
switch switch
Retract position
X0 1 2 3
Extend
position
Retract
position
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-28-US 1.14
133
Accessories
Control
Valves
x5 / 1
Power Supply
(Phase and Neutral)
x5 / 4
x5 / 2
Feedback position
x4 / 1
x4 / 2
x4 / 3
+
4 - 20 mA
-
2 - 10 V
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-28-US 1.14
134
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
135
Control
Valves
Available types
The actuators are available with 3 supply variants. 230 Vac,115 Vac and
24 Vac. The standard version is suitable for VMD (Valve Motor Drive)
input power signal. If required the actuator can be fitted with a position-
er input card that can accept 4 - 20 mA or 2 - 10 Vdc control signals.
The actuators are fitted as standard with 1kΩ potentiometer. This
can either be used in conjunction with the positioner for 2 - 10 V or
4-20 mA input signals, or as feedback for VMD. Also available are
auxiliary limit switches and anti-condense heater. See TI-P358-06 US 2
for futher details on the accessories.
These actuators can be used with the SPIRA-TROL valve range with
an appropriate valve adaptor and mounting flange.
Technical data
Model EL560_ EL561_ EL562_ EL563_ EL564_ EL565_
Supply voltage 230 Vac / 115 Vac / 24 Vac + 10%
Supply frequency Hz 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
53 / 53
Power consumption VA* 9.2 / 10.4 10.9 / 12.6 25 /27 (24 V supply 78 / 78 142 / 142
is 36 VA)
Enclosure rating I P65 (For outdoor installations provide adequate shelter)
Actuator speed mm/s 0.25 0.5 0.5 0.5 0.6 1.0
Actuator thrust maximum .738 ft.lbs (1kN) 1.47 ft.lbs (2kN) 3.3 ft.lbs (4.5 kN) 5.9 ft.lbs (8kN) 8.8 ft.lbs (12kN) 18.4 ft. lbs (25kN)
Ambient limits - 4° to 140°F (-20 to + 60°C) -4° to 120°F (-20 to +50°C) with positioner card fitted
Motor Asynchronous capacitor reversing motor
Terminations 1.5 mm 2
Manual Handwheel
Conduit entries 2 x PG13 3 x PG16
Positioner power consumption 1.0 VA
* Power consumption is relative to 50 / 60 Hz respectively.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P358-07-US 08.11
136
EL5600 Series Electric Actuator
Control
Valves
for 1/2" to 4" K & L Series Valves
Approvals
This equipment is CE marked, and conforms to EN 50081-1 and EN 50082-2 (EMC), EN 61010-1/A2 (Safety), following the provisions of directives
89/336/EEC amended by 92/31/EEC and 93/68/EEC (EMC) amended by 93/68/EEC (LVD).
Class IV Shut-off
Actuators
Linear
PTFE and Graphite Stem Seals
Maximum Differential Pressures (psi)
Actuator ½" ¾" 1" 1¼" 1½" 2" 2½" 3" 4"
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
EL5601-2-3 432 215 319 149 185 71 150 61 39 18
EL5611-2-3 740 740 740 718 567 452 445 357 167 128 109 81 47 20 22 5 7
EL5621-2-3 740 740 740 740 740 486 448 337 309 175 149 104 87 58 48
EL5631-2-3 740 470 656 628 354 328 219 202 130 120
EL5641-2-3 740 740 559 533 350 334 212 201
EL5651-2-3 740 740 740 740 478 467
Class VI Shut-off
PTFE and Graphite Stem Seals
Maximum Differential Pressures (psi)
Actuator ½" ¾" 1" 1¼" 1½" 2" 2½" 3" 4"
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
EL5601-2-3 644 427 508 337 339 225 262 174 113 74 80 53 42 16 27 10 16
EL5611-2-3 740 740 740 740 721 606 558 469 241 202 171 144 93 67 60 43 37 26
EL5621-2-3 740 740 740 740 560 522 399 372 222 194 142 125 88 78
EL5631-2-3 740 470 718 691 401 375 256 240 160 149
EL5641-2-3 740 740 606 580 388 371 241 231
EL5651-2-3 740 740 740 740 507 497
Class IV Shut-off
Bellows Stem Seals with PTFE and Graphite Secondary Packing
Maximum Differential Pressures (psi)
Actuator ½" ¾" 1" 1¼" 1½" 2" 2½" 3" 4"
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
EL5601-2-3
EL5611-2-3 71 35
EL5621-2-3 740 740 740 740 740 740 717 629 279 241 187 160 57 31 27 11
EL5631-2-3 740 740 727 688 506 479 237 211 142 126 81 71
EL5641-2-3 740 740 740 740 442 413 274 257 163 152
EL5651-2-3 740 740 700 684 429 418
Class VI Shut-off
Bellows Stem Seals with PTFE and Graphite Secondary Packing
Maximum Differential Pressures (psi)
Actuator ½" ¾" 1" 1¼" 1½" 2" 2½" 3" 4"
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
EL5601-2-3
EL5611-2-3 283 67 223 52 149 34 115 26 49 10 35
EL5621-2-3 740 740 740 740 740 740 740 740 368 330 262 235 114 88 73 56 45 35
EL5631-2-3 740 740 582 554 293 267 188 171 117 107
EL5641-2-3 740 740 499 472 319 302 199 188
EL5651-2-3 740 740 740 729 464 454
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-07-US 08.11
© Spirax Sarco, Inc. 2003
137
EL5600 Series Electric Actuator
Control
Valves
B
Selection example C
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-07-US 08.11
138
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
139
Control
Valves
Actuators
Description
The EL5600 series electric actuators are reversible having linear output.
Available types
The actuators are available with 3 supply variants, 230 Vac, 115 Vac and Engage button
24 Vac. The standard version is suitable for VMD (Value Motor Drive) input for handwheel
power signal. If required the actuator can be fitted with a positioner input
card that can accept (4 - 20 mA or 2 - 10 Vdc) control signals. All the
actuators are fitted as standard with 1 kΩ potentiometer.
This can either be used in conjunction with the positioner for 2 - 10 V or 4
- 20 mA input signals, or as feedback for VMD. Also available are auxiliary
limit switches and anti-condense heater. See TI-P358-06 US for further
details on the accessories.
These actuators can be used with the following valves, in conjuntion with
a mounting flange 3581527 and valve adaptor EL5955.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P358-09-US 08.11
140
EL5650 Series Electric Actuators
Control
Valves
6" to 8" Spira-Trol Valves
Maximum differential pressures for Class IV shut off
Unbalanced Flow Under
Actuators
KE and KEA (PTFE or Graphite stem seal)
Linear
6" 8"
Actuator
PTFE Graphite PTFE Graphite
EL5651-2-3 130 116 58 58
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-09-US 08.11
141
EL5650 Series Electric Actuators
Control
Valves
31.75"
(807)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-09-US 08.11
© Spirax Sarco, Inc. 2003
142
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
143
Control
Valves
Actuators
Linear
Positioner card
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P358-06-US 09.03
© Spirax Sarco, Inc. 2003
144
Accessories for EL5600 Series Actuator
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-06-US 09.03
145
Control
Valves
AEL6 Series
Actuators
Linear
2
2
1
1
Description
The AEL6 series electric actuators are reversible having linear output.
Available types 2
The actuators are available with 4 supply variants: 230 Vac (2-wire, 2
single phase), 115 Vac, 24 Vac and 24 Vdc. The standard version is
available for VMD
(Valve Motor Drive), 0 / 4 - 20 mA or 0 / 2 - 10 Vdc input control
signals. These actuators can be used with the following valves, in 3
conjunction with an appropriate valve adaptor and mounting flange: 3
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P358-23-US 1.14
146
AEL6 Series
Control
Valves
Smart Electric Actuators
for ½" to 4" Control Valves
Technical data
Actuator type AEL6221_ AEL6321__ AEL6323_ AEL6421_ AEL6422_ AEL6532_ AEL6631_
Actuators
Linear
Supply voltage 230 Vac (2-wire, single phase), 115 Vac, 24 Vac, 24 Vdc
Supply frequency 50 Hz / 60 Hz / continuous
Maximal power consumption VA Note: power
consumption is relative to 50 / 60 Hz / con- 13 19 57 25 72 65 88
tinuous respectively
Stroke (mm) inches 2 (50) 2 (50) 2 (50) 2 (50) 2 (50) 2½ (65) 21/3 (60 *)
Actuator speed mm/s Note: Speed is relative
0.9 0.9 4.5 0.7 1.7 1.3 0.4
to 50 / 60 Hz / continuous respectively
Enclosure rating IP65 (for outdoor installations adequate shelter)
Actuator thrust (kN) lbf 517 (2.3) 1,012 (4.5) 1,012 (4.5) 1,798 (8) 1,798 (8) 3,147 (14) 5,620 (25)
Ambient limits -4°F to 140°F (-20°C to 60°C)
Analog position set valve input Adjustable: 0 / 4 - 20 mA or 0 / 2 - 10 Vdc
Positioner function Dead-band ajustable between 0.5 - 5% of set value range, maximum resolution 0.1 mA or
0.05 V at 2" (50 mm) stroke
Active valve position feedback Adjustable: 0 / 4 - 20 mA or 0 / 2 - 10 Vdc
Automatic commissioning Drives to torque dependant stop(s) and moves throught the whole valve travel. Autoscale of
set value and feedback in accordance to valve travel
Characteristic curve correction Up to 16 interpolation points, input inccuracy 1%
Torque increase Adjustable up to 150% torque for up to 2.5s to break away a valve in the end position
Status indication 2 LEDs under actuator cover
Internal fault monitoring Torque, position set value, active value, position, temperature of electonic board
Diagnostics function Stores cumulated operation data (motor and total running time, number of motor starts) and
data sets of current values (set value, feedback value, torque, temperature)
*Notes:
1. 115 Vac and 230 Vac models of the AEL6631_ have a stroke limited to 21/3 (60 mm).
2. 24 Vac and 24 Vdc models of the AEL6631_ are capable of up to 4" (100 mm) stroke.
Optional extras:
- Additional position switches - AEL6951 (NC) and AEL6952 (NO)
- Local control - (non retrofitable for the AEL66_) - AEL6955 (2.3 to 14 kN) and AEL6956 (25 kN)
- Fault indicator relay - AEL6973
- Communication software including data cable - AEL6957
- Space heater - AEL6953 (24 Vac) and AEL6954 (115 Vac and 230 Vac)
Approvals
This equipment is CE marked and conforms to the following:
- EEC regulation 89 / 336 - EEC for Electromagnetical compatibility and 72 / 23 - EEC for low voltage directive.
- EN 61000 - 2 -2 / 2001 and EN 61000 - 6 - 4 for EMC, and 61010 - 1 / 1995 for safety.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-23-US 1.14
147
AEL6 Series
Control
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
Travel (mm) 20 20 20 20 20 20 20 20 20 20 20 20 30 30 30 30 30 30
Seat area
201 201 254 254 380 380 491 491 1134 1134 1590 1590 2827 2827 4418 4418 7088 7088
(mm2)
Seat
circumference 50 50 57 57 69 69 79 79 119 119 141 141 188 188 236 236 298 298
(mm)
Stem diameter
(mm)
Stem pressure
area (mm2)
Recommended
pinch for Class
6000 6000 6000 6000 6000 6000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000
IV shut-off
(N/m)
Required
seating thrust 302 302 339 339 415 415 393 393 597 597 707 707 942 942 1178 1178 1492 1492
(N)
Static gland
packing 100 400 100 400 100 400 100 400 100 400 100 400 150 660 150 660 150 660
friction
Bellows Seal
1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 2100 2100 2100 2100 2100 2100
(N)
Total thrust
needed to 402 702 439 739 515 815 493 793 697 997 807 1107 1092 1602 1328 1838 1642 2152
close valve (N)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-23-US 1.14
148
AEL6 Series
Control
Valves
Smart Electric Actuators
for ½" to 4" Control Valves
Maximum differential pressures for Class VI shut-off (soft seal)
Valve size ½" ¾" 1" 1¼" 1½" 2" 2½" 3" 4"
Actuators
Linear
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
Travel (mm) 20 20 20 20 20 20 20 20 20 20 20 20 30 30 30 30 30 30
Seat area
201 201 254 254 380 380 491 491 1134 1134 1590 1590 2827 2827 4418 4418 7088 7088
(mm2)
Seat
circumference 50 50 57 57 69 69 79 79 119 119 141 141 188 188 236 236 298 298
(mm)
Stem diameter
(mm)
Stem pressure
area (mm2)
Recommended
pinch for Class
150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
IV shut-off
(N/m)
Required
seating thrust 8 8 8 8 10 10 12 12 18 18 21 21 28 28 35 35 45 45
(N)
Static gland
packing 100 400 100 400 100 400 100 400 100 400 100 400 150 660 150 660 150 660
friction
Bellows Seal
1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 2100 2100 2100 2100 2100 2100
(N)
Total thrust
needed to 108 408 108 408 110 410 112 412 118 418 121 421 178 688 185 695 195 705
close valve (N)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-23-US 1.14
149
AEL6 Series
Control
Mounting Position
B
C
90° 90°
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-23-US 1.14
150
AEL6 Series
Control
Valves
Smart Electric Actuators
for ½" to 4" Control Valves
AEL6 series actuators - Product nomenclature and selection example:
Actuators
Linear
Product A = Actuator A
Type E = Electric E
Movement L = Linear L
Series 6 6
2 = 517 (2.3)
3 = 1,102 (4.5)
Thrust
lbf (kN) 4 = 1,798 (8) 2
5 = 3,147 (14)
6 = 5,620 (25)
Selection:
1 off Spirax Sarco AEL6221-2PS electric actuator.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P358-23-US 1.14
151
Control
Valves
Actuators
Features
Fast travel speed – the actuator can open or close a valve between 3
seconds for ¾” travel valve and 20 seconds for a 2” travel valve.
Multiple control signal options - the standard actuator operates on Technical information
a 4-20mA signal and provides 4-20mA position feedback (an auxiliary
24V d/c supply is required to drive this loop). Options are available to Linearity (4-20mA signal) ≥0.5% full scale
allow interfacing with HART®, Profibus or Foundation Fieldbus network
control. Resolution (4-20mA signal) ≥0.1% of signal
Status indication relay – a user configurable relay is available for Signal voltage drop 7 V @ 20 mA
status and availability indication. This can be configured to indicate a
number of parameters. Duty rating S9 (continuous modulation)
Valve diagnostics – a data-logger is provided which helps detect poten- Ambient temperature Standard -22°F to 158°F
tial valve problems before they occur. It stores operational data relating
Low temp. (option) -40°F to 140°F
to the valve position and load which can be monitored over time.
Enclosure Standard NEMA 4&6, IP68
Dual Sensor™ technology – two independent position sensors mini-
mize backlash and positional errors. Haz. Area (option) Class I, Div 1, Groups B,C,D
Class II, Div 1, Groups E,F,G
Brushless DC motor – highly reliable, maintenance free and provides
full, continuous, unrestricted modulation duty (S9). Finish Polyester powder coated
Power supply flexibility – Incorporated within each AC actuator is a Status relay Single pole, normally open, 8A/120VAC/30VDC
switch mode power supply, which can accept a range of input volt-
ages from 100-240 VAC 50/60 Hz. An optional 24 VDC supply can be Power consumption Stationary 4.7W @ 110 VAC
catered for.
Full load 32.1W @ 110 VAC
Reserve power - For fail-to-position action on loss of supply, the actu- Peak 58.2W @ 110 VAC
ator can be fitted with an optional reserve power-pack, which consists
of ‘super capacitors’. The reserve power-pack will allow the actuator Model Min. Rated Max. Spindle Full stroke
to move to a predetermined position on power failure. thrust thrust stroke speed time*
(lb.f) (lb.f) (inches) (inches/sec) (sec)
Drive-train – simple yet durable spur gear drive, lubricated for life with
proven durability. CVL500 200 500 1.5 0.25 6
CVL1000 400 1000 2 0.1 20
Anti Back Drive Mechanism – the actuator is capable of resisting any
CVL1500 600 1500 2 0.1 20
back drive from the valve up to 125% of the rated force. For applica-
tions where loss of power requires increased “fail-in-position” capabil- * Time shown is for the maximum actuator stroke. This time is reduced
further for valves with a shorter stroke e.g. A ½" SPIRA-TROL has a stroke
ity, an optional solenoid locking mechanism is available.
of ¾", when fitted with a CVL500 it will open or close in 3 seconds.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-523-US 12.09
152
Rotork CVL Electric Actuators For
Control
Valves
SPIRA-TROL Control Valves
Differential Pressures for SPIRA-TROL Control Valves with Rotork CVL Electric Actuators
Class IV Shut-off
Actuators
Linear
PTFE and Graphite Stem Seals
Maximum Differential Pressures (psi)
Actuator 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4”
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
CVL500 740 740 740 740 652 538 511 423 195 157 129 102 58 32 29 13 12
CVL1000 740 740 740 740 480 441 332 305 172 146 102 86 57 47
CVL1500 740 740 740 726 535 507 286 260 175 159 103 92
Class VI Shut-off
PTFE and Graphite Stem Seals
Maximum Differential Pressure (psi)
Actuator 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4”
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
CVL500 740 740 740 740 740 692 624 535 269 231 192 164 105 79 67 50 42 31
CVL1000 740 740 740 740 554 515 394 367 219 193 140 123 87 77
CVL1500 740 740 740 740 597 570 333 307 213 196 133 122
Class IV Shut-off
Bellows Stem Seals with PTFE and Graphite Secondary Packing
Maximum Differential Pressure (psi)
Actuator 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4”
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
CVL500 233 16 162 80 45
CVL1000 740 740 740 740 740 740 702 613 273 234 182 155 55 29 26
CVL1500 740 740 740 740 557 519 385 358 169 143 99 82 54 43
Class VI Shut-off
Bellows Stem Seals with PTFE and Graphite Secondary Packing
Maximum Differential Pressure (psi)
Actuator 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4”
PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph PTFE Graph
CVL500 445 228 351 180 234 120 181 92 77 39 55 28
CVL1000 740 740 740 740 362 323 258 230 111 85 71 54 44 34
CVL1500 740 740 740 740 646 608 460 433 225 199 144 127 90 79
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-523-US 12.09
153
Rotork CVL Electric Actuators For
Control
Valves
Transmission L - Linear L up the actuator provided we are given the requirements at the time of
the order.
Size 500 – 500 lb.f (2,224 N) 500
1000 – 1,000 lb.f (4,448 N) Local configuration can be done using a Bluetooth enabled PDA/Smart-
1500 – 1,500 lb.f (6,672 N) phone running a windows O/S or a Bluetooth enabled PC. The Rotork
Enlight software must be installed and is available for free download
Power Supply Blank – 110/230 VAC from the Rotork website at www.rotork.com.
D – 24 VDC
Alternatively, if the HART option card is installed, a HART communica-
Control Signal Blank – 4-20 mA tor or PC with HART interface and software can be used.
H – 4-20 mA + HART H
F – Foundation Fieldbus
P – Profibus-PA Dimensions and weights (in and lb)
Valve
Back-up power Blank – Programmable fail-safe Actuator A B C D Weight
Size
S – Stay-put
CVL500 ½" to 4" 19.82 8.95 6.2 6.13 40
Manual over-ride Blank – None CVL1000 ½" to 4" 21.4 10.14 6.3 7.51 53
M – Manual Override (hand wheel) M CVL1500 ½" to 4" 21.4 10.14 6.3 7.51 53
C D B
¾" NPT
Conduit
Entry (4)
2.00
10.00
4.00 6.00
© Spirax Sarco, Inc. 2009
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-523-US 12.09
154
Control
Valves
Actuators
Linear
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
155
Control
Valves
Positioners
& Switches
B
Technical Data
Input signal range 3 - 15 psi (0.2 to 1 bar)
Output signal range 0 to 100% supply air pressure
Supply air pressure 20 to 90 psig (1.4 to 6 barg)
Stroke range .4 to 4" (10 to 100mm) D A
Amplification Adjustable
Hysterisis Less than 0.5%
Enclosure rating IP65
Steady State Air consumption 13.06 ft3/h at 90 psi (0.7m3/hr at 6 bar) Materials
Pneumatic connections 1/4" NPT Base plate and cover Die cast aluminum with
Ambient conditions -4° F to 250° F (-20 to 80°C) anti corrosive paint
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-610-US 1.14
156
PP5 Pneumatic Positioner
Control
Valves
Accessories 1.2"
A fixing kit is available to mount an air filter / regulator to the FK21 / FK28 fixing kit
pneumatic actuator.
Fixing kit Actuator type
Positioners
& Switches
FK21 PN9100 Series 1.6"
FK28 PN9200 or PN9300 Series
2.4"
Installation
Full details are contained in the appropriate Installation & Maintenance Instructions supplied with the product.
Gauge
block
connections
Gauge block
2"
51 mm
4"
100 mm Supply
Output to actuator
2"
51 mm
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-610-US 1.14
© Spirax Sarco, Inc. 2014
157
Control
Valves
Positioners
& Switches
Description
The EP5 is a 2-wire Positioner requiring a 4-20 mA input signal, and
is for use with linear pneumatic actuators. The positioner compares
the electrical signal from a controller with the valve position feedback, How To Specify
and varies a pneumatic output signal to the actuator accordingly. The 1- EP5 Electro pneumatic positioner.
valve position is therefore guaranteed for any controller output signal
and the effects of varying differential pressure, stem friction and dia-
phragm hysterisis are overcome. A mounting kit is supplied with each
positioner for mounting to either columns or yoke in accordance with
IEC60534-6-1 standards. Dimensions
(nominal) in inches and millimeters
The positioners can be used with the following actuators: A B C D E Weight
PN1000/2000, 3000/4000, 9000. 6.5 4.3 7.0 4.3 1.0 5.5 lb
165 110 175 110 30 2.8 kg
Technical Data E A
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-611-US 06.07
158
EP5 Electro Pneumatic Positioner
Control
Valves
ISP5 Intrinsically Safe E/P Positioner
Installation
Positioners
& Switches
Full details are contained in the appropriate Installation &
Maintenance Instructions supplied with the product.
output to actuator
Gauge block
2"
51 mm
4"
100 mm Supply
Output to actuator
2"
51 mm
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-611-US 06.07
© Spirax Sarco, Inc. 2004
159
Control
Valves
SP400
Positioners
& Switches
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P343-36-US 02.11
160
SP400 Electropneumatic Smart Positioner
Control
Valves
Dimensions (approximate) in inches F
A B C D E F G
5.7 4.4 4.1 1.6 4.3 1.2 6.8
Positioners
& Switches
Programmable functions
B E
Autostroke Automatic commissioning routine
Valve type 2-port or 3-port
Selectable 0 - 100% or 100% - 0%
% travel
depending on valve / actuator configuration
Control action Direct or reverse action (4-20 or 20-4 mA)
OFF range 4-20 mA A D
Split range Low range 4-13 mA
High range 11-20 mA Centre bolt for 'U' bolts for pillar
0.5% yoke mounted mounted actuators
1.5% actuators
Deadband
3.0%
5.0%
Reset Resets all programmed values
Input signal Visualisation of input mA signal
Available spares
G
Pressure gauge only
Pressure gauge Available ranges:
0 to 30 psig, 0 to 60 psig or 0 to 100 psig
C
Filter plug kit Plug plus 3 off filters and 'O' rings
Approvals 0 = Standard 0
24 0 = Not mounted
V power supply 0
Remote sensor 0 = No 0
Extended stroke 0 = No 0
0
= Not mounted
G2 = Full scale 30 psig
Gauge block G4
G4 = Full scale 60 psig
G7 = Full scale 100 psig
How to order
Please include all the required optional extras as described on the first page.
Example: 1 off Spirax Sarco SP400 000 000 0G4 electropneumatic smart linear positioner equipped with gauge block for full scale
pressure of 60 psig.
Caution: The SP400 smart positioner must have a high quality air supply. A Spirax Sarco MPC2 filter regulator with coalescing filter
or equivalent must be used.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P343-36-US 02.11
161
Control
Valves
SP500
Positioners
& Switches
The SP500 smart valve positioner supports optional expansion to Technical data
include the HART® communication protocol, enabling complete con- Input signal range 4 - 20 mA nominal
figuration using a PC or handheld device.
Minimum input signal 3.4 mA
Air supply Standard 280 Ω
Input impedence
The SP500 smart positioner must be provided with a high With aux. power supply 50 Ω
quality air supply. A Spirax Sarco MPC2 filter regulator with Minimum air 15 psig above minimum
coalescing filter or equivalent must be used. A fixing kit is supply pressure spring range pressure
available to mount the MPC2 filter regulator onto the actuator.
For further product data regarding the MPC2 see Technical Maximum air supply pressure 100 psig
Information sheet TI-1-609-US. Air supply must be dry, oil and dust free
Air quality
to ISO 8573-1 class 2:3:1
Applications
Output pressure 0 to 100% supply pressure
The SP500 can be used with the following pneumatic actuators:
PN1000 and PN2000 series, PN9000 series, PM series, Linear valves ½" to 4"
Stroke range
PNS3000 and PNS4000 series, and the TN2277SE and TN2277SR Quarter turn valves 5° to 120°
Action Single action / fail vent
Optional extras Operating temperature 14°F to 176°F
Complete manifold block with two 2.5 cfm @ 20 psig
Maximum air flow
Gauge block two pressure gauges (supply pressure 5 cfm @ 90 psig
and pressure to the actuator Steady state air consumption Less than 0.01 scfm
Retransmission 4 - 20 mA valve position retransmission Air connections Screwed ¼" NPT
and switch board and 2 adjustable software switches
Cable gland M20
Allows 4 wire configuration:
Power supply 2 for 4 - 20 mA input signal and Spring clamp terminals for
Electrical connections
15 to 32 AWG
board 2 for independent 24 V power supply
reducing positioner impedance to 50 Ω Enclosure rating IP65
HART® board Enables communication using the HART®
Characteristics
Linear, Equal % (ratio 1:50) or
protocol Fast opening (ratio 50:1)
Resolution (maximum) 0.1% F.S. (Full Scale)
Materials
4 - 20 mA retransmission
Part Material Finish 4 - 20 mA retransmit (optional)
of valve position
Anti-corrosive paint to Software travel Two software configured 1 x normally closed
Case and cover Die cast aluminium
RAL5010 switches (optional) travel switches 1 x normally open
Magnet bracket Die cast aluminium
Shipping weight 4.85 lb
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P343-34-US 6.12
162
SP500 Electropneumatic Smart Positioner
Control
Valves
Programmable functions Dimensions (approximate) inches
Autostroke Automatic commissioning routine A B C D E F G
Valve type 2-port or 3-port 5.7 4.4 4.1 1.6 4.3 1.2 6.8
Selectable 0 - 100% or 100% - 0%
% travel
depending on valve / actuator configuration F
Positioners
& Switches
Control action Direct or reverse action (4-20 or 20-4 mA)
Travel limits Setting of minimum and maximum travel limits
Signal span 4-20 mA or split ranged (minimum span 4 mA)
Positional accuracy
Deadband
(minimum 0.2% to max. 10% of valve travel)
B E
Tight shut-off Fully vent or inflate at preset input signals
Linear, = % or fast opening
Characteristic
input signal to valve travel relationship
Travel time Slows down valve opening or closing
Software configured travel switch setting
Travel switches
(range 0 - 100%) A D
Reset Resets all programmed values
Calibrate Centering
Input signal Visualisation of input mA signal
Auto operation / vent Option of automatic operation or Centre bolt for 'U' bolts for pillar
vent (actuator) whilst reprogramming yoke mounted mounted actuators
actuators
Data logging Diagnostic record of total number of valve
strokes and completed hours run time.
Available spares
Pressure gauge only
Pressure gauge Available ranges:
0 to 30 psig, 0 to 60 psig, 0 to 100 psig
Filter plug kit Plug plus 3 off filters and 'O' rings
Retransmission 4 - 20 mA valve position retransmission G
and switch board and 2 adjustable software switches
Allows 4 wire configuration: C
Power supply 2 for 4 - 20 mA input signal and
board 2 for independent 24 V power supply
reducing positioner impedance to 50 Ω
HART® board enables communication using the HART®
protocol
SP300
Pneumatic Positioner
Description
The SP300 series is a microprocessor based positioner range that
provides fast and accurate positioning of linear and rotary pneumatic
actuated control valves. The instrument produces a pneumatic pressure
output to accurately position the valve according to the input signal from
external controller (4÷20 mA) or from a bus network (Hart, Foundation
Fieldbus, Profibus PA).
SP300 are compact and easy to maintain and operate. Local calibra-
tion and parameter setting can be done without the need for external
devices.
Operation
Output Module (Fig. A)
The main parts of the output module are: pilot, servo, Hall effect sensor
and output control circuit.
The instrument CPU sends an electronic setpoint signal to the control
circuit. The control circuit receives an actual valve position feedback
signal from a Hall Effect sensor. By comparing the two signals the control
circuit applies a voltage to the baffle (piezo) for the right valve positioning. Rotary Magnet
The pneumatic section is based on the well known nozzle-baffle and
spool valve technology.
A piezoelectric disk is used as baffle in the pilot stage. The baffle is
deflected upon receiving the voltage according to the required position
change. A small variation of the air flow through the nozzle causes a
Linear
change of pressure in the pilot chamber (pilot pressure). Magnet
Because pilot pressure is too low, with no flow capacity, it has to be or
Rotary
therefore boosted. This is done in the servo section which acts as a Remote Magnet
Sensor
transducer. The servo section has one diaphragm in the pilot chamber, (optional)
and another smaller diaphragm in the spool chamber. The pilot pressure
applies a force to the pilot side diaphragm which, at steady state, will be
equal to the force that the spool valve applies to the smaller diaphragm.
When a change in position is required, pilot pressure increases or
decreases as explained for the pilot stage. A change in pilot pressure
forces the spool valve up or down changing the output 1 and the output
2 pressure until the desired position is reached.
Flow Piezo
restriction Baffle
Nozzle The mounting arrangement for linear actuators complies with IEC534-6
Fig A Pilot
Pilot Chambe The mounting arrangement for rotary actuators complies with VDI/
Magnetic Sensor Diaphragm
VDE3845
Spool
Disphragm The “Hall effect" sensor can be remotely mounted upto 65 ft from the
Vent 2 instrument. This is particularly useful for applications subject to high
Air Output 2 ambient temperatures or heavy vibration.
Supply Output 1
Spool Vent 1
Valve
Spring
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P370-19-US 6.07
164
SP300 Pneumatic Positioner
Control
Valves
Models & Protocols Common Technical Features
The communication protocols of all SP300 are industry standard, Functional Specifications
which means they are easily interfaced with the control system and Travel
therefore reduce installation and maintenance costs. Linear Motion: 1/8" (3 to 100 mm)
Rotary Motion: 3 to 120° Rotation angle
Output Signal
SP 301 4 to 20 mA + HART® Valve Positioner
Positioners
& Switches
Output to actuator 0 to 100 psig supply air pressure.
The SP301 microprocessor based pneumatic valve positioner
Single or double action.
operating in a current loop system. It produces a pressure output as
Pressure Supply
required to position a control valve according to a 4 to 20mA input 1.4 to 7 barg (20 to 100 psig).
signal. The communications of the SP301 are based on the HART® Free of oil, dust and water.
protocol. Indication
Calibration and setting of parameters can be carried out via local 41/2-digit LCD indicator and 5 alphanumeric characters.
adjustment or using portable equipment as a PDA with HART interface Hazardous Location Certification
or with a PC including HART® software. Explosion proof, weather proof and intrinsically safe from ATEX, CSA,
SP 302 Foundation Fieldbus Valve Positioner FM.
The SP302 is a Foundation Fieldbus device. It is a micro-
processor based pneumatic valve positioner operating in a Fieldbus Temperature Limits
system. Operation: -40 to 185°F (-40 to 85°C)
The SP302 produces a pressure output as required to position a con- Storage: -40 to 194°F (-40 to 90°C)
trol valve according to an input received over the Fieldbus network. Display: 14 to 140°F (-10 to 60°C) operation
Calibration and setting of parameters can be carried out via local -40 to 185°F (-40 to 85°C) without damage.
adjustment or using a remote configurator (es. Syscon) Humidity Limits Turn-on Time Update Time
0 to 100% RH. Approx. 10 seconds Approx. 0.2 seconds
Flow Characterization
SP 303 PROFIBUS PA Valve Positioner Linear, Equal Percentage, Quick Opening, 16 freely selectable points.
The SP303 is a Profibus PA device. It is a microprocessor based pneu- Through software or locally adjustable.
matic valve positioner operating in a Fieldbus system. Gain
The SP303 produces a pressure output as required to position a con- Through software or locally adjustable.
trol valve according to an input received over the Fieldbus network. Travel Time
Calibration and setting of parameters can be carried out via local Through software or locally adjustable.
adjustment or using a remote configurator (es. PDM Simatic) Actual Position Sensing
Magnet sensor (non contact) via Hall effect.
Specific Technical Features
SP 301
Communication Protocol HART® (is superimposed on the current
Performance Specifications
Sensitivity / Resolution Repeatability Hysteresis
signal)
Input Signal Two-wire, 4 to 20 mA controlled according to NAMUR < 0.1 % F.S. < 0.1 % F.S. < 0.1 %
NE43 Specification, with superimposed digital communication F.S. (Full Scale)
(HART® Protocol) Consumption
Power Supplied by the 4 to 20 mA current. No external supply 0.25 Nm3/h (0.15 SCFM) at 1.4 barg (20 psig) supply.
required. 0.70 Nm3/h (0.40 SCFM) at 5.6 barg (80 psig) supply.
Voltage drop 11 Vdc max / 20 mA (equivalent to 550 W) Output Capacity
Mininum current 3.8 mA 46.7 Nm3/h (28 SCFM) at 5.6 barg (80 psig) supply.
Reverse Polarity Protection Is provided to prevent internal circuit Ambient Temperature Effect
damage in the event of reversal of the 4 to 20 mA supply signal. 0.8% / 20°C (68°F) of span.
SP 302 Supply Pressure Effect
Communication Protocol Foundation™ Fieldbus. Negligible.
Input Signal Digital only. Foundation™ Fieldbus, complies with IEC Vibration Effect
1158-2 (H1): 31.25 Kbit/s and voltage mode with bus power. ± 0.3% / g of span during the following conditions:
Voltage drop Bus powered: 9 to 32 Vdc. Quiscent current consump- 5 to 15 Hz at 4 mm (1/8") constant displacement;
tion 12 mA 15 to 150 Hz at 2g;
Function Blocs: 150 to 2000 Hz at 1g.
RES - Resource TRD - Transducer Reference SAMA PMC 31.1 1980, Sec. 5.3, Condition 3, Steady State.
DSP - Display transducer DIAG - Diagnostics Transducer
PID - PID Control EPID - Enhanced PID Electro-Magnet Interference Effect
AO - Analog Output ARTH - Arithmetic Designed to comply with IEC 61326: 2000.
INTG - Integrator ISEL - Input Selector
CHAR - Signal Characterizer SPLT - Splitter
AALM - Analog Alarm SPG - Set Ramp Generator Physical Specifications
TIME - Timer LLAG - Lead-Lag Electrical Connections 1/2" - 14 NPT, Pg 13,5 or M20 x 1,5.
OSDL - Output Selector / CT - Constant Pneumatic Connections Supply and output: 1/4" - 18 NPT.
Dynamic limiter Gauge: 1/8" 27 NPT.
SP 303 Material of construction
Communication Protocol PROFIBUS PA. Injected low copper aluminium with polyester painting or 316 stain-
Input Signal Digital only. PROFIBUS PA, commplies with IEC 1158-2 less steel housing, with Buna N ‘O’rings on cover (NEMA 4x, IP 67)
(H1): 31.25 Kbit/s and voltage mode with bus power.
Power Supply Bus powered: 9 to 32 Vdc / Quiescent current con- Weight
sumption 12mA. Without display and mounting bracket: Std. body 2.7 kg (6 lbs)
Output impedance (from 7.8 to 39 kHz). SS body 5.8 kg (12.8 lbs)
Function Blocs: PHY - Physical TRD - Transducer Add, for digital display: 0.1 kg (0.22 lbs)
DSP - Display AO - Analog Output
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P370-19-US 6.07
165
SP300
Control
Valves
Pneumatic Positioner
Local Display Drawing Configuration / Connection Diagram
all SP300 positioners are fitted with a digital in 4 : 20 mA + Hart Protocol
indicator that allows you to: Magnetic
Positioners
& Switches
Magnetic
Tool
Configuration Station Spur Spur
Dimensions Rotary
Magnet
Valve Positioner
Linear
Magnet
Travel Dimension A
Up to 15 mm 44 mm
Up to 30 mm 50 mm
Up to 50 mm 109 mm
Up to 100 mm 185 mm
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P370-19-US 5.06
166
SP300 Pneumatic Positioner
Control
Valves
SP30 Positioner with digital display
Sufffix Protocol
1 4 - 20 mA + Hart
2 Foundation Fieldbus
*3 Profibus PA
Suffix Bracket Mounting Kit **
Positioners
& Switches
0 Without kit
*1 With kit (bracket + magnet)
Suffix Electrical Connections
*0 1/2- 14 NPT
A M20 x 1,5
B PG 13,5 DIN
Suffix Type of Actuator **
*1 Rotary - Single Action
2 Rotary - Double Action
*3 Linear - Single Action
4 Linear - Double Action
5 Other Specify
Suffix Indication Gauge
0 Without Gauge
1 With Gauge - input
2 With Gauge - Output 1
*3 With 2 Gauges - input and Output 1
4 With 2 Gauges - Output 1 and 2
5 With 3 Gauges
Z Other Specify
Suffix Options
H1 316 SST Housing and body
R1 Remote sensor
I2 Explosion Proof (ATEX)
I4 Intrinsically Safe (ATEX)
J1 Tag on label
SZ Specify special application
KMS 3 2 I 000 Typical Kit model: Stainless Steel bracket for Spirax Sarco linear
valve - magnet for up to 30 mm valve stroke - Yoke & Pillar mounting,
right side, Stock Code 3700500
* Standard
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P370-19-US 5.06
167
Control
Valves
Positioners
& Switches
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
168
Control
Valves
Positioners
& Switches
IPC4A Convertor
Description
The IPC4A converter is a two wire, wall mounted, electropneumatic
converter requiring a standard 4-20 mA input signal to provide a
3 - 15 psi compressed air output signal.
The converter is compatible with Spirax Sarco linear pneumatic
actuators series PN5000 and PN6000 and the PP4 pneumatic
positioner.
Applications
The convertor can be used with the following actuators:
Actuator types PN5000 series
PN6000 series
Technical data
Input signal range 4-20 mA
Output signal range 3-15 psi
Supply air pressure Minimum 20 psi
Maximum 50.7 psig
Enclosure rating IP54
Air consumption .4 scfm (average)
Pneumatic connections 1/8" NPT
Electrical connections PG9
Working temperature 0 to 175° F
Input impedence 220 ohms
I Max 50 mA
Linearity 0.5%
Hysteresis 0.2% Safety information, installation and maintenance
Full details are contained in the appropriate Installation and
Maintenance Instructions supplied with the product.
Materials
Base plate Die cast aluminum with
anti corrosive paint
Cover Reinforced polymer (ABS) Air and electrical connections
Air connections 1/8" NPT
Electrical connection PG9
Dimensions (approximate) in inches and pounds
A B C Weight
3.0 6.0 3.3 2.0 lb
Wall or
Pipe Mounting
Conections
Board
Mounting Strips
B
(DIN track)
Electrical Connection
C A
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P343-07-US 1.14
169
Control
Valves
Positioners
& Switches
Temperature ˚C
100 37.8
50 10
0
0 20 40 60 80 100 120 140 160
(1.3) (2.7) (4.1) (5.5) (6.8) (8.2) (9.6) (11.03)
145
Pressure psig (barg) (10)
The product should not be used in shaded area.
Construction Materials C
No. Part Material
1 Body Aluminum
2 Body Finish Electrophoretic Epoxy
A
Internal and External
3 Bowl Polycarbonate
4 Bonnet Assembly Polycarbonate
5 Filter Element MicroFibre/Stainless Steel
6 Valve Nitrile
B
Pressure Gauge
1-1/2" gauge with face in psi and bar is supplied with each
MPC2.
Pressure Range: 0 to 100 psig (0 - 7 barg)
E
Dimensions Withdrawal Distance
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification.
TI-1-609-US 09.97
170
MPC2 High Efficiency Compressed Air
Control
Valves
Filter/Regulator
FK21 Fixing Kit
All MPC2’s come complete with FK21 Fixing Kits to allow Spare Parts
Positioners
& Switches
direct mounting onto the Spirax Sarco range of PN Pneumatic
Actuators.
G
H
Dimensions (nominal)
in inches and millimeters
E E F G H J
1.5 1.2 2.4 1.26 0.31
40.0 30.5 61.5 32.0 8.2
J
F
Performance Selection D
For any specified primary filtration pressure, there is a maxi-
mum recommended air flow rate. Keeping within this, will
ensure that the element performance maintains the stated high
efficiency levels, particularly for the removal of oil and water
C
contaminants.
Air flow scfm
0 1 2 3 4 5 6 7
7
100
6
80 A
Primary pressure barg
5
flow
d
4 de 60
en
m
3 c om
re 40
um
im
2 ax
M
20
1
0 0
0 1 2 3
Air flow dm3/s
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-1-609-US 09.97
© Spirax Sarco, Inc. 1997
171
Control
Valves
Positioners
& Switches
Description
The Stonel Limit Switch is for use with the K Series pneumatic control
valves and PN5000/6000 actuators. It is mounted on the PN5000/6000
actuators and can provide visual indication if the valve is fully open, fully
closed, partially open (0-100%) or partially closed (0-100%). By comparing
flow rates over time with your valve position, you can determine valve wear.
Technical Data
Model No. PQ5XE2R
Junction Features (1) 3/4" NPT and (1) 1/2" NPT conduit entries Installation
Full details are contained in the appropriate Installation & Maintenance
Visual Indicator OPEN - Green
Instructions supplied with the product.
CLOSED - Red
Enclosure Rating Factory Mutual and Canadian Standards
(Aluminum Cover) approved for:
Class I: Groups C &D. Divisions 1 and 2.
.625"
.75"
Class II: Groups E, F, G. Division 1.
Class II: Groups F & G. Division 2.
NEMA 4, 4X and 6
1.50"
Output Signal Two wire, 4-20mA 1/2" NPT* 3/4" NPT 1/2" NPT
Recommended Supply 24VDC, 50mA minimum 4.75"
Voltage Range 10 to 40 VDC at terminals
Maximum Loading 700 ohms @ 24 VDC
Sensors 2XSST Solid State Sensors
Electrical Ratings 0.3A @ 120VAC (continuous) .75" .75"
Temperature Range -40° to 180°F (-40° to 82°C) .27 Ø/2
.38"
Operating Life unlimited
3.25"
Construction Materials
Part Material
Cover Features Epoxy coated anodized aluminum cover
(optional clear Lexan cover)
O-Ring Seals Viton .156 Ø Pins/2 #6-32 Pan Head Screw
Shaft and Drive All materials are 303 or 316 stainless steel
Internal Fasteners Stainless Steel
* * The 1/2" Conduit Entry is
Located on the Left Side
of the 3/4" Conduit Entry
3.65"
.718"
6.0"
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-616-US 09.03
172
Control
Valves
Positioners
& Switches
Stonel Limit Switch
Description
The Stonel Limit Switch is for use with the K Series pneumatic control
valves and PN5000/6000 actuators. It is mounted on the PN5000/6000
actuators and can provide visual indication if the valve is fully open, fully
closed, partially open (0-100%) or partially closed (0-100%).
The Stonel Limit Switch has fully adjustable cams which allow the
switches to be set to be actuated at any desired valve travel.
Technical Data
Model No. PQ2SE2R
Function 2 switches
Switch Data 2x SPDT. Maxx-Guard LED Proximity switches
Junction Features (1) 3/4" NPT and (1) 1/2" NPT conduit entries
Visual Indicator OPEN - Green
CLOSED - Red
Enclosure Rating Factory Mutual and Canadian Standards
(Aluminum Cover) approved for: Installation
Class I: Groups C &D. Divisions 1 and 2. Full details are contained in the appropriate Installation & Maintenance
Class II: Groups E, F, G. Division 1. Instructions supplied with the product.
Class II: Groups F & G. Division 2.
NEMA 4, 4X and 6
Sensors SPDT
Electrical Ratings 0.3A @ 120VAC
Temperature Range -23° to 180°F (-40° to 82°C)
Seal Hermetically Sealed
Operating LIfe 5,000,000 cycles
.625"
.75"
Maximum Voltage 3.5 volts @ 10 mA
Drop 6.5 volts @ 100 mA
Minimum Current for
1.50"
LED Illumination 2.0 mA
1/2" NPT* 3/4" NPT 1/2" NPT
4.75"
Construction Materials
Part Material
Cover Features Epoxy coated anodized aluminum cover
(optional clear Lexan cover)
O-Ring Seals Viton .75" .75"
Shaft and Drive All materials are 303 or 316 stainless steel .27 Ø/2
Internal Fasteners Stainless Steel .38"
3.25"
.718"
3.65"
.718"
6.0"
.156 Ø Pins/2 #6-32 Pan Head Screw
* The 1/2" Conduit Entry is Located on the Left Side of the 3/4" Conduit Entry
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-1-617-US 09.03
173
Control
Valves
Trans. & Sensors
Controllers
Available Types
Temperature control
Model Control function Scale range
662-T5-M5* Proportional (+ Manual reset) 212°F
662-T5-M5 Proportional (+ Manual reset) 122 - 302°F
662-T5-M5* Proportional (+ Manual reset) 77 - 257°F
662-T5SY-M5 Proportional (+ Manual reset) 77 - 257°F
Pressure Control
622 Proportional (+ Manual reset) 0 - 102 psi
622 Proportional (+ Manual reset) 0 - 290 psi
Measuring elements
Pressure
Bourdon tube AISI 316L stainless steel
Connection NPT
Maximum pressure +25% of scale range
Temperature
Bulb and capillary AISI 316L stainless steel
- Cylindrical bulb for liquids
- Sanitary bulb for sterile applications
(Option available with spiral bulb for air /gas)
Bulb connection NPT
Capillary length 16.5 ft
32 ft (in some ranges)
(Other options available)
Max. measured temperature +25% of scale range
Pocket - Type W30S (optional)
Material AISI 316L Stainless steel
Connection NPT
Maximum pressure PN40
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P320-47-US 1.14
174
PN600 Series Pneumatic Controllers
Control
Valves
Technical data
Controller Sensor
Controllers
¾" NPT No groove on SY
Scale length 100mm sterile bulb
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P320-47-US 1.14
© Spirax Sarco, Inc. 1999
175
Control
Valves
Trans. & Sensors
SX80
Controllers
Process Controller
Description
The SX80 controller is a 1/16 DIN panel mounted unit, suitable for single and multiple set point applications utilising the Spirax Sarco
range of pneumatic or electric control valves and electrical and electropneumatic instruments. The SX80 has both VMD (3 point)
and analogue (4 - 20 mA) outputs in the same unit and features quick start codes for ease of commissioning.
SX80 features:
- Universal input - Resistance thermometers, thermocouples, mA and mV.
- Universal output - VMD (valve motor drive), mA and voltage for continuous, relay and logic for switching control.
- Auxiliary power supply - For external transmitter requiring 18 Vdc.
- Text messages - Scrolling text messages can be configured to alert the user to process conditions.
- Quick codes - 5-digit quick codes enable easy set-up and commissioning of the controllers.
Approvals
These controllers conform to the Council Directive 93 / 68 / EEC and the regulations on the essential protection requirements in Electrical
Apparatus EN 61010-1: 90
- EMC emissions specification: EN 61326-1: 1997 Class B (including amendments A1, A2 and A3).
- EMC immunity specification: EN 61326-1: 1997 Industrial locations (including amendments A1, A2 and A3).
176
SX80
Control
Process Controller
Valves
Technical data
Controllers
Mounting arrangement Panel mounted 1/16 DIN
Power supply 85 to 265 Vac, 6 W maximum
Electrical connections Screw connection terminal block
Panel sealing IP65 – plug in from front panel, NEMA 4X
Operating temperature / humidity 0 to 55°C, 5 to 85% RH
Atmospheres Not suitable for use in explosive or corrosive atmospheres
Electromagnetic compatibity (EMC) EN 61326
Electrical safety BS EN 61010 Installation Category II
Weight 0.6 lb (250 g)
Approvals CE
Control action
Proportional band 1 - 9999 Engineering units or 0.01 to 300 %age or 0.1 - 3000
Integral time Off - 9999
Derivative time Off - 9999
One shot tune, or natural frequency tune. The controller will automatically select the best
Error band
method according to the process conditions.
Auto tuning Hysteresis from 0.01 to 300.0 or 0.1 to 3000 Engineering units
On-off control 1 - 9999 Engineering units or 0.01 to 300 %age or 0.1 - 3000
Cut back To minimise overshoot on critical processes.
Auto / manual modes Selectable from keyboard.
Relays
Isolation 300 Vac double insulated
Output range 0 – 20 mA, 4 – 20 mA
Resolution 13.5 bits
Contact rating Maximum 2 A @ 264 Vac resistive
Note: Maximum 2 A per terminal limit applies where relays have common terminals (2 amps maximum for terminal AB).
Isolated dc output
© Spirax Sarco, Inc. 2013
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P323-28-US 12.13
177
SX80
Process Controller
Control
Valves
Wiring diagrams
Warning: Safe operation of this product can only be guaranteed if it is properly installed, commissioned, used and maintained by qualified
personnel as stated in the IMI supplied with the unit. It is the duty of the Company Safety Officer to ensure that the product specific data
Trans. & Sensors
and Safety information within the supplied IMI has been fully understood and complied with.
Controllers
IO1 1A LA AA
Relay output A
Output 3
1B LB AB Normally open relays
B Output 4
+ 2A LC AC
Output 2
Analogue
- 2B VI
Sensor input
+ R = 2.49Ω
L HE V+
Line supply +
+
100 to 230 Vac ±15% V
48 to 62 Hz R
N HF V-
- -
Pt100 mA Thermocouple
1A LA AA
1B LB AB
2A LC AC
2B Transducer VI
supply
L V+
HE +24v
V = 10-50 mV 2 R49
N 0v V-
HF
i < 30 mA i = 4-20 mA
1 (+) (-) 2
© Spirax Sarco, Inc. 2013
4 Screen
4-20 mA sensor
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P323-28-US 12.13
178
Control
Valves
Trans. & Sensors
Controllers
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
179
Control
Valves
Trans. & Sensors
Controllers
SX90
Process Controller
Description
The SX90 is a panel mounted 1/8th DIN controller, suitable for constant set point control of systems having fixed pre-programmed
set points. The controller has universal inputs, and outputs using PID for close control of industrial processes. The SX90 controller is
for use with the Spirax Sarco range of pneumatic and electric control valves and electrical and electropneumatic instruments.
SX90 features:
- Universal input - Resistance thermometers, thermocouples, mA and mV.
- Universal output - VMD (valve motor drive), mA and voltage for continuous, relay and
logic for switching control.
- Auxiliary power supply - For external transmitter requiring 24 Vdc.
- Set point - The SX90 can operate with local set point, remote set point, or a choice of 4
set points can be selected.
- Ramps - There are 2 independent ramps (ramp up and ramp down) for rate of change
from one set point to another.
- Remote set point - For cascade control (master/slave) using 2 controllers working
together, or to remotely control the set point.
- Retransmission - For retransmission of the process value, set value, or as second
analogue output.
- Event alarm - 4 programmable relay outputs for deviation, band, and process alarms.
- Quick codes - 5-digit quick codes enable easy set-up and commissioning of the
controllers
- Serial communications - For connecting via a serial port RS 485 (5 wire), up to 64
controllers into a supervisory system.
- Auto / man - The automatic to manual mode can be changed via the key board, or logic
inputs.
- Logic inputs - 3 logic inputs to provide a variety of selectable functions.
- Potentiometer Input - For feedback of valve position.
- Text messages - Scrolling text messages can be configured to alert the user to process
conditions.
- Forced output - Forced output level defined by instrument parameter and activated by a
logic input or by writing to the parameter.
Approvals
These controllers conform to the Council Directive 93 / 68 / EEC and the regulations on the essential protection requirements in Electrical
Apparatus EN 61010-1.90.
- EMC emissions specification: EN 61326-1: 1997 Class B (including amendments A1, A2 and A3).
- EMC immunity specification: EN 61326-1: 1997 Industriallocations (including amendments A1, A2 and A3).
See the next two pages for SX90 Process Controller technical data
Dimensions
(approximate) in inches (mm)
1.9" 4.0"
(48 mm) (101 mm) Panel cut-out
3.8"
(96 mm) 3.6"
(92 mm) - 0.0
+0.8
1.7"
3.5" (45 mm)
(90 mm) -0.0
+0.6
How to order example: 1 off Spirax Sarco SX90 process controller.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P323-30-US-US 12.13
180
SX90
Process Controller
Control
Valves
Technical data
General details
Controllers
Power supply 85 to 265 Vac, 9 W maximum
Electrical connections Screw connection terminal block
Panel sealing IP65 – plug in from front panel, NEMA 4X
Operating temperature / humidity 0 to 55°C, 5 to 85% RH
Atmospheres Not suitable for use in explosive or corrosive atmospheres
Electromagnetic compatibity (EMC) EN 61326
Electrical safety BS EN 61010 Installation Category II
Weight 0.8 lb (350 g)
Approvals CE
Control action
Proportional band 1 - 9999 Engineering units or 0.01 to 300 %age or 0.1 - 3000
Integral time Off - 9999
Derivative time Off - 9999
One shot tune, or natural frequency tune. The controller will automatically select the best
Error band method according to the process conditions.
Auto tuning Hysteresis from 0.01 to 300.0 or 0.1 to 3000 Engineering units
On-Off control 1 - 9999 Engineering units or 0.01 to 300 %age or 0.1 - 3000
Cut back To minimise overshoot on critical processes.
Auto / manual modes Selectable from keyboard.
Relays
Isolation 300 Vac double insulated
Comms
Isolation 300 Vac double isolation
Hardware EIA 485 5 wire (EIA 422 compatible)
Protocol Modbus RTU slave
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P323-30-US-US 12.13
181
SX90
Process Controller
Control
Valves
Pot input
Pot resistance range 100 - 10 kΩ
Excitation voltage 0.46 to 0.54 V
Resolution 0.006% of Span (>14Bits)
Sample rate 1 Hz
Short circuit pot detection < 25 Ω
Open circuit pot detection > 2 MΩ
Open circuit wiper detection > 5 MΩ
Maximum 2A @ 264 Vac resistive
Contact rating Note: Maximum 2A per terminal limit applies where relays have common terminals.
(2 amps maximum for terminal AB)
Outputs
Output 1 SPST N/O contact
Output 2 0 – 20 mA, 4 – 20 mA, 300 Vac double insulated, 13.5 bits resolution (<550 Ω)
Output 3 0 – 20 mA, 4 – 20 mA, 300 Vac double insulated, 13.5 bits resolution (<550 Ω)
Output 4 Changeover relay contacts
Outputs 5 and 6 (VMD) 2 SPST interlocked N/O relays
Input filter Off to 59.9 seconds
Zero offset User adjustable over full range
User calibration 2 point gain and offset
Open circuit wiper detection > 5 MΩ
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P323-30-US-US 12.13
182
SX90
Process Controller
Control
Valves
Wiring diagrams
Warning: Safe operation of this product can only be guaranteed if it is properly installed, commissioned, used and maintained by qualified
personnel as stated in the IMI supplied with the unit. It is the duty of the Company Safety Officer to ensure that the product specific data
Controllers
Terminal diagram
Digital inputs C and D
1A 4A AA
IO1 C
Relay output
1B 4B AB Output 4
(Changeover relay)
D
2A 4C AC
Output 2
Analogue
2B 5A RV
+ 3A PH
Output 3
Analogue 4-20 mA Potentiometer input
3B HB PW Valve position control
-
+ 3C HC PL
Transmitter supply V
24 V ±10%
3D HD VI
- Sensor input
R = 2.49Ω
+
L HE V+ +
Line supply
100 to 230 Vac R
48 to 62 Hz
N HF V- -
-
Pt100 mA Thermocouple
RTD mV mV Tc
Digital communications
EIA422
© Spirax Sarco, Inc. 2013
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P323-30-US-US 12.13
183
SX90
Process Controller
Control
Valves
1A 4A AA
1B 4B AB
2A 4C AC
2B 5A RV
LB 5B RI
LC 5C RC
3A PH
3B HB PW
Transmitter supply
3C +24v HC PL
3D HD VI
0v
L HE V+
V = 10-50 mV 2R49
N HF V-
i < 30 mA i = 4-20 mA
1 (+) (-) 2
4 Screen
4-20 mA sensor
© Spirax Sarco, Inc. 2013
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P323-30-US-US 12.13
184
Control
Valves
Trans. & Sensors
Controllers
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
185
Control
Valves
Trans. & Sensors
Controllers
Description
Dimensions (approximate) in inches
EL2270
The EL2270 is a Pt100 platinum resistance temperature sensor for EL2270* EL2271
general industrial use. The sensing device is an RTD 3 wire device Product Standard Miniature Quick repsonse
that meets EN 60751: Class A. This sensor can be connected range and duplex
directly to any temperature indicator or controller that has a 3 wire quick response
Pt100 input. A quick response version (1.57" insertion length only)
is also available for applications such as plate heat exchanger A 3.5 2.3 3.5 3.5
control. A miniature version of the EL2270 may also be ordered. B 5.1 2.4 6 5.1
This has a ¼" BSP taper thread, and a tip length of 1.53". C 3 2.5 3 3
EL2271 1, 2, 3,
The EL2271 is a combined Pt100 sensor and transmitter D 5, 9, 1.53 1.57 1, 2,
assembly. The sensing element is a 3 wire device that meets 29 3, 5
EN 60751: Class A and the transmitter has a 4 - 20 mA output. E .25 .25 .18 .25
The transmitter (only) meets ATEX II 1G EExia IIC / IIB T4 / T5 / T6.
The in-head transmitter can be configured to any range from *Notes: The quick response EL2270 is only available with an
-58°F to 932°F to special order. The 4 - 20 mA output can insertion length of 1.57".
be connected directly to any temperature indicator, controller
or flow computer that has a 4 - 20 mA input. Contact Spirax Pockets
Sarco for further details. Transmitters with 3 point calibration Standard Hygenic
are available to special order. Product Fabricated Solid 1½" sanitary
range drilled clamp con-
Pockets (thermowells) nector
General Fabricated
Three types of pockets are available: F 8, 28 1, 2, 4 1, 2, 4, 8
1. Thin wall with a ½" NPT process connection.
2. Drilled taper with a ½" NPT process connection.
3. Hygienic, to 3A sanitary standard, with a 1½" sanitary clamp EL2270 and
connection (ASME BPE) electro-polished to 16Ra (A Declaration EL2271
of Conformity is available). A
Note: No pocket is available for the miniature EL2270.
Selection
Pockets are sized to suit the probe tip length 'D', and are
specified as 'pocket to suit a __ inch probe'. B
Notes:
- The pocket dimension 'F' is 1" shorter than the probe
length 'D', which appears to be incorrect. The reason is that the
threaded body of the pocket acts as a stand-off, and therefore Enclosure
allows adequate clearance between the probe tip and the end
of the pocket.
- Pockets to suit 9" and 29" probes are for non-flow
applications only.
½"
NPT
Pocket
26A /F
C Probe
½" NPT
½" NPT
(¼" BSPT
EL2270
miniature
Drilled taper version
version)
F shown dotted D
E
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P322-06-US 06.07
186
Mechanical data
Control
EL2270* EL2271
Valves
Product range Note: A quick response version of the
EL2270 is also available to order
Enclosure KNE - aluminium alloy - epoxy coated KNE - aluminium alloy - epoxy coated
Probe 316 stainless steel 316 stainless steel
Controllers
Enclosure rating IP65 IP65
Maximum ambient temperature 158°F Maximum 185°F (dependant on ATEX requirement)
* The EL2270 quick response sensor has a time constant of 1.7 seconds.
Electrical data
-58°F to 932°F
Available ranges -58°F to 932°F 32°F to 212°F
212°F to 482°F
Output Pt100 to EN 60751: Class A Loop powered 4 - 20 mA
Output on sensor failure - 23 mA typical
Supply - 10 to 30 Vdc
636 W at 24 Vdc
Maximum loop resistance -
909 W at 30 Vdc
Transmitter - Thermal drift ± 0.1% / 10 KTAMB
-
measuring deviation per EN 60770 ± 0.2%
Approvals
Ex-protection
ATEX II 1G EExia IIC / IIB T4 / T5 / T6
per Directive 94 / 9 /EC ATEX. -
(Transmitter only)
Intrinsic Safety per EN 50020
-58°F … +185°F with T4
Permissible ambient temperature - -58°F … +167°F with T5
-58°F … +140°F with T6
Maximum values for connection Uo = 30 Vdc Io = 120 mA
of the current loop circuit - Pi = 800 mW Ci = 6.2 μF
(connections + and -) L i = 110 μH
Uo = 6.4 Vdc Io = 42.6 mA
Po = 37.1 mW
Maximum values for connection
Group II B:
of the sensor circuit -
Co = 500 μF L o = 50 mH
(connections 1 up to 3)
Group IIC:
Co = 20 μF L o = 10 mH
EMC emissions EMC directive 89 / 336 / EEC
-
and susceptibility EN 61326:1997 / A1, 1998 / A2.2001
Pressure and temperature limits of temperature probe. Pressure and temperature limits of additional pocket.
(ANSI 300 rated) (ANSI 600 rated)
1022 932
932
Temperature °F
Temperature °F
752 752
572 572
392 392 Steam saturation curve
Steam saturation curve
212 212
-58 -58
145 290 435 580 725 290 580 870 1160 1450
Pressure psig Pressure psig
The product must not be used in this region. The product must not be used in this region.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P322-06-US 06.07
187
Control
Valves
Trans. & Sensors
Controllers
Description
The EL2600 is a combined pressure sensor and transmitter which
is designed for general and industrial use.
It has a 2-wire 4-20 mA current loop, and a ¼" NPT process con-
nection. Two syphon tube and valve assemblies are available,
one with a maximum design pressure of 362 psig, and one with a
maximum design pressure of 1160 psig.
Available ranges
Calibrated pressure range Overpressure P max (psig)
0 - 23.2 psig, 36 psig 145
0 - 1.45 psig 145
0 - 3.62 psig 29
0-8.7 psig 58
0-14.5 psig 72
0-23.2 psig, 36 psig 145
0-58 psig 246
0-87 psig, 0-145 psig 507
0-232 psig, 362 psig 1160
0-580 psig 1740
0-870 psig 2900
0-1450 psig* 4640
0-2320 psig* 7250
0 - 3626 psig* 11600
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P322-02-US 06.07
188
Control
Dimensions /weights (approximate) inches and pounds
Valves
EL2600 D
EL2600
A B C D Weight
4.1 2.25 1.1 1.9 0.44
C
'U' Syphon and isolating valve
E F G H J K Weight
Controllers
A B
How to order
Example: 1 - Spirax Sarco EL2600 pressure transmitter, range
F 0 - 232 psig, with low pressure 'U' syphon and isolating valve.
¼" NPT
parallel
(NPSM)
G
¼" NPT
parallel
(NPSM)
K
© Spirax Sarco, Inc. 2007
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P322-02-US 06.07
189
Control
Valves
Actuated Valves
PF6 Series
Piston
Available range
Butt weld Flanged Socket weld Sanitary
Valve action BSP or NPT (EN 1092 or ANSI) clamp
NC - Normally Closed PF61G - 1NC PF62G - 1NC - PF64G - 1NC PF65G - 1NC
(flow over seat) PF61G - 2NC PF62G - 2NC PF63G - 2NC PF64G - 2NC PF65G - 2NC
PF61G - 3NC PF62G - 3NC PF63G - 3NC PF64G - 3NC PF65G - 3NC
PF61G - 1NO PF62G - 1NO - PF64G - 1NO PF65G - 1NO
NO - Normally Open
(flow under seat) PF61G - 2NO PF62G - 2NO PF63G - 2NO PF64G - 2NO PF65G - 2NO
PF61G - 3NO PF62G - 3NO PF63G - 3NO PF64G - 3NO PF65G - 3NO
BD - Bi-Directional normally closed PF61G - 1BD PF62G - 1BD - PF64G - 1BD PF65G - 1BD
(flow over or under seat) PF61G - 2BD PF62G - 2BD PF63G - 2BD PF64G - 2BD PF65G - 2BD
PF61G - 3BD PF62G - 3BD PF63G - 3BD PF64G - 3BD PF65G - 3BD
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P373-13-US 05.07
190
PF6 Series
Control
Valves
Stainless Steel Piston Actuated On/Off Valves
Pressure / temperature limits
Actuated Valves
375
356
Piston
300
212
120
32
14
0 145 230 290 360 435 580
Body NPT, BSP butt weld, and socket weld 1/2" - 2"
design Flanged ANSI 150
1/2" - 2"
conditions Sanitary clamp compatible connections PN10 1/2" - 2"
PMA Maximum allowable pressure Refer to the graph left
TMA Maximum allowable temperature 356°F
Minimum allowable temperature 14°F
PMO Maximum operating pressure 130 psig @ 356°F
TMO Maximum operating temperature 356°F
Minimum operating temperature (Note: For lower operating temperatures consult Spirax Sarco.) 14°F
∆∆PMX Maximum differential pressure (see page 4)
Designed for a maximum cold hydraulic test pressure of: 1.5 x PMA (PN rating)
PTMX Maximum test pressure is equal to the √∆PMX
Technical details
Leakage PTFE soft seal ANSI class V1
Flow characteristic Fast opening On/off
PF6_G-NC Flow over seat Port 1 to 2
Flow direction PF6_G-NO Flow under seat Port 2 to 1
PF6_G-BD Flow over seat Port 1 to 2
Flow under seat Port 2 to 1
Pilot media Air or water 140°F maximum
Actuator rotation 360°
Pilot connection Maximum pilot pressure
Actuator type and size Type 1 = 45 mm diameter 1/8" BSP 150 psig
Type 2 = 63 mm diameter 1/4" BSP 150 psig
Type 3 = 90 mm diameter 1/4" BSP 115 psig
Cv values
Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-13-US 05.07
191
PF6 Series
Control
Valves
8
8
10
10 9
2 2
5 5
6 6
3
11 and 12 11 and 12
3 1 4
1
4
8
Materials
No. Part Material
1 Body Stainless steel AISI 316L
10 2 Bonnet Stainless steel AISI 316L
9 3 Plug Stainless steel AISI 316L
4 Valve plug seal PTFE
5 Valve stem Stainless steel AISI 316
2 6 Stem seals PTFE chevrons
7 Stem ‘O’ ring Viton
5 6 8 Actuator housing Glass filled polyamide
9 Piston Glass filled polyamide
11 and 12 10 Piston lip seal Viton
3 11 Gasket PTFE
4 1
12 ‘O’ ring Viton
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
TI-P373-13-US 05.07
192
PF6 Series
Control
Valves
Stainless Steel Piston Actuated On/Off Valves
DPMX - Maximum differential pressures for PF6 piston actuated valves
*Notes:
Actuated Valves
1. Maximum differential pressure for saturated steam service is 130 psig.
2. Sanitary clamp connections are limited to PN10 pressure rating.
Piston
3. ANSI flange connections are limited to ANSI 150 pressure rating.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-13-US 05.07
193
PF6 Series
Control
Valves
115 2"
2" 115
90 90 1-1/2"
1-1/2" 1-1/4"
60 1-1/4" 60
41 1"
30 1" 30
15
15 0
0 0 60 115 175 230
0 60 115 175 230 290
Media pressure psig
Media pressure psig
115 3/4"
90 1/2"
60
30
0
0 60 115 175 230
Media pressure psig
2" 1-1/2"
115 1-1/4"
1"
90 3/4"
1/2"
60
55
30
0
0 60 115 175 230
Media pressure psig
PF6_G-3BD flow over seat (1 to 2) 2"
115
Pilot pressure psig
90 1-1/2"
1-1/4"
60 1"
48
30
0
0 60 115 175 230
Media pressure psig
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-13-US 05.07
194
PF6 Series
Control
Valves
Stainless Steel Piston Actuated On/Off Valves
Actuated Valves
Screwed, Sanitary clamp Flanged
Valve Actuator socket weld and butt weld (to ISO 2852) EN ANSI
Piston
size type 1092 150
and size A1 B1 C D† Weight A2 B2 C Weight A3 A4 B3 C Weight
1/2 “ 1 (45 mm) 2.56 5.67 4.85 .20 1.8 4.02 6.43 4.85 1.9 - - - - -
2 (63 mm) 2.56 7.56 6.74 .20 2.7 4.02 8.28 6.70 2.9 5.12 5.51 8.59 7.65 5.5
3/4“ 1 (45 mm) 2.96 6.11 4.97 .28 2.0 4.49 6.58 4.93 2.5 - - - - -
2 (63 mm) 2.96 7.80 6.93 .28 2.9 4.49 8.55 6.93 3.3 5.91 6.00 9.30 8.28 6.4
1" 2 (63 mm) 3.55 8.35 7.29 .32 3.3 5.08 9.10 7.29 4.0 6.31 6.50 9.42 8.20 8.2
3 (90 mm) 3.55 8.79 7.72 .32 4.9 5.08 9.58 7.73 5.3 6.31 6.50 9.85 8.63 9.5
1-1/4" 2 (63 mm) 4.33 8.87 7.60 .39 4.2 5.52 9.46 7.57 5.3 7.09 7.26 9.93 8.51 12.2
3 (90 mm) 4.33 9.22 7.96 .39 5.3 5.52 9.89 8.04 6.2 7.09 7.26 10.37 8.95 13.0
1-1/2" 2 (63 mm) 4.73 9.06 7.80 .47 5.3 6.27 9.81 7.76 6.2 7.88 8.00 10.13 8.67 14.2
3 (90 mm) 4.73 9.42 8.16 .47 5.8 6.27 10.25 8.24 7.1 7.88 8.00 10.56 9.14 15.2
2" 2 (63 mm) 5.91 9.77 8.16 .63 6.4 7.49 10.52 8.12 8.0 9.06 9.00 10.84 9.06 19.0
3 (90 mm) 5.91 10.13 8.51 .63 7.3 7.49 11.00 8.55 8.9 9.06 9.00 11.27 9.46 20.0
Notes: * Add 0.5 lbs. for travel switch or flow regulator options (not available for use with the Type 1 actuator).
† Dimension ‘D’ is for socket weld connections only.
* Travel switch * Flow regulator
3.03" 3.27"
B1 B2 (Sanitary Clamp)
(Screwed, socket and B3 (Flanged)
weld and butt weld)
C
C
2 1 2 1
Note: Dimension’D’
D is for socket weld
A1 connections only.
(Screwed, socket A2 (Sanitary clamp)
weld and butt weld) A3 (EN 1092) and A4 (ANSI)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-13-US 05.07
195
PF6 Series
Control
Valves
Valve F
F = Fast opening
characteristic
Body G
6 = Stainless steel
material
1 = BSP or NPT
- DIN 11850 pipe
2 = Butt weld Note: state pipeline connection when ordering: - ANSI B 36.10 / ISO 65 pipe
Connections - ISO 4200 pipe 1
3 = Flanged EN 1092 or ANSI Class 150 (welded on flanges)
4 = Socket weld Note: state pipeline connection ANSI B 36.10 / ISO 65 pipe when ordering
5 = Sanitary clamp ISO 2852
Valve G = PTFE G
plug seal
1 = 45 mm diameter
Actuator 2 = 63 mm diameter 2
type 3 = 90 mm diameter
NC = Normally Closed
Valve NC
NO = Normally Open
position BD = Bi-Directional
Valve size 1/2", 3/4", 1", 1-1/4", 1-1/2", 2" 1"
Provides indication of open or closed valve position through a
magnetic reed switch with volt free contacts.
I = Travel switch Maximum rating: Voltage (V) = 500 V,
Current (I) = 0.5 A,
Optional Power (P) = 30 VA. I
Available on Type 2 and Type 3 actuators with suffix ‘I’ if this option is required.
Provides manual control of maximum flow through the valve.
R = Flow regulator Can also provide manual shut-off on normally open valves.
Available on Type 2 and Type 3 actuators with suffix ‘R’ if this option is required.
How to order
Example: 1 of Spirax Sarco PF61G-2NC-1" NPT- I stainless steel piston actuated on/off valve having NPT connections,
with travel switch
Spare parts
A seal kit is available for all valve and actuator sizes comprising: Piston lip seal, stem ‘O’ ring, valve head seal (PTFE),
body seal and ‘O’ ring.
Installation note: These valves can be mounted in any orientation. The actuator can be rotated 360° in the direction indicated
on the product label to facilitate easy pilot mounting connection.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-13-US 05.07
196
PF6 Series
Control
Valves
Stainless Steel Piston Actuated On/Off Valves
Associated equipment
Actuated Valves
Piston
Pilot solenoid
Type DM 3-port two way electropneumatic pilot solenoid valve that can be directly mounted (banjo connection) to the PF61G-NC, NO and BD
series piston actuated valves to provide actuator pilot pressure to open normally closed or close normally open valves. Suitable for air or water
operating media. The valve is supplied with a DIN connector. For full details refer to the relevant Technical Information Sheet.
Available types
Frequency/ Actuator Line
Model Type Actuator Voltage Connection Connection
DM11N 1 45 mm 230/50 or 240/60 Vac 1/8" BSP 1/8" NPT
DM12N 1 45 mm 110/50 or 120/60 Vac 1/8" BSP 1/8" NPT
DM13N 1 45 mm 24/50 or 24/60 Vac 1/8" BSP 1/8" NPT
DM14N 1 45 mm 24 Vdc 1/8" BSP 1/8" NPT
DM21N 2 63 mm 230/50 or 240/60 Vac 1/4" BSP 1/8" NPT
DM22N 2 63 mm 110/50 or 120/60 Vac 1/4" BSP 1/8" NPT
DM23N 2 63 mm 24/50 or 24/60 Vac 1/4" BSP 1/8" NPT
DM24N 2 63 mm 24 Vdc 1/4" BSP 1/8" NPT
DM31N 3 90 mm 230/50 or 240/60 Vac 1/4" BSP 1/8" NPT
DM32N 3 90 mm 110/50 or 120/60 Vac 1/4" BSP 1/8" NPT
DM33N 3 90 mm 24/50 or 24/60 Vac 1/4" BSP 1/8" NPT
DM34N 3 90 mm 24 Vdc 1/4" BSP 1/8" NPT
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-13-US 05.07
197
Control
Valves
Actuated Valves
PF51G Bronze
Piston
Description
A 2-port pneumatically actuated on / off bronze valve for use on water, air, oil
and gases. It can also be used on lower specification steam applications.
A pneumatic signal acts on the actuator piston to open or close the valve
with a spring return action. The valve plugs have a PTFE soft seal (G) to
provide a tight shut-off. A valve position indicator is included on standard
and flow regulator models.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification.
Control
Valves
Piston Actuated On/Off Valves
Actuated Valves
Piston
70
Technical details
Leakage PTFE soft seal ANSI class V1
Flow characteristic Fast opening On/off
PF51G- NC Flow over seat Port 1 to 2
Flow direction PF51G- NO Flow under seat Port 2 to 1
Flow over seat Port 1 to 2
PF51G-BD
Flow under seat Port 2 to 1
Pilot media Air or water 140°F maximum
Actuator rotation 360°
Pilot connection Maximum pilot pressure
Actuator type and size Type 1 = 45 mm diameter 1/8" BSP 150 psig
Type 2 = 63 mm diameter 1/4" BSP 150 psig
Type 3 = 90 mm diameter 1/4" BSP 115 psig
Cv values
Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2"
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
199
PF51G Bronze
Control
Valves
8
8
10
10 9
2 2
5 5
6 6
3
11 and 12 11 and 12
3 1 4
1
4
Materials
8 No. Part Material
1 Body Bronze EN1982 CC491K
2 Bonnet Brass EN 12165 CW617N
10 3 Plug Stainless steel AISI 316L
9 4 Plug seal PTFE
5 Valve stem Stainless steel AISI 316
6 Stem seals PTFE chevrons
2 7 Stem ‘O’ ring Viton
8 Actuator housing Glass filled polyamide
5 9 Piston Glass filled polyamide
6
10 Piston lip seal Viton
11 Gasket PTFE
11 and 12
3
4 1
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
200
PF51G Bronze
Control
Valves
Piston Actuated On/Off Valves
Actuated Valves
DPMX - Maximum differential pressures for PF51G piston actuated valves
Piston
PF51G-NC (Normally closed)
Maximum
Actuator Flow differential Pilot Pressure
Model Valve size diameter direction pressure Minimum Maximum
(mm) (port 1 to 2) (psig) (psig) (psig)
1/2" 45 over seat 230 26 150
PF51G-1NC
3/4" 45 over seat 230 26 150
1" 45 over seat 230 26 150
1/2" 63 over seat 290 22 150
3/4" 63 over seat 290 22 150
PF51G-2NC 1" 63 over seat 290 22 150
1-1/4" 63 over seat 230 44 150
1-1/2" 63 over seat 230 44 150
2" 63 over seat 160 44 150
1" 90 over seat 290 15 115
PF51G-3NC 1-1/4" 90 over seat 230 36 115
1-1/2" 90 over seat 230 36 115
2" 90 over seat 220 36 115
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
201
PF51G Bronze
Control
Valves
1"
90 3/4"
psig
60 1/2"
2630 26
0
0 60 115 175 230
Media pressure (psig)
Pilot pressure
(psig)
2" 1½"
(psig)
Pilot pressure
115 115
1¼"
90 1¼" 1" 90 1"
60 ¾" 60 ¾"
45 ½"
30 30 ½"
22 22
60 115 175 230 290 60 115 175 230
Media pressure (psig) Media pressure (psig)
PF51G-3NC flow over seat (1 to 2)
115
2"
Pilot pressure
90
1-1/2"
(psig)
60
1-1/4"
3630 1"
15
0
0 60 115 175 230 290
Media pressure (psig)
115
90 1"
psig
1/2"
5560 3/4"
30
0
0 60 115 175 230
Media pressure (psig)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
202
PF51G Bronze
Control
Valves
Piston Actuated On/Off Valves
Dimensions and weights (approximate) in inches and lbs.
Actuated Valves
Valve size Actuator type and size A1 B1 C D Weight
Piston
1/2 “ 1 (45 mm) 2.56 5.67 5.36 4.85 1.8
2 (63 mm) 2.56 7.56 7.25 6.74 2.7
3/4" 1 (45 mm) 2.96 5.87 5.60 4.97 2.0
2 (63 mm) 2.96 7.80 7.57 6.94 2.9
1 (45 mm) 3.55 5.87 6.35 5.56 2.5
1" 2 (63 mm) 3.55 8.35 8.08 7.29 3.3
3 (90 mm) 3.55 8.79 8.51 7.73 4.9
1-1/4" 2 (63 mm) 4.33 8.87 8.55 7.61 4.2
3 (90 mm) 4.33 9.22 8.94 7.96 5.3
1-1/2" 2 (63 mm) 4.73 9.06 8.87 7.80 5.3
3 (90 mm) 4.73 9.42 9.26 8.16 5.8
2" 2 (63 mm) 5.91 9.77 9.50 8.16 6.4
3 (90 mm) 5.91 10.13 9.85 8.51 7.3
Notes: * Add 0.4 lbs. for travel switch or flow regulator options (not available for use with the Type 1 actuator).
3.04" 3.27"
B1
2 1
A1
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
203
PF51G Bronze
Control
Valves
How to order
Example: 1 of Spirax Sarco PF51G-2NC-1" NPT bronze piston actuated on/off valve having screwed BSP connections.
Spare parts
A seal kit is available for all valve and actuator sizes comprising: Piston lip seal, stem ‘O’ ring, valve head seal (PTFE) body seal.
Installation note: These valves can be mounted in any orientation. The actuator can be rotated 360° in the direction indicated
on the product label to facilitate easy pilot mounting connection.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
204
PF51G Bronze
Control
Valves
Piston Actuated On/Off Valves
Associated equipment
Actuated Valves
Piston
Pilot solenoid
Type DM 3-port two way electropneumatic pilot solenoid valve that can be directly mounted (banjo connection) to the PF51G-NC, NO and BD
series piston actuated valves to provide actuator pilot pressure to open normally closed or close normally open valves. Suitable for air or water
operating media. The valve is supplied with a DIN connector. For full details refer to the relevant Technical Information Sheet.
Available types
Frequency/ Actuator Line
Model Type Actuator Voltage Connection Connection
DM11N 1 45 mm 230/50 or 240/60 Vac 1/8" BSP 1/8" NPT
DM12N 1 45 mm 110/50 or 120/60 Vac 1/8" BSP 1/8" NPT
DM13N 1 45 mm 24/50 or 24/60 Vac 1/8" BSP 1/8" NPT
DM14N 1 45 mm 24 Vdc 1/8" BSP 1/8" NPT
DM21N 2 63 mm 230/50 or 240/60 Vac 1/4" BSP 1/8" NPT
DM22N 2 63 mm 110/50 or 120/60 Vac 1/4" BSP 1/8" NPT
DM23N 2 63 mm 24/50 or 24/60 Vac 1/4" BSP 1/8" NPT
DM24N 2 63 mm 24 Vdc 1/4" BSP 1/8" NPT
DM31N 3 90 mm 230/50 or 240/60 Vac 1/4" BSP 1/8" NPT
DM32N 3 90 mm 110/50 or 120/60 Vac 1/4" BSP 1/8" NPT
DM33N 3 90 mm 24/50 or 24/60 Vac 1/4" BSP 1/8" NPT
DM34N 3 90 mm 24 Vdc 1/4" BSP 1/8" NPT
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P373-14-US 4.07
205
Control
Valves
Actuated Valves
Piston
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
206
Control
Valves
Actuated Valves
Type DM Solenoid Valves
Piston
for use with Piston Actuated Valves
Description
A 3 way normally closed electropneumatic pilot solenoid valve that can
be directly mounted (banjo connection) to the PF51G, and PF61G-NC,
NO and BD series piston actuated valves.
Suitable for air, water or inert gas operating media. The valve is supplied
with a DIN connector and fitted with manual override as standard.
Technical details
Mounting Banjo connection
Manual override Fitted as standard Dimensions / weights (approximate) in inches and lbs.
Form B DM11N, DM12N, DM13N, and DM14N
Connector Form B DM21N, DM22N, DM23N, and DM24N Type A B C Weight
DIN 43650 Form A DM31N, DM32N, DM33N, and DM34N DM11N, DM12N, DM13N and DM14N 1.22 3.03 1.06 0.60
DM11N to DM14N 1/8" NPT
Pilot media DM21N, DM22N, DM23N and DM24N 1.38 3.07 1.06 0.60
DM21N to DM24N 1/8" NPT
connection
DM31N to DM34N DM31N, DM32N, DM33N and DM34N 1.38 3.74 1.06 0.84
AC 9 (holding)
DM11N, DM12N
DM13N, DM14N
AC 14 (inrush)
DC 6
AC 9 (holding)
Coil DM21N, DM22N
consumption AC 14 (inrush)
DM23N, DM24N
DC 6 Ground
AC 15 (holding) terminal B
DM31N, DM32N
DM33N, DM34N AC 30 (inrush)
DC 10 DIN
connector
(rotatable)
Limiting conditions
Maximum media temperature 140°F
Minimum media temperature 14°F
Protection class IP65 (with connector) C A
Operating pressure 0 - 150 psig
Note: DM3XN Series shown
Materials
Part Material
Installation
The valve can be directly mounted (banjo connection)
Body ELNP Niploy coated brass
onto the actuator.
Seal FKM
How to order
Spare parts Example: 1-DM21N Solenoid Valve 240 VAC
Coil and/or DIN connector available, consult SSI.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification.
TI-P373-04-US 08.06
207
Control
Valves
Actuated Valves
Description
A series of 3 way normally closed, solenoid operated, manifold pilot
valves that are joined together and supply pressure to operate a cor-
reponding number of Piston Actuted Valves. This manifold assembly
may be mounted in any posiiton. They are suitable for air or water
media.
Technical details
Construction material: Body — Brass
Seals — Viton
Mounting: Universal, any position
Accepts #6 machine screws
Manual Override: Slotted 180° turn-button
Pilot Valve Connections: 1/8" NPT common “IN"
1/8" NPT individual “OUT"
Electrical Connection: DIN 43650 Form B
Coil Consumption: AC: 9 VA (holding)
14 VA (inrush)
DC: 7 W
Limiting conditions
Maximum media temperature: 140°F
Minimum media temperature: 14°F
Protection class: IP65 (with DIN connector)
Operating pressure: 0 - 150 psig
C Weight
Station inches pounds
2 3.00 1.3 Left Center Right
B919CVCM B920CVCM B921CVCM
3 4.00 1.9 3
4
4 5.00 2.5
5 6.00 3.1
6 7.00 3.7
7 8.00 4.3
8 9.00 4.9
3.06"
2
.38"
IN
2.32"
typ. 1.35" .98"
typ.
CL Mounting
typ.
CL Mounting
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-8-500-US 1.14
208
Type MDM Manifold Pilot Valves
Control
Valves
for use with Piston Actuated Valves
Installation
The manifold valve assembly can be directly mounted to a system plate in any position. Incoming pilot pressure to connect with the common “IN"
Actuated Valves
port (end). Outgoing pilot pressure to connect from the individual “OUT" ports (sides).
Piston
Each “Out" port line to connect to a correponding Piston Actuated Valve actuator. Note: When attaching to the PAV’s with 63mm or 90mm actuator
heads, it will be necessry to bush up from 1/8" NPT to 1/4" NPT.
Order Information
Example: MDM92N-4
A (4) station manifold Pilot Valve assembly, 120V AC,
1/8" NPT for a 45mm or 63mm Piston Actuate Valve.
MDM92N-4
MDM 4
Manifold Pilot Valve Assembly (4) station banked assembly
9 N
For a remote banked installation NPT port connections
2
120V AC Voltage
Available Types
Pav Port
Model Number Actuator Voltage/Frequency Connections
MDM91N-X* 45, 63mm** 240V AC 1/8" NPT
MDM92N-X* 45, 63mm** 120V AC 1/8" NPT
MDM93N-X* 45, 63mm** 24V AC 1/8" NPT
MDM93N-X* 45, 63mm** 24V DC 1/8" NPT
* X denotes number of manifold stations. Number may be from (2) to (8) depending on amount of PAV’s requiring service. For
information on additional stations, consult Spirax Sarco, Inc.
**90mm Actuators, consult Spirax Sarco, Inc.
Materials
No. Description Part No.
1 Valve - Left B919CVCM
Valve - Center B920CVCM
Valve - Right B921CVCM
2 Adaptor 72415
3 Coil 270R - 240VAC
240R - 120VAC
220R - 24VAC
© Spirax Sarco, Inc. 2014
225R - 24VDC
4 Connector 001
DIN 43650
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-8-500-US 1.14
209
Boiler Controls
for level control/alarm and TDS control.
Accurate control of
water level/alarm within
the boiler or tank while
maintaining the proper
TDS level of the boiler
water, are vital in the
boiler room.
210
Boiler Controls
INDEX
Boiler Controls Table of Contents
Tech. Illus. Model / Description Page No.
TI-9-114-US LP 10-4 Level Probe 212
TI-P402-39-US LP 20 Capacitance Level Probe 214
TI-P402-66-US PA 20 Pre-Amplifier
ntrols 216
TI-P402-132-US LC 1350 Level Controller
Lev el Co 217
TI-P402-133-US LC 2250 Level Controller 220
TI-P402-134-US LC 2650 Level Controller 224
TI-9-401-US APS 1 Probe Simulator 228
TI-P403-41-US DS 1000 Digital Display 231
TI-P402-43-US LP 30 Self Monitoring Level Probe
Ala rms 232
TI-P402-81-US LP 31 High Level Alarm Probe Level 234
TI-P402-135-US LC 3050 Level Controller 236
TI-P403-57-US BCS1 Blowdown System Pipeline Set 240
TI-9-403-US S20 Sensor Chamber, TP20 Temperature Sensor, CP10 & PT2 Plug Tail 242
TI-9-202-US CP 30 Conductivity Probe 244
TI-P403-59-US CP 32 Twin Tip Conductivity Probe 246
TI-P403-91-US BC 3150 Blowdown Controller 248
D
TI-P403-90-US BC 3250 Controllers & CC 252
n
TI-P403-60-US BCV 1 & BCV 20 Blowdown Valve
w dow 256
lo
TI-9-305-US 3/4" BCV 30 Blowdown Control Valve l er B 258
TI-P403-72-US 1-1/2" BCV 30 Blowdown Control Valve Boi 260
TI-P403-36-US 3/4" BCV 31 Blowdown Control Valve 262
TI-P403-74-US 1-1/2" BCV 31 Blowdown Control Valve 264
TI-9-402-US MS 1 Conductivity Meter 267
TI-P405-40-US BT150 Boiler Blowdown Timer
do wn 268
TI-P405-47-US KRV40i B low 272
m
TI-P405-45-US ABV40i
Botto 274
211
LP 10-4
Level Probe
Description
The Spirax Sarco LP10-4 level probe is used with Spirax Sarco LC1300
series level controllers to provide on / off level control and alarm functions in
steam boilers, tanks or other vessels.
The four tip probe is particularly suitable where 3-lamp ‘electric gauge
glass’ alarm/ level indicators are fitted. The probe body is grounded through
its screwed connection and the boiler or tank normally forms the ground
return path. The probe may also be used in concrete or plastic tanks by
using one of the tips as a ground return, or by providing a separate ground
rod or plate. The LP10-4 probe has four detachable level sensing tips which
are cut to length on installation to give the required switching levels. Note:
Tips are ordered separately, and are 39" long. Two sets of tips may be
connected for a maximum probe length of 82". When a tip is immersed in
conductive liquid it completes an electrical circuit to ground. When the level
drops below the tip, the resistance to ground becomes high, indicating to
the controller that the tip is out of the liquid.
• Single probe provides all the controls needed on a tank
• Suitable for use with steam boilers up to 464 psig (32 barg) 1
Controls
Approvals
The LP10-4 is also available with a 1" NPT screwed connection.
Caution
The probe is not suitable for outside installation without additional en-
Controls
Level
vironmental protection.
Technical data
Protection rating IP54
Maximum cable length (probe to controller) 98ft (30 m)
Maximum sensing depth 82.5" (2 095 mm)
Minimum sensing depth 3" (75 mm)
Minimum conductivity (when used with an LC1300 level controller)
1µS/cm @ 77°F (25°C)
Materials
No. Part Material
1 Probe body Austenitic stainless steel Type 304L/ 1.4306
2 Probe tips Austenitic stainless steel Type 316/ 316L
3 Tip insulation PFA (Per Fluor Alkoxy)
sleeving
4 Lower housing PPS (Polyphenyline sulphide)
5 Upper housing PPS (Polyphenyline sulphide)
6 Gland support pad Thermoplastic elastomer
7 Cable gland PA (Polyamide)
8 Tip steady PEEK (Polyaryletherketone) Grade 450G
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-9-114-US 1.14
212
LP 10-4 Level Probe
Safety information Dimensions / weight (approximate) in inches and lbs.
WARNING
A B C D Weight
Your attention is drawn to Safety Information Leaflet IM-GCM-10,
2.4 1.0 3.0 2.0 2.5
as well as to any National or Regional regulations.
This product is designed and constructed to withstand the forces
encountered during normal use.
Use of the product for any purpose other than as a level probe
could cause damage to the product and may cause injury or fatal-
ity to personnel.
This product contains materials including plastics which can
give off toxic fumes if exposed to excessive heat. Additional envi-
ronmental protection is needed for installation outdoors.
Installation
This document does not contain sufficient information to install the
product safely. See the Installation and Maintenance Instructions
provided with every unit.
The LP10-4 is designed for installation in a 1" NPT threaded flange
or cover. The probe tips are screwed to the probe body using the
extension connectors and lock-nuts provided, then cut to length
before installation to give the required switching levels. Tip steadies
provide lateral support as well as insulation between the tips. For deep
tanks/ boilers, the switching level may be extended to a maximum of
82" by fitting a second probe tip. A minimum 3" (80 mm) nominal bore
protection tube is recommended if installing the probe in a boiler, or in
a tank which is subject to very turbulent conditions.
Controls
Boiler
Controls
How to specify Level
Conductivity probe with austenitic stainless steel body and
probe tips, PFA tip insulation, suitable for steam boiler operation up
Wiring to 464 psig (462°F)
Wiring is straightforward on the LP10-4, as crimp connectors are
used. Extra connectors are available as a spares kit. Terminal posts How to order
are colour coded for easy identification. Example: 1 of Spirax Sarco LP10-4 probe with 39" tip assembly.
The wiring loom may be disconnected and removed without dis-
turbing the cable gland by lifting the gland carrier out of the lower Available spares
housing. LP10-4 connector set (electrical)
Comprising: 6 flat crimp connectors and 2 ring crimps
Maintenance LP10-4 tip mounting kit
No special maintenance is required, though boiler water level con- Comprising: 1 set of 4 tip connectiors, 8 lock-nuts and 2-tip supports
trols do require periodic testing and inspection which is described in
separate literature.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-9-114-US 1.14
© Spirax Sarco, Inc. 2014
213
LP 20 Capacitance Level Probe
Description PA20
The Spirax Sarco LP20 is a capacitance probe designed for modulating level Preamplifier 5
connector
control in conductive liquids, in conjunction with a PA20 preamplifier, which is
supplied separately. It can also be used for adjustable on/off control.
The LP20 may be used with one or more controllers or transmitters to provide
level control, level alarms, and/or outputs to a building management system.
The probe is normally installed in a steam boiler or metal tank where it is
earthed through the ½" NPT screwed connection, the boiler or tank forming
the earth return path.
It may be used in a non-conductive tank (e.g. plastic or concrete) if an earth 6
rod is provided.
The PA20 preamplifier (described in separate literature), is screwed to the top
of the probe and hand tightened, enabling easy removal without the need to
disturb the probe. 2
Approvals:
The LP20 is available with a ½" NPT screwed connection.
Controls
Boiler
Note: Probe length includes the 1" (25 mm) 'dead' length at its tip. The probe
must not be cut to length.
Materials
No. Description Material
1 Probe body Austenitic BS EN 10088-3
stainless steel (1.4306)
2 Cover assembly Austenitic Type 316L
stainless steel
3 Probe (sheathed) Stainless steel ASTM A269 Gr. 316L
tube
4 Probe sheathing PTFE BS 6564 Grade UA Type 1
5 'O' ring Nitrile rubber
6 Name-plate Polycarbonate
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-39-US 1.14
214
LP 20 Capacitance Level Probe
Dimensions (approximate) in inches Weights (approximate) in pounds including immediate packaging
Probe length 14.6 18.5 21.6 23.6 25.6 29.5 31.5 35.4 37.4 41.3 47.2 53.1 59.1
Weight 1.8 1.8 2.0 2.1 2.2 2.3 2.5 2.7 2.9 3.1 3.3 3.6 3.7
Controls
35.4 (900) 0.9 (23)
Boiler
37.4 (950) 1.0 (25)
41.3 (1050) 1.1 (27)
27 A / F
47.2 (1200) 1.2 (30)
53.1 (1350) 1.3 (34)
½" NPT
59.1 (1500) 1.5 (38)
The LP20 is available
with a ½" NPT screwed Do not cover the vent and drain holes on the body.
Controls
connection.
Level
Maintenance note:
No special maintenance is required. Boiler water level controls and alarms
do, however require periodic testing and inspection, which is described in
separate literature.
How to specify
Capacitance level probes shall be Spirax Sarco type LP20 with stainless
steel body, cover assembly and probe, and PTFE probe insulation. They
shall be suitable for modulating and on/off level control and be fitted with a
screwed connection for attaching a Spirax Sarco PA20 preamplifier.
How to order
Example: 1 off Spirax Sarco LP20 capacitance level probe with NPT
(L) connection. Probe length 18.5".
Probe
length
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-39-US 1.14
© Spirax Sarco, Inc. 2014
215
PA 20 Pre-Amplifier
4
Boiler
Approvals:
½" NPT
The PA20 is with a ½" NPT screwed connection.
Please note that this version will not be marked and is not suitable .2" (5 mm) Weight
for Europe. approximately .6 lbs (0.25 kg)
Ø26 including packaging.
mm
Controls
Caution: The probe is not suitable for outside installation without Materials
Level
How to specify
Preamplifiers shall be Spirax Sarco type PA20 for use with Spirax Sarco
capacitance probes. Preamplifiers shall have austenitic stainless steel
bodies and a screwed connection, with a DIN 43650 connector.
Controls
- Infrared comms.
Boiler
Approvals
This product complies with the Electromagnetic Compatibility Directive
2004 / 108 / EC and all its requirements.
The LC1350 is suitable for Class A Environments (e.g. industrial). A LC1350
fully detailed EMC assessment has been made and has the reference
number UK Supply BH LC1350 2008.
Controls
Level
The LC1350 complies with the Low Voltage Directive by meeting the
standards of:
- EN 61010-1:2010 safety requirements for electrical equipment for
measurement, control, and laboratory use.
The LC1350 has been type-tested as a level control by meeting the LCD
standard: display
- Vd TÜV requirements for water level control and limiting devices,
Water Level 100 (07.2010).
Application
Typical application example – on/off control of a feedtank:
- Pump on Note: probes can be mounted in
- Pump off external chambers if boiler mounting
- High alarm is not possible.
- Low alarm
Function
Inputs AL
The LC1350 input options are: 5 button
- High alarm or low alarm from a conductivity probe. display
- Pump on/off control from two conductivity probes.
Function / outputs OK
The controller reacts to a change in probe conductivity (open /closed
circuit) and energizes / de-energizes a relay. This action switches a
pump or sounds an alarm.
Other features:
- Additional filters can be selected to increase the damping effect for
turbulent conditions.
- To prevent unwanted or inadvertent changes being made, all
commissioning parameters are protected with a fixed pass code.
- The product can communicate via an infrared link between adjacent
boiler house controllers. It is designated as a slave unit.
- A panel mounted external test switch may be fitted if required.
Clamping screw
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-132-US 10.13
217
LC1350
Level Controller
Technical data LC1350
Termination
Mains and Safety and Approvals may be compromised otherwise.
signal connector Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
Stripping length 5 - 6 mm (0.2")
Type High temperature
Shield type Screened
Controls
Level
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-132-US 10.13
218
LC1350
Level Controller
Safety information, installation and maintenance
Warning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially fatal
mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
In most countries, steam boilers operating with limited supervision require two self-monitoring level probes and controllers to provide
two independent low level alarms. A high level alarm is also advised, and is compulsory in some countries. The LC1350 is not self-
monitoring.
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
52 mm 120 mm
Controls
(2.05") (4.72")
Boiler
Controls
Level
LC1350
140 mm 120 mm
(5.51") (4.72")
AL
OK
How to specify
Conductivity level controller to provide on/off control of a pump plus two configurable alarms, and to have infrared communications.
How to order
Example: 1 off Spirax Sarco LC1350 level controller.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-132-US 10.13
219
LC2250
Level Controller
Description
The Spirax Sarco LC2250 is a level controller for on/off or modulating
control of conductive liquid levels. Clamping
screw
The LC2250 has two alarm outputs that can be configured high
or low.
The controller is suitable for use with liquids having an electrical
conductivity of 5 µS/cm or 5 ppm, when used with an LP20, PA20, or LC2250
PA420 capacitance probe.
The LC2250 may be used on boilers, tanks, or vessels operating at up
to 32 bar g at 239°C (464 psig@462°F).
The front panel has a 3 digit LCD display and a five-button keypad. Graphic
display
The unit can be be panel, DIN rail, or chassis mounted. %
Principal features:
- Level controller for modulating or on/off control of boilers.
- Universal power supply – 110 Vac to 240 Vac @ 50/60 Hz.
Controls
Boiler
- TÜV approvals.
- Alarm – high or low.
- Input filter for turbulent conditions. AL
- 0/4-20 mA retransmit. 5 button
display
- Infrared communications. OK
Controls
Level
Approvals
This product complies with the Electromagnetic Compatibility
Directive 2004 / 108 / EC and all its requirements.
The LC2250 is suitable for Class A Environments (e.g. industrial). A Clamping
fully detailed EMC assessment has been made and has the reference screw
number UK Supply BH LC2250 2008.
The LC2250 complies with the Low Voltage Directive by meeting the
standards of: Function
The product compares the input signals with the Set Point selected
- EN 61010-1:2010 safety requirements for electrical equipment by the user. It then changes its output signal to control the water level
for measurement, control, and laboratory use. in the boiler or tank.
The LC2250 has been type-tested as a level control by meeting the Inputs
standard: The product has two inputs to accept the following signals:
- Vd TÜV requirements for water level control and limiting devices, - Level probe or transmitter 1 - 6 V or 4 - 20 mA.
Water Level 100 (07.2010). - A 1 K potentiometer input ~ for Valve Motor Drive (VMD).
Outputs
Typical applications The output control signal can be configured / wired to work with a
On/off control: pump or a modulating control valve. It also provides a relay output
for high or low level alarms and can provide an isolated 4 - 20 mA
- Pump control. retransmission output.
- Two alarm output. Other features:
- 4 - 20 mA level output. - An additional filter can be selected to increase the damping effect
Note: A solenoid valve may be used instead of a pump.
for turbulent conditions.
Modulating control: - Commissioning parameters are protected with a pass code.
Modulating valve control using valve motor drive or 4 - 20 mA control
signals. - The LC2250 can communicate via an infrared link between
adjacent controllers. It enables the parameters to be passed to a
- Two alarm output. product fitted with RS485 (User). The LC2250 is designated as a
- 4 - 20 mA level output. slave unit – no set-up or adjustment is needed.
Note: The 4 - 20 mA level output is only available when the product Important: Do not cover or obstruct the infrared beam between
is configured for valve motor drive systems. products.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-133-US 10.13
220
LC2250
Level Controller
Technical data LC2250
Controls
Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd.
Mains
Boiler
Safety and Approvals may be compromised otherwise.
and signal
Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
connector
Stripping length 5 - 6 mm (0.2")
Type High temperature
Cable / wire Shield type Screened
Controls
and Level probe Number of cores 3 LP20/PA20, 2 (LP20/PA420 4-20mA Transducer)
Level
connector cable / wire Gauge 1 – 1.5 mm² (18 - 16 AWG)
data Maximum length 100 m (328 ft)
Type Twisted pair
4 - 20 mA Shield type Screened
output Number of pairs 1
cable / wires Gauge 0.23 - 1 mm² (24 - 18 AWG)
Maximum length 100 m (328 ft)
Minimum voltage 0 Vdc or 1 V (with OUTRANGE function selected)
Maximum voltage 6 Vdc (absolute maximum = 7 Vdc)
Input impedance 28 KΩ
Level Accuracy 5% FSD over operating range
voltage Repeatability 2.5% FSD over operating range
Resolution 14 bit (0.15 mV approximately)
Input
Sample time 260 Hz
technical
Minimum current 0 mA
data
Maximum current 22 mA
Input impedance 11 KΩ
4 - 20 mA Accuracy 5% FSD over operating range
Repeatability 2.5% FSD over operating range
Resolution 14 bit (1 µA - approximately)
Sample time 260 Hz
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-133-US 10.13
© Spirax Sarco, Inc. 1997
221
LC2250
Level Controller
Technical data LC2250 (continued)
Safety
1 information, installation Dimensions / weight (approximate) in mm and g.
and maintenance Weight 430 g. (0.95lb)
This document does not contain sufficient information to
install the unit safely. The unit operates at a potentially
fatal mains voltage. Before attempting to install the 52 mm 120 mm
unit read the Installation and Maintenance Instructions (2.05") (4.72")
supplied with it.
Boiler water level controls and level alarms do, however, How to order
require testing and inspection. Example: 1 off Spirax Sarco LC2250 level controller.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-133-US 10.13
222
Controls
Boiler
Controls
Level
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
223
LC2650
Level Controller
Description
The Spirax Sarco LC2650 is a level controller for conductive liquids.
Clamping
screw
It provides on/off or modulating control of liquid levels in boilers,
tanks, and vessels operating up to 32 bar at 239ºC (464 psi@462ºF).
The controller is suitable for use with liquids having an electrical 100
conductivity as low as 5 μS/cm or 5 ppm (when used with an LP20 Graphic
or PA20 capacitance probe). display
The front panel has an LCD screen and a five-button keypad. The 50
LCD display screen can show either operating information (in run
mode), or a trend graph that displays a record of the variation in
level over a set time. 0
%
In run mode the general data is shown on several consecutive SP PV AL
screen displays.
Controls
Boiler
screw
Level
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-134-US 10.13
224
LC2650
Level Controller
Technical data LC2650
Controls
Boiler
Rising clamp plug-in terminal blocks with screw connectors.
Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd.
Mains
Safety and Approvals may be compromised otherwise.
and signal
Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
connector
Stripping length 5 - 6 mm (0.2")
Type High temperature
Controls
Level
Level probe, Shield type Screened
feedback, Number of cores 3 (LP20/PA20), 2 (LP20 4-20 mA Transducer)
steam meter and water Gauge 1 – 1.5 mm² (18 - 16 AWG)
cable / wire Maximum length 100 m (328 ft)
Prysmian (Pirelli) FP200,
Recommended type
Delta Crompton Firetuf OHLS
Type Twisted pair
Shield type Screened
0/4-20 mA output(s) Number of pairs 1
cable/wire Gauge 0.23 - 1 mm² (24 - 18 AWG)
Maximum length 100 m (328 ft)
Type EIA RS485 twisted pair
Shield type Screened
RS485 communication Number of pairs 2 or 3
cable / wire Gauge 0.23 mm² (24 AWG)
Maximum length 1200 m (4000 ft)
Recommended type Alpha Wire 6413 or 6414
LAN Cat 5 or Cat 5E ScTP (screened), FTP (foil) or STP (shielded) cable can be used, but limited to 600 m.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-134-US 10.13
225
LC2650
Level Controller
Technical data LC2650 (continued)
alarm-current
Boiler
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-134-US 10.13
226
LC2650
Level Controller
Safety information, installation and maintenance
Warning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially fatal
mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
Caution: before installing and connecting the power ensure there is no condensation within the unit. The product may be installed on
a DIN rail, on a chassis plate, or in a panel cutout. A bezel is supplied.
The product must be installed in a suitable industrial control panel or fireproof enclosure to provide impact and environmental protection.
A minimum of IP54 (EN 60529) is required. Spirax Sarco can provide suitable plastic or metal enclosures
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
All wiring materials and methods shall comply with relevant standards where applicable.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
52 mm 120 mm
(2.05") (4.72")
Controls
Boiler
Controls
LC2650
Level
100
50
140 mm 120 mm
(5.51") (4.72")
0
%
SP PV AL
OK
How to specify
Multi-voltage level controller having two alarms, configurable high or low, infrared communication as a master or slave unit.
How to order
Example: 1 off Spirax Sarco LC2650 level controller.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-134-US 10.13
© Spirax Sarco, Inc. 2000
227
APS 1 Probe Simulator
•
A valuable diagnostic aid for Spirax Sarco boiler control
installations
• Compatible with all TDS/level probes and controllers
• No need to fire boiler or alter water levels
• No battery or power supply needed
CP10
• Easy to operate Connector
Test
Description Sockets
The APS 1 probe simulator is used in place of a level or conductivity
probe to verify the correct operation of Spirax Sarco controllers. It
can also be used to diagnose wiring/probe faults. It is connected to Toggle
the level probe or conductivity probe wiring, avoiding the need to fire Switches
the boiler or alter water levels, and is quick and easy to use.
Controls
The APS 1 has switch settings covering all Spirax Sarco probe types
Boiler
and ranges.
A potentiometer provides the variable input to a capacitance control-
ler, and 4mm test sockets are provided for connection of a multime- Potentio-
meter
ter, which is used to check the voltage when simulating capacitance
probes.
Switches simulate wet or dry (high or low resistance) conductivity
Controls
level probe conditions, and resistors are built in to represent various DIN 43650
Level
Limiting conditions
Maximum ambient temperature 130°F (55°C)
Protection rating IP 40
Technical data
Conductivity probe settings 22Ω, 68Ω, 220Ω, 680Ω,
2.2kΩ, 6.8kΩ, 22kΩ
Level probe settings
LP 31 6.8kΩ/15kΩ
LP 30 6.8kΩ/15kΩ
LP 10/EL 9 (High sensitivity) 68kΩ/150kΩ
LP 10/EL 9 (Low sensitivity) 6.8kΩ/15kΩ
Capacitance probe range 0-10 Volts output
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-9-401-US 12.13
228
APS 1 Probe Simulator
5.4" 3.4"
(138) (86)
3.3"
(85)
4.3"
5.2" (110)
(132)
Controls
Boiler
Weight 1lb (450g)
Materials
Controls
Level
Case Die-cast aluminium
Coating Nylon (grey)
How to order
Spirax Sarco APS 1 probe simulator.
TI-9-401-US 12.13
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
© Spirax Sarco, Inc. 2002
229
Controls
Boiler
Controls
Level
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
230
TI-P403-41
AB Issue 3
Controls
�
panel mounted
Principalcase and has a .5" (12.7 mm) high 3½ digit LCD, with
Boiler
features:
a selectable decimal point.
- Loop powered 4-20 mA input. Materials
Because- the instrument isforloop
Pre-calibrated poweredindication.
percentage it needs no external power Front bezel / back panel Nylon 6-glass filled
supply. It requires less than 3 volts from the loop for operation. Case Aluminium
- Can be scaled for any engineering units. Technical data (at 20°C)
Principal features:
- IP65 front panel seal. Technical
Input
data 68°F (20°C)
4 - 20 mA 2 wire
- Loop powered 4-20 mA input. Input 4-20mA 2 wire
Alarms
Display 12.7 mm high LCD 3½ digit
Level
- Pre-calibrated for percentage indication.limits Display 0.5" (12.7mm) high LCD
Pressure / temperature Volt drop <3 Volt
- Can be scaled for any engineering units. 3-1/2 digit
Maximum ambient temperature 50°C Volt drop Zero <3±1Volt
- IP65 front panel seal. 000 counts
Minimum ambient temperature 0°C Zero ± 1000
Span 200 / 2counts
000 counts
Pressure / temperature limits Span
Decimal point
200/2000 counts
Any position
Safety
Maximum information,
ambient temperature installation and maintenance
122° F (50°C) Rangeability Decimal point
Rangeability
Any position
Forambient
Minimum full details see the installation
temperature and
32°F maintenance instructions
(0°C) Accuracy
Accuracy ± 1±1count
count
supplied with the product. Sample
Sample rate
rate 3 readings/second
3 readings/second
Installation note: Fuse rating
Fuse
rating 63mA
63 mA (PCB mounted)
(PCB mounted)
Safety
Theinformation, installation
DS1000 is fitted in a 92 x 44 mm and maintenance
aperture in the boiler panel. Protection
For fullIt should
details not
seebethe
installed adjacent
installation andto switch gear, electromagnetic
maintenance instructions Protection rating
rating IP65 (Front panel
IP65 (Front panelonly)
only)
starters,
supplied contacters,
with the product. thyristor power units, or motors.
How
How to
to specify
specify
Materials
Installation note: 4-20mA
4 - 20 mAloop
looppowered
powereddigital
digitaldisplay
displaywith
withlegend
legendsheet.
sheet.
The DS1000 is fitted in a 3.62" x 1.73" (92 x 44 mm) aperture in the
Front bezel / back panel Nylon 6-glass filled
boiler panel. It should not be installed adjacent to switch gear, electro- How to order example
magnetic starters, contacters, thyristor power units, orAluminium
Case motors. 1 off Spirax Sarco DS1000 digital display.
Dimensions
Dimensions
approximate in inches in
(approximate) (millimeters)
millimetres
Panel cutout 3.62" x 1.73" (92x44)
Panel cutout 92 x 44
DS1000
������ 1.89"
(48)
% 48
Made in UK
Principal features:
- High integrity, self-monitoring low level alarm probe.
- Suitable for pressures up to 0° psig @ 462°F (32 bar g at 239°C).
Controls
- No maintenance required.
Boiler
Technical data
Maximum probe cable length 164 ft (50m)
Cable socket protection rating IP65
Materials
No. Description Material
1 Probe body Austenitic BS EN 10088-3
stainless steel (1.4306)
2 Cover assembly Austenitic stainless steel Type 316L
3 Name-plate Polycarbonate
4 Cable socket and Polyamide, glass filled
probe connector
5 Connector gasket Silicone elastomer
6 Comparator tip Austenitic stainless steel Type 316L 9
7 Primary insulator and PTFE BS 6564 Grade
secondary insulator UA Type 1
8 Retaining pin Austenitic stainless steel Type 302 / 304
9 Probe tip Austenitic stainless steel Type 316L
10 Lock-nut Austenitic stainless steel BS 6105 A4 80
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-43-US 1.14
232
LP30 High Integrity,
Self-monitoring Low Level Alarm Probe
Dimensions (approximate) in inches and (millimeters) Weight (approximate) in lb (kg) including immediate packaging
Probe 19.7" 39.4" 59"
Tip length
(500 mm) (1000 mm) (1500 mm)
Weight 1.11 lb .61 lb 1.21 lb 3.6 lb
Withdrawal distance (.52 kg) (.28 kg) (.55 kg) (.8 kg)
for cable socket 0.6" (15)
Installation note:
The probe is designed to work with a Spirax Sarco LC3050 controller.
Two probes and controllers are normally fitted in steam boilers, giving
first and second low alarms.
A protection tube is required for boiler shell or turbulent tank fitting.
Install the probe in a ½" NPT (½" BSP) female connection.
Note: Do not install the probe outdoors without additional weather
8.3" (210) 11.6" (295)
protection.
The LP30 is Warning: It is essential that the probe tip of the LP30 low level alarm
available with a probe does not touch any part of the boiler. Standards require that
½" NPT screwed
connection. the tip is at least 14 mm from the protection tube, and this must be
checked when the probe is installed.
Controls
Boiler
27 A/F Maintenance note:
No special maintenance is required.
Boiler water level controls do, however, require periodic testing and in-
½" BSP taper (R½)
connection spection, which is described in separate literature.
Alarms
High integrity self-monitoring low level alarm probes shall be Spirax
Level
Sarco type LP30 with austenitic stainless steel bodies and probe tips,
PTFE probe sleeving, and cable socket with Pg 11 cable gland. They
must have a comparator tip to compensate for scaling, and a positively
located probe tip. They must be used with an appropriate Spirax Sarco
controller.
Ø10 (0.4)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-43-US 1.14
© Spirax Sarco, Inc. 2014
233
LP 31 High Integrity, Self-Monitoring
High Water Level Alarm Probe
Description
The Spirax Sarco LP31 is used in conjunction with an LC3050 controller to Cable socket
provide a high integrity, self-monitoring alarm for detection of high water levels in
steam boilers and other vessels. 1
The probe is normally installed direct in the boiler shell in a protection tube, but Pg 11
2 Cable gland
can be mounted in an external chamber if regulations permit.
3
The LP31 is supplied in three nominal tip lengths, and is cut to the exact length
required prior to installation.
In normal operation, the tip is above the water level, and has a high resistance
path to earth. If the water level rises to touch the probe tip, the resistance to 4
earth drops, causing the alarm relays in the controller to be de-energised and
the alarm to sound.
The LP31 is designed so that its tip and wiring connection integrity is monitored
by the controller, causing an alarm signal in the event of a fault occurring.
The LP31 can also be used as a simple (non self-monitoring) high or low level 5
probe with an LC1350 level controller.
A DIN 43650 cable socket with Pg 11 cable gland is supplied with the unit.
Controls
Boiler
Approvals:
The LP31 is available with a ½" NPT screwed connection.
Caution: The probe is not suitable for outside installation without additional
environmental protection.
Alarms
6 Probe body
19.7" (500), 39.4" (1000) and 59" (1500).
Limiting conditions
Nominal pressure rating PN40
Maximum boiler pressure 464 psi g (32 bar g)
Maximum temperature 462°F (239°C)
Maximum ambient temperature 158°F (70°C)
7
Technical data
Maximum probe cable length 164 ft (50 metres)
Cable socket protection rating IP65
Minimum conductivity LC1350 1 mS/cm or 1 ppm
LC3050 30 mS/cm or 30 ppm
Materials
No. Description Material
1 Cable socket Polyamide, glass filled
2 Flat gasket Silicone rubber 8
3 Probe connector Polyamide, glass filled
4 Cover assembly Austenitic stainless steel Probe tip
5 Name-plate Polycarbonate
6 Body Austenitic BS EN 10088-3 (1.4306)
stainless steel
7 Probe tip sleeving PTFE
8 Probe tip Austenitic stainless steel ASTM A276 316L
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-81-US 1.14
234
LP 31 High Integrity, Self-Monitoring
High Water Level Alarm Probe
Dimensions (approximate) in inches and millimeters Weights (approximate) in lb (kg)
Tip length 19.7"500 mm) 39.4" (1000 mm) 59.1" (1500 mm)
Weight 1.1 (0.51) 1.3 (0.59) 1.5 (0.67)
Withdrawal distance
for cable socket 0.6" (15) Safety information, installation and maintenance
This document does not contain sufficient information to install the
product safely. See the Installation and Maintenance Instructions
provided with each unit.
1.5" (39)
Installation note:
The LP31 tip is cut to length and de-burred prior to installation.
The LP31 has been designed to work with a Spirax Sarco LC3050
controller.
A protection tube is required for boiler shell or turbulent tank fitting.
Install the probe in a ½" NPT parallel (½" BSP) female connection using
PTFE tape.
Note: Do not install the probe outdoors without additional weather
protection.
Maintenance note:
7.2" (183) No special maintenance is required.
Boiler water level controls do, however, require periodic testing and
inspection, which is described in separate literature.
Spare parts
1.1" (Ø28) There are no available spare parts for this unit.
Controls
Boiler
How to specify
High integrity high level alarm probes shall be Spirax Sarco self-
monitoring type LP31 with an austenitic stainless steel body and probe
tip, PTFE probe sleeving, and DIN 43650 cable socket with Pg 11 cable
27 A /F gland. They shall be cut to length on installation and be used with an
appropriate Spirax Sarco controller.
Alarms
How to order
Level
The LP31 is
available with a Example: 1 off Spirax Sarco LP31 high integrity, self-monitoring, high
½" NPT screwed water level alarm probe with 39.4" (1000 mm) tip.
connection.
0.24" (Ø6)
Tip length
19.7"(500), 39.4"(1 000)
or 59"(1500)
0.2" (Ø5)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-81-US 1.14
© Spirax Sarco, Inc. 2014
235
LC3050
Level Controller
Description
The Spirax Sarco LC3050 is a level limiting alarm for use in Clamping
conductive liquids as a high or a low alarm, and is defined as a screw
'special design water level limiter' in the context of EN 12952-11. It
is suitable for use with steam or hot water boilers operating up to 32
bar at 239ºC (464psig@462°F). LC3050
The LC3050 is a dual voltage unit, 230 Vac or 115 Vac for use with
Spirax Sarco high or low level, self-monitoring high integrity probes.
ALARM
The LC3050 has two LED’s, indicating normal and alarm conditions,
and a test button (AL). The other buttons on the keypad are non-
functional. OK
A test button is fitted so that a full test of the probe, controller, and button
Boiler
Principal features:
- High integrity, self-monitoring low or high level alarm. Function / Inputs / Outputs
- TÜV approved.
- Dual mains supply, 230 / 115 Vac. Function
- LED indication of status. The LC3050 is normally configured to warn of a change in level
- Infrared communications. outside normal limits for steam or hot water boilers, tanks or
vessels, by engaging an alarm relay. Spirax Sarco high-integrity,
Approvals self-monitoring probes can indicate internal faults or water ingress.
This product complies with the Electromagnetic Compatibility
Directive 2004 / 108 / EC and all its requirements. The LC3050 compares the resistance to earth from the probe,
through the water, to the boiler or vessel shell. If a change in water
This product meets all the Requirements of the Directive and is level causes this resistance to change beyond a set limit, a timer
suitable for Class A Environments (eg Industrial). The LC3050 is engaged which alters the state of internal relays after a pre-set
meets the requirements of the Directive by meeting the Controlling delay. This signal is normally used to trigger an alarm, and cut the
standard: supply to the burner.
- EN 61326-1: 2006 - Electrical equipment for measurement
control and laboratory use - EMC requirements Part 1: General Input / output
requirements. The product accepts inputs from the LP30 low level probe or the
LP31 high level probe.
In addition the LC3050 meets the EMC requirements of the following
standards: With the water level normal the green LED will be lit, and the boiler
- EN 12953-9: 2007 - Shell boilers Part 9: Requirements for limiting panel will indicate a normal water level. The green LED briefly
devices of the boiler and accessories. extinguishes every few seconds showing that the automatic cyclic
- EN 12952-11: 2007 - Water-tube boilers and auxiliary installations test is being carried out.
Part 11: Requirements for limiting devices of the boiler and
accessories. A compensation tip on the probe signals an alarm if the probe
should become faulty through water ingress or an internal wiring
The LC3050 has been type-tested as a Special Design Water Level fault.
Limiter by meeting the Standard:
- Vd TÜV requirements for water level control and limiting devices, Outputs can be remotely accessed via the RS485 / MODBUS
Water Level 100 (07.2010). communications.
The product complies with Low Voltage Directive (2006 / 95 / EC) by Other features
meeting the standards of: The LC3050 can communicate via an infrared link between adjacent
- EN 61010-1:2001 Safety requirements for electrical equipment for controllers. It enables the alarm status of the LC3050 to be passed
measurement, control and laboratory use. to a product fitted with RS485 (user). User products are those fitted
with a graphics display. The LC3050 is defined as a slave unit. No
set-up or adjustment is needed.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P402-135-US 10.13
236
LC3050
Level Controller
Technical data LC3050
Controls
Solder Tin / lead (60 / 40%)
Boiler
Rising clamp plug-in terminal blocks with screw connectors.
Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd. -
Mains
Safety and Approvals may be compromised otherwise.
and signal
Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
connector
Cable / wire Stripping length 5 - 6 mm (0.2")
and Type High temperature
Alarms
Level
connector Shield type Screened
data Level probe Number of cores 4
cable / wire Gauge 1 – 1.5 mm² (18 - 16 AWG)
Maximum length 50 m (164 ft)
Recommended type Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-135-US 10.13
© Spirax Sarco, Inc. 2005
237
LC3050
Level Controller
Safety information, installation and maintenance
Warning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially fatal
mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
Caution: before installing and connecting the power ensure there is no condensation within the unit. The product may be installed on
a DIN rail, on a chassis plate, or in a panel cutout. A bezel is supplied.
The product must be installed in a suitable industrial control panel or fireproof enclosure to provide impact and environmental
protection. A minimum of IP54 (EN 60529) is required. Spirax Sarco can provide suitable plastic or metal enclosures
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
52 mm 120 mm
(2.05") (4.72")
Controls
Boiler
LC3050
Alarms
Level
ALARM
OK
140 mm 120 mm
(5.51") (4.72")
AL
How to specify
High-integrity self-monitoring level controller with fail-safe operation and self-testing facilities. LED indication of alarm and safe status.
Infrared communications facility. A test button facility shall be provided on the front panel.
How to order
Example: 1 off Spirax Sarco LC3050 level high-integrity, self-monitoring level controller.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P402-135-US 10.13
238
Controls
Boiler
Alarms
Level
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
239
BCS1 Blowdown System Pipeline Set
Blowdown
from
boiler
strainer
• For blowdown rates up to 1,300 lb/h (590 kg/h) M10 ball valve
& CCD
Description
The BCS1 pipeline set is a kit of components selected to enable Blowdown
straightforward installation of a TDS control system where the probe to heat recovery
assembly is to be mounted in the pipeline, rather than directly in the system
boiler shell.
The BCS1 pipeline set consists of the following items: BC1100
1 x S10 sensor chamber ½" NPT. • DIN rail or chassis plate mounting.
1 x CP10 sensor and gasket. • LED indication of blowdown status.
1 x PT2 plug tail. (3/8" BSP) • Potentiometer adjustment of set point and calibration.
1 x Sensor chamber plug ¼" BSP. • Choice of purge duration.
1 x BCV1 solenoid valve 120 V. • 0 -20 or 4 - 20 mA output.
1 x LCV1 check valve ½" NPT. • Selectable ranges (ppm or μS/cm).
1 x y type cast iron strainer (1/2" NPT, 20 Mesh). Also available:-Wall-mounting plastic enclosure with DIN rail.
2 x M10 ball valves ½" NPT.
Alternative products are available, but not as part of a kit. BC3200
A controller is also required, and should be selected from the Spirax • Wall mounting.
Sarco range. • Two button commissioning, calibration, and operation.
The BC3150 and BC3250 are all suitable, and offer a choice of fea- • Selectable ranges (ppm or μS/cm).
tures. Full details are available in separate literature. • Four digit LED display of TDS and system status.
Main features are listed opposite. • High TDS alarm relay output.
• 0 -20 or 4 - 20 mA output.
Materials • Patented automatic probe cleaning circuit.
S10 sensor chamber Stainless steel BS 970 303 S31 • Temperature compensation facility.
CP10 sensor body and pin Stainless steel BS 970 303 S31 • Selectable security feature.
PT2 plug tail Brass body • Optional front cover lock available.
Sensor chamber plug Carbon steel
BCV1 solenoid valve Brass body, stainless steel seat, BC3210
PTFE seal. • As BC3200, but boiler panel mounting.
LCV1 check valve Bronze • Optional lockable cover available.
Strainer Cast iron
M10 ball valve Zinc plated forged carbon steel
See individual product literature for further information.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P403-57-US 12.13
240
BCS1 Blowdown System Pipeline Set
Limiting conditions Safety information
Maximum boiler pressure 203 psig (14 bar g). WARNING: Your attention is drawn to Safety Information Leaflet
IM-GCM-10, as well as to any National or Regional regulations.
Capacities The products contained in the BCS1 pipeline set are designed and
The capacity of the system is limited by the blowdown valve capacity constructed to withstand the forces encountered during normal use.
at various boiler pressures. Use of the BCS1 pipeline set other than for the control of TDS could
cause damage to the products and may cause injury or fatality to
Boiler Low to medium Medium to high personnel.
pressure flowrates flowrates The BCV1 valve and CP10 sensor contain PTFE which can give off
psig (bar g) (Standard setting*) (High setting*) toxic fumes if exposed to excessive heat.
14.5 (1) 60 175
29.0 (2) 85 250
58.0 (4) 115 350 Installation
87.0 (6) 130 385 This document does not contain sufficient information to install the
116.0 (8) 150 445 product safely. See the Installation and Maintenance Instructions
145.0 (10) 165 495 provided with each kit.
203.0 (14) 200 590
*At 'Standard setting' the controller is set to open the valve for Available spares
10 seconds every 30 seconds. Armature and spring set for BCV1 blowdown valve (kit).
When blowing down at 'High setting' the controller opens the valve Stock No. 4034080
continuously.
How to order
Weight Example: 1 off Spirax Sarco BCS1 pipeline set.
Boxed kit approximately 8.2 lbs (3.7 kg).
Electrical data
BCV1 solenoid (blowdown) valve
Controls
Voltage range 209 V to 264 V
Boiler
Frequency range 50 to 60 Hz
Power consumption 40 VA (inrush)
16 VA/10 W (hold)
Protection rating IP65
Boiler Blowdown
& CCD
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-57-US 12.13
241
S20 Sensor Chamber, TP20 Temperature Sensor,
CP10 Sensor and PT2 Plug-tail Cast Iron Valves
• Purpose designed sensor chamber for in-line mounting
• Simple removal of sensors for cleaning
• Allows continuous temperature compensated measurement
Limiting Conditions
Boiler Blowdown
Maximum media temperature 302°F (150°C) Caution: Do not install the sensor outdoors without additional
weather protection.
CP10 conductivity sensor Fit the sensor chamber in a vertical or horizontal pipeline with suit-
Maximum pressure 464 psig (32 barg) able isolation valves to allow inspection/cleaning of the sensors.
Maximum media temperature 462°F (239°C) Reducers may be fitted if required. Flow can be in either direction.
Torque rating 44 lb./f (60 Nm) The sensors themselves must be horizontal.
The TP20 has a taper thread, and may be installed using PTFE seal-
PT2 Plug-tail ing tape if required.
Cable temperature range -67 to 248°F (-55 to 120°C)
The CP10 sensor is provided with an S-type stainless steel gasket for
Supplied cable length 50" (1.25m)
sealing and does not require sealing tape.
Maximum voltage 20Vdc, 14Vac
Maximum current 10mA Fit the sensors to the chamber and tighten.
Fit PT2 plug tail (or other Spirax Sarco plug tail) to the CP10 sensor
and tighten.
Red wire to
CP10 PT2 sensor pin
Sensor Plug-tail
To blow-
down
controller
Insulation
Sensor pin Screen
3/8" Blue wire ground- Junction box
24mm Nut 1 ed via PT2 and
BSP (For connection to conduit)
AF CP10 body.
25mm
AF
The supply to the Sensor and Plug-tail must be provided by a low voltage limited power source.
Spirax Sarco Blowdown controllers provide this type of supply.
Flexible metal conduit (M16) can be connected to the PT12 by removing the nut (1)
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-9-403-US 08.11
242
S20 Sensor Chamber, TP20 Temperature Sensor,
CP10 Sensor and PT2 Plug-tail
Maintenance How to Specify
The equipment requires no specific maintenance other than periodic In line sensor chamber with conductivity and temperature sensors.
inspection and cleaning. CP10 Conductivity Sensor and PT2 Plug-tail.
Materials
S20 sensor chamber How to Order
Stainless steel ASTM 8582303 BS 970 303 S31 Spirax Sarco’s S20 sensor chamber complete with CP10 sensor,
PT2 plug tail, 1/4" BSP blanking plug, and TP 20 temperature
PT2 Plug-tail sensor.
Body Brass
Nuts Brass (2off)
Insulator Polyphenylene Sulphide Resin (glass filled)
Controls
Boiler
Dimensions (approximately) in inches
Boiler Blowdown
4"
& CCD
S-type stainless
2-1/4" steel gasket
CP10 sensor
(shown with PT2
Standard plug tail fitted).
length 50"
4-3/4"
1/4" BSP
50" sample
connection
TP20
temperature
sensor
1" NPT
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-9-403-US 08.11
© Spirax Sarco, Inc. 2001
243
CP 30 Conductivity Probe
Description
The Spirax Sarco CP30 conductivity probe is used in conjuction with a control-
ler to measure the conductivity or TDS of water, usually in a steam boiler for the
purpose of monitoring and controlling blowdown. The probe may be installed in
a Spirax Sarco probe elbow, a screwed flange, or directly in a boiler connection.
The CP30 is supplied in four nominal tip lengths, and is cut to the exact length
required prior to installation.
A DIN 43650 cable socket with 1/2" NPT conduit thread and four 18AWG wires
are supplied with the unit.
Controls
Boiler
Limiting conditions
Maximum boiler pressure 464 psig (32 barg)
Maximum temperature 462°F (239°C)
Hydraulic ambient temperature 158°F (70°C)
Boiler Blowdown
Installation
Probes with tip lengths up to 19.7" (500mm) can be installed vertically or
horizontally. Vertical installation only is recommended for longer lengths.
The probe must be installed in a position where it can sense the conductivity of
the boiler water, away from the feed water inlet if possible. Full instructions on
cutting the probe tip to length, wiring, and maintenance are given in the
Installation and Maintenance Instructions supplied with each unit.
Available Spares
Tip shroud and spring assembly, stock No. 4031280.
How to Specify
Conductivity probe with all wetted parts in austenitic stainless steel and
PTFE, 1/2" NPT, tip length 19.7" (500mm).
Tip shroud
How to Order
Spirax Sarco UL CP30 (1/2" NPT) probe with 19.7" (500mm) tip.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-9-202-US 08.11
244
CP 30 Conductivity Probe
Withdrawal distance for
Dimensions (approximate) in inches cable socket 0.6" (15)
and millimeters
Installation Examples
1.5" (39)
1
2 Installation on a probe Probe elbow
elbow, ideally on the
horizontal center line
3
of the boiler.
To blowdown valve
7.0" (178)
5
Installation on a boiler
(screwed or flanged)
Controls
Boiler
1/2" NPT
Thread
Boiler Blowdown
& CCD
Tip
8 Length
Vertical installation on
a boiler standpipe
9
Materials
No Description Material
1 Cable socket Polyamide, glass filled
2 Flat gaket Silicone rubber
10 3 Probe connector Polyamide, glass filled
4 Cover assembly Austenitic stainless steel
Terminal box
Wiring 5 Nameplate Aluminum foil
6 Body Austenitic stainless steel Type 316Ti
W/S No. 1.4571
CP30 7 Probe tip Austenitic stainless steel
Connector ASTM A276 316L
8 Probe tip sleeving PTFE
Probe tip Grounded to 9 Tip shroud PTFE
probe body 10 Spring Austenitic stainless steel
BS 2056 316 S42
Approvals 1
1 Flying leads Copper conductor, PVC insulation
UL UL61010 18AWG CSA TEW 105oC,
United States UL1015 105oC, 600V
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-9-202-US 08.11
© Spirax Sarco, Inc. 2001
245
CP 32
Twin Tip Conductivity Probe
Description
The Spirax Sarco CP32 conductivity probe is used in conjunction with
a controller to measure the conductivity (or TDS) of water, usually in a
steam boiler, for the purpose of monitoring and controlling blowdown.
The CP32 has a built-in temperature sensor, and when used with
an appropriate controller, is able to detect scaling (UK Patent No.
2297843). It also automatically initiates a probe conditioning cycle 2
(internal)
(UK Patent No. 2276943). This causes any scale on the probe to
become porous or fall off, allowing the probe to continue to sense at 1
its original calibration level.
WARNING: This feature is not a substitute for adequate boiler
water treatment. If scale is occuring on a probe, it is also accur-
ing inside the boiler, and a competent water treatment specialist
must be consulted to avoid a potentially dangerous situation.
4 3
The CP32 is supplied in three nominal tip lengths, and has a ½" NPT
Controls
Principal features :
- Twin tip conductivity probe for use in TDS control systems.
- Built-in temperature sensor - only one boiler connection needed.
Boiler Blowdown
Technical data
Protection rating (terminal head / cable gland only) IP65
Minimum tip distance from boiler tubes 0.4" 10
Minimum immersion depth
4.0"
(vertically installed probes)
Maximum cable length
328 ft
(probe to controller)
Minimum conductivity 10 ppm
Materials
No. Part Material
1 Terminal
Aluminium
head
2 'O' ring Nitrile rubber
3 Cover tube Austenitic stainless steel Type 316L
4 Name-plate Polycarbonate
5 Body Austenitic stainless steel Type 304L 1.4306 7
6 Spring Austenitic stainless steel 302 S26 6 and 8
7 Insulator PEEK (Internal)
8 Driver tip Austenitic stainless steel Type 316
9 Sensor tip Austenitic stainless steel UGINE 4632
10 Rod Austenitic stainless steel Type 316 / 316L 9
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P403-59-US 08.08
246
CP 32 Twin Tip Conductivity Probe
Dimensions (approximate) in inches Safety information
For full details see the Installation and Maintenance Instructions sup-
plied with the product, which gives full wiring, commissioning and
operating instructions.
Warning:
This product contains materials including PTFE which can give off
toxic fumes if exposed to excessive heat.
M20
4.3
Installation Note:
Do not install the probe outdoors without additional weather protection.
11.8" and 19.7" probes can be installed vertically or horizontally.
CAUTION: 39.4" probes must be installed vertically only. The probe
must be installed in a position where it can sense the conductivity of
the boiler water, away from the feedwater inlet if possible.
The CP32 contains no user serviceable components, and periodic
cleaning is all that is required. Any attempt to dismantle the probe will
result in permanent damage.
Spare parts
The spare parts available are detailed below. No other parts are sup-
6.4 plied as spares.
Available spares
Enclosure 'O' ring 2
How to order spares
Always order spares by using the description given in the column
27 A / F headed 'Available spares' and state which product they are for.
Example: 1 off Enclosure 'O' ring for a Spirax Sarco CP32 twin tip
½" NPT
conductivity probe.
Controls
Boiler
How to specify
TDS conductivity probes shall be Spirax Sarco type CP32 with
nickel alloy sensor tips and built-in temperature sensor. They must
incorporate a patented facility to check the sensor tips for scaling.
Boiler Blowdown
When used in conjunction with an appropriate Spirax Sarco control-
ler, they must also be able to automatically initiate a patented probe
& CCD
cleaning feature, which, if unable to clean the probe, will activate a
warning on the controller’s display panel and / or a remote alarm. The
system must also be able to automatically compensate for any polari-
sation effects at the sensors. They must be suitable for boiler pres-
sures up to 464 psig and a maximum working temperature of 462°F.
They must be available in 11.8", 19.7" and 39.4" lengths, and have a
1/2" NPT boiler connection.
Tip length
11.8, 19.7 or 39.4
How to order
Example: 1 of Spirax Sarco CP32, twin tip conductivity probe having
a ½" NPT connection and 11.8" tip length.
Weights (approximate) in lb
Tip length 11.8" 19.7" 39.4"
Weight 2.2 2.6 3.5
© Spirax Sarco, Inc. 2008
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-59-US 08.08
247
BC3150
Blowdown Controller
Description
The BC3150 is a blowdown controller for steam boilers. It controls Clamping
TDS (total dissolved solids – salts in solution) by opening and screw
closing a blowdown valve. It works in conjunction with a Spirax
Sarco conductivity sensor, a boiler blowdown valve or condensate
dump valve. BC3150
The product can be panel, DIN rail or chassis mounted and powered
by a 110 to 240 Vac mains supply.
The front panel has a 3 digit LCD and a five-button keypad.
The product has no battery. The programmed settings are held x1000
LCD display
in non-volatile memory (Flash) and are written to after changing a x100
Principal features:
- Blowdown controller with temperature compensation.
- Type approved as a TDS limiter and controller.
- Works with CP10, CP30 or CP32 conductivity probes.
Controls
x 1000). CLN AL
- LCD display with direct probe condition indicator. 5 button
display
- Infrared communications. OK
Approvals
This product complies with the Electromagnetic Compatibility
Boiler Blowdown
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P403-91-US 10.13
248
BC3150
Blowdown Controller
Technical data BC3150
Controls
Boiler
Mains Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd. -
Safety and Approvals may be compromised otherwise.
and signal
connector Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
Stripping length 5 - 6 mm (0.2")
Type High temperature
Boiler Blowdown
Shield type Screened
& CCD
Gauge 1 – 1.5 mm² (18 - 16 AWG)
TDS probe 0 - 9.99 range - 10 metres (33ft)
Maximum length 0 - 99.90 range - 30 metres (100ft)
0-999.0 range and 0-9990 ranges - 100 metres (328ft)
Recommended type Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
Cable / wire Type High temperature, twisted
and
Shield type Screened
connector
Pt100 probe Number of cores 3
data
cable / wire Gauge 1 - 1.5 mm² (18 - 16 AWG)
Maximum length 100 m (328 ft)
Recommended type Various
Type Twisted pair
Shield type Screened
4 - 20 mA
Number of pairs 1
output
Gauge 0.23 - 1 mm² (24 - 18 AWG)
cable / wires
Maximum length 100 m (328 ft)
Recommended type Various
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-91-US 10.13
© Spirax Sarco, Inc. 2001
249
BC3150
Blowdown Controller
Technical data BC3150 (continued)
Time 20 seconds
Boiler
Minimum current 0 mA
Maximum current 20 mA
Open circuit voltage
19 Vdc
(maximum)
Boiler Blowdown
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-91-US 10.13
250
BC3150
Blowdown Controller
Safety information, installation and maintenance
Warning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially fatal
mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
Caution: before installing and connecting the power ensure there is no condensation within the unit. The product may be installed on
a DIN rail, on a chassis plate, or in a panel cutout. A bezel is supplied.
The product must be installed in a suitable industrial control panel or fireproof enclosure to provide impact and environmental
protection. A minimum of IP54 (EN 60529) is required. Spirax Sarco can provide suitable plastic or metal enclosures
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
Dimensions / weight (approximate)
Weight 1 lb
52 mm 120 mm
(2.05") (4.72")
Controls
Boiler
Boiler Blowdown
BC3150
& CCD
x1000
x100
x10
140 mm 120 mm
(5.51") (4.72")
CLN AL
OK
How to specify
Blowdown controller with LCD display and five-button keypad, and infrared communications.
How to order
Example: 1 off Spirax Sarco BC3150 blowdown controller.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-91-US 10.13
251
BC3250
Blowdown Controller
Description
The BC3250 is a blowdown controller for steam boilers. It controls
TDS (total dissolved solids - salts in solution) by opening and closing Clamping
a blowdown valve. screw
The front panel has an LCD graphics display and five-button keypad
to select, view, and change functions.
0
%
In run mode (standard setting) the display is divided into three
sections: SP PV AL
Controls
ii) Information line, displays the various control states and process
5 button
units. display
iii) Three bar graphs, which show a percentage of full scale of: OK
- PV Process Variable highest and lowest recorded value.
- SP Set Point and hysteresis point.
- AL High Alarm and hysteresis point.
Boiler Blowdown
Clamping
An additional filter can be selected to increase the damping effect screw
where the probe is fitted directly in the boiler. This avoids over-
& CCD
The BC3250 can communicate via an infrared link between adjacent Function
controllers. It can be designated as either a master unit or a slave unit. Inputs
The BC3250 can accept a signal from a Spirax Sarco CP10, CP30 or
The unit can be panel, DIN rail or chassis mounted. CP32 conductivity probe, and a Pt100 temperature sensor.
252
BC3250
Blowdown Controller
Technical data BC3250
Controls
Mains
Boiler
Safety and Approvals may be compromised otherwise.
and signal
Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
connector
Stripping length 5 - 6 mm (0.2")
Type High temperature
Shield type Screened
Boiler Blowdown
Number of cores 4
TDS cable / wire
& CCD
Gauge 1 – 1.5 mm² (18 - 16 AWG)
0 - 9.99 range - 10 metres (33ft)
Maximum length 0 - 99.90 range - 30 metres (100ft)
0-999.0 range and 0-9990 ranges - 100 metres (328ft)
Prysmian (Pirelli) FP200,
Recommended type
Delta Crompton Firetuf OHLS
Type High temperature, twisted
Shield type Screened
Pt100 probe Number of cores 3
cable / wires Gauge 1 – 1.5 mm² (18 - 16 AWG)
Maximum length 100 m (328 ft)
Type Twisted pair
Shield type Screened
0/4-20 mA output(s) Number of pairs 1
cable/wire Gauge 0.23 - 1 mm² (24 - 18 AWG)
Maximum length 100 m (328 ft)
Recommended type various
Type EIA RS485 twisted pair
Shield type Screened
RS485 communication Number of pairs 2 or 3
cable / wire Gauge 0.23 mm² (24 AWG)
Maximum length 1200 m (4000 ft)
Recommended type Alpha Wire 6413 or 6414
LAN Cat 5 or Cat 5E ScTP (screened), FTP (foil) or STP (shielded) cable can be used, but limited to 600 m.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-90-US 10.13
© Spirax Sarco, Inc. 2001
253
BC3250
Blowdown Controller
Technical data BC3250 (continued)
4 - 20 mA Resolution 1% FSD
Maximum output load 500 ohm
Isolation 100 V
Output rate 10 / second
Contacts 2 x single pole changeover relays (SPCO)
Voltage ratings (maximum) 250 Vac
Resistive load 3 amp @ 250 Vac
Output Inductive load 1 amp @ 250 Vac
technical Relays ¼ HP (2.9 amp) @ 250 Vac
ac motor load
data 1
/10 HP (3 amp) @ 120 Vac
Pilot duty load C300 (2.5 amp) - control circuit / coils
Electrical life (operations) 3 x 10 5 or greater depending on load
Mechanical life (operations) 30 x 10 6
Physical layer RS485 4-wire full or 2-wire half duplex
Protocol Modbus RTU format
RS485 Isolation 60 Vac/dc
Receiver unit load (256 devices - maximum)
Output rate Up to 10 frames / second
Physical layer IrDA
Baud 38 400
Infrared Range 10 cm (4")
Working angle 15°
Exempt from EN 60825-12: 2007 Safety of laser products -
Eye safety information
does not exceed the accessible emission limits (AEL) of Class 1
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-90-US 10.13
254
BC3250
Blowdown Controller
Safety information, installation and maintenance
Warning: This document does not contain sufficient information to install the unit safely. The unit operates at a potentially
fatal mains voltage. Before attempting to install the unit read the Installation and Maintenance Instructions supplied with it.
The product must be installed in a suitable industrial control panel or fireproof enclosure to provide impact and environmental
protection. A minimum of IP54 (EN 60529) is required.
The product may be installed on a DIN rail, a chassis plate, or in a panel cut-out. A bezel is supplied.
Install the product in an environment that minimizes the effects of heat, vibration, shock and electrical interference.
Do not install the product outdoors without additional weather protection.
Do not attempt to open the product - it is sealed and has no replaceable parts or internal switches.
Do not cover or obstruct the infrared beam between products.
No special servicing, preventative maintenance or inspection of the product is required.
Boiler water level controls and level alarms do, however, require testing and inspection.
Dimensions / weight (approximate)
Weight 1.21 lb
52 mm 120 mm
(2.05") (4.72")
Controls
Boiler
BC3250
Boiler Blowdown
& CCD
100
50
140 mm 120 mm
(5.51") (4.72")
0
%
SP PV AL
OK
How to specify
Blowdown controller with integral bottom blowdown timer and infrared comms.
How to order
Example: 1 off Spirax Sarco BC3250 blowdown controller.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-90-US 10.13
255
BCV1 and BCV20
Blowdown Valves
Description
The BCV1 and BCV20 valves are small bore, normally closed
valves with a brass body and corrosion resistant internal
components. They are primarily intended for low and medium
pressure boiler blowdown applications.
BCV1 and BCV20 valves are identical apart from the orifice size, the
BCV1 having a 3 mm (1/8") orifice and the BCV20 a 6 mm (¼") ori-
fice. Valves are supplied complete with a mains connector, which
is protected to IP65 and is suitable for 3 x 1 mm² (18 AWG) cable.
Limiting conditions
BCV1
Controls
Maximum boiler or
steam pressure 9 bar g (130 psi g)
Medium temperature range -40 to +180°C (-40 to +356°F)
Medium Water and steam
Maximum ambient temperature 55°C (130°F)
BCV20
Maximum boiler or
steam pressure 4 bar g (58 psi g)
Medium temperature range -40 to +180°C (-40 to +356°F)
Medium Water and steam
Maximum ambient temperature 55°C (130°F)
Electrical data
230 V version 207 V to 253 V
110 V version 99 V to 121 V
120 V version 108 V to 132 V
Frequency 50 - 60 Hz
40 VA (inrush)
Maximum power consumption
16 VA /12 W (hold)
Protection rating IP65 (Nema 4)
Materials
Body Brass
Soft seal PTFE
Internal components Stainless steel
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P403-60-US 11.11
256
BCV1 and BCV20
Blowdown Valves
Dimensions /weight (approximate) in mm (ins) and kg (Ibs) Spare parts
The spare parts available are detailed below. No other parts are
A B C D E Weight supplied as spares.
40 110 74.5 94.5 73 0.75 Available spares
(1.57) (4.33) (2.93) (3.72) (2.87) (1.65)
Armature and spring set (kit). Stock No. 4034080
E
Solenoid coil 230 V Stock No. 4034081
A
Solenoid coil 110 /120 V Stock No. 4034082
How to order spares
Always order spares by using the description given in the column
headed 'Available spares' and state the valve type.
Example: 1 off Armature and spring set (Stock No. 4034080) for
D a Spirax Spirax BCV20 blowdown valve.
B
Capacities
Model BCV1 BCV20
Solenoid coil
Orifice size 3 mm (1/8") 6 mm (¼")
Cv value 0.3 0.9
For conversion: Cv (UK) = Kv x 0.963 Cv (US) = Kv x 1.156
Spring
Controls
When used for boiler blowdown purposes, the valve will be
Boiler
controlling a mixture of water and flash steam, so the following Armature with
capacity table applies:- PTFE valve seat
Capacity kg /h (Ib /h)
Boiler
pressure
bar g (psi g) BCV1 BCV20
1 (14.5) 175 (385) 560 (1232)
Boiler Blowdown
2 (290) 250 (550) 790 (1738)
4 (580) 350 (770) 1120 (2464)
& CCD
6 (870) 385 (847) -
8 (1160) 445 (979) -
10 (1450) 495 (1089) -
14 (2030) 590 (1298) -
How to specify
BCV1
Solenoid valves shall be Spirax Sarco normally closed blowdown
valve type BCV1 or BCV1 (UL/CSA) with brass bodies and stain-
less steel valve seat with a PTFE seal.
BCV20
Solenoid valves shall be Spirax Sarco normally closed, low pres-
sure blowdown valve type BCV20 with brass bodies and stainless
steel valve seat with a PTFE seal.
How to order
Example: 1 off Spirax Sarco BCV1 or BCV20 blowdown valve
having screwed NPT connections, 120 V.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-60-US 11.11
© Spirax Sarco, Inc. 2001
257
(24v Version)
wheel clockwise.
A 1/4’’ BSP tapping is provided for a sample cooler.
& CCD
12
Full installation, adjustment and maintenance information is pro-
13 25
vided with the valve. 11
10
Sizes and Pipe Connections
3/4’’ Flanged ANSI 300
Operation 9
The valve is spring loaded to the closed position.
When power is applied to the actuator the valve opens to the posi-
3
tion set by the internal limit switch.
4
Limiting Conditions 5 16
Maximum pressure 464 psig (32 barg) 6 15
8
Maximum temperature 462˚F (239˚C)
Maximum ambient temperature 122˚F (50˚C) 22
Protection rating (IP54)
Outdoor installation is not recommended without additional protection. 23
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification.
TI-9-305-US 11.11
258
3/4" BCV 30 Blowdown Control Valve
Materials Safety Information
Valve WARNING
Body Cast carbon steel DIN 17245 GS-C25 Your attention is drawn to Safety Information Leaflet IM-GCM-10,
Bonnet Forged steel carbon DIN 17234 C 22.8 as well as to any National or Regional regulations. This product is
Stuffung box Martenistic stainless steel Type 431 designed and constructed to withstand the forces encountered dur-
Bottom Cover Carbon steel BS 907 230 M07 ing normal use. Use of the product for any purpose other than a
Internals Martenistic stainless steel Type 431 blowdown control valve could cause damage to the product and may
(Valve cone and seat hardened) cause injury or fatality to personnel.
Actuator
Casing Die cast Aluminum Installation
Cover ABS This document does not contain sufficient information to install the
Cylinder/piston Aluminum product safely. See the Installation & Maintenance Instructions pro-
vided with every unit. Do not install the valve outside without addi-
tional weather protection.
Dimensions/Weights (approximate) in inches and lbs.
Size A B C D Weight Maintenance
3/4’’ 6’’ 15-3/8’’ 5’’ 1/4’’ BSP 20 lb. It is recommended that the valve is examined annually and parts
replaced if necessary. For detailed maintenance instructions, see
Installation & Maintenance Instructions (IM-P403-15).
C
UL Listed
12
Valve Sealing
Arrangement
13
11
Controls
B 20
Boiler
10
Boiler Blowdown
& CCD
D Sample bake-off 45
A
How to order
Example: Spirax Sarco BCV30 blowdown valve, 24V, flanged
3/4" ANSI 300, and approved by Underwriters Laboratory as a
Listed Product.
Spare parts
Spare parts are available as listed below. No other parts are
available as spares.
Gasket & packing set
24V (UL) Stock No. 4034480 4,9,10,11,12,13,16,20,22
115/230V Stock No. 4034482 4,9,13,16,22,41
Valve cone, seat & stem set
24V (UL) Stock No. 4034481 3,5,6,7,8,15
115/230V Stock No. 4034483 3,5,6,7,8,15,16,45 + Gasket
and packing set
Adjustable stuffing box kit Blowdown Valve Capacity in lb/h
115/230V Stock No. 4034484 40,42,43,44 + Gasket and Boiler Pressure Low Flowrates Medium flowrates High flowrates
packing set psig .4’’ stroke (10mm) .6’’ stroke (15 mm) .8’’ stroke (20 mm)
Note: The adjustable graphite seal system is not currently Approved
80 880 1210 1900
for use on the UL Listed valve.
102 1015 1565 2540
Actuator with limit switch assembly 145 1260 2100 3310
115V Stock No. 4034466 218 1540 2540 3640
230V Stock No. 4034467 290 1720 2760 3750
24V (UL) Stock No. 4034468 464 2075 3090 3970
Actuator limit switch assembly: 24 (UL) /115/230V versions
Stock No. 4034419
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-9-305-US 11.11
© Spirax Sarco, Inc. 2003
259
1-1/2" BCV 30 Blowdown Control Valve
• Electrohydraulically actuated valve with manual override
• Cast steel body with stainless steel internals
• Articulated valve cone ensures tight shut-off and correct align-
ment
• Spring closure on power failure
• Valve position indicator Cover
Description
The Spirax Sarco BCV30 is an electrohydraulically actuated control Casting
valve for the blowdown of steam boilers or other high pressure drop,
low flowrate applications.
It is generally used with a blowdown controller as part of an auto-
matic TDS control system.
The flowrate is adjusted by limiting the spindle stroke to regulate the Cylinder/
size of the orifices that are uncovered. piston
The valve, which is supplied adjusted to a flowrate setting of 0.4’’
stroke, is especially designed to minimize seat erosion and ensure
Controls
Operation Bonnet
The valve is spring loaded to the closed position.
When power is applied to the actuator the valve opens to the posi- Guide bush
tion set by the internal limit switch. Stroking time for the full 0.8"
Body
stroke is approximately 2 minutes to open and 8 seconds to close.
Materials
Valve Material
Body Cast carbon steel DIN 17245 GS-C25
Bonnet Forged steel carbon DIN 17243 C 22.8
Stuffing box Martensitic stainless steel/ ASTM A276
assembly graphite seals 316L
Internal
Bottom Cover Carbon steel BS 970 230 M07
components
Internals Martensitic stainless steel Bottom cover
Type 431
components (valve cone and seat hardened)
Guide bush Phosphor bronze BS EN 12163 CW451K
Casing Die cast Aluminum
Cover ABS Electrical data
Cylinder/piston Aluminum Supply 19 V - 28 V 50-60 HZ
Stem Martensitic stainless steel ASTM A276 431 Power consumption 16 VA
260
1-1/2" BCV 30 Blowdown Control Valve
Dimensions/Weights (approximate) in inches and lbs. Spare parts
Spare parts are available as listed below.
Size A B C D Weight No other parts are available as spares.
1-1/2" 7.5" 18.9’’ 7.0’’ 1/4" BSP 49 Available spares
Gasket & stem seal set Stock No. 4034880 9, 13, 40, 41,
C
42, 43, 44
Valve head, seat & stem set Stock No. 4034881 3, 4, 6, 7, 8, 22
44
43
13
42
41
Controls
40
Boiler
D Sample take-off
A
Capacity
Boiler Blowdown
Boiler Blowdown valve capacity lb/h
Presure 0.2" 0.4" 0.6" 0.8" 9
& CCD
(psig) stroke stroke stroke stroke
72.5 990 6394 7607 7827 7
3
101.5 1047 7276 9040 9922
145 1102 8158 10473 12017
4
217.5 1212 10032 14222 15765
290 1764 12678 17860 19073
464 2866 18522 22711 24365
8
Note: Intermediate flowrate strokes can be set on the 1-1/2 BCV30.
6
Safety Information
WARNING
This product is designed and constructed to withstand the forc-
es encountered during normal use. Use of the product for any
purpose other than a blowdown control valve could cause dam-
age to the product and may cause injury or fatality to personnel.
Installation 22
This document does not contain sufficient information to install the
product safely. See the Installation & Maintenance Instructions pro-
vided with every unit. Do not install the valve outside without addi-
tional weather protection.
Maintenance
It is recommended that the valve is examined annually and parts How to order spares
replaced if necessary. The gland may be adjusted if required as Always order spares by using the description given above and state
described in the installation and Maintenance Instructions. the size and flange type of blowdown control valve.
Example: 1 off Gasket and stem seal set Stock No. 4034880
How to order for Spirax Sarco 1-1/2" BCV30 blowdown control valve flanged BS
Example: 1 off Spirax Sarco 1-1/2" BCV30 blowdown control 1560 Class 300.
valve, 24 V, flanged BS 1560 Class 300
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-72-US 07.03
© Spirax Sarco, Inc. 2003
261
¾" BCV31
Blowdown Control Valve
Description
The Spirax Sarco BCV31 is a pneumatically operated control Diaphragm
valve for the blowdown of steam boilers. It is normally used with housing
a controller as part of an automatic TDS control system, though
it can also be used for other high pressure drop, low flowrate Diaphragm
applications.
The flowrate is adjusted by limiting the spindle stroke to regulate
the number of orifices that are uncovered.
The valve, which is specially designed to minimise seat erosion
Spindle
and ensure consistent tight shut-off, is supplied adjusted to its low
flowrate setting of 10 mm.
It can be adjusted to give 15 mm stroke for medium flowrates, or
to 20 mm stroke for high flowrates. The actuator has a mechanical
stroke indicator and incorporates a rolling diaphragm. Yoke
A ¼" NPT plug at the base of the valve may be removed to allow a
sample cooler to be fitted (available from Spirax Sarco).
The BCV31 requires a regulated and filtered air supply (¼" NPT),
which should be free of oil and water, and a solenoid valve, (avail-
able from Spirax Sarco). Connector
Controls
Boiler
Operation:
The valve is spring loaded to the closed position (spring retract),
and is also held closed by the boiler pressure. When the solenoid
valve opens, air is admitted to the actuator causing the valve to
open to the selected stroke. Stuffing box
assembly
Boiler Blowdown
Steam
saturation Internal
curve components
Body
Bottom cover
Pressure bar g
Maximum operating pressure 32 bar g (464 psi g)
Maximum operating temperature 239°C (462°F) Materials
Maximum ambient temperature 110°C (230°F) Part Material
Minimum ambient temperature 0°C (32°F) Body Cast carbon steel DIN 17245 GS-C25
Minimum operating temperature 0°C (32°F)
Air pressure range 3 to 6 bar g (44 to 87 psi g) Bonnet Forged carbon steel DIN 17243 C 22.8
Air consumption - normal Stuffing box Stainless steel / ASTM A276
0.48 litres (0.017 ft³)
(20 mm travel) assembly graphite seals 316L
262
¾" BCV31
Blowdown Control Valve
Dimensions /weight (approximate) in inches and pounds
Size A B C D Weight
DN20 5.9 14.2 11.7 ¼" NPT 24.7
(maximum)
C
4
B
9
D Sample take-off 17, 18
A
Controls
Boiler
For full details see the Installation and Maintenance Instructions
supplied with the product.
Important:
Your attention is drawn to Safety Information Leaflet IM-GCM-10, 30
as well as to any national or regional regulations.
Boiler Blowdown
Installation note: 10
The valve itself may be installed outdoors without additional pro-
tection. The solenoid valve however, must be installed indoors, or
& CCD
adequately protected against outdoor conditions.
Maintenance note:
We recommend that the valve and actuator are examined annually
and parts replaced as necessary.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P403-36-US 11.11
© Spirax Sarco, Inc. 2004
263
1-1/2" BCV 31 Blowdown Control Valve
Description Air connection
The Spirax Sarco BCV31 is a pneumatically operated control valve
for the blowdown of steam boilers. It is normally used with a con-
troller as part of an automatic TDS control system, though it can Diaphram
also be used for other high pressure drop flowrate applications. housing
The flowrate is adjusted by limiting the spindle stroke to regulate
the size of the orifice that is uncovered.
The valve, which is specially designed to minimise seat erosion and
ensure consistent tight shut-off, is supplied adjusted to a flowrate
setting of 10 mm.
It can be adjusted to give different flowrates. The actuator has a
mechanical stroke indicator and incorporates a rolling diaphragm.
A ¼" NPT plug at the base of the valve may be removed to allow a
sample cooler to be fitted (available from Spirax Sarco).
The BCV31 requires a regulated and filtered air supply (¼" NPT),
which should be free of oil and water, and a solenoid valve, (avail-
able from Spirax Sarco).
Operation:
Controls
The valve is spring loaded to the closed position (spring retract), Spindle
Boiler
and is also held closed by the boiler pressure. When the solenoid
valve opens, air is admitted to the actuator causing the valve to Yoke
open to the selected stroke.
Connector
Sizes and pipe connections
Boiler Blowdown
Steam
saturation
curve
Internal
Body components
Pressure bar g
Bottom cover
Maximum operating pressure 32 bar g (464 psi g)
Maximum operating temperature 239°C (462°F) Materials
Maximum ambient temperature 110°C (230°F) Part Material
Minimum ambient temperature 0°C (32°F) Body Cast carbon steel DIN 17245 GS-C25
Minimum operating temperature 0°C (32°F)
Air pressure range 2.5 to 6 bar g (36 to 87 psi g) Bonnet Forged carbon steel DIN 17243 C 22.8
Air consumption - normal Stuffing box Stainless steel / ASTM A276
1.606 litres (0.565 ft³)
(20 mm travel) assembly graphite seals 316L
Bottom cover Carbon steel BS 970 230 MO7
Capacities
Boiler Blowdown valve capacity kg / h (lb/h) Internal Stainless steel Type 431
pressure 5 mm 10 mm 15 mm 20 mm components (valve cone and seat are hardened)
bar g stroke stroke stroke stroke Guide bush Phosphor bronze BS EN 12163 CW451K
5 450 (992) 2 900 (6393) 3450 (7606) 3550 (7826) Diaphragm housing Pressed steel
7 475 (1047) 3300 (7275) 4100 (9039) 4500 (9921) Diaphragm Reinforced NBR
10 500 (1102) 3700 (8157) 4750 (10472) 5450 (12015)
Yoke SG iron
15 550 (1212) 4550 (10031) 6450 (14210) 7150 (15763)
20 800 (1764) 5750 (12677) 8100 (17857) 8650 (19070) Spindle Stainless steel
32 1 300 (2866) 8400 (18519) 10300 (22708) 11050 (24361) Connector Carbon steel
Note: Intermediate flowrate strokes can be set on the 1½" BCV31. Note: These items are clearly shown overleaf.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P403-74-US 11.11
264
1-1/2" BCV 31 Blowdown Control Valve
Dimensions /weight (approximate) in inches and pounds
Size A B C D Weight
DN40 7.8 15.9 11.8 ¼" NPT 64
17, 18
D Sample take-off
Controls
Boiler
Safetyinformation, installation and maintenance 9
For full details see the Installation and Maintenance Instructions
supplied with the product. 30
Important:
Your attention is drawn to Safety Information Leaflet IM-GCM-10, 10
Boiler Blowdown
as well as to any national or regional regulations.
Installation note:
& CCD
The valve itself may be installed outdoors without additional pro-
tection. The solenoid valve however, must be installed indoors, or
adequately protected against outdoor conditions.
Maintenance note: 17, 18
We recommend that the valve and actuator are examined annually
and parts replaced as necessary.
How to order
Example: 1 off Spirax Sarco 1½" BCV31 blowdown control
valve having flanged ANSI 300 connections.
265
Controls
Boiler
Boiler Blowdown
& CCD
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
266
MS1 Conductivity Meter
Controls
Boiler
measurements to be made on installed conductivity probes in
order to check their condition. Calibration to a master instrument or
standard solution is possible using the adjustment screw on the
side of the case. The instrument is supplied in a protective wallet.
Limiting conditions
Boiler Blowdown
Maximum recommended sensor
operating temperature 113°F (45°C).
& CCD
Specification
Ranges 0 to 199.9µS/cm, 0 to 1.999mS/cm,
0 to 19.99mS/cm.
Range indication Decimal Point and LED above selection key.
Temperature Automatic, 2%/°C.
compensation Reference temperature 77°F (25°C).
Resolution 0.1µS/cm.
Accuracy +/-1.5% or +/-3 digits (whichever is greatest)
at 77°F (25°C).
Calibration range +/-20%. 20 turns (approx).
On/off Auto-off timer.
Sensor PVC cell with carbon electrodes.
Extension cable Twin core, jack plug and crocodile clips.
Battery PP3 or equivalent. A low battery warning
indicator is fitted.
How to specify
1 - Spirax Sarco MS 1 Conductivity Meter.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-9-402-US 09.97
267
BT1050
Boiler Blowdown Timer
Description Clamping screw
The BT1050 is a timer for the control of a bottom blowdown valve.
It allows the bottom blowdown valve to open, removing precipitated
solids that could otherwise build up and eventually cause damage.
The BT1050 has three timers. These allow different blowdown cycle
times and durations to be set, for example, MON - FRI. Up to three
blowdown cycles can be selected in one day. The timers can also be
used to prioritise boiler blowdown cycles.
The product can be panel, DIN rail or chassis mounted and is
powered by a 110 to 240 Vac at 50/60 Hz mains supply. BT1050
The front panel has an LCD graphic display and five-button keypad.
A test function provides the operator with a diagnostic tool.
The BT1050 can communicate via an infrared link between adjacent
units. It can be designated as either a slave or a master unit, and
Controls
Boiler
Clamping screw
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P405-40-US 10.13
268
BT1050
Boiler Blowdown Timer
Technical data BT1050
Controls
Front panel Material Silicone rubber, 60 shore.
Boiler
Solder Tin / lead (60 / 40%)
Rising clamp plug-in terminal blocks with screw connectors.
Mains Termination Caution: Use only the connectors supplied by Spirax Sarco Ltd.
Safety and Approvals may be compromised otherwise.
and signal
connector Cable size 0.2 mm² (24 AWG) to 2.5 mm² (12 AWG).
Blowdown
Stripping length 5 - 6 mm (0.2")
Bottom
Type High temperature
Shield type Screened
Switch box
Number of cores 2
and Lockout
Gauge 1 – 1.5 mm² (18 - 16 AWG)
(link) circuit
Cable / wire Maximum length 100 m (328 ft)
and Recommended type Prysmian (Pirelli) FP200, Delta Crompton Firetuf OHLS
connector Type EIA RS485 twisted pair
data Shield type Screened
Please note that LAN Cat 5 or
RS485 Number of pairs 2 or 3 Cat 5E ScTP (screened), FTP (foil) or
communication Gauge 0.23 mm² (24 AWG) STP (shielded) cable can be used,
Maximum length 1200 m (4000 ft) but limited to 600 m.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-40-US 10.13
© Spirax Sarco, Inc. 1997
269
BT1050
Boiler Blowdown Timer
Technical data BT1050 (continued)
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-40-US 10.13
270
BT1050
Boiler Blowdown Timer
Dimensions/weight (approximate)
Weight (0.9 lb)
52 mm 120 mm
(2.04") (4.72")
BT1050
140 mm 120 mm
(5.51") (4.72")
Controls
Boiler
OK
Blowdown
Bottom
Safety information, installation and maintenance
This document does not contain sufficient information to install the product safely. See the Installation and Maintenance Instructions
supplied with the product, which gives full wiring, commissioning and operating instructions.
Attention is drawn to Safety Information Leaflet IM-GCM-10, as well as to any national regulations concerning blowdown. In particular,
your attention is drawn to the danger of working on a shut down boiler whilst other boilers are operating.
Warnings:
- Isolate the mains supply before installing the controller as live terminals at mains voltage are exposed.
- Only use the screws provided with the product.
- Do not install the product outdoors without additional weather protection.
- Do not drill the product case or use self-tapping screws.
Caution:
- A 15 mm (0.6") gap is required between multiple controllers for cooling.
How to specify
Blowdown timer with; three integral timers, LCD display, valve malfunction alarm and infrared communications.
How to order
Example: 1 off Spirax Sarco BT1050 blowdown timer.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-40-US 10.13
271
KBV 40i
Key Operated Boiler Blowdown Valve
Description
The key operated boiler blowdown valve consists of a carbon steel
reduced bore ball valve with carbon reinforced PTFE seats and a
key operated mechanism in stainless steel. Two types of key are
sold as optional extras and are available as follows:
- Standard length key.
- Extended length 'T' bar type key for use where access to the
valve is limited.
To ensure compliance with boiler regulations the key cannot
be removed when the valve is open.
Note: The standard length key and extended length 'T' bar type
key are sold separately. It is recommended that an extended length
'T' bar type key is purchased for valve sizes 2" and 2-½".
Standards
These products comply with the requirements of the European
Controls
Certification 392
These products are available with certififcation to EN 10204 3.1. 302 Steam
Blowdown
212
curve
the time of order placement. 122
32
Sizes and pipe connections 20
1", 1-¼", 1-½", 2", and 2-½" Flanged ASME (ANSI) B 16.5 Class 300. 145 290 435 580 740
Available flange options: Pressure psig
Flange Face-to-face Flange thickness The product must not be used in this region.
ASME (ANSI) 300 ASME B 16.10 ASME B 16.5
Body design conditions ASME 300
PMA Maximum allowable pressure 740 psig @ 100°F
Materials TMA Maximum allowable temperature 500°F @ 0 psig
Zinc plated Minimum allowable temperature 20°F
Body and insert ASTM A216 WCB
carbon steel
Maximum operating pressure
Stem seals Antistatic R-PTFE PMO 250.1 psig
for saturated steam service
Vented ball Austenitic stainless steel AISI 316 TMO Maximum operating temperature 500°F @ 0 psig
2-½" Austenitic stainless steel AISI 316 Minimum operating temperature 20°F
Stem
1" - 2" Martensitic stainless steel AISI 420 Note: For lower operating temperatures consult Spirax Sarco
Carbon and graphite ∆PMX Maximum differential pressure is limited to the PMO
Seats PDR 0.8
reinforced PTFE Designed for a maximum cold hydraulic test pressure of 1109 psig
Valve coefficients
Size 1" 1-¼" 1-½" 2" 2-½"
Cv value 34.6 46.2 93.6 119.1 227.8
How to specify
1-½" key operated boiler blowdown valve, flanged ANSI300 with carbon reinforced seats and stainless steel key.
How to order
Example: 1 off Spirax Sarco 1-½" KBV40i key operated boiler blowdown valve having ANSI300 flanged connections.
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P405-47-US 08.13
272
KBV 40i Key Operated Boiler Blowdown Valve
Dimensions / weights (approximate) in mm and kg
E
Caution - The ball must be installed with the vent hole on the upstream side
Controls
of the valve.
Boiler
A
Blowdown
Caution - The ball must be installed with the vent hole on the upstream
Bottom
side of the valve.
5 5 6
7 5 5 7 6
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-47-US 08.13
273
ABV40i Air Actuated Boiler Blowdown Valves
Description
The Spirax Sarco ABV40i one piece end entry, reduced bore ball valves is fitted with 90° rotary spring return pneumatic actuator, for boiler blowdown
duties. It is used in conjunction with a Spirax Sarco blowdown timer to provide timed control of bottom blowdown, ensuring that the recommended
boiler blowdown cycles occur with minimum heat loss, avoiding duplication or omission. The pneumatic actuator, (which can also be operated with
other non-corrosive gases), moves through 90° to open the valve, and has a spring return fail-close operation. A switch box is mounted on the actua-
tor, and either or both microswitches may be wired to a Building Management System if required.
Note: The BT1050 blowdown timer uses one switch only to indicate 'valve fully closed' or 'valve not fully closed' positions, and does not indicate
that the valve has opened fully. A solenoid valve is required, which may be directly mounted to the NAMUR (VDI / VDE 3845) interface on the actuator.
A suitable solenoid valve may be selected from the Spirax Sarco MV range. Alternatively, an air supply may be connected directly to the actuator port
'A' (¼" BSP), where it is necessary to install the solenoid valve remote from the actuator. A standard ¼" BSP 3-way solenoid valve may also be used.
Principal features:
Boiler
Standards
These products comply with the requirements of the European
Pressure Equipment Directive 97 / 23 / EC and carries the mark
Blowdown
when so required.
Bottom
Local regulation may restrict the use of this product below the conditions quoted. Limiting conditions refer to standard connections only.
In the interests of development and improvement of the product, we reserve the right to change the specification. TI-P405-45-US 08.13
274
ABV40i Air Actuated Boiler Blowdown Valves
Pressure / temperature limits
ABV40i
500
Temperature °F
392
302 Steam
212 saturation
curve
122
32
-20
145 290 435 580 739
Pressure psig
The product must not be used in this region.
Valve
Body design conditions ABV40i ASME 300
PMA Maximum allowable ABV40i 740 psig @ 100°F
pressure
TMA Maximum allowable temperature 500°F @ 0 psig
Minimum allowable temperature -20°F
PMO Maximum operating pressure 250.1 psig
for saturated steam service
TMO Maximum operating temperature 500°F @ 0 bar g
Minimum operating temperature -20°F
Note: For lower operating temperatures consult Spirax Sarco
Controls
∆PMX Maximum differential pressure is limited to the PMO
Boiler
Designed for a maximum cold
hydraulic test pressure of: ABV40i 1109 psig
Actuator
Maximum ambient temperature 176°F
Blowdown
Minimum ambient temperature 32°F
Bottom
Maximum air supply pressure 116 psig
Minimum air supply pressure Depends on operating conditions
MV series solenoid
Maximum ambient temperature 122°F
Minimum ambient temperature 32°F
Valve coefficients
Size 1" 1-¼" 1-½" 2" 2-½"
Cv value 34.6 46.2 93.6 119.1 227.8
Materials
Valve
Body and insert
Zinc plated
ASTM A216 WCB
How to specify
carbon steel Air actuated ball valve, 1-¼", ANSI 300 with carbon reinforced
Stem seals Antistatic R-PTFE seats, 90 degree rotary pneumatic actuator and switch box.
NAMUR compatible solenoid valve 220 / 240 Vac.
Vented ball Austenitic stainless steel AISI 316
2-½" Austenitic stainless steel AISI 316
Stem How to order
1" - 2" Martensitic stainless steel AISI 420 Example: 1 off Spirax Sarco 1-¼", ABV40i air actuated boiler
Carbon and graphite blowdown valve having ANSI 150 flanged connections plus
Seats PDR 0.8
reinforced PTFE 1 off MV11 solenoid valve 220 / 240 Vac.
Actuator
Body, piston and end caps Aluminium - anodised
Pinion Carbon steel - nickel plated
'O' ring seals Nitrile rubber
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-45-US 08.13
275
ABV40i Air Actuated Boiler Blowdown Valves
Dimensions / weights (approximate) in inches and pounds
G E
H F
Spare parts
The spare parts available are detailed below. No other parts are
available as spares.
Please note: There are no spares available for the switch box.
To ensure correct operation and maintain the warranty, use only Spirax
Sarco original parts.
Before actioning any maintenance programme observe the 'Safety
Information' in Section 1 of IM-P405-46 supplied with the unit.
A
Actuator
Controls
Boiler
Port A
air connection
¼" BSP (G). Spare parts for the BVA300S /14
The available spare parts for the BVA300S /14 are listed opposite.
No other parts are available as spares.
Blowdown
D
Bottom
5
13
14
15 11
Exploded view 17
of the spring set 12 8
6
6
Spare parts
The spare parts available are detailed below. No other parts are
supplied as spares.
5 16
Available spares
10
'O' rings set (NBR) 7, 8, 11, 12, 16
BVA300 series
13, 14, 15
maintenance kit Pinion washers
Others 5, 6, 10, 17, 18
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-45-US 08.13
276
ABV40i Air Actuated Boiler Blowdown Valves
Valve
Available spares
Seats, insert 'O' ring and stem seals 5, 6, 9, 10
Insert tool - Required to aid the removal
Not shown
of the ball valve insert (2)
Caution - The ball must be installed with the vent hole on the
upstream side of the valve.
10
9
Ball valve insert (2)
(not an available spare).
Please note: You will need
to order the Insert tool
listed in the table above
to aid removal.
Controls
Boiler
headed 'Available spares' and state the size and type of ball valve.
Example: 1 set of seats, insert 'O' ring and stem seals for a
Spirax Sarco 2" ABV40i boiler blowdown valve.
5 5 6
Blowdown
The spare parts available are shown in solid outline. Parts drawn in broken line are not supplied as spares.
Bottom
Available spares
Seats, insert 'O' ring, seat 'O' ring,
stem 'O' ring, lower stem seals 5, 6, 7, 8, 11, 12
and upper stem packing Ball valve insert (2)
Insert tool - Required to aid the removal of (not an available spare).
Not shown Please note: You will need
the ball valve insert (2)
to order the Insert tool
listed in the table above
Caution - The ball must be installed with the vent hole on the to aid removal.
upstream side of the valve. 12
8
11
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222 TI-P405-45-US 08.13
277
Engineering Data
Engineering
Data
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
278
Properties of Saturated Steam
Gauge Temper- Heat in Btu/lb Specific Gauge Temper- Heat in Btu/lb Specific
Pressure ature Volume Pressure ature Volume
psig ˚F Sensible Latent Total ft3/lb psig ˚F Sensible Latent Total ft3/lb
25 134 102 1017 1119 142 160 371 344 853 1197 2.60
INS. VAC.
20 162 129 1001 1130 73.9 165 373 346 851 1197 2.54
15 179 147 990 1137 51.3 170 375 348 849 1197 2.47
10 192 160 982 1142 39.4 175 377 351 847 1198 2.41
5 203 171 976 1147 31.8 180 380 353 845 1198 2.34
0 212 180 970 1150 26.8 185 382 355 843 1198 2.29
1 215 183 968 1151 25.2 190 384 358 841 1199 2.24
2 219 187 966 1153 23.5 195 386 360 839 1199 2.19
3 222 190 964 1154 22.3 200 388 362 837 1199 2.14
4 224 192 962 1154 21.4 205 390 364 836 1200 2.09
5 227 195 960 1155 20.1 210 392 366 834 1200 2.05
6 230 198 959 1157 19.4 215 394 368 832 1200 2.00
7 232 200 957 1157 18.7 220 396 370 830 1200 1.96
8 233 201 956 1157 18.4 225 397 372 828 1200 1.92
9 237 205 954 1159 17.1 230 399 374 827 1201 1.89
10 239 207 953 1160 16.5 235 401 376 825 1201 1.85
12 244 212 949 1161 15.3 240 403 378 823 1201 1.81
14 248 216 947 1163 14.3 245 404 380 822 1202 1.78
16 252 220 944 1164 13.4 250 406 382 820 1202 1.75
18 256 224 941 1165 12.6 255 408 383 819 1202 1.72
20 259 227 939 1166 11.9 260 409 385 817 1202 1.69
22 262 230 937 1167 11.3 265 411 387 815 1202 1.66
24 265 233 934 1167 10.8 270 413 389 814 1203 1.63
25 267 234 933 1169 10.3 275 414 391 812 1203 1.60
26 268 236 933 1169 10.3 280 416 392 811 1203 1.57
28 271 239 930 1169 9.85 285 417 394 809 1203 1.55
30 274 243 929 1172 9.46 290 418 395 808 1203 1.53
32 277 246 927 1173 9.10 295 420 397 806 1203 1.49
34 279 248 925 1173 8.75 300 421 398 805 1203 1.47
35 281 250 924 1174 8.6 305 423 400 803 1203 1.45
36 282 251 923 1174 8.42 310 425 402 802 1204 1.43
38 284 253 922 1175 8.08 320 427 405 799 1204 1.38
40 286 256 920 1176 7.82 330 430 408 796 1204 1.34
42 289 258 918 1176 7.57 340 433 411 793 1204 1.31
44 291 260 917 1177 7.31 350 435 414 790 1204 1.28
Engineering
45 292 261 916 1177 7.21 360 438 417 788 1205 1.24
46 293 262 915 1177 7.14 370 441 420 785 1205 1.20
Data
48 295 264 914 1178 6.94 380 443 422 783 1205 1.18
50 298 267 912 1179 6.68 390 446 425 780 1205 1.14
55 300 271 909 1180 6.27 400 448 428 777 1205 1.12
60 307 277 906 1183 5.84 450 460 439 766 1205 1.00
65 312 282 901 1183 5.49 500 470 453 751 1204 .89
70 316 286 898 1184 5.18 550 479 464 740 1204 .82
75 320 290 895 1185 4.91 600 489 473 730 1203 .75
80 324 294 891 1185 4.67 650 497 483 719 1202 .69
85 328 298 889 1187 4.44 700 505 491 710 1201 .64
90 331 302 886 1188 4.24 750 513 504 696 1200 .60
95 335 305 883 1188 4.05 800 520 512 686 1198 .56
100 338 309 880 1189 3.89 900 534 529 666 1195 .49
105 341 312 878 1190 3.74 1000 546 544 647 1191 .44
110 344 316 875 1191 3.59 1250 574 580 600 1180 .34
115 347 319 873 1192 3.46 1500 597 610 557 1167 .23
120 350 322 871 1193 3.34 1750 618 642 509 1151 .22
125 353 325 868 1193 3.23 2000 636 672 462 1134 .19
130 356 328 866 1194 3.12 2250 654 701 413 1114 .16
140 361 333 861 1194 2.92 2500 669 733 358 1091 .13
145 363 336 859 1195 2.84 2750 683 764 295 1059 .11
150 366 339 857 1196 2.74 3000 696 804 213 1017 .08
155 368 341 855 1196 2.68
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
279
Calculating Condensate Loads
When the normal condensate load is not known, the load can be approximately
determined by calculations using the following formulae.
Cp = Specific heat of the material pounds per hour Controlled Air Heater Coils
∆T = Temperature rise of the material ˚F Wf = Final wether of the material — and Converters, and Siphon
L = Latent heat of steam Btu/lb pounds per hour applications
t = Time in hours ∆T = Temperature rise of the material ˚F
L = Latent heat of steam Btu/lb
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
280
Warm-up and Condensate Load Tables
Warm-up Load in Pounds of Steam per 100 ft of Steam Main (based on a start-up timer of 1 hour)
Ambient Temperature 70˚F. Based on Sch. 40 Pipe to 250 psi, Sch. 80 Above 250 Except Sch. 120 5" and Larger Above 800 psi.
S team Pressure 0˚F
Pressure Correction
(psig) 2" 2-1/2" 3" 4" 5" 6" 8" 10" 12" 14" 16" 18" 20" 24" Factor*
0 6.2 9.7 12.8 18.2 24.6 31.9 48 68 90 107 140 176 207 208 1.50
5 6.9 11.0 14.4 20.4 27.7 35.9 48 77 101 120 157 198 233 324 1.44
10 7.5 11.8 15.5 22.0 29.9 38.8 58 83 109 130 169 213 251 350 1.41
20 8.4 13.4 17.5 24.9 38.8 44 66 93 124 146 191 241 284 396 1.37
40 9.9 15.8 20.6 29.3 39.7 52 78 110 145 172 225 284 334 465 1.32
60 11.0 17.5 22.9 32.6 44 57 86 122 162 192 250 316 372 518 1.29
80 12.0 19.0 24.9 35.3 48 62 93 132 175 208 271 342 403 561 1.27
100 12.8 20.3 26.6 37.8 51 67 100 142 188 222 290 366 431 600 1.26
125 13.7 21.7 28.4 40 55 71 107 152 200 238 310 391 461 642 1.25
150 14.5 23.0 30.0 43 58 75 113 160 212 251 328 414 487 679 1.24
175 15.3 24.2 31.7 45 61 79 119 169 224 265 347 437 514 716 1.23
200 16.0 25.3 33.1 47 64 83 125 177 234 277 362 456 537 748 1.22
250 17.2 27.3 35.8 51 69 89 134 191 252 299 390 492 579 807 1.21
300 25.0 38.3 51 75 104 143 217 322 443 531 682 854 1045 1182 1.20
400 27.8 43 57 83 116 159 241 358 493 590 759 971 1163 1650 1.18
500 30.2 46 62 91 126 173 262 389 535 642 825 1033 1263 1793 1.17
600 32.7 50 67 98 136 187 284 421 579 694 893 1118 1367 1939 1.16
800 38 58 77 113 203 274 455 670 943 1133 1445 1835 2227 3227 1.156
1000 42 72 86 126 227 305 508 748 1052 1264 1613 2048 2485 3601 1.147
1200 47 72 96 140 253 340 566 833 1172 1407 1796 2280 2768 4010 1.140
1400 52 79 106 155 280 376 627 922 1298 1558 1988 2525 3064 4440 1.135
1600 57 87 117 171 309 415 692 1018 1432 1720 2195 2787 3383 4901 1.130
1750 62 94 126 184 333 448 746 1098 1545 1855 2367 3006 3648 5286 1.128
1800 63 97 129 189 341 459 765 1126 1584 1902 2427 3082 3741 5420 1.127
*For outdoor temperature of 0˚F, multiply load value in table for each main size by correction factor shown.
Condensate Load in Pounds per Hour per 100 ft. of Insulated Steam Main
Ambient Temperature 70˚F — Insulation 80% Efficient. Load Due to Radiation and Convection for Saturated Steam
S team Pressure 0˚F
Engineering
Pressure Correction
Data
(psig) 2" 2-1/2" 3" 4" 5" 6" 8" 10" 12" 14" 16" 18" 20" 24" Factor*
10 6 7 9 11 13 16 20 24 29 32 36 39 44 53 1.58
40 8 9 11 14 17 20 26 32 38 42 48 51 57 68 1.50
60 10 12 14 18 24 27 33 41 49 54 62 67 74 89 1.45
100 12 15 18 22 28 33 41 51 61 67 77 83 93 111 1.41
125 13 16 20 24 30 36 45 56 66 73 84 90 101 121 1.36
175 16 19 23 26 33 38 53 66 78 86 98 107 119 142 1.38
250 18 22 27 34 42 50 62 77 92 101 116 126 140 168 1.36
300 20 25 30 37 46 54 68 85 101 111 126 138 154 184 1.33
400 23 28 34 43 53 63 80 99 118 130 148 162 180 216 1.32
500 27 33 39 49 61 73 91 114 135 148 170 185 206 246 1.32
600 30 37 44 55 68 82 103 128 152 167 191 208 232 277 1.31
800 36 44 53 69 85 101 131 164 194 214 244 274 305 365 1.30
1000 43 52 63 82 101 120 156 195 231 254 290 326 363 435 1.27
1200 51 62 75 97 119 142 185 230 274 301 343 386 430 515 1.26
1400 60 73 89 114 141 168 219 273 324 356 407 457 509 610 1.25
1600 70 85 103 132 163 195 253 315 375 412 470 528 588 704 1.22
1750 77 93 113 145 179 213 278 346 411 452 516 580 645 773 1.22
1800 79 96 117 150 185 221 288 358 425 467 534 600 667 800 1.21
*For outdoor temperature of 0˚F, multiply load value in table for each main size by correction factor shown.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
281
Heat Transfer Calculations
Pipe Exposed Up to 80˚F 1.8 .45 200 2680 320 3000 320 53 29 20
Line 80 to 260˚F 2.75 .7
Data
For rough calculations it may be taken that 1 ton of fuel oil occupies
36 .4 ft3. The specific heat capacity of heavy fuel is 0.45 to 0.48
Btu/lb ˚F.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
282
Steam Tracing
Designing of Steam Tracing Steam Size Connections for Jacketed Lines
Recommended number of 1/2" tracers to meet average requirements
Type A Type B Type C Steam
General frost Where solidi- When solidifica- Product Line Jacket Diameter Connection
protection or fication may tion may occur 2-1/2" 4" 1/2"
where solidi- occur at temps. at temps. 3" 6" 3/4"
fication may between 75 - between 150 -
occur at temps. 150˚F 300˚F 4" 6" 3/4"
below 75˚F 6" 8" 3/4"
Product Number of Number of Number of 8" 10" 1"
Line Size 1/2" Tracers 1/2" Tracers 1/2" Tracers 10" 12" 1"
1" 1 1 1
1-1/2" 1 1 2 Length of jacket should not exceed 20 ft. In most cases 1/2" condensate outlet
2" 1 1 2 would be adequate but it is usual to make this same size as the steam connec-
3" 1 1 3 tion as it simplifies installation.
4" 1 2 3
6" 2 2 3
8" 2 2 3 Recommended Header Size
10"-12" 2 3 6 for Supplying Steam Tracer Lines
14"-16" 2 3 8
18"-20" 2 3 10 Header Size Number of 1/2" Tracers
3/4" 2
As a general rule, length of tracers to 3/8" size should not exceed 60 ft. Larger 1" 3 to 5
size tracers should not exceed 150 ft. in length. 1-1/2" 6 to 15
2" 16 to 30
Engineering
10.0 24"
Data
9.0
8.0
7.0
6.0
5.0
4.0
3.0
Pressure Drop psi/100 ft
2.0
1.0
.9
.8
.7
.6
.5
.4
.3
.2
.1
100 200 300 400 500 1,000 2 3 4 5 10,000 2 3 4 5 6 7 8 100,000 2 3 4 5 1,000,000 2
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
283
Steam Pipe Sizing
How to Size Steam Pipes for
Various Pressure and Velocity
Conditions
To select pipe size in long mains and wher-
ever supply pressure is critical, use the pres-
sure drop chart to assure it is within allowable
limits. Most saturated steam lines may be Steam Pipe Sizing
sized for a velocity of 4800 to 7200 ft/min;
higher velocities should be avoided unless
appreciable superheat is present. Pipe Size
Reasonable (Schedule 40 pipe)
Piping at pressure reducing stations should Steam Velocities 20000
1"
be sized for the same velocity on both sides in Pipes 1- 1/2
of the PRV. This generally results in a valve 1-1 1/4" "
/2" 3/4 12000
smaller than the supply piping with still Process Steam 2 " 10000
larger downstream pressure piping due to 8000 to 12000 ft/min 2-1 "
/2" 8000
Velocity ft/min
the increase in steam volume (see example
below.)
3"
F G 6000
Heating Systems 4" 5000
4000 to 6000 ft/min
Trap discharge piping contains a bi-phase 5" C D 4000
flash steam/condensate mixture, and a lower 6"
Flash Vent Lines 3000
velocity of 4000 to 6000 ft/min to the receiver 3000 ft/min 8"
encourages gravity separation. The receiver 2000
vent line is sized for the amount of flash 10
1 "
vented at atmospheric pressure at a velocity 14 2"
of 3000 to 4000 ft/min. 16 "
"
1000
Velocity Chart Example
Given a steam heating piping system with
a 100 psig inlet pressure ahead of a control 50000
valve with a capacity of 1,000 lb/h of steam 40000
reduced to 25 psig, find the smallest sizes of Multiply chart velocity
30000 by factor below to get
upstream and downstream piping for reason- velocity in schedule
able quiet steam velocities. 80 pipe
20000 Pipe Size Factor
Upstream Pressure Piping Sizing 1/2" 1.30
Enter the velocity chart above at A for steam 3/4" & 1" 1.23
flow of 1,000 lb/h. Go over to point B where 10000 1-1/4" & 1-1/2" 1.17
the 100 psig diagonal line intersects. Follow
8000 2" to 16" 1.12
up vertically to C where an intersection with 25 00
a diagonal line falls inside the 4,000-to-6,000 6000
Capacity lb/h
2 0
0
15 25
3000
25
2000
5
800
4,000-to-6,000 ft/min velocity band. Actual 600
Data
400
1 00
1 5
7
V = 2.4Q Vs 200
10
A
5
Where:
V = Velocity in ft/min 100
Q = Flow lb/h steam
Vs = Sp. Vol. in cu. ft3/lb at the Steam Pressure psig
flowing pressure (Saturated Steam)
A = Internal area of the pipe — in2
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
284
Condensate Line Sizing
Condensate return lines on the discharge side Percent Flash Steam
of steam traps must be able to accomodate
the flow of both water and flash steam. While Produced when Condensate is discharged to atmosphere or into a flash tank controlled at various pressures.
the percentage, by weight, of flash steam may
be rather low, its overall volume in compari- Atmo-
son to the liquid is very large. By determining Pressure sphere Flash Tank Pressure — psig
the quantity of flash steam and sizing the psig 0 2 5 10 15 20 30 40 60 80 100
return line for velocities between 4,000 and
6,000 ft/min, the two-phase flow within the 5 1.7 1.0 0
pipe can be accomodated. The information 10 2.9 2.2 1.4 0
required for sizing is the condensate load in 15 4.0 3.2 2.4 1.1 0
lb/h, inlet pressure to steam trap(s) in psig and 20 4.9 4.2 3.4 2.1 1.1 0
return line system pressure. 30 6.5 5.8 5.0 3.8 2.6 1.7 0
40 7.8 7.1 6.4 5.1 4.0 3.1 1.3 0
Example: 60 10.0 9.3 8.6 7.3 6.3 5.4 3.6 2.2 0
Size a condensate return line from a 160 psig 80 11.7 11.1 10.3 9.0 8.1 7.1 5.5 4.0 1.9 0
steam trap discharging to 20 psig. flash tank. 100 13.3 12.6 11.8 10.6 9.7 8.8 7.0 5.7 3.5 1.7 0
Load is 3,000 lb/h. 125 14.8 14.2 13.4 12.2 11.3 10.3 8.6 7.4 5.2 3.4 1.8
1. Determine percent flash steam produced 160 16.8 16.2 15.4 14.1 13.2 12.4 10.6 9.5 7.4 5.6 4.0
using table. With a steam pressure of 160 200 18.6 18.0 17.3 16.1 15.2 14.3 12.8 11.5 9.3 7.5 5.9
psig and a flash tank pressure of 20 psig 250 20.6 20.0 19.3 18.1 17.2 16.3 14.7 13.6 11.2 9.8 8.2
read a value of 12.4%. 300 22.7 21.8 21.1 19.9 19.0 18.2 16.7 15.4 13.4 11.8 10.1
2. Next, multiply the condensate load by the 350 24.0 23.3 22.6 21.6 20.5 19.8 18.3 17.2 15.1 13.5 11.9
percent flash from step #1 to determine the 400 25.3 24.7 24.0 22.9 22.0 21.1 19.7 18.5 16.5 15.0 13.4
flowrate, of flash steam produced.
3,000 lb/h x .124 = 372 lb/h.
3. Enter Condensate
Recovery Sizing Condensate Recovery Sizing
chart at the flash
steam flowrate of Velocity Velocity
372 lb/h at “A" and (ft/sec) Pipe Size (schedule 40) (ft/min) Recommended
move horizontally to Service
100 6000
the right to the flash C Condensate Return
tank pressure of 20 66 4000
Line Sizing
psig “B". Rise verti- E 3000
Vent Pipe Sizing
50
cally to choose a con-
densate return line 33 2000
30 28" 26 24 20 18 16 14 12 10 8" 6" 5" 4" 3" 2-1 2" 1-1 1-1 1" 3/4 1/2
size which will give " " " " " " " " " /2" /2" /4" " "
a velocity between
4,000 and 6,000 ft/ 17 1000
min, “C". In this
example, an 1-1/2" 10 D 600 Flash Tank
schedule 40 pipe with Diameter Sizing
a velocity of approxi-
50,000
mately 5,000 ft/min.
Multiply chart velocity
If schedule 80 pipe by factor below
10 0
in schedule 80 pipe
60 0
Pipe Size
3 0
20,000 Factor
of chart. Multiply the
2
1/2" 1.30
10
Engineering
26" to 30" 1.0
acceptable limits.
Flash Steam Flowrate (lb/h)
Data
5000
10 0
3000
0
8
60 0
4 0
3 0
2000
2
10
5
0
1000
800
500
A B
300
200
10 0
0
8
100
60 0
4 0
3 0
80
2
60
10
5
50
0
40
30
P
c re
20
nk te
(p lin
si e
g) or
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
285
Flash Tank and Vent Line Sizing
How to Size Flash Tanks
and Vent Lines Flash Vessel Sizing
Whether a flash tank is to be atmospheric or
pressurized for flash recovery, the procedure
for determining its size is the same. The most Flash Steam
Horizontal Flash Vessel outlet or vent pipe
important dimension is the diameter. It must
be large enough to provide adequate separa-
tion of the flash and condensate to minimize
condensate carry over.
Condensate
Example: inlet
Size a 20 psig flash recovery vessel based on
the information in the example on page 582
(condensate line sizing). Length Diameter
1. Using the calculated flash steam quantity of Length = 2 x diameter or
372 lb/h enter Condensate Recovery Sizing 24" minimum
chart on page 112 at “A" and move horiz-
intally to the right to the flash tank pressure
of 20 psig “B". Rise vertically to the flash
tank diameter line (600 ft/min) at “D". Read
tank diameter of 5". If schedule 80 pipe is Condensate
to be installed, the table within the body of outlet
the chart can be used to determine whether
the velocity will exceed the recommended
limit of 600 ft/min.
2. From point “D" continue to rise vertically
to “E" to determine the size of vent pipe to
give a velocity between 3000 and 4000 ft/ Vertical Flash Vessel Flash steam outlet
or vent pipe
min. In this case 2" schedule 40 pipe. As
before, use the table within the body of
chart for schedule 80 pipe.
35% of
height
Condensate
outlet
Engineering
Data
For proper installation of flash vessels, controls and traps refer to Design of Fluid Systems Hook-Ups.
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
286
Steam Trap Selection Guide
As the USA’s leading provider of steam system solutions, Spirax Sarco recognizes that no two steam trapping systems are
identical. Because of the wide array of steam trap applications with inherently different characteristics, choosing the correct
steam trap for optimum performance is difficult. Waterhammer, superheat, corrosive condensate, or other damaging operat-
ing characteristics dramatically affect performance of a steam trap. With over 80 years of experience in steam technology,
Spirax Sarco is committed to helping it’s customers design, operate and maintain an efficient steam system. You have our
word on it!
Engineering
Bulk Storage Tanks 3 3
Data
Line Heaters 3
Tanks & Vats
Bulk Storage Tanks
3 3
Process Vats
3 3
Vulcanizers 3 3
Evaporators 3 3
Reboilers 3 3
Rotating Cylinders
3
Freeze Protection 3
Spirax Sarco, Inc., 1150 Northpoint Blvd., Blythewood, SC 29016 • Phone: (803) 714-2000 • Fax: (803) 714-2222
287
Model Designation Index
ABV 40i............................. 275 CE63 5" to 8" Stainless Steel MDM................................. 208
AEL5 Accessories............ 132 ........................................... 86 MPC2............................... 170
AEL5................................. 124 C Series Spares................. 89 MS 1................................. 267
AEL6................................. 146 C Series Options................ 90 PA 20................................ 216
APS 1............................... 228 CP10................................. 242 PF51G (Bronze)................ 198
BC3150............................ 248 CP 30............................... 244 PF6 (SS)........................... 190
BC3250............................ 252 CP 32............................... 246 PM Series for B Series....... 14
BCS 1............................... 240 DM.................................... 207 PN1000 2-1/2" to 4"........ 106
BCV1................................ 256 DS1000............................. 231 PN1000 6" & 8"................ 108
BCV20.............................. 256 EL2270............................. 186 PN1000/2000 for C Series. 112
BCV30 3/4".................... 258 EL2271............................. 186 PN600 Series................... 174
BCV30 1-1/2"................. 260 EL2600............................. 188 PN9000............................... 98
BCV31 3/4".................... 262 EL5600............................. 136 PP5................................... 156
BCV31 1-1/2"................. 264 EL5600 Accessories......... 136 PT2................................... 242
Belimo AFB Series Electric EL5650............................. 140 Rotork CVL....................... 152
Actuator............................ 122 Engineering Data.............. 278 S20................................... 242
Belimo NV Series Electric EP5................................... 158 SP300............................... 164
Actuator............................ 120 IPC4A Converter.............. 169 SP400............................... 160
B Series 1/2" to 2"............. 16 KBV 40i............................. 272 SP500............................... 162
BT 1050............................ 268 K Series ............................. 30 Steam Sizing Chart............ 12
CE43 1" to 4" Carbon Steel K Series 6" to 8"................ 50 STERI-TROL 'S' Series...... 59
........................................... 76 LC1350............................. 217 Stonel Limit Switch.......... 209
CE43 5" to 8" Carbon Steel LC2250............................. 220 Stonel Position Transmitter
........................................... 78 LC2650............................. 224 ......................................... 172
CE83 1" to 4" Alloy Steel LC3050............................. 236 SX80................................. 176
........................................... 80 LP10-4.............................. 212 SX90................................. 180
CE83 5" to 8" Alloy Steel LP 20................................ 214 TN2000............................... 92
........................................... 82 LP 30................................ 232 TP20................................. 242
CE63 1" to 4" Stainless Steel LP 31................................ 234
........................................... 84 L Series.............................. 18