Sie sind auf Seite 1von 2

General E Glass Fiber Preformed Pipe Sections Application Procedure

Material On Insulation On Aluminum Cladding


Pipe Cover
Installation Longitudinal joints are preferably at 2-4 O’ clock & Standard grooving shall be carried out. Ensure
8-10 O’ clock position. However, as per practical site overlapping of at least 50 mm on longitudinal joints
condition this may very. Two pipe cover insulation and 100 mm on circumferential joints. Keep
shall be pushed firmly at circumferential joints and adequate distance wherever support or any metal
longitudinal for air tight installation. Use of “Russi” is obstacle in order to avoid additional heat losses.
preferred to hold it on in airtight position while
installing.
Aluminum Glass Coated Tape To be applied on each seam & longitudinal joints of Not required
(ALGC) pipe cover/ elbows for sealing it in air tight manner.
SS 304 Wires To be applied in case of double layer insulation, first Not required
layer of insulation is fixed by SS 304 wires.
SS 304 Straps & Clips To be applied on thermal insulation to hold it To be applied on aluminum cladding to hold it with
insulation in airtight manner with hot pipe for life. insulation in airtight manner.
(In case of double layer, on outer layer of
insulation).
25 mm E Glass Fiber Needle To be applied as expansion joint at every 3-15 Not required
Punched Felt Expansion meters depending up on temperature, pipe size.
Joints To be applied at both the ends of Elbow to manage
expansion of pipes
Aluminum Glass Coated Tape To be applied on each seam & longitudinal joints of Not required
(ALGC) pipe cover/ elbows for sealing it in air tight manner.
Tar Felt Not required To be applied on longitudinal joints in 30 mm width
to seal the joints.
Screw Not required Minimum usage recommended (only wherever
required)
Elbows, Valves and Fittings
Elbows To be prepared in MITRE form. Each piece shall be Standard grooving shall be carried out. Ensure
stapled with industrial pins and sealed with ALGC adequate overlapping on longitudinal and
tape for airtight holding of joints. circumferential joints. SS 304 Straps and clips shall
be provided and in addition if required, some
screwing shall be carried out
Valves, Tees and Other Instead of pipe cover, Felt shall be used and Standard grooving shall be carried out. Ensure
uneven shapes tightened with SS 304 wire. adequate overlapping on all joints.

Pipe Cover shall be placed at around 2-4 O’ Clock Position

पाइपकवर के लोंगिटुड़ीनल जॉइंट जहा तक संभव है वहा तक घड़ी के 2-4 बजे के पास और 8-10
बजे के आसपास रखे. दोनो हहस्सो को रस्स़ी सेबरोबार टाइट करे . एएलज़ीस़ी टे प को लोंगिटुड़ीनल
जॉइंट पर लिाए. इसके बाद एसएस 304 के तार से बााँधे. उसके बाद एसएस 304 के स्रॅ प को
टाइटननंि टूल की मदद से फिट करे . इसके बाद दस
ू रा पाइपकवर को ले और बाजू वाले फिट फकए
िये पाइपकवर के साथ इकदम सटाके लिाए और ध्यान रखेकी कोई एरिॅप ना रहे ने पाए और उपर
वाली पूरी प्रफिया दब
ु ारा करे . दोनो पाइपकवर के सककमिेरनससयाल जॉइंटके ब़ीचमे एएलज़ीस़ी
टे पको लिाए.

हरे क एल्बो के दोनो साइडमे 35-45 MM िॅप छोडके पाइपकवर लिाना होिा. यह िॅपमे िेल्ट को
उल्टा यू की तारह एक्षपान्सन जॉइंट को लिाना है . अिर दो एल्बोके ब़ीचकी दरू ी अिर कुछ म़ीटरसे
ज़्यादा है (लाइनसाइज़ 12 इंच से ज़्यादा के सलए 8-10 म़ीटर और कम लाइनसाइज़के सलए 12-14
म़ीटर से ज़्यादाके सलए), तो दो पाइपकवरके ब़ीचमे 35-45 MM िॅप छोडके एक्षपान्सन जॉइंट को
लिाना है .

ये सब प्रफिया बहोत ध्यान और बबना ग़लत़ीसे और जज़म्मेवारीसे करना हमारा कतकव्य है .


GENERAL BASIC INSTALLATION

SINGLE LAYER INSULATION DOUBLE LAYER INSULATION

E GLASS FIBER PIPE SECTIONS

E GLASS FIBER FLAT & ROUND BOARDS