Sie sind auf Seite 1von 3

EQUIPMENT DATA SHEET

Document No: G080356


Generator Revision: D
Created By: G. Rabone
NHC20/DC16 45A 500kVA AI 2010 Approved By: C. Shrive
Approval Date: 15/07/2016
Page: 1 of 3

Model
Model reference GN0500GHPLON
Model size and rating 500 kW
Bill of Material reference number 602128 B

Manufacturer
Model Reference NHC20/DC16 45A (10.26) NHC20/DC16 45A (10.26)

Electrical Output
Electrical Output Hz (Hz) 50.0 (50) 60.0 (60)

Performance Data
Maximum Ambient °C (°F) 40.0 (104) 45.0 (113)

Electrical (ISO 8528-1) *


Continuous Power (COP) kW (kVA) 362.0 (452.5) 352.0 (440)
Prime Power (PRP) kW (kVA) 404.0 (505) 394.0 (492.5)
Permissible Average of PRP 70% 70%

Electrical (ISO 3046-1) **


Single Step Load Application 65% 65%
Fuel Stop Power/Standby kW (kVA) 441.0 (551.25) 435.0 (543.75)

Alternator
Class F Temp Rise (105°C) Three Phase 440/440 kW (550/550 kVA) 500/540 kW (625/675 kVA)

Ends Out 12 12
Make & Type Newage HCI534E Newage HCI534E
AVR MX341 +PMG MX341 +PMG
Regulation +/- 1.0 % +/- 1.0 %

Circuit Breaker
Make & Type Merlin Gerin NS 1600 Merlin Gerin NS1600
Number of Poles 4 4

This document Contains PROPRIETARY and CONFIDENTIAL information and may NOT be copied or reproduced in any media without written permission from Aggreko.
Technical Information contained herein is subject to change without notice. Some data may vary on machines.

ISO references apply to Aggreko Manufacturing built equipment only


* ISO 8528-1 Reciprocating Internal Combustion Engine Driven Alternating Current Generating Sets:
Part 1 - Application, Ratings and Performance
** ISO 3046-1 Reciprocating Internal Combustion Engines: Performance:
EQUIPMENT DATA SHEET

Document No: G080356


Generator Revision: D
Created By: G. Rabone
NHC20/DC16 45A 500kVA AI 2010 Approved By: C. Shrive
Approval Date: 15/07/2016
Page: 2 of 3

Rating Amp (Amp) 1600.0 (1600) 1600.0 (1600)


Trip Unit Type Micrologic 5.0 Micrologic 5.0
Overload Protection Range 640-1600 640-1600
Short Circuit Protection Range 960-16000 960-16000

Load Terminals
Type Busbar M12 Busbar M12

Engine
Make & Type Scania DC16 45A (10.26) Scania DC16 45A (10.26)
Cylinders & Form V8 - 90° V8 - 90°
Aspiration Turbo Charged & Charge Air Turbo Charged & Charge Air
Cooled Cooled
Governor Make & Type Scania (EMS) Engine Management Scania (EMS) Engine Management
System S6 System S6
Steady State Frequency +/- 0.5 % +/- 0.5 %
Battery Voltage Volts (Volts) 24.0 (24) 24.0 (24)

Fuel Consumption
Standby/Fuel Stop L/hr (US 102.9 (27.166) 103.6 (27.35)
gal/hr)
100% Prime Power L/hr (US 94.2 (24.869) 93.3 (24.631)
gal/hr)
75% Prime Power L/hr (US 70.65 (18.652) 69.97 (18.472)
gal/hr)
50% Prime Power L/hr (US 47.1 (12.434) 46.6 (12.302)
gal/hr)

Running Hours
100% Prime Power Hours (Hours)13.4 (13.4) 13.5 (13.5)
75% Prime Power Hours (Hours)17.9 (17.9) 18.0 (18)
50% Prime Power Hours (Hours)26.8 (26.8) 27.1 (27.1)

Exhaust Emissions
Measurement Method (Certified to EU TA Luft EPA-MOH/CARB
Stage II)
Specific Load 100% Prime ± 2% 100% Prime ± 2%

This document Contains PROPRIETARY and CONFIDENTIAL information and may NOT be copied or reproduced in any media without written permission from Aggreko.
Technical Information contained herein is subject to change without notice. Some data may vary on machines.

ISO references apply to Aggreko Manufacturing built equipment only


* ISO 8528-1 Reciprocating Internal Combustion Engine Driven Alternating Current Generating Sets:
Part 1 - Application, Ratings and Performance
** ISO 3046-1 Reciprocating Internal Combustion Engines: Performance:
EQUIPMENT DATA SHEET

Document No: G080356


Generator Revision: D
Created By: G. Rabone
NHC20/DC16 45A 500kVA AI 2010 Approved By: C. Shrive
Approval Date: 15/07/2016
Page: 3 of 3

NOx - Oxides of Nitrogen 5.888 g/kWh 5.6 g/kWh


PM - Particulate Matter 0.06 g/kWh 0.07 g/kWh
CO - Carbon Monoxide 0.586 g/kWh 0.42 g/kWh
HC - Unburnt Hydrocarbons 0.273 g/kWh 0.241 g/kWh
O2 - Oxygen 5% N/A

Exhaust Silencer
Make & Type Discom Discom
Certificate Number M11624 M11624
Permissible Back Pressure 6.3mm (0.25 ins) Hg 6.3mm (0.25 ins) Hg

Noise Data
Sound Power Level 95 Lwa 95 Lwa
Certificate Number R020544 R020544
Sound Pressure at 1m/3ft 74.0 dBA 77.1 dBA
Sound Pressure at 7m/21ft 65.4 dBA 66.9 dBA

Other Capacities and Dimensions


Lube Oil Capacity - Total L (US gal) 35.0 (9.24) 35.0 (9.24)
Coolant (Engine) L (US gal) 35.0 (9.24) 35.0 (9.24)
Coolant (Radiator) L (US gal) 37.0 (9.768) 37.0 (9.768)
External Fuel Supply - Max Above Base m (ft) 3.5 (11.484) 3.5 (11.484)
External Fuel Supply - Max Below Base m (ft) 2.0 (6.562) 2.0 (6.562)

Physical Characteristics
Length 6.06 m 19.88 ft
Width 2.44 m 8.01 ft
Height 2.6 m 8.53 ft
Gross Weight 11067 kg 24398.56 lbs
Net Weight 9979 kg 21999.93 lbs
Gross Fuel 1289 lit 340.52 US gal
Net Fuel 1262 lit 333.39 US gal

This document Contains PROPRIETARY and CONFIDENTIAL information and may NOT be copied or reproduced in any media without written permission from Aggreko.
Technical Information contained herein is subject to change without notice. Some data may vary on machines.

ISO references apply to Aggreko Manufacturing built equipment only


* ISO 8528-1 Reciprocating Internal Combustion Engine Driven Alternating Current Generating Sets:
Part 1 - Application, Ratings and Performance
** ISO 3046-1 Reciprocating Internal Combustion Engines: Performance:

Das könnte Ihnen auch gefallen