Sie sind auf Seite 1von 16

1/4 turn ACTELEC OA3 to BS100

Type series bookiet


8521.12/4--10 (BERNARD)
Direct 1/4 turn electric actuators
ACTELEC BERNARD OA3 to BS100

Output torques up to 1000 Nm

Applications Construction
• All sectors of Water, Energy and industry markets. • In standard version, ACTELEC actuators are designed to
ensure the on--off function, intermittent duty S4 -- 30%.
• Remote electric control.
General feature
Basic equipments
• The range series direct 1/4 turn electric actuators ACTELEC
OA 3 to BS 100 covers output values up to 1000 Nm. • Electric motor protection by:
• These actuators have been designed for all applications and -- integrated thermic protection,
for the operation of any type ¼ turn valves (centred or double -- 2 travel limit microswitches (1 microswitch on opening
eccentric disc valves, ball valves,...). position and 1 on closing position)
• The mounting interface is in accordance with ISO 5211 -- Torque limit system (except on ACTELEC OA3 to OA15).
standard. • Heating resistance anti--condensation.
• Equipped with an interchangeable insert, they can be easily • Manual emergency control by handwheel.
fitted on different valve shaft (square end, flat end, key,...). • Position indication.
• The actuator is mounted directly or by means of an adaptador • Mechanical adjustable end stop(s).
onto the valve mounting plate. Other constructions
• Irreversible kinematic in any position. • Motor for continuous duty -- Repetitive startings (S4 -- 50%
-- 1200 startings/hour).
• Throttling duty with 4--20 mA integrated positioner.
Protection • Integral electric control and remote control = INTEGRAL
• They are hose and fine dust proof and are protected against version.
accidental immersion: protection level IP 67. • Explosion--proof protection EExe.
• Motor: insulation class F.
Power supply
• Standard version:
External coating -- 3--phase 230 VAC / 400 VAC -- 50 Hz,
-- 1--phase 230 VAC -- 50 Hz.
• Epoxy paint, thickness 60 µm, color blue RAL 5002.
• On request:
-- 24 or 48 VDC.
Temperature range
• From --20° C up to +70° C.
Options on request (Please, consult us)
• Additional microswitches adjustables on the whole travel for
remote position signalisation (limit position and/or intermediate
Standard variant position.
• Position transmission by potentiometer 1000 Ω or 4--20 mA
• ATEX version in accordance with 94/9/EC directive.
electronic transmitter.
• Communication interface -- Intelligence -- Fieldbus.
• Other power supplies.
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
ACTELEC OA3 to BS100 electric actuators are based on a direct ¼ turn servomotor with a mounting interface in accordance with
ISO 5211.
These actuators are available in on--off function or throttling duty.

On--off function

Production range

Nominal Maximal allowable dimension for shaft


ISO 5211
Type output torque Driving by Driving by Driving by
mounting plate* Height
(Nm) square flat key
OA3 45 F05--F07 30 16 14
OA6 70 F05--F07 30 16 14
OA8 100 F05--F07 32 19 19
OA15 150 F05--F07 32 19 19
Please
Please,
AS18 200 F07--F10 40 25 22
consult us
AS25 300 F07--F10 40 25 22
AS50 600 F07--F10 45 25 22
AS80 800 F12 50 30 27
BS100 1000 F12 55 36 36
* Direct adaptation onto identical mounting plate.
Adaptation by intermediate flange onto different plate (different size or shape).

Definition
ACTELEC OA3 OA6 OA8 OA15 AS18 AS25 AS50 AS80 BS100
Nominal torque (Nm) 45 70 100 150 200 300 600 800 1000
Standard 6 6 6 15 5 10 30 30 60
Operating time
in seconds 35 or 5, 30 or
Option 25 60 60
60 50
Basic equipments
Opening and closing travel limit
Standard
switches
Mechanical adjustable travel limit
Standard
stops
Opening and closing torque limit
Standard
switches
Heating resistance 6 W Standard
Emergency control
20 20 20 20 11 11 8 14 14
Number of handwheel turns
Power supply
3--phase 230 or 400 VAC
S 50000/04
Wiring diagram
1--phase 230 VAC
S 50250/01 S 50000/04
Wiring diagram
24 V or 48 VDC Option / Please, consult us
Other constructions
Continuous duty Yes
Yes Yes
Integral control:
Wiring diagram Wiring diagram
INTEGRAL version
S 20050/01 S 20000/04
Explosion--proof protection Yes / Please, consult us

2
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

On/off function

Characteristics actuator

3--phase 400 VAC 50 Hz


Electric
actuator Actuator
Nominal power Nominal intensity Starting intensity
type output speed
sec/90° kW A A
OA6 6 0,03 0,3 0,5
OA8 6 0,10 0,6 1,1
OA15 15 0,03 0,3 0,5
AS18 5 0,10 0,6 1,1
AS25 10 0,10 0,8 1,6
AS50 30 0,06 0,3 0,8
AS80 30 0,06 0,3 0,8
BS100 60 0,06 0,3 0,8

1--phase 230 VAC 50 Hz


Electric
actuator Actuator
Nominal power Nominal intensity Starting intensity
type output speed
sec/90° kW A A
OA3 6 0,03 0,8 0,9
OA6 6 0,03 0,6 0,9
OA8 6 0,06 1,2 1,7
OA15 15 0,03 0,6 0,9
AS18 5 0,20 2,5 3,5
AS25 10 0,10 1,8 2,5
AS50 30 0,06 1,2 1,7
AS80 30 0,15 2,0 3,0
BS100 60 0,06 1,2 1,7

3
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

On/off function:
OA6 -- OA8 -- OA15 -- AS18 -- AS25 -- AS50 -- AS80 -- BS100 -- 3--phase 400 VAC 50 Hz
AS18 -- AS25 -- AS50 -- AS80 -- BS100 -- 1--phase 230 VAC 50 Hz

Wiring diagram S 50000/04

1/4 Turn: AS 18 -- AS25 -- AS50 -- AS80 -- BS100 1/4 turn: OA6 -- OA8 -- OA15

ACTUATOR WITH Motor terminals ACTUATOR WITHOUT


TORQUE LIMITING (connections TORQUE LIMITING DEVICE Motor terminals
DEVICE detailed below)
(connections
Torque limit switch detailed below)
Open

Torque limit switch Travel limit switch


Closed Open

* Torque switches give short


duration contact
Travel limit switch
Closed
* Travel limit switches
give maintened contact

FUNCTION OF SWITCHES
Direction of rotation
Travel limit switch I -- Anticlockwise
Open (normally opening)
II -- Clockwise
(normally closing)
Travel limit switch
Closed Thermal motor
protection
Thermal motor
protection
Heater resistance
Heater resistance

Direction of rotation seen on opposite side of fixing Direction of rotation seen on opposite side of fixing
flange of actuator flange of actuator

OPTIONAL ACCESSORIES MOTOR MOTOR


THREE PHASE SINGLE PHASE
Extra travel limit switch
Open

Extra travel limit switch


DIRECTION I

Closed

Electronic position transmitter


TAM 4--20 mA
12 to 32 VCC
2 wires
DIRECTION II

Potentiometer
NOTA : 3--phase direct = DIrection II

4
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

On/off function:
OA3 -- OA6 -- OA8 -- OA15 -- 1--phase 230 VAC 50 Hz

Prewired version -- Wiring diagram S 50250/01

ACTUATOR WIRING CUSTOMER WIRING

Capacitor

Open

Thermal motor protection


Closed Single phase supply

Open

Travel limit switches Open

Closed

Closed

Heater resistance

OPTIONS
Extra travel limit switches

Open

Extra travel limit switches

Closed

Position transmitter

Position transmitter 4--20 mA

TAM

Potentiometer

Potentiometer

5
6
Capacitor Motor Direction 2 Closed
Thermal motor protection Heater
Limit >
switch

Direction 1 Open
Extra opening travel
limit switch

Extra closing travel


OA6 -- OA8 -- AO15

limit switch

C12701 BOARD

Common
Direction 1
Direction 2 TAM (2 wires) 12 to 32 VDC
Logic
control
Recopie de position 4--20 mA
Possibility to use supply 24 VDC on terminals 32--33
Wiring diagram S 20050/01 Integral version
On/off function: INTEGRAL version

Local control

Fault relay
Potentiometer
Contacts 61--63 closed
actuator available

Wiring according to actuator supply


Indication assignment see configuration table
Single phase Three phase Legend Con-- Item
Designation Repère Designation
tact
supply supply Emergency shut down Limit switch open Torque switch open
Closing Limit switch closed Torque switch closed
Limit switch open Torque switch open
Fuse
Connection for control Selector on local Selector on remote
Local inhibition by contact Actuator opening electrically
> Supply type Actuator running electrically
Limit switch closed Torque switch closed
The order in phase is not important Opening
ESD command received Actuator closing electrically
If one phase is missing, the actuator will not start
Selector on local Selector on remote
and gives a signal (fault relay) Signaling
Each contact can be selected open or close (standard is open)
Stop Only one option can be selected for each indication
Transformer 10 à 55 V Power off, contacts are open

Configuration 7A 7B Note: 55 to 250 V


To cancel self holding
Direction1 Opening Closing Do not connect terminal 34 Connection for control
by voltage
Direction2 Closing Opening
(BERNARD)
1/4 turn ACTELEC OA3 to BS100
Capacitor Motor Thermal motor Direction 2 Option SD : Direction 2 Direction 1
protection Closed Wheel security Closed Open Heater
Limit >
switch
Direction 1
Open Torque limit switches
Extra opening travel
limit switch

Extra closing travel


limit switch

C12701 CARD

Common
Direction 1
Direction 2 TAM (2 wires) 12 to 32 VDC
Logic
control
AS18 -- AS25 -- AS50 -- AS80 -- BS100

Wiring diagram S 20000/04 intégral version

Position transmitter 4--20 mA


Possibility to use supply 24 VDC on terminals 32--33
On/off function: INTEGRAL version

Local control

Fault relay
Contacts 61--63 closed Potentiometer
Actuator available

Wiring according to actuator supply


Indication assignment see configuration table
Single phase Three phase Legend Con-- Item
Designation Item Designation
tact
supply supply Emergency shut down Limit switch open Torque switch open
Closing Limit switch closed Torque switch closed

Fuse Limit switch open Torque switch open


Connection for control Selector on local Selector on remote
Local by contact
> Supply type inhibition Actuator running electrically Actuator opening electrically
Limit switch closed Torque switch closed
Opening
The order in phase is not important EDS command received Actuator closing electrically
If one phase is missing, the actuator will not start Selector on local Selector on remote
Signaling
and gives a signal (fault relay)
Stop Each contact can be selected open or close (standard is open)
Only one option can be selected for each indication
Transformer 10 à 55 V Power off. Contacts are open

Configuration 7A 7B Note: 55 à 250 V


To cancel self holding
Direction1 Opening CLosing Do not connect terminal 34
Connection for control
Direction2 Closing Opening by voltage

7
(BERNARD)
1/4 turn ACTELEC OA3 to BS100
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

On/off function -- 3--phase supply

Overall dimensions (mm) and weight (kg)

A B D
C

ACTELEC OA3, OA6, OA8 and OA 15


H

ØE
ØV

4 equidistant holes ø d2 2 PG no.16

Drilling diameter ø d1

A B D
C

ACTELEC AS18, AS25,


AS50, AS80 and BS100
ØV ØE H

4 equidistant holes ø d2 2 PG no.16


Drilling diameter ø d1

Mounting plate ISO 5211 Weight


Type A B C D øE H øV
réf. ø d1 ø d2 kg
F05 50 M6
ACTELEC OA3 116 148 65 150 106 224 90 6
F07 70 M8
F05 50 M6
ACTELEC OA6 116 260 65 150 106 224 90 6
F07 70 M8
F05 50 M6
ACTELEC OA8 116 260 65 150 106 224 90 7
F07 70 M8
F05 50 M6
ACTELEC OA15 116 260 65 150 106 224 90 7
F07 70 M8
F07 70 M8
ACTELEC AS18 167 312 89 226 139 177 100 16
F10 102 M10
F07 70 M8
ACTELEC AS25 167 312 89 226 139 177 160 18
F10 102 M10
F07 70 M8
ACTELEC AS50 169 340 89 226 139 177 250 17
F10 102 M10
ACTELEC AS80 169 340 89 226 139 208 250 F12 125 M12 18
ACTELEC BS100 172 392 133 284 139 167 250 F12 125 M12 26

Nota: For overall dimension On/Off function with integral control: Overall dimension idem throttling duty -- Class III integral ver-
sion with positioner.

8
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

Throttling duty -- Class III Integral version with positioner 4-- 20 mA

Production range

Nominal Maximal allowable dimension for shaft


ISO 5211
Type output torque Driving by Driving by Driving by
mounting plate* Height
(Nm) square flat key
OAP 80 F05--F07 32 19 19
OA15 150 F05--F07 32 19 19
Please
Please,
ASP 250 F07--F10 40 25 22
consult us
AS50 520 F07--F10 45 25 22
BS100 1000 F12 55 36 36
* Direct adaptation onto identical mounting plate.
Adaptation by intermediate flange onto different plate (different size or shape).

Definition
ACTELEC OAP OA15 ASP AS50 BS100
Nominal torque (Nm) 80 150 250 520 1000
Operating standard time in seconds 60 25 50 60 60
Basic equipments
Opening and closing travel limit switches Standard
Mechanical adjustable travel limit stops Standard
Opening and closing torque limit switches Standard
Heating resistance 6 W Standard
Emergency control
20 20 11 8 14
Number of handwheel turns
Standard -- Standard --
Integral control
Wiring diagram Wiring diagram
incorporated positioner 4--20 mA
S 25050/01 S 25000/04
Power supply
3--phase 230 or 400 VAC Yes
1--phase 230 VAC Yes
24 V or 48 VDC Option / Please, consult us
Other construction
Explosion--proof protection Yes / Please, consult us

9
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

Throttling duty -- Class III Integral version with positioner 4-- 20 mA

Characteristics actuator

3--phase 400 VAC 50 Hz


Electric
actuator Actuator
Nominal power Nominal intensity Starting intensity
type output speed
sec/90° kW A A
OAP 60 0,03 0,3 0,5
OA15 25 0,03 0,3 0,5
ASP 60 0,03 0,3 0,5
AS50 60 0,06 0,6 0,9
BS100 60 0,06 0,3 0,8

1--phase 230 VAC 50 Hz


Electric
actuator Actuator
Nominal power Nominal intensity Starting intensity
type output speed
sec/90° kW A A
OAP 60 0,03 0,6 0,9
OA15 25 0,03 0,6 0,9
ASP 60 0,03 0,6 0,9
AS50 60 0,08 1,5 2,4
BS100 60 0,06 1,2 1,7

10
Capacitor Motor Thermal motor
Direction 2 Closed Heater potentiometer
Limit >
switch

Direction 1 Open
OAP -- OA15

Extra opening travel


limit switch

Extra closing travel


limit switch

C12701 CARD

Common
Direction 1
Direction 2
Logic
control

RD
Fault relay
Wiring diagram S 25050/01 integral version

Contacts 61--63
closed =
TAM (2 wires) 12 to 32 VDC
Actuator
available

Position trans mitter 4--20 mA


Positioner
GAMK Possibility to use supply 24 VDC on terminals 32--33

Wiring according to actuator supply Indication assignment see configuration table


Con-- Item Designation Item Designation
Single phase Three phase tact
supply supply Legend Limit switch open Torque switch open
Emergency shut down Tlorque switch closed
Input Limit switch closed
Closing signal
4--20 mA Limit switch open Torque switch open
0--20mA Selector on local Selector on remote
Fuse (260 ohms)
Connection for control 0--10 V Actuator running electrically Actuator opening electrically
Closed contact = by contact (10kohms)
On/off control Limit switch closed Torque switch closed
> Supply type ESD command received Actuator closing electrically
Throttling duty -- Class III Integral version with positioner 4-- 20 mA

Opening Selector on local Selector on remote


The order in phase is not important.
If one phase is missing, the actuator will not start Signaling Each contact can be selected open or close (standard in open)
Only one option can be selected for each indication
and gives a signal (fault relay) Stop Power off. Contacts are open
Transformer 10 to 55 V Output
signal
Configuration 7A 7B
Note: 55 to 250 V 4--20 mA
Direction1 Opening Closing 0--20mA
To cancel self holding (300 ohms
Connection for control
Direction2 Closing Opening Do not connect terminal 34 by voltage max)
(BERNARD)
1/4 turn ACTELEC OA3 to BS100

11
12
Direction 2 Option SD : Direction 2 Direction 1
Capacitor Motor Thermal motor Closed > Wheel security Closed Open heater Potentiometer

Limit
switch Direction 1
Open Torque limit switches

Extra opening travel


limit switch

Extra closing travel


limit switch
ASP -- AS50 -- BS100

C12701 CARD

Common
Direction 1
Direction 2
Logic
control
RD
Fault relay
Contacts 61--63
Wiring diagram S25000/04 integral version

fclosed =
actuator TAM (2 wires) 12 to 32 VDC
available

Positioner position transmitter 4--20 mA

possibility to use supply 24 VDC on terminals 32--33

Wiring according to actuator supply


Indication assignment see configuration table
Single phase Three phase Con-- Item
Legend Designation Item Designation
supply supply tact
Emergency shut down Limit switch open Torque switch open
Input
signal Torque switch closed
Closing 4--20 mA Limit switch closed
0--20mA Limit switch open Torque switch open
Fuse (260 ohms) Selector on local Selector on remote
Connection for control 0--10 V
Closed contact by contact (10kohms) Actuator running electrically Actuator opening electrically
On/off control
> Supply type Limit switch closed Torque switch closed
ESD command received
Throttling duty -- Class III Integral version with positioner 4-- 20 mA

The order in phase is not important Opening Actuator closing electrically


i one phase is missing, the actuator will not start Selector on local Selector on remote
Signaling
and gives a signal (fault relay) Each contact can be selected open or close (standard is open)
Stop Only one option can be selected for each indication
Outout Power off, contacts are open
Transformer 10 to 55 V signal
Configuration 7A 7B 4--20 mA
55 to 250 V 0--20mA
Direction1 Opening Note:
Closing (300 ohms)
To cancel self holding max)
Connection for control
Direction2 Closing Opening Do not connect terminal 34 by voltage
(BERNARD)
1/4 turn ACTELEC OA3 to BS100
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

Throttling duty -- Class III Integral version with positioner 4-- 20 mA

Overall dimensions (mm) and weight (kg)

A B D
C

ACTELEC OAP and OA 15

ØE

4 equidistant holes ø d2 ØV

Drilling diameter ø d1
3 PG no.16

A B D
C

ACTELEC ASP, AS50


and AS80

ØV ØE

4 equidistant holes ø d2

Drilling diameter ø d1 3 PG no.16

Mounting plate ISO 5211 Weight


Type A B C D øE H øV
ref ø d1 ø d2 kg
F05 50 M6
ACTELEC OAP 128 260 65 283 106 224 90 11
F07 70 M8
F05 50 M6
ACTELEC OA15 128 260 65 283 106 224 90 11
F07 70 M8
F07 70 M8
ACTELEC ASP 167 340 89 226 139 335 160 22
F10 102 M10
F07 70 M8
ACTELEC AS50 169 340 89 226 139 335 250 21
F10 102 M10
ACTELEC BS100 172 392 133 353 139 167 250 F12 125 M12 34

13
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

Notes

14
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

Notes

15
1/4 turn ACTELEC OA3 to BS100
(BERNARD)

and may be amended without notice.


This leaflet is not contractual
04.04.06
8521.12/4--10

KSB S.A.S.
4, allée des Barbanniers • 92635 Gennevilliers Cedex (France)
Tél. : +33 1 41 47 75 00 • Fax : +33 1 41 47 75 10 • www.ksb.com

Das könnte Ihnen auch gefallen