Beruflich Dokumente
Kultur Dokumente
A ventilation rate of 20 cfm per person corre- In summary, a more accurate means of measuring
sponds to an indoor to outdoor CO2 differential the differential CO2 levels is needed to provide a
of 525 PPM. To avoid ventilation rates below 20 much tighter span of control.
cfm per person when the differential CO2 sensor
measurement error can be up to + 150 PPM, the Operating Costs Related To CO2 Sensor
CO2 control point must be set to 375 PPM so Calibration and Maintenance
that given normal sensor tolerances, the ventila- The use of conventional Demand Control
tion rates will not fall below 20 cfm per person. Ventilation can potentially involve a large number
of CO2 sensors. In addition to the high first cost,
As shown in Fig. 1, the DCV system will then
the cost of calibrating and maintaining these
control the outside air to maintain a minimum
sensors is significant and can be a deterrent from
of 20 cfm/person even when the combined
employing DCV.
sensor error is + 150 PPM. However when the
combined error is instead -150 PPM the DCV “Other issues discouraging widespread DCV
system will then effectively set the differential adoption include the need for savvy system
CO2 level to 225 PPM, which corresponds to installation and operational personnel, which
about 46.7 cfm per person or about 133% addi- cost more and are hard to find; CO2 sensor
tional outside air! maintenance issues; and the limited number of
control systems that support CO2 sensor input
Even if the errors are not at the extremes corre-
for ventilation control.” 2
sponding to either 20 cfm per person (+150 PPM)
or 46.7 cfm per person (-150 PPM), the midpoint Focusing on the issue of CO2 maintenance, real
of these is still 67% more outside air than is world experience has shown that twice a year
required. As a point of reference, a typical 100,000 verification and potential calibration of the CO2
sq. ft. office building in Chicago operating at 67% sensors is needed to maintain the desired levels of
higher outside air during occupied hours will energy savings. Further support for this level of
consume approximately an extra $12,750/year or sensor maintenance is provided in section 8.4.1.7
$0.127 sq. ft./year in energy costs. of the ASHRAE 62.1-2004 ventilation standard
that states:
Fig. 2 The table summarizes the recommended air parameters for MpDCV in addition to CO2.
recommended. Increased ventilation will prevent sharing of signal processing overhead, power and
potential mold growth resulting from excess packaging. One disadvantage of this combined
humidity levels. For example, humidity levels can approach versus individual sensors is that it offers
increase due to a water spill, wet carpets or other less control in selecting the quality level of the
sources of condensation or moisture that origi- sensors used. Some of the sensors in these combi-
nate in the space versus from outside or from the nation units may be of a lower commercial grade
supply air. with higher drift and lower accuracies which are
not appropriate for this application.
Implementing Multiple-parameter DCV
One approach to implementing MpDCV is to Beyond the potential first cost and installation
use an individual sensor for each of the contami- implications of sensing 6 parameters in each space
nants listed in the guidelines, in addition to a or duct, it is important to remember, that many
CO2 sensor, for a total of 6 sensors per each sensors (i.e. metal oxide TVOC or formaldehyde)
room or air duct. Sampling data from the sensors potentially have significant drift. The amount of
can be combined by a BMS system to provide drift will vary from sensor to sensor creating inac-
the required combined MpDCV control signals. curate differential sensing as well as significant
A major drawback of this approach is the cost calibration expenses. Additionally, sensing out-
impact of having numerous individual sensor door humidity is also difficult to accomplish
packages that must be separately mounted and using commercial humidity sensors. To accurately
wired into the BMS system. measure humidity, more expensive, industrial
grade devices are needed to operate properly due
A more cost effective approach is to use sensor to the extremes of temperature, humidity levels
equipment that combines at least two or more and atmospheric dust that can significantly
sensors into one enclosure or onto one circuit degrade and affect outdoor sensors.
board. For example, several manufacturers
combine temperature, humidity and carbon An improved concept over these conventional
dioxide sensors into one package. As a result approaches is needed to overcome the aforemen-
perhaps only 2 or 3 sensor units need to be tioned issues and meet the requirements for
mounted and wired to accomplish sensing the 6 healthier, more energy efficient DCV.
required parameters. The total cost of the sensors
themselves should also be reduced due to some