Sie sind auf Seite 1von 10

OptiNet™ Applications

A Healthier, More Energy


Efficient Approach to Demand
Control Ventilation

White Paper Series


A Healthier, More Energy Efficient Approach
to Demand Control Ventilation

Conventional Demand Control


Ventilation
Demand Control Ventilation (DCV) is a design article in the ASHRAE Journal states:
approach that has been applied for the past
“Field experience indicates that actual occupancy
dozen or more years with varying degrees of
levels are at least 25% to 30% lower and perhaps
success. The concept is simple; vary the amount
as much as 60% to 75% lower in some buildings
of outside air delivered within a building based
than design levels.” 2
on the occupancy level of a given area. This is
normally accomplished by deploying a large Contributing further to this unnecessary energy
number of individual carbon dioxide (CO2) consumption is the common response to nearly
sensors throughout the building and integrating all indoor air quality complaints: increase the
the feedback with the building control system. amount of outside air into a building before
When the CO2 level is detected to be lower than analyzing air content and knowing whether addi-
the design value, outside air may be reduced tional outside air is truly needed or not. Thus,
until the building ventilation requirement is met. even if the building was initially designed prop-
This ventilation requirement or rate is generally erly, over time, outside air (OA) levels tend to
calculated by multiplying the expected number increase unnecessarily.
of occupants by a recommended amount of air,
Demand Control Ventilation provides a potential
expressed as cubic feet per minute (CFM). The
energy saving solution to this excess use of
recommended amount of outside air is generally
outside air by controlling its levels in proportion
15 to 20 CFM for an office environment, but is
to the actual number of people in a building.
much higher for other types of spaces such as
This is accomplished by varying the amount of
operating rooms and laboratories. No matter
outside air into the building based on controlling
what the design value is for a given type of space,
to a set value of the difference in sensed carbon
all outside air must be heated, cooled and distrib-
dioxide values indoors vs. outdoors. The resulting
uted throughout the building — at a significant
total level of CO2 within the building is then
energy cost. The quantity of outside air is usually
diluted, as outside air is introduced, to a level of
set to a fixed value based on the ANSI/ASHRAE
CO2 above ambient outdoor levels based on the
62.1 standard1 and an assumed maximum design
volume of outside air. This concept of varying
level of occupancy for a building, irrespective of
the amount of outside air to maintain a setpoint
the actual occupancy of that building. Due to the
difference of CO2 value between indoors and
fact that most designs tend to be conservative
outdoors represents a simple control approach
and building use fluctuates over time, the result
that can produce a healthy, building environment
is that the majority of buildings are over venti-
that also conserves energy.
lated, in some cases significantly so. A July 2003

2 A Healthier, More Energy Efficient Approach to Demand Control Ventilation


With current energy costs at record levels, poten- minimum area component of the outdoor air
tial paybacks of one to two years are realistic for ventilation requirements that is typically 60 cfm
most geographic areas of the US. While it would per 1000 sq ft. However, in many cases this
appear that DCV should be a common building airflow level may be insufficient to eliminate
ventilation design practice, unfortunately that is complaints, especially during periods of low
not the case even given strong interest in DCV. occupancy.
This white paper identifies the major obstacles to
For example, in a typical multi-zone office envi-
widespread use of DCV and offers some solu-
ronment with conference rooms or areas with
tions to address these problems.
occasional dense occupancies, ventilation levels
have typically been set to values equaling 140 cfm
to 200 cfm per 1000 sq. ft. Since, DCV is rarely
Major Issues Inhibiting Widespread used, these levels effectively represent a fixed or
Use of DCV minimum level of ventilation. As such, the
Three major issues with conventional DCV are ASHRAE 62.1-2004 minimum value of 60 cfm
limiting its widespread application in buildings: per 1000 sq. ft. to handle non-human pollutants
represents a much lower level than has been used
1. Inability to appropriately address non-human
in the past. Additionally, published research refer-
pollutants
enced by ASHRAE has indicated that minimum
2. Inaccuracy of control leading to excess use of ventilation levels for non-human pollutants
outside air required to satisfy at least 80% of the people in a
3. Carbon dioxide sensor calibration and mainte- space has varied from a minimum of 30 cfm up
nance considerations. to and potentially beyond 400 cfm per 1000 sq.
ft in an office environment.
Concerns over Insufficient Ventilation of
As another point of comparison the California
Non-Human Pollutants
Energy Commission, in their Title 24 energy effi-
According to the ASHRAE Journal the single most
ciency legislation, mandates that 150 cfm per
important issue preventing greater use of DCV is
1000 sq. ft is the minimum ventilation allowable
the concern around non-human pollutants:
in an office to meet potential non-human pollu-
“Currently, most buildings do not use DCV tant levels at minimal occupancy. Furthermore,
because of concerns about nonhuman indoor an ASHRAE Journal article by William Fisk, et.
pollutants mentioned previously.” 3 al.3 that analyzed and summarized twenty one
ventilation rate studies indicated that a minimum
During periods of low occupancy, DCV can
of 20 cfm of outside air per person was recom-
reduce ventilation levels low enough that poten-
mended for both health and comfort reasons. It
tial building contaminant concentrations can
was further noted that:
increase to the point of causing occupants to
complain. These contaminants can be created by “Existing data do not indicate whether outside air
off gassing from new furnishings or construction supply per person or per unit floor area is more
materials, or increased levels of air contaminants strongly associated with health and perceived
from cleaning materials, high particle or dust IAQ.” 3
levels or other episodic occurrences such as spills
In fact, experience has shown that setting too low
of odorous liquids or volatile organic compounds
of a minimum ventilation level, whether in
(VOCs). ASHRAE has tried to address the issue
conjunction with DCV or statically, will cause
of non-human pollutants by recommending a
complaints. In response, the operations and

A Healthier, More Energy Efficient Approach to Demand Control Ventilation 3


maintenance group often disconnects the DCV Excess Use of Outside Air Due to the Normal
system and/or readjusts the minimum outside air Tolerances of CO2 Sensors
level to a much higher fixed level that is Another problem with conventional DCV
frequently higher than appropriate values and involves inaccurate control of outside air that can
wastes significant amounts of energy. waste significant amounts of energy. To accurate-
ly control outside air, CO2 sensors need to meas-
The truth is there is no fixed value of minimum
ure both the outside and indoor levels to obtain
outside air whether 60, 150 or 400 cfm per 1000
an accurate measure of the differential CO2 level.
sq. ft that is correct for even a single given area
A body of real time measurements across the
over time. Instead the appropriate value of venti-
country as well as many references4,5,6 state that
lation should be based on the amount of
CO2 readings often can vary by over 100 PPM,
ventilation required to dilute the level of contami-
even in a single day, in a typical range of 300 to
nants present in the indoor air at any given point
500 PPM. Additionally, readings above 500 PPM
in time. For example, a newly renovated area that
are also common due to re-entrainment from the
has been flushed out may have off gassing mate-
air handler’s own exhaust outlet, from other
rials for a period of time after occupancy that at
nearby air handlers’ exhaust outlets, or CO2
low ventilation rates can create contaminant levels
emissions from nearby combustion sources such
that exceed recommended guidelines. Specifically,
as flue exhaust, traffic sources, etc.
formaldehyde, particle or TVOC (Total Volatile
Organic Compounds) levels may be high enough Additional inaccuracies result from the use of two
to require a slightly higher ventilation level sensors to measure indoor and outside CO2,
initially, but can gradually be decreased over time. which doubles the error of the differential CO2
Another area of complaints and potential health measurement. For example, a typical accuracy
and allergy problems can result from high levels specification of a common CO2 sensor used for
of airborne dust and fine particles due to seasonal DCV is + 75 PPM. Since each sensor can have an
or occupant activities. These levels can rise to error range of + or – 75 PPM, the accuracy of the
noticeable complaint levels if proper ventilation differential measurement is double that of an
doesn’t dilute them to normal background levels. individual sensor or + 150 PPM. To underscore
Even high levels of moisture in the air due to the impact of this type of error on the control of
excessive rainfall, flooding or wet carpet cleaning outside air, assume a typical office building oper-
can create mold growth in a facility with reduced ating with at least a 20 cfm per person ventilation
levels of outside air in a short amount of time. level. A large body of evidence shows that occu-
pant health and perceived IAQ will usually be
In summary, Demand Control Ventilation’s
improved by maintaining ventilation rates of at
ability to lower the ventilation to minimum
least 20 cfm per person. The results of twenty one
levels below that appropriate for occasional high
CO2 ventilation studies involving over 30,000
levels of contaminants or humidity levels can
subjects in over 400 buildings concluded that:
create dissatisfaction and potential disabling of an
installed system. As a result, what is needed to “This review provides persuasive evidence that
make DCV healthier and more effective with less health and perceived air quality will usually
occupant complaints is a means to increase venti- improve with increased outside air ventilation.
lation (or at least not reduce ventilation to …The available data indicate that occupant
unoccupied levels) when high levels of non- health and perceived IAQ will usually be
human pollutants are present. improved by avoiding ventilation rates below 20
cfm (9 L/s) per occupant…” 3

4 A Healthier, More Energy Efficient Approach to Demand Control Ventilation


Fig. 1 A significant amount of energy can be wasted due to the doubling of sensor

A ventilation rate of 20 cfm per person corre- In summary, a more accurate means of measuring
sponds to an indoor to outdoor CO2 differential the differential CO2 levels is needed to provide a
of 525 PPM. To avoid ventilation rates below 20 much tighter span of control.
cfm per person when the differential CO2 sensor
measurement error can be up to + 150 PPM, the Operating Costs Related To CO2 Sensor
CO2 control point must be set to 375 PPM so Calibration and Maintenance
that given normal sensor tolerances, the ventila- The use of conventional Demand Control
tion rates will not fall below 20 cfm per person. Ventilation can potentially involve a large number
of CO2 sensors. In addition to the high first cost,
As shown in Fig. 1, the DCV system will then
the cost of calibrating and maintaining these
control the outside air to maintain a minimum
sensors is significant and can be a deterrent from
of 20 cfm/person even when the combined
employing DCV.
sensor error is + 150 PPM. However when the
combined error is instead -150 PPM the DCV “Other issues discouraging widespread DCV
system will then effectively set the differential adoption include the need for savvy system
CO2 level to 225 PPM, which corresponds to installation and operational personnel, which
about 46.7 cfm per person or about 133% addi- cost more and are hard to find; CO2 sensor
tional outside air! maintenance issues; and the limited number of
control systems that support CO2 sensor input
Even if the errors are not at the extremes corre-
for ventilation control.” 2
sponding to either 20 cfm per person (+150 PPM)
or 46.7 cfm per person (-150 PPM), the midpoint Focusing on the issue of CO2 maintenance, real
of these is still 67% more outside air than is world experience has shown that twice a year
required. As a point of reference, a typical 100,000 verification and potential calibration of the CO2
sq. ft. office building in Chicago operating at 67% sensors is needed to maintain the desired levels of
higher outside air during occupied hours will energy savings. Further support for this level of
consume approximately an extra $12,750/year or sensor maintenance is provided in section 8.4.1.7
$0.127 sq. ft./year in energy costs. of the ASHRAE 62.1-2004 ventilation standard
that states:

A Healthier, More Energy Efficient Approach to Demand Control Ventilation 5


Sensors: Sensors whose primary function is as if it is the assumed outdoor background level
dynamic minimum outdoor air control, such as of 400 PPM. Over time this will cause a sensor
flow stations at an air handler and those used for error of 200 PPM.
demand control ventilation, shall have their accu-
A second problem is that outdoor background
racy verified as specified in the Operations and
levels can vary significantly by more than 100
Maintenance Manual. This activity shall occur at
PPM. As a result, if in the middle of the night
a minimum of once every six months or periodi-
the building did reach outdoor background
cally in accordance with the Operations and
levels, this level is likely not to be the assumed
Maintenance Manual. A sensor failing to meet
400 PPM and will probably vary over time. If
the accuracy specified in the Operations and
instead the nighttime level is 500 PPM, and the
Maintenance Manual shall be recalibrated or
assumed background level is 400 PPM this alone
replaced.
will create an error of 100 PPM.
The cost of checking sensors every six months
The third error source is use of a one point
and recalibrating them as needed is significant,
or an offset only calibration method by the auto-
but critical due to concerns about sensor accuracy.
calibration system. As a minimum, any recalibra-
As a potential way to reduce the cost of calibra-
tion process should use a two-point recalibration,
tion many CO2 vendors offer an auto-calibration
enabling a gain and offset adjustment for accept-
feature stating that their sensors do not need to be
able accuracy. For example, if the sensor’s gain
calibrated for 5 years. Although this is a tanta-
has drifted by 10%, an offset only recalibration
lizing concept, it is important to understand the
at 400 PPM will still generate an error in the
underlying assumptions that make it less than
differential indoor to outdoor value of 10%,
ideal for use with DCV applications. Auto-cali-
representing a change in outdoor airflow of 10%.
bration assumes that in the middle of the night or
In total, all three error sources can result in
early morning hours, the building will have been
combined errors of several hundred PPM.
flushed to outdoor background levels which
should be constant at about 400 PPM. Based on In summary, since commercial quality CO2
this, the sensor averages the nighttime values and sensors can have significant drift characteristics,
periodically recalibrates its offset using a one for many applications the auto-calibration
point calibration to this averaged nighttime value. routine is a good concept because it limits the
sensor error to only a few hundred PPM or less
This auto-calibration function often causes more
depending on the application. Unfortunately,
accuracy problems than it solves, particularly
auto-calibration is not appropriate for DCV
when used with DCV, due to three major flaws
applications where more accurate differential
and problems. First, in many buildings, particu-
readings are required to save energy. The poten-
larly during the week, nighttime CO2 building
tial level of outside flow error generated can be
levels do not reach background or outdoor levels,
extremely costly. As a result, twice a year CO2
particularly if fans are turned off at night, or the
sensor checking and potential sensor recalibration
flow levels are reduced during unoccupied times.
as required by ASHRAE 62.1 is necessary and
This latter case is often true since at night the
appropriate for ensuring the desired energy
DCV controls should be significantly reducing
savings. To make certain that sensor calibration
outdoor airflow rates to some minimum level. As
and maintenance does not consume a large
a result, outdoor background levels may not be
percentage of the expected operating savings,
reached inside the building. Consequently, the
what is needed is a simpler, less expensive
CO2 sensor will read a level higher than the
approach.
background level, such as 600 PPM, and operate

6 A Healthier, More Energy Efficient Approach to Demand Control Ventilation


The Solution: Multi-parameter DCV Creating a Single Multi-parameter DCV
Control Signal
Requirements for Healthier, More Energy Implementing MpDCV is relatively straightfor-
Efficient DCV ward and very similar to using DCV except that
To remedy the stated concerns that have limited rather than employing a feedback signal equal to
widespread use and effectiveness of DCV, an the difference in carbon dioxide levels between
improved approach needs to meet the following indoor and outdoors, MpDCV uses a single
unique requirements: composite feedback signal. This composite
1. Economic sensing and control of non-human combines differential air signals from a number of
pollutants and humidity air quality based sensors with the differential CO2
signal used for conventional DCV. This is done
2. Accurate differential sensing of CO2 and other
by scaling each differential signal around the same
parameters
action or trigger level above which increased
3. Cost effective, simple sensor calibration and ventilation is warranted. The individual air
maintenance. parameter signals are then high selected together
An excellent solution to the first requirement is to create a single demand control ventilation
to implement DCV to vary ventilation based not signal. To determine which air parameters are
only on the level of occupancy in a space using important to sense, current EPA7 and State of
CO2, but also react to the real-time levels of Washington IAQ standards and guidelines for
multiple contaminants in an area or space. evaluating building indoor environmental quality
Expanding the number and type of sensed are used. These same guidelines for determining
parameters to include other key air quality indi- good Indoor Environmental Quality (IEQ)
cators, including non-human pollutants is known conditions within buildings are also referenced by
as multi-parameter DCV or MpDCV. With this the U.S. Green Building Council LEED® NC
concept, if the air in a space is clean and the version 2.2 rating system (EQ Credit 3.2 for flush
occupancy level is low, there is no reason to out of new or renovated buildings). It recom-
dilute clean indoor air with clean outdoor air. mends measurement of TVOC, particles, carbon
Instead, the minimum ventilation levels can be monoxide, and formaldehyde due to their occur-
decreased to those stated in the ASHRAE 62.1- rence as common building contaminants strongly
2004 standard. Potentially, levels can be even influenced by outside air ventilation levels.
lower during unoccupied times as long as the Appropriate levels of these materials are clearly
building’s positive pressurization level is main- stated by these guidelines and may be used to
tained. Conversely, when CO2, contaminant, or establish control levels for DCV similar to those
humidity levels are higher than recommended; commonly used for CO2. Many Asian and
ventilation levels can be increased to dilute the European countries have already adopted similar
room air to restore a healthy environment. guidelines for measuring indoor air pollutants.
Additionally, the level of outdoor contaminants An additional parameter that influences IEQ is
can be checked and if the source of the contami- relative humidity or dewpoint temperature. If the
nant is from outdoors, then airflow into the dewpoint temperature or similarly the absolute
building can be reduced to minimum levels to humidity of a space is significantly higher than
limit the entry of these contaminants. the supply air feeding the space, and is in excess
of 65%, then increased ventilation is highly

A Healthier, More Energy Efficient Approach to Demand Control Ventilation 7


MpDCV Air Parameters Typical Sources
Cleaning compounds, new building materials and
TVOC furnishings, carpets, paints, consumable products
Construction activity, smoke, dust, combustion products,
Fine particles aerosols, deteriorating materials, cooking
Leaking vented furnace, combustion, or flue gas exhaust,
Carbon monoxide unvented combustion appliances, parking garages

Formaldehyde Pressed wood products, furniture and furnishings

Water spills, rain leaks minor flooding, leaking and


Relative humidity condensing pipes

Fig. 2 The table summarizes the recommended air parameters for MpDCV in addition to CO2.

recommended. Increased ventilation will prevent sharing of signal processing overhead, power and
potential mold growth resulting from excess packaging. One disadvantage of this combined
humidity levels. For example, humidity levels can approach versus individual sensors is that it offers
increase due to a water spill, wet carpets or other less control in selecting the quality level of the
sources of condensation or moisture that origi- sensors used. Some of the sensors in these combi-
nate in the space versus from outside or from the nation units may be of a lower commercial grade
supply air. with higher drift and lower accuracies which are
not appropriate for this application.
Implementing Multiple-parameter DCV
One approach to implementing MpDCV is to Beyond the potential first cost and installation
use an individual sensor for each of the contami- implications of sensing 6 parameters in each space
nants listed in the guidelines, in addition to a or duct, it is important to remember, that many
CO2 sensor, for a total of 6 sensors per each sensors (i.e. metal oxide TVOC or formaldehyde)
room or air duct. Sampling data from the sensors potentially have significant drift. The amount of
can be combined by a BMS system to provide drift will vary from sensor to sensor creating inac-
the required combined MpDCV control signals. curate differential sensing as well as significant
A major drawback of this approach is the cost calibration expenses. Additionally, sensing out-
impact of having numerous individual sensor door humidity is also difficult to accomplish
packages that must be separately mounted and using commercial humidity sensors. To accurately
wired into the BMS system. measure humidity, more expensive, industrial
grade devices are needed to operate properly due
A more cost effective approach is to use sensor to the extremes of temperature, humidity levels
equipment that combines at least two or more and atmospheric dust that can significantly
sensors into one enclosure or onto one circuit degrade and affect outdoor sensors.
board. For example, several manufacturers
combine temperature, humidity and carbon An improved concept over these conventional
dioxide sensors into one package. As a result approaches is needed to overcome the aforemen-
perhaps only 2 or 3 sensor units need to be tioned issues and meet the requirements for
mounted and wired to accomplish sensing the 6 healthier, more energy efficient DCV.
required parameters. The total cost of the sensors
themselves should also be reduced due to some

8 A Healthier, More Energy Efficient Approach to Demand Control Ventilation


New Technology Provides Better, Very then “de-multiplexed” for each sampled area or
Cost Effective MpDCV air stream to create distinct sensor signals that
can be used for multi-parameter DCV as well as
A new sensing architecture known as a
other applications.
Multiplexed Sensing System or MSS solves the
issues identified in preceding sections and This sensing concept can also make “true” differ-
changes the age-old paradigm of sensing while ential measurements without the accuracy
decreasing calibration and maintenance expenses. concerns mentioned previously for commercial
grade CO2 sensors. Since the same sensor is used
Multiplexed Sensing System Architecture for both indoor/outdoor CO2 and other param-
and Benefits eter levels nearly simultaneously, any sensor
This new architecture, rather than locating mul- errors will be the same from both measurements
tiple sensors in each area or room, routes packets and will thus cancel out, enabling a very accurate
or samples of air from multiple locations sequen- measurement. Additionally, since only one sensor
tially, in a multiplexed fashion, to a shared set of is required for every 20 or so locations, more
sensors (Fig. 3). Every 30 to 45 seconds a sample accurate industrial grade sensors can be used for
of air from a different area or duct is routed on a even more precise measurements.
common air sampling backbone to the same set
of multi-parameter sensors, including CO2. Due to the limited number of sensors deployed,
Groups of sensors are housed in a unit known as and the central location of such sensors, calibra-
a sensor suite which can be customized to meas- tion expense is minimized. The calibration
ure any number of non-human pollutants, dew- process is streamlined through an exchange
point temperature, as well as specialty gases (i.e. program whereby a factory set of calibrated
ammonia). These sequential measurements are sensors periodically replaces the on site sensors,

Fig. 3 Facility-wide sensing architecture.

A Healthier, More Energy Efficient Approach to Demand Control Ventilation 9


such as every 6 months. The system is therefore Good: Use sensing supply air properties to
assured to operate at peak performance with control outdoor air intake.
minimal, or no disruption to facility operation.
Better: Sense multiple room spaces and control
How the MSS Creates Multi-parameter DCV outdoor air intake based on the room with the
Control Signals highest levels.
One other powerful advantage of the multiplexed Best: Sense multiple room spaces and sequence
sensing system is that it significantly reduces the individual control of room supply air based on
cost of implementing DCV by eliminating much high air parameters with control of outdoor air
of the signal processing and programming need- intake based on the room with the highest levels.
ed to implement multi-parameter or MpDCV.
This is because the MSS is a facility-wide inte-
grated sensing system that can possess significant
pre-programmed signal processing power specifi- Summary
cally designed for DCV applications. As such it
Demand Control Ventilation has always offered
removes much of the computational processing,
the opportunity for significant energy savings but
programming and project commissioning costs
has never realized its full potential due to con-
that MpDCV or even normal DCV can add to a
cerns about the presence of non-human pollu-
building controls system’s first cost.
tants, inaccurate control of outside air due to
For example, rather than having to high select, differential sensing errors, and the cost and com-
combine, and difference what could be dozens of plexity of system sensor calibration and mainte-
different sensor signals, the MSS does all of this nance. A new approach called multi-parameter
instantly. It then sends a single demand control DCV provides a solution to maximize energy
ventilation signal to the BMS that can be used in savings while still maintaining excellent indoor
a simple airflow control loop to command the environmental quality. It does so by maintaining
outside air flow of an air handling unit. building ventilation at lower levels of outdoor air
Furthermore, when multiple control loops are unless increased levels of non-human pollutants
used, a BACnet interface can provide a single dig- are sensed. Implementing MpDCV with a
ital connection for all the control and potentially Multiplexed Sensing System provides a simple,
monitoring signals while further lowering the cost very cost effective solution that has both high
of integration and installation. differential sensing accuracy and low sensor cali-
bration and maintenance expenses to preserve
The specific signal processing algorithms and
high operating savings. The result is a healthier
control approach required for a given MpDCV
indoor environment operating with maximum
application depends on the amount of energy
energy efficiency.
savings that is desired versus the first cost
required to achieve them. There are three major
levels of multi-parameter DCV applications that
can be implemented that provide a good, better,
best approach in terms of increasing building
energy savings for multiple zone HVAC systems:

10 A Healthier, More Energy Efficient Approach to Demand Control Ventilation

Das könnte Ihnen auch gefallen