BAR SIZE DIAMETER, IN. AREA, IN WEIGHT, LB/FT
a. Source: Wire Reinforcement Institute (WRI): Manual of Standard Practice – Structural Welded Wire Reinforcement (Hartford, CT: WRI, 2008).
b. The number following W or D identifies the cross-sectional area of the wire in hundreths of a square inch.
c. ASTM A82, available fy = 65,000 psi to 80,000 psi in 2500 psi increments.
d. ASTM A496, available fy = 70,000 psi to 80,000 psi in 2500 psi increments.
GENERAL DESIGN INFORMATION CHAPTER 15
Design Aid 15.4.4 Required Development Lengths,a in., for Reinforcing Bars (Grade 60)
Tension development length: (f) For tension lap splices, item (e) does not apply.
d Lap splice lengths must conform to ACI 318-05,
ld = 2400 b ' ; min. 12 in. (#6 and smaller)
fc Section 12.15.
db Compression development length:
ld = 3000 ; min. 12 in. (#7 and larger) 1200d b
fc' ldc = larger of or 18db but no less than 8 in.
fc'
Note: For Grade 40 bars, replace 2400 and 3000 with 1600
and 2000, respectively. Note: For Grade 40 bars, replace 1200 with 800 and 18 with
12.
Multiply ld values by : Multiply ld values by:
(a) 1.3 for lightweight concrete (a) As (required)/As (provided) for excess
(b) 1.3 for “top bars”b reinforcement
(c) 1.5 for epoxy-coated bars with cover < 3db or clear (b) 0.75 for adequate spiral or tie enclosure
spacing < 6db, otherwise multiply by 1.2 (see ACI 318-05, Section 12.3.3b)
Note: Product of factors (b) and (c) need not exceed Compression splice lap length:
1.7. Lap length = 30db; min. 12 in. for fy = 60,000 psi
(d) 1.5 for bars with less than minimum stirrups or ties, Lap length = (0.0009fy – 24) db for fy > 60,000 psi
clear spacing less than 2db, or clear cover less than
db
The values of fc' used in these equations shall not exceed
(e) As (required)/As (provided) for excess reinforce-ment
100 psi (see ACI 318-05, Section 12.1.2).
unless development of fy is specifically required. This
multiplier is not to be applied to lap splices per
ACI 318-05, Section R12.15.1. 15
fc' = 3000 psi fc' = 4000 psi fc' = 5000 psi fc' = 6000 psi
Bar Com- Com- Com- Com- Min.
size, Tension pres- Tension pres- Tension pres- Tension pres- comp.
# sion sion sion sion splice
ld 1.3ld 1.5ld ld ld 1.3ld 1.5ld ld ld 1.3ld 1.5ld ld ld 1.3ld 1.5ld ld
3 16 21 25 8 14 18 21 8 13 17 19 8 12 15 17 8 12
4 22 28 33 11 19 25 28 9 17 22 25 9 15 20 23 9 15
5 27 36 41 14 24 31 36 12 21 28 32 11 19 25 29 11 19
6 33 43 49 16 28 37 43 14 25 33 38 14 23 30 35 14 23
7 48 62 72 19 42 54 62 17 37 48 56 16 34 44 51 16 26
8 55 71 82 22 47 62 71 19 42 55 64 18 39 50 58 18 30
9 62 80 93 25 54 70 80 21 48 62 72 20 44 57 66 20 34
10 70 90 104 28 60 78 90 24 54 70 81 23 49 64 74 23 38
11 77 100 116 31 67 87 100 27 60 78 90 25 55 71 82 25 42
fc' = 7000 psi fc' = 8000 psi fc' = 9000 psi fc' ≥ 10,000 psi
Bar Com- Com- Com- Com- Min.
size, Tension pres- Tension pres- Tension pres- Tension pres- comp.
# sion sion sion sion splice
ld 1.3ld 1.5ld ld ld 1.3ld 1.5ld ld ld 1.3ld 1.5ld ld ld 1.3ld 1.5ld ld
3 12 14 16 8 12 13 15 8 12 12 14 8 9 12 14 8 12
4 14 19 22 9 13 17 20 9 13 16 19 8 12 16 18 8 15
5 18 23 27 11 17 22 25 11 16 21 24 8 15 20 23 8 19
6 22 28 32 14 20 26 30 14 19 25 28 9 18 23 27 9 23
7 31 41 47 16 29 38 44 16 28 36 42 11 26 34 39 11 26
8 36 47 54 18 34 44 50 18 32 41 47 13 30 39 45 12 30
9 40 53 61 20 38 49 57 20 36 46 54 14 34 44 51 14 34
10 46 59 68 23 43 55 64 23 40 52 60 16 38 49 56 15 38
11 51 66 76 25 47 61 71 25 45 58 67 17 41 54 62 17 42
a. For limitations and items related to hooked bars, stirrups or ties in excess of minimum, and spacing of non-contact lap splices, etc., see ACI 318-05, Chapter 12.
b. A top bar is any horizontal reinforcement placed such that more than 12 in. of fresh concrete is cast below the development length.
Note: comp. = compression; min. = minimum.
Design Aid 15.4.4 Required Development Lengthsa, in., for Reinforcing Bars (Grade 60) (Cont.)
AsFy AsFy
db
12db
Note: Check minimum requirements for temperature and shrinkage steel. c/c = center to center.
How to use this design aid. Given a design (or minimum Example. A design that requires reinforcement at 0.62 in.2/
temperature/shrinkage) reinforcement required per foot, enter ft, with bar size restricted to #7 or smaller. Enter the design aid in
the design aid along right column or bottom row. Select one the 0.50 to 0.75 in.2 range located along the bottom row. Follow
of the bar area ranges from that given in.2/ft, and follow the the shaded band up to the top of the table. Select one of the fol-
range band upward and/or to the left. Select the combination of lowing combinations: one layer of #4 at about 3.5 in. on center,
bar size and spacing satisfying the design and spacing require- #5 at 6 in. on center, #6 at 8.5 in. on center, or #7 at 11.5 in. on
ments for the section. center. Similar spacing(s) could be determined for two reinforce-
ment layers, if desired.
J
A or G
A or G
12db for #6, 7, 8
Hook
D 6db for #3, 4, 5
J
Detailing
Detailing
Detailing
dimension db 6db Table 25.3.2—
db D
for stirrups, t
Type of stan-
D D dard hook
A or G
D 12db
90-degree
180° 90° 90° 135° hook
Bar size,
D D
# A or G J A or G A or G A or G H
3 2 ⁄4
1
5 3 6 1 ⁄2
1
4 4 /4 1
21⁄2
4 3 6 4 8 2 41⁄2 41⁄2 3
135-degree
5 33⁄4 7 5 10 21⁄2 6 51⁄2 33⁄4
hook
6 41⁄2 8 6 1–0 41⁄2 1–0 8 41⁄2
7 51⁄4a 10 7 1–2 51⁄4 1–2 9 51⁄4
8 6a 11 8 1–4 6 1–4 101⁄2 6
9 9 1–3 111⁄4 1–7
180-degree
10 10 1–5 1–01⁄2 1–10 hook
U.S. customary units: in. or ft-in.
11 11 1–7 1–13⁄4 2–0
14 1–51⁄2 2–3 1–9 2–7 [1]
A standard hook for
18 1–101⁄2 3–0 2–3 3–5 be permitted to use a
anchorage capacity of
a. ASTM A767 requires that bars bent cold prior to hot-dip galvanizing must be fabricated to a minimum bend diameter equal to 7 in. for #7
bar and 8 in. for #8 bar.
H G A G A G A G
A H H
A G
B D B D B D B D B D
C C C C C
S1 S2 S3 S4 S5
Lap - G
D
A G B B G
U A
G
A C
B D H C E C E (circumference)
C
( Blength
= total
) D D
B O
S6 S11 T1 T2 T3
A E K K
B A E
A G G
C E B D B D A
H H G
B
D C C
T6 T7 T8 T9
15
A G A
A G
J
B B B
1 1A 2
O O O
B F B F B F
J C E J C E C E
H H A H G
A D G A D D
3 3A 4
O
O O
B F B
G B
J C E H J C C
A H J A H G
D A D D
4A 5 6
Notes:
1. All dimensions are out-to-out of bar except A and G on standard 180 and 135 deg hooks.
2. J dimensions on 180 deg hooks to be shown only where necessary to restrict hook size, otherwise ACI standard hooks are to be used.
3. Where J is not shown, J will be kept equal or less than H on Types 3, 5, and 22. Where J can exceed H, it should be shown.
4. H dimension stirrups to be shown where necessary to fit within concrete.
5. Where bars are to be bent more accurately than standard fabricating tolerances, bending dimensions that require closer fabrication should
have limits indicated.
6. Figures in circles show types.
7. For recommended diameter D of bends and hooks, and for dimensions of hooks, see Design Aid 15.4.1.
8. Type S1 through T3, T6 through T9; apply to bar sizes #3 through #8.
9. Source: American Concrete Institute (ACI): Details and Detailing of Concrete Reinforcement (ACI 315-99) (Farmington Hills, MI: ACI, 1999).
O B
R
C E A
H H
A J G G
B
D O
K
7 8 9
R B O K
C
J
A B D
B J H
H A
A C R
C D
O O
10 11 12
K
K
C C
B
J J
B B H
D H
A A R G
H
C
O O D
15 O
12A 12B 13
O O O
A E A A
H B D H B D H B
C C
K K
14 14A 14B
K K
C C
D D
B H B H B D
A
C
O O
16 16A 17
Notes:
1. All dimensions are out-to-out of bar except A and G on standard 180 and 135 deg hooks.
2. J dimensions on 180 deg hooks to be shown only where necessary to restrict hook size, otherwise ACI standard hooks are to be used.
3. Where J is not shown, J will be kept equal or less than H on Types 3, 5, and 22. Where J can exceed H, it should be shown.
4. H dimension stirrups to be shown where necessary to fit within concrete.
5. Where bars are to be bent more accurately than standard fabricating tolerances, bending dimensions that require closer fabrication should
have limits indicated.
6. Figures in circles show types.
7. For recommended diameter D of bends and hooks, and for dimensions of hooks, see Design Aid 15.4.1.
8. Type S1 through T3, T6 through T9; apply to bar sizes #3 through #8.
9. Source: American Concrete Institute (ACI): Details and Detailing of Concrete Reinforcement (ACI 315-99) (Farmington Hills, MI: ACI, 1999).
O
K
B A
B
J H C
C B C D
17A 18 19
O
F
B B B
H C C E K
C J H
D G
A D
19A 20 22
O Standee D
F A (isometric
B
C E G J view) C
A H K E
B H
D
G
23 24 B
K
F
D D 25
Standee Standee
(isometric view)
C
(isometric
C 15
E B E
B view)
F F B
26 26A
C
J D D
D D
Standee H
Standee C
(isometric D
(isometric C view) B
view) K D
B
26C 26B
Enlarged view showing
bar bending details
Notes:
1. All dimensions are out-to-out of bar except A and G on standard 180 and 135 deg hooks.
2. J dimensions on 180 deg hooks to be shown only where necessary to restrict hook size, otherwise ACI standard hooks are to be used.
3. Where J is not shown, J will be kept equal or less than H on Types 3, 5, and 22. Where J can exceed H, it should be shown.
4. H dimension stirrups to be shown where necessary to fit within concrete.
5. Where bars are to be bent more accurately than standard fabricating tolerances, bending dimensions that require closer fabrication should
have limits indicated.
6. Figures in circles show types.
7. For recommended diameter D of bends and hooks, and for dimensions of hooks, see Design Aid 15.4.1.
8. Type S1 through T3, T6 through T9; apply to bar sizes #3 through #8.
9. Source: American Concrete Institute (ACI): Details and Detailing of Concrete Reinforcement (ACI 315-99) (Farmington Hills, MI: ACI, 1999).
z Cover
Stirrup
or tie
Main
reinforcement
To determine location of main reinforcement, add specified cover to the z dimension from the table.
3 5
4 ld
1 11/ " maximum 2
5 2
2
/3d maximum
h d
Vua + Nu(h-d) Ah
Av As D
H
Nu Ash
a H-d ld
Vu Assh
A'
lp
Critical, minimize
5 D
H
Ash
Critical, minimize
H-D ld
Fig. 5.6.3 Potential failure modes and required reinforcement in dapped-end connections.
where:
φ = 0.9
Fy = material yield strength
Zp = plastic section modulus
Allowableb Designc
Electrode
working stress, ksi strength, ksi
E70 21 31.5
6
E80d 24 36.0
E90d 27 40.5
E100d 30 45.0
a. For partial penetration welds loaded in shear parallel to the axis of the weld.
b. Based on AISC Steel Construction Manual.4
c. Based on AISC Steel Construction Manual. Includes φ = 0.75.
d. Refer to AWS D1.1 Table 3.1 – Prequalified Base Metal – Filler Material Combinations for Matching Strength.
Design Aid 6.15.3 Minimum Length of Weld to Develop Full Strength of Bar. Weld Parallel to Bar
Lengtha,b,c
tw = 0.2db db
6 tw = 0.3db
15° maximum db
0.2db
lw 0.2db
Splice
Plate
Minimum length of weld, in.a Min.
thickness
Electrode Bar splice
in. 1/4 5/16 3
/8 7/16 1
/2
size, # length, in.
3 11/4 11/4 11/4 11/4 11/4 1
4 1 /4
3
1 /4
3
1 /4
3
1 /4
3
1 /4
3
11/4
5 21/4 21/4 21/4 21/4 21/4 11/2
6 2 /4
3
2 /2
1
2 /2
1
2 /2
1
2 /2
1
13/4
E80d 7 33/4 3 3 3 3 2
8 5 4 31/2 31/2 31/2 21/4
9 61/4 5 41/4 33/4 33/4 21/2
10 8 61/4 51/4 41/4 41/4 3
11 9 /4
3
7 /4
3
6 /2
1
5 /2
1
4 /4
3
31/4
3 11/4 11/4 11/4 11/4 11/4 1
4 1 /2
1
1 /2
1
1 /2
1
1 /2
1
1 /2
1
1
5 2 2 2 2 2 11/4
6 23/4 21/4 21/4 21/4 21/4 11/2
E90d 7 33/4 3 23/4 23/4 23/4 13/4
8 5 4 3 /4
1
3 3 2
9 6 /4
1
5 4 /4
1
3 /4
3
3 /2
1
21/4
10 8 61/4 51/4 41/2 4 21/2
11 9 /4
3
7 /4
3
6 /2
1
5 /2
1
5 23/4
a. Lengths above the heavy line are governed by weld strength. Lengths below the heavy line are governed by plate shear.
Basis: bar fy = 60 ksi; plate Fy = 36 ksi; shear on plate limited to 0.9(0.6)(36) = 19.44 ksi.
b. Weld length listed is the required effective length of weld. Engineer should consider whether weld at start and stop is fully effective.
c. Refer to Design Aid 15.4.2 for specifications of flare bevel groove welds.
d. Refer to AWS D1.1 Table 3.1 – Prequalified Base Metal – Filler Material Combinations for Matching Strength and AWS D1.4 Table 5.1 Matching Filler Metal
Requirements. Use E80 Electrodes for ASTM A706 rebar; use E90 electrodes for ASTM A615 rebar.
Design Aid 6.15.4 Size of Fillet Weld Required to Develop Full Strength of Bar. Butt Weld.
BAR PERPENDICULAR
TO PLATE, WELDED db a
ONE SIDE
⎛
lw = π ⎜ d b + ⎟
a⎞
Weld size 6
⎝ 2⎠
Plate = Fy = 36 ksi
Grade 40 bar
3 3
/16 1
/4 3
/16 1
/4 3
/16 1
/4
4 1
/4 1
/4 3
/16 1
/4 3
/16 1
/4
5 1
/4 1
/4 1
/4 1
/4 1
/4 1
/4
6 5
/16 1
/4 1
/4 1
/4 1
/4 1
/4
7 3
/8 5
/16 5
/16 5
/16 5
/16 5
/16
8 7
/16 5
/16 1
/8 5
/16 5
/16 1
/8
9 7
/16 1
/8 7
/16 1
/8 1
/8 1
/8
10 1
/2 1
/8 7
/16 7
/16 7
/16 7
/16
11 /16
9 7
/16 1
/2 7
/16 7
/16 1
/2
Grade 60 bard
3 3
/16 1
/4 3
/16 1
/4
4 1
/4 1
/4 1
/4 1
/4
5 5
/16 1
/4 5
/16 5
/16
6 3
/8 5
/16 3
/8 5
/16
7 7
/16 3
/8 3
/8 3
/8
8 1
/2 7
/16 7
/16 7
/16
9 9
/16 1
/2 1
/2 1
/2
10 5
/8 1
/2 9
/16 9
/16
11 11
/16 9
/16 5
/8 5
/8
a. Refer to AWS D1.1 Table 3.1 – Prequalified Base Metal – Filler Material Combinations for Matching Strength and AWS D1.4 Table 5.1 Matching Filler Metal
Requirements. Use E80 Electrodes for ASTM A706 rebar; use E90 electrodes for ASTM A615 rebar.
b. A minimum of 3/16 in. weld size is suggested.
c. Theoretical thickness for shear stress on base metal = 0.9(0.6)(36) ksi. A more practical thickness might be taken as 1/2 db as used with headed studs. A mini-
mum of 1/4 in. plate thickness is suggested.
d. E70 electrodes are not permitted for grade 60 reinforcement.
Design Aid 6.15.5 Size of Fillet Weld Required to Develop Full Strength of Bar. Weld Through Hole.
BAR PERPENDICULAR db a
TO PLATE, WELDED BOTH SIDES
2 Weld
⎡ a⎤ size
lw = π ⎢d b + ⎥
6 ⎣ 2⎦
tpl
Plate = Fy = 36 ksi
Plate area = π(db + 2a)tpl
Grade 40 bar
3 3
/16 1
/4 3
/16 1
/4 3
/16 1
/4
4 3
/16 1
/4 3
/16 1
/4 3
/16 1
/4
5 3
/16 1
/4 3
/16 1
/4 3
/16 1
/4
6 3
/16 5
/16 3
/16 5
/16 3
/16 5
/16
7 3
/16 3
/8 3
/16 3
/8 3
/16 3
/8
8 1
/4 3
/8 3
/16 7
/16 3
/16 7
/16
9 1
/4 7
/16 1
/4 7
/16 3
/16 7
/16
10 5
/16 1
/2 1
/4 1
/2 1
/4 1
/2
11 5
/16 9
/16 5
/16 9
/16 1
/4 9
/16
Grade 60 bard
3 3
/16 1
/4 3
/16 1
/4
4 3
/16 5
/16 3
/16 5
/16
5 3
/16 3
/8 3
/16 3
/8
6 1
/4 7
/16 3
/16 7
/16
7 1
/4 1
/2 1
/4 1
/2
8 5
/16 9
/16 1
/4 9
/16
9 5
/16 5
/8 5
/16 5
/8
10 3
/8 11
/16 5
/16 11
/16
11 3
/8 3
/4 3
/8 3
/4
a. Refer to AWS D1.1 Table 3.1 – Prequalified Base Metal – Filler Material Combinations for Matching Strength and AWS D1.4 Table 5.1 Matching Filler Metal
Requirements. Use E80 Electrodes for ASTM A706 rebar; use E90 electrodes for ASTM A615 rebar.
b. A minimum of 3/16 in. weld size is suggested.
c. Theoretical thickness for shear stress on base metal = 0.9(0.6)(36) ksi. A more practical thickness might be taken as 1/2 db as used with headed studs. A mini-
mum of 1/4 in. plate thickness is suggested.
d. E70 electrodes are not permitted for grade 60 reinforcement.