TURBINE PROTECTIONS

ELECTRICAL PROTECTIONS
1. CONDENSER VAC.V.LOW
This protection acts only when the vac.raises above 540 mmHg and then drops
2. LUB.OIL PRESSURE VERY LOW

This protection acts when 2 out of the following 3 pr.switches act


a. MAV 43 CP 016 XG 51
b. MAV 43 CP 017 XG 51
c. MAV 43 CP 018 XG 51
3. FIRE PROTECTION SWITCH OPERATED AT UCB
MAY 00 EY 001
4. OIL TANK LEVEL VERY LOW

This protection acts when 2 out of 3 level switches acts for 2 secs,and the oil tank level MIN
switch MAV 10 CL 001 has acted
a.MAV 10 CL 006
b.MAV 10 CL 007
c.MAV 10 CL 008
This protection will not act when GVG is open
5.MAIN STEAM TEMP VERY LOW

This protection acts only when the temp raises >520degC and then decreases, sensed by
LBA 10 CT 0018 - Left
LBA 20 CT 0018 - Right
6.TURBINE TRIP SWITCH FROM UCB
MYA 01 E 2001
7.COMMAND FROM AUTOMATIC RUN UP SYSTEM
MAA 00 EL 00 X 554
8.GENERATOR PROTECTION
9.MASTER FUEL TRIP RELAY ENERGISED
10.BOILER DRUM LEVEL VERY HIGH
11.REVERSE POWER RELAY 1/2 OPERATED

The above protections TRIP the Turbine through Turbine Trip Relay-1 which activates TRIP SOV MAX 51 AA 001 and Turbine Trip Relay-2 which activates
MAX 51 AA 002
PROTECTIONS

< 540mmHg -- K132

< 1.2 Ksc

K134

>900mm from top

< 480 degC on both sides of MS Line

h activates TRIP SOV MAX 51 AA 001 and Turbine Trip Relay-2 which activates TRIP SOV
AX 51 AA 002