Beruflich Dokumente
Kultur Dokumente
,
A u r é l i o M o r ei r a L u i z , &
H i l t o n Le ã o d e P . M . Fi l h o
W
hen designing
electrical installations in
an industry that processes
flammable products, it is
necessary to know where the classified
locations are. These locations are identi-
fied in drawings to direct the specifica-
tion of adequate electrical and electronic
equipment. This article shows why the
figures’ copy-and-paste practice does not
guarantee a cost-effective installation. It
also presents comparisons between gas
dispersion models, aiming to help pro-
all-free-download.com
fessionals perform reliable hazardous-
area-classification studies.
Area
IEEE In dustry A p plication s M ag az in e • jan |f eb 2016 • www.ieee.or g/ia s
Classification
Is Not a
Copy-and-Paste
Process
28 Performing reliable hazardous-area-classification studies
1077-2618/16©2016IEEE
Area Classification in 1955, and it is used worldwide with
A hazardous area is designated as any The objective some misconceptions [3].
location in which a combustible material In Europe, the Directive 1999/92/
is or may be present in the atmosphere in of an area- EC of the European Parliament on min-
sufficient concentration to produce an imum requirements for improving the
ignitable mixture. The North American classification safety and health protection of workers
area-classification method identifies these potentially at risk from explosive atmo-
areas by Class, Division, and Group, study is to spheres [4] permits the use of any stan-
while the International Electrotechni- dard, provided essential health and
cal Commission (IEC) designates define and safety requirements are met. Use of
them by zone and group.
While many countries accept the
show the CENELEC standards (which are often
very close to the IEC standards and use
American system, there are others that volumes at the concepts of zones 0, 1, and 2) gives
use the IEC zone system to identify only a presumption of conformity. This
their hazardous locations [1]. The which the concept is somewhat destabilizing for
U.S. National Electrical Code (NEC) professionals whose preference is to refer
recognizes the zone system and allows concentration to a given standard [5].
its use in the United States under Depending on the method chosen,
Article 505 [2]. In Europe, the zone of flammable the equipment selection and installation
system defined in European Commit-
tee for Electrotechnical Standardiza-
gases exceeds must comply with the relevant codes.
I E E E I ndu str y Appl ic ations Ma gazin e • jan |feb 2 016 • ww w.ieee .o rg /ias
Area classification is not intended to consider cata-
strophic failures of plant items but is applied to abnormal Area-Classification Documents
single-mode events that are predictable, e.g., accidental In industrial projects, it is necessary to develop a draft of
spillage of gasoline into sewage systems. the area-classification map during the basic design phase.
Very often, the process information at this stage is still
The Area-Classification Procedure incomplete, and, as a consequence, the documents are
The area-classification procedure can be described in issued in a preliminary version.
steps as follows: A survey related to the area-classification documents
1) establish the method that will be used (zones or divi- was carried out in the American oil, gas, and petrochemi-
sions) and the appropriate reference codes and stan- cal industries [6], and it revealed that
dards for the project ■■ 20% of designers used just a text description
2) obtain pertinent information, e.g., process-flow ■■ 20% failed to mention the gas group
diagrams, material balance sheets, material safety ■■ 25% included the recommended temperature class for
data sheets, processes data sheets, and an updated electrical and electronic equipment to be installed in
plot plan the area
3) identify and assess all continuous, primary, and sec- ■■ the reliability of these documents was assigned a rating
ondary sources and their interactions with the local of six, with ten being the highest rating.
ventilation IEC Standard 60079-10-1, Explosive Atmospheres—Part
4) define the boundaries of each zone or division and 10-1: Classification of Areas—Explosive Gas Atmospheres
plot them on appropriate drawings (that must [7], establishes that the area-classification documents,
include plot plans and elevation views). which may be issued on paper or electronically, need to
include plans and elevations showing the types
Area-Classification Method and extents of zones, the gas groups, the auto-ignition
In 1947, the NEC introduced the concept of area classifi- temperature, and the recommended temperature class of
cation and the Division 1 and 2 probability factors. The the electrical equipment. The standard also recom-
American Petroleum Institute (API) began formal work mends referring to the data used as the basis for the
toward an area-classification document in 1951. API RP study, such as
500, Recommended Practice for Classification of Areas for Elec- ■■ recommendations from codes and standards
29
trical Installations in Petroleum Refineries, was first published ■■ the gas dispersion data
■■ the ventilation parameters in relation to the releases of What You See Is Not What You Get
flammable material, so that the availability and effec- As the installation designer needs to know where the gas
tiveness of ventilation can be assessed. concentrations can reach their LEL to specify the right
The area-classification map should show the zone electrical equipment, the definition and location of clas-
boundaries, gas groups, and flammable gases’ ignition sified areas is the primary concern.
temperatures because it will help inspectors when veri- Sixty years ago, when computational resources were not
fying the suitability of the Ex equipment. The impor- easily available, documents were issued to familiarize
tance of this documentation is also emphasized in other designers with the safety distances that should be consid-
standards such as National Fire Protection Agency ered in petroleum installations, where the processes
(NFPA) 70B, Recommended Practice for Electrical Equip- involved flammable materials.
ment Maintenance [8]. API RP 500 is a recommended practice for area classifi-
Unfortunately, it is very common to find area-classifica- cation in petroleum facilities that was originally issued in
tion drawings that do not reflect the installation details, 1951. The second edition, in 1957, included some refer-
and the extents of the classified areas are often direct ence diagrams, as shown in Figure 1 [3].
reproductions of the figures found in API RP 505 [9] and Note 1 under the original figure read “Distances given
API RP 500 [10]. are for average refinery installations; they must be used
with judgment, with consideration
given to all factors discussed in RP 500.”
The 2012 edition of API RP 500 [10,
Area of Restricted Ventilation Source of Hazard Fig. 22] kept the same illustration, as
Inside Enclosure shown in Figure 2. Note 2 under the
original figure is “Distances given are for
10 ft
10 ft
used with judgment, with consideration
2 ft
I E E E I ndu str y Appl ic ations Ma gazin e • jan |feb 2 016 • ww w.ieee .o rg /ias
be reproduced verbatim for all oil and gas projects. size is in the range of 5,000 to 25,000 gal, whatever the
As the parameters considered for elaboration of the fig- process, but this is not correct.
ures are not described in the RP 500/505 texts, the extents The subtlety is that NFPA 497 does not identify what
of the classified locations given by them tend to be arbitrary substances were considered when these figures were
and large. The interiors of vessels are well defined, but, developed, so they cannot be applied to any industrial
when the less hazardous areas—such as zone/Division 1 and plant, as expressed in 5.7.6: “...where the available
particularly zone/Division 2—are considered, it is not equipment diagrams indicate the size small (low) to
uncommon to find the entire plant as classified, instead of a moderate, and the equipment falls in the large (high)
limited area just around the process equipment. category, greater extent distances could be considered.
NFPA 497 [13] is another recommended practice, and The extent distances presented in these figures are for
its purpose is to provide the user with an understanding of combustible materials with low lower flammable limits
the parameters that define the degree and extent of hazard- (LFLs). A reduction in the extent distance could be con-
ous areas. Similarly to API RP 500/505, it is not intended sidered for combustible materials with comparatively
to immediately provide the area-classification extent by higher LFL.”
copying the figures; the extent’s definition is the user’s This reminds us that sound judgment is the key point
responsibility. in the assessment, as expressed in as highlighted in API
TABLE 1. THE RELATIVE MAGNITUDES OF TABLE 2. MASS FLOW FOR CH4 USING
PROCESS EQUIPMENT AND PIPING THAT HANDLE COX’S MODEL (g/s).
COMBUSTIBLE MATERIALS [13, TABLE 5.7.4]. Pressure
Process
Equipment Units Small Moderate Large 1 MPa 2 MPa
Size gal <5,000 5,000–25,000 >25,000 Hole Area (mm2) Hole Area (mm2)
Pressure lbf/in2 <100 100–500 >500 0.25 2.5 25.0 0.25 2.5 25.0
Mass
Flow rate g/min <100 100–500 >500 flow 0.3 2.6 26.0 0.5 5.2 52.0 31
RP 500/505 as well as NFPA 497 sec- The extent of hazardous areas
tion 5.8.4. We can say, in this case,
that what you see is not what you get.
because there depends on the wind speed at the
vicinity of the sources of release and the
is no proven ventilation availability. For these esti-
Mathematical Models mates, the equations are valid for well-
Several attempts have been made to way to ventilated areas and with adequate
include calculating procedures, but dis- ventilation ability, i.e., outdoors with
agreements over their accuracy have predict the wind speed between 0.5 and 2 m/s.
almost always resulted in a failure to Four approaches for defining the area-
agree on their inclusion [14]. consequences classification extent using mathemati-
Inexperienced persons think that
classifying locations is an easy task,
of an cal models are described in this article:
Cox’s model, McMillan’s model, the
but, in fact, it is difficult to do in a explosion, modified Cox model, and the IEC
reliable way. The lack of information 60079-10-1 model.
with which to estimate the mass flow it is not
rate of the leak, especially for acciden- Cox’s Model
tal releases, leads to subjective opinions reasonable to The model proposed by Cox for the gas
and complicates the adoption of a mass flow considered the Gaussian
given mathematical model. Some sim- use this EPL plume model under the simplest case: a
plifications were introduced as alterna- subsonic jet issuing from a circular ori-
tives, but a consistent judgment is underrating. fice [17]. This gives the axial jet concen-
required [15]. tration C for circular holes, as in (1).
The basis for mathematical models The fundamental assumptions of the
relies on the estimate of media flow through specially Gaussian plume model equation are
designed openings to ensure the maximum flow rate ■■ level terrain
with minimal energy. This research is modeled by the ■■ constant winds with unidirectional speed
discipline of fluid dynamics, and statistical data are ■■ homogeneous and stationary atmospheric turbulence.
welcome to help in the task [16]. There is concern
c m , (1)
regarding the usage of mathematical models because Cx = 5 do tA
people without the knowledge to identify their limita- Co x to
tions could adopt them improperly.
where
IEEE In dustry A p plication s M ag az in e • jan |f eb 2016 • www.ieee.or g/ia s
TABLE 3. MASS FLOW FOR CH4— TABLE 4. NFPA 497: FIGURE 5.9.1 (B). THE MATERIAL
McMILLAN’S MODEL [g/s]. BEING HANDLED IS A FLAMMABLE LIQUID.
Pressure Small/Low Moderate Large/High
1 MPa 2 MPa Process equip- —
Hole Area (mm ) 2
Hole Area (mm2) ment size
I E E E I ndu str y Appl ic ations Ma gazin e • jan |feb 2 016 • ww w.ieee .o rg /ias
X = distance from the source of release until the LEL ically be either 0.25 or 0.5 times the LEL, given by (5).
is reached (m)
M = molar mass (kg/kmol) f # c dV m
T = ambient temperature (K). dt min
Vz = f # Vk = , (5)
As long as the speed of the gas release is higher than C
the considered wind speed (0.5 to 2.0 m/s ), (3) is valid. If
it is lower, the gas flow will cease to be dominant, becom- where
ing more dependent on atmospheric conditions at the
location of the leak.
2.5
The Modified Cox Model 2.3
Two adjustment factors in Cox’s model were introduced
2.0
to consider the effects of the pressure and density of the 1.9
flammable gas on the classified-area extent, as shown in
(4) [20]. 1.5
(m)
10.00
0.04
5.00
0.02
0.00
00 50 100 150 0
(kgf/cm2) 0 2 4 6 8 10 12 14
Modified Cox McMillan Cox Pressure (barg)
6 7
A comparison of the Cox, modified Cox, and McMillan The variation of the gas cloud volume of CH4 releases versus
34
models for CH4. pressure, considering V z and CFD.
■■ CFD-validated soft-
ware for 50% LEL 1.5
■■ CFD-validated soft- 1.45
ware for 100% LEL 1.4
1.35
[24]. 1.3
The greatest differences 1.25
were found in the larg- 1.2
est enclosures. This 1.15
1.1
implies that use of IEC 1.05
60079-10-1 for calcu- 1
lating Vz significantly 0.95
overestimates the haz- 0.9
0.85
ard and, therefore, leads
Height (m)
0.8
to larger classified areas. 0.75
Additional concerns 0.7
in the current IEC 0.65
0.6
60079-10-1 approach 0.55
are that the definition of 0.5
classified-area extent is 0.45
not provided and there 0.4
0.35
are no warnings that the 0.3
frequency and duration 0.25
of gas releases can vary 0.2
significantly between 0.15
0.1
similar sources of release. 0.05
0
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
2.8
3
3.2
3.4
3.6
3.8
4
4.2
4.4
4.6
4.8
5
The NFPA 497 and CFD
Models, Considering Horizontal Distance (m)
Process Temperature 8
Simulations were done Isopentane’s LEL concentration plume extent due to a leakage at 30 °C.
with isopentane at a
given pressure, consider-
I E E E I ndu str y Appl ic ations Ma gazin e • jan |feb 2 016 • ww w.ieee .o rg /ias
ing three temperatures: 30, 90, and 120 °C. In these con-
TABLE 5. A COMPARISON OF CFD SIMULATION AND
ditions, the distances in Figure 3 and Table 4 are
NFPA FIGURE 5.9.1 (b): above-LEL concentration
applicable, but the simulation results show that the dis-
of isopentane releases at different
tances for each case differ.
temperatures.
Figures 8–10 show the dimensions of the plume until
the LEL is achieved due to an isopentane’s source of release Distance (m)
at 1 m height [25]. The differences are summarized in Isopentane
Table 5. (oC) CFD (m) NFPA 497 (m)
30 4.9 3.0
The NFPA 497 and CFD models,
Considering Process Pressure 90 3.7 3.0
Simulations were done using hexane at 30 oC for two pres-
sures, 14.22 and 497.8 lbf/in2. Under NFPA 497, in both 120 3.3 3.0
situations, the Figure 3 and Table 4 distances are applicable.
As expected, however, the results show that the distances
until the LEL is reached in each case are very different [25].
In Figures 11 and 12, the dimensions of the plume until
the LEL is achieved due to a hexane’s source of release at TABLE 6. A COMPARISON OF CFD SIMULATION AND
0.5 m height are shown in meters. The maximum distances NFPA Fig. 5.9.1 (b): ABOVE-LEL CONCENTRATION
found in this simulation considering these two pressures OF HEXANE RELEASES AT DIFFERENT PRESSURES.
are summarized in Table 6.
Distance (m) Difference
Limitations of Mathematical Models
Methods for determining the release rates and the explosive Hexane Absolute Relative
atmosphere extent created by a given leak have been the (lbf/in2) NFPA 497 CFD (m) (%)
subject of much discussion. It has proved almost impossible 14.22 3.0 1.8 -1.2 -40
to settle on a method with full confidence of all relevant
interests. Experimental validation of mathematical models 497.8 3.0 5.2 +2.2 +73 35
is necessary, and some results have been achieved [26].
One very important
1.5 parameter for modeling
1.45
1.4
the source of a gas leak
1.35 is its mass release rate.
1.3 This can be computed
1.25 using the known up-
1.2
1.15
stream temperature and
1.1 pressure. The method
1.05 used will depend on
1 whether the release is
0.95
0.9
subsonic or choked, and
0.85 it is known that choked
0.8 releases are sonic at the
Height (m)
6
0.6
8
0.8
2.2
2
2.4
4
2.6
6
2.8
8
3.2
2
3.4
4
3.6
6
3.8
8
4.2
2
4.4
4
4.6
6
4.8
8
1.2
2
1.4
4
1.6
6
1.8
8
3
0
5
largely based on ideal
Horizontal Distance (m) releases from nozzles
9 rather than the acciden-
Isopentane’s LEL concentration plume extent due to a leakage at 90 oC. tal leaks that can occur
due to failure of such
containment elements as
IEEE In dustry A p plication s M ag az in e • jan |f eb 2016 • www.ieee.or g/ia s
0.6
0.8
2.2
2.4
2.6
2.8
3.2
3.4
3.6
3.8
4.2
4.4
4.6
4.8
1.2
1.4
1.6
1.8
0
3.2
3.4
3.6
3.8
4
4.2
4.4
4.6
4.8
5
5.2
3
5.4
selves sources of ignition.”
Horizontal Distance (m)
11
Conclusions Hexane’s LEL concentration extent due to a leakage at 14.22 lbf/in . 2
The most common char-
acteristic found in area-
classification drawings is
I E E E I ndu str y Appl ic ations Ma gazin e • jan |feb 2 016 • ww w.ieee .o rg /ias
the mere reproduction 1.5
of the figures presented 1.45
1.4
in API RP 500/505 and 1.35
in NFPA 497 [25]. Al- 1.3
though these documents 1.25
express in many parts of 1.2
1.15
their texts that it is nec- 1.1
essary to consider the 1.05
real conditions of the 1
plant under study and 0.95
0.9
not only the figures, 0.85
there is a misconception
Height (m)
0.8
that they can be used in- 0.75
dependently of the plant 0.7
0.65
characteristics, like a 0.6
cookbook that could 0.55
allow people with no ex- 0.5
perience in the subject 0.45
0.4
to quickly create area- 0.35
classification drawings. 0.3
The dilemma of ap- 0.25
plying classified loca- 0.2
0.15
tions’ extent has been a 0.1
concern for a long time. 0.05
The typical-figure pro- 0
0.4
0.2
0.6
0.8
2.2
2.4
2.6
2.8
3.2
3.4
3.6
3.8
4.2
4.4
4.6
4.8
5.2
5.4
1.2
1.4
1.6
1.8
An effective design for a classified area’s alert sign. With a simple design that follows ISO 3864-1, Graphi-
cal Symbols—Safety Colours
and Signs [29] recommenda-
tions, it has the “Ex” inside a
1.00e - 02 yellow triangle over a red-
9.50e - 03 colored background and
9.00e - 03 shows the zone, the gas
8.50e - 03 group, and the temperature
8.00e - 03 class of permitted electrical
7.50e - 03 and electronic equipment to
7.00e - 03 be used in a particular classi-
6.50e - 03 fied area. This is important
6.00e - 03 information not only for
5.50e - 03 maintenance workers but
5.00e - 03 also for safety officers and
4.50e - 03 installation inspectors.
4.00e - 03 The referenced area-clas-
3.50e - 03 sification drawing number
3.00e - 03 is also indicated on the sign,
2.50e - 03 stating that the document
2.00e - 03 exists and also making it
1.50e - 03
easier for the user to get
1.00e - 03
additional information,
Z
such as the limits of classi-
5.00e - 04 Y fied area.
0.00e + 00 X Copying generic figures
14 is not the correct way to
38
A three-dimensional indication of the region where the flammable atmosphere reaches its LEL. perform area classification.
On the other hand, the question is not easily solved using [10] Recommended Practice for Classification of Locations for Electrical Installations at
an equation. It is necessary to know the processes’ charac- Petroleum Facilities Classified as Class I, Division 1 and Division 2, API
RP-500, 2012.
teristics and the limitations of the mathematical models [11] P resentation of the Area Classification Plan, Petrobras Standard
used [30], [31]. NI-2706, Brazil, 2007.
There are a number of methods available for measuring [12] N. Penny and Z. Peceli, “Electrical area classification—Basic applica-
and calculating ventilation rates, and any method applied to tion, experience, and judgment,” IEEE Trans. Ind. Aplicat., vol. IA-23,
area classification must be straightforward and give a rea- no. 1, pp. 19–27, Jan. 1987.
[13] Recommended Practice for the Classification of Flammable Liquids, Gases, or
sonable degree of accuracy [32]. Vapors and of Hazardous (Classified) Locations for Electrical Installations in
Despite the progress in this subject, there is still a long Chemical Process Areas, NFPA Standard 497, 2012.
way to go, especially in dealing with flammable-mixture [14] D. M. Webber, M. J. Ivings, and R.C. Santon, “Ventilation theory
analysis. The IEC 60079-10-1 standard is considered to and dispersion modelling applied to hazardous area classification,” J.
Loss Prev. Process Ind., vol. 24, no. 5, pp. 612–621, Sept. 2011.
have an arbitrary outdoor methodology of little, if any, [15] J. E. Propst, L. A. Barrios Jr., and B. Lobitz, “Applying the API alter-
value [24]. nate method for area classification,” in Proc. IEEE PCIC Conf. Rec.,
Considering that the concepts of gas dispersion are used Denver, CO, 2005, pp. 51–62.
as the basis for modeling gas leaks and that fluid dynamics is [16] Health and Safety Laboratory, “Offshore hydrocarbon releases 2001–
2008,” HSE, U.K., Tech. Rep. RR 672, 2008.
outside the scope of electrical engineering, area-classification [17] A. W. Cox, F. P. Lees, and M. L. Ang, Classification of Hazardous Loca-
cannot be the duty of one electrical professional. The area- tions. London, U.K.: IChemE, 1989.
classification assessment should be the result of the consensus [18] A. H. Otsuka, “Quantitative analysis of classified areas extent,” M.Sc.
of a group consisting of process engineers, safety profession- thesis, UFS Univ., Brazil, 2011.
[19] A. McMillan, Electrical Installations in Hazardous Areas. Oxford, U.K.:
als, plant operators and the project management. Conse- Butterworth-Heinemann, 1998.
quently, standards for this subject would be better written if [20] A. M. Luiz and H. L. P. M. Filho, “Gas dispersion evaluation for area
issued in the international context by ISO, instead of IEC, classification using CFD,” Petrobras, Brazil, Tech. Rep. AEDC
because the latter is an organization represented only by elec- 01/2014: 2014.
[21] Explosive Atmospheres—Part 17: Electrical Installations Inspection and
trotechnology professionals, who are not familiar with fluid
Maintenance, IEC Standard 60079-17, 2007.
dynamics principles [22], [33]. [22] E. Rangel Jr. and C. A. Sanguedo, “International standards on explo-
The area-classification drawings are the final result of sive atmospheres: Harmonization is a hard but necessary task,” in Proc.
the assessment and must express the most probable occur- 8th PCIC Europe Conf. Rec., Rome, Italy, 2011, pp. 91–94.
rence of explosive atmospheres, elaborated under all regis- [23] Brazilian Criminal Code, Title VIII, Chapter I, Article 251, Decree
tered considerations found in the assessment dossier. 2848, 1940.
[24] Health and Safety Laboratory, “Area classification for secondary releas-
Figure 14 shows a three-dimensional visualization es from low pressure natural gas systems,” HSE Books, U.K., Tech.
using colors to identify the different concentrations of the Rep. RR630, 2008.
flammable atmosphere under a process leakage. The extent [25] C. Schlegel, A. Pfuetzenreiter, and J. Costa, “Reliability on area classi-
I E E E I ndu str y Appl ic ations Ma gazin e • jan |feb 2 016 • ww w.ieee .o rg /ias
can be used in the area-classification drawings to allow the fication studies,” in Proc. 13th Brazil Automation Congr., São Paulo, Bra-
correct specification of electrical and electronics equip- zil, 2009, pp. 87–101.
ment and also to guide the issuing of work permits for [26] R. Tommasini and E. Pons, “Classification of hazardous areas pro-
duced by maintenance interventions on NG distribution networks and
maintenance services. in presence of open surface of flammable liquid,” in Proc. IEEE PCIC
Oil and gas companies are realizing that the reproduc- Conf. Rec., Toronto, ON, Canada, 2011, pp. 211–220.
tion of the figures shown in recommended-practices docu- [27] T. Rains and B. Satavalekar, “Harmonizing ventilation requirements
ments cannot be accepted as a reliable area-classification for indoor lighter than air hazardous atmospheres,” in Proc. IEEE PCIC
plan for their industrial sites [11]. Conf. Rec., San Antonio, TX, 2010, pp. 119–127.
[28] Requirements for the Elaboration of the Classified Locations’ Alert Sign,
Petrobras Standard NI-2657, Rio de Janeiro, Brazil, 2005.
References [29] Graphical Symbols—Safety Colours and Safety Signs—Part 1: Design Princi-
[1] E. Rangel Jr., “Brazil moves from divisions to zones,” in Proc. 49th ples for Safety Signs and Safety Markings, ISO Standard 3864-1, 2011.
IEEE PCIC Conf. Rec., New Orleans, LA, 2002, pp. 23–29. [30] Model Code of Safe Practice—Part 15: Area Classification Code For Instal-
[2] National Electrical Code (NEC), NFPA 70, 2011. lations Handling Flammable Fluids, IP-15, 2005.
[3] Recommended Practice for Classification of Areas for Electrical Installations in
Petroleum Refineries, API RP 500, 1957. [31] E. Rangel Jr., “Assessment and definition of classified locations using
[4] Directive 1999/92/EC, Minimum Requirements for Improving the Safety international standards,” in Proc. 8th ENASSMA National Conf. Health,
and Health Protection of Workers Potentially at Risk from Explosive Atmo- Safety and Environment, Florianópolis, Brazil, 2001.
spheres (ATEX 137), EU, 1999. [32] A. Bozek and V. Rowe, “Flammable mixture analysis for hazardous
[5] R. Tommasini, E. Pons, and F. Palamara, “Area classification for explosive area classification,” in Proc. IEEE PCIC Conf. Rec., Cincinnati, OH,
atmospheres: Comparison between European and North American 2008, pp. 83–92.
approaches,” in Proc. IEEE PCIC Conf. Rec., Chicago, IL, 2013, pp. 57–63. [33] P. Leroux, “Area classification. Why? Where? How? Who? When?”
[6] R. J. Buschart, “Electrical area classification drawings: A comparison,” in Proc. IECEx Int. Conf., Dubai, UAE, 2012, pp. 56–71.
in Proc. IEEE PCIC Conf. Rec., Denver, CO, 1995, pp. 21–25.
[7] Explosive Atmospheres—Part 10-1: Classification of Areas—Explosive Gas Estellito Rangel Jr. (estellito@petrobras.com.br), Aurélio Moreira
Atmospheres, IEC Standard 60079-10-1, 2008. Luiz, and Hilton Leão de P.M. Filho are with Petrobras, Rio de
[8] Recommended Practice for Electrical Equipment Maintenance, NFPA Stan- Janeiro, Brazil. Rangel Jr. is a Senior Member of the IEEE.
dard 70B, 2013.
[9] Recommended Practice for Classification of Locations for Electrical Installa-
This article first appeared as “Area Classification Is Not a Copy
tions at Petroleum Facilities Classified as Class I, Zone 0, Zone 1 and Zone and Paste Process” at the 2014 IEEE IAS Petroleum and Chem-
2, API RP-505, 2012. ical Industry Committee Technical Conference.
39