Applications Construction
• All sectors of Water, Energy and industry markets. • In standard version, ACTELEC actuators are designed to
ensure the on--off function, intermittent duty S4 -- 30%.
• Remote electric control.
General feature
Basic equipments
• The range series direct 1/4 turn electric actuators ACTELEC
OA 3 to BS 100 covers output values up to 1000 Nm. • Electric motor protection by:
• These actuators have been designed for all applications and -- integrated thermic protection,
for the operation of any type ¼ turn valves (centred or double -- 2 travel limit microswitches (1 microswitch on opening
eccentric disc valves, ball valves,...). position and 1 on closing position)
• The mounting interface is in accordance with ISO 5211 -- Torque limit system (except on ACTELEC OA3 to OA15).
standard. • Heating resistance anti--condensation.
• Equipped with an interchangeable insert, they can be easily • Manual emergency control by handwheel.
fitted on different valve shaft (square end, flat end, key,...). • Position indication.
• The actuator is mounted directly or by means of an adaptador • Mechanical adjustable end stop(s).
onto the valve mounting plate. Other constructions
• Irreversible kinematic in any position. • Motor for continuous duty -- Repetitive startings (S4 -- 50%
-- 1200 startings/hour).
• Throttling duty with 4--20 mA integrated positioner.
Protection • Integral electric control and remote control = INTEGRAL
• They are hose and fine dust proof and are protected against version.
accidental immersion: protection level IP 67. • Explosion--proof protection EExe.
• Motor: insulation class F.
Power supply
• Standard version:
External coating -- 3--phase 230 VAC / 400 VAC -- 50 Hz,
-- 1--phase 230 VAC -- 50 Hz.
• Epoxy paint, thickness 60 µm, color blue RAL 5002.
• On request:
-- 24 or 48 VDC.
Temperature range
• From --20° C up to +70° C.
Options on request (Please, consult us)
• Additional microswitches adjustables on the whole travel for
remote position signalisation (limit position and/or intermediate
Standard variant position.
• Position transmission by potentiometer 1000 Ω or 4--20 mA
• ATEX version in accordance with 94/9/EC directive.
electronic transmitter.
• Communication interface -- Intelligence -- Fieldbus.
• Other power supplies.
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
ACTELEC OA3 to BS100 electric actuators are based on a direct ¼ turn servomotor with a mounting interface in accordance with
ISO 5211.
These actuators are available in on--off function or throttling duty.
On--off function
Production range
Definition
ACTELEC OA3 OA6 OA8 OA15 AS18 AS25 AS50 AS80 BS100
Nominal torque (Nm) 45 70 100 150 200 300 600 800 1000
Standard 6 6 6 15 5 10 30 30 60
Operating time
in seconds 35 or 5, 30 or
Option 25 60 60
60 50
Basic equipments
Opening and closing travel limit
Standard
switches
Mechanical adjustable travel limit
Standard
stops
Opening and closing torque limit
Standard
switches
Heating resistance 6 W Standard
Emergency control
20 20 20 20 11 11 8 14 14
Number of handwheel turns
Power supply
3--phase 230 or 400 VAC
S 50000/04
Wiring diagram
1--phase 230 VAC
S 50250/01 S 50000/04
Wiring diagram
24 V or 48 VDC Option / Please, consult us
Other constructions
Continuous duty Yes
Yes Yes
Integral control:
Wiring diagram Wiring diagram
INTEGRAL version
S 20050/01 S 20000/04
Explosion--proof protection Yes / Please, consult us
2
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
On/off function
Characteristics actuator
3
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
On/off function:
OA6 -- OA8 -- OA15 -- AS18 -- AS25 -- AS50 -- AS80 -- BS100 -- 3--phase 400 VAC 50 Hz
AS18 -- AS25 -- AS50 -- AS80 -- BS100 -- 1--phase 230 VAC 50 Hz
1/4 Turn: AS 18 -- AS25 -- AS50 -- AS80 -- BS100 1/4 turn: OA6 -- OA8 -- OA15
FUNCTION OF SWITCHES
Direction of rotation
Travel limit switch I -- Anticlockwise
Open (normally opening)
II -- Clockwise
(normally closing)
Travel limit switch
Closed Thermal motor
protection
Thermal motor
protection
Heater resistance
Heater resistance
Direction of rotation seen on opposite side of fixing Direction of rotation seen on opposite side of fixing
flange of actuator flange of actuator
Closed
Potentiometer
NOTA : 3--phase direct = DIrection II
4
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
On/off function:
OA3 -- OA6 -- OA8 -- OA15 -- 1--phase 230 VAC 50 Hz
Capacitor
Open
Open
Closed
Closed
Heater resistance
OPTIONS
Extra travel limit switches
Open
Closed
Position transmitter
TAM
Potentiometer
Potentiometer
5
6
Capacitor Motor Direction 2 Closed
Thermal motor protection Heater
Limit >
switch
Direction 1 Open
Extra opening travel
limit switch
limit switch
C12701 BOARD
Common
Direction 1
Direction 2 TAM (2 wires) 12 to 32 VDC
Logic
control
Recopie de position 4--20 mA
Possibility to use supply 24 VDC on terminals 32--33
Wiring diagram S 20050/01 Integral version
On/off function: INTEGRAL version
Local control
Fault relay
Potentiometer
Contacts 61--63 closed
actuator available
C12701 CARD
Common
Direction 1
Direction 2 TAM (2 wires) 12 to 32 VDC
Logic
control
AS18 -- AS25 -- AS50 -- AS80 -- BS100
Local control
Fault relay
Contacts 61--63 closed Potentiometer
Actuator available
7
(BERNARD)
1/4 turn ACTELEC OA3 to BS100
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
A B D
C
ØE
ØV
Drilling diameter ø d1
A B D
C
Nota: For overall dimension On/Off function with integral control: Overall dimension idem throttling duty -- Class III integral ver-
sion with positioner.
8
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
Production range
Definition
ACTELEC OAP OA15 ASP AS50 BS100
Nominal torque (Nm) 80 150 250 520 1000
Operating standard time in seconds 60 25 50 60 60
Basic equipments
Opening and closing travel limit switches Standard
Mechanical adjustable travel limit stops Standard
Opening and closing torque limit switches Standard
Heating resistance 6 W Standard
Emergency control
20 20 11 8 14
Number of handwheel turns
Standard -- Standard --
Integral control
Wiring diagram Wiring diagram
incorporated positioner 4--20 mA
S 25050/01 S 25000/04
Power supply
3--phase 230 or 400 VAC Yes
1--phase 230 VAC Yes
24 V or 48 VDC Option / Please, consult us
Other construction
Explosion--proof protection Yes / Please, consult us
9
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
Characteristics actuator
10
Capacitor Motor Thermal motor
Direction 2 Closed Heater potentiometer
Limit >
switch
Direction 1 Open
OAP -- OA15
C12701 CARD
Common
Direction 1
Direction 2
Logic
control
RD
Fault relay
Wiring diagram S 25050/01 integral version
Contacts 61--63
closed =
TAM (2 wires) 12 to 32 VDC
Actuator
available
11
12
Direction 2 Option SD : Direction 2 Direction 1
Capacitor Motor Thermal motor Closed > Wheel security Closed Open heater Potentiometer
Limit
switch Direction 1
Open Torque limit switches
C12701 CARD
Common
Direction 1
Direction 2
Logic
control
RD
Fault relay
Contacts 61--63
Wiring diagram S25000/04 integral version
fclosed =
actuator TAM (2 wires) 12 to 32 VDC
available
A B D
C
ØE
4 equidistant holes ø d2 ØV
Drilling diameter ø d1
3 PG no.16
A B D
C
ØV ØE
4 equidistant holes ø d2
13
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
Notes
14
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
Notes
15
1/4 turn ACTELEC OA3 to BS100
(BERNARD)
KSB S.A.S.
4, allée des Barbanniers • 92635 Gennevilliers Cedex (France)
Tél. : +33 1 41 47 75 00 • Fax : +33 1 41 47 75 10 • www.ksb.com