BEMS POINT SCHEDULE & MCC LOAD DIAGRAM

CHILLER HALL MCC #01

Starting Gear Rating A

Load Item Power kW


Cable Size mm2 Cu.
Control Cable Cores

Starting Gear Type


Analouge or Digital

Compartment #

Core Cables
Nr of Points

Cable Type

Load Item
Location
Device

X-G-MCC-01
X-G-P-01 X-G-P-01
Chiller C-P CW Pump Enable C C-P 1 D 2 AT 200 2 4 120 75kW CW Shunt Pump
Pump Starter Status MCC 2 D 3 1
Pump Pressure Switch 1 Pipe 1 D 2
Pump Pressure Switch 2 Pipe 1 D 2
CW F temp detector Pipe 1 A 2
CW R temp detector Pipe 1 A 2
Motorised Valve Pipe 1 D 3
Motorised Valve prove open Pipe 1 D 2

X-G-P-02 X-G-P-02
Chiller C-P CW Pump Enable C C-P 1 D 2 AT 200 2 4 120 75kW CW Shunt Pump
Pump Starter Status MCC 2 D 3 2
Pump Pressure Switch 1 Pipe 1 D 2
Pump Pressure Switch 2 Pipe 1 D 2
CW F temp detector Pipe 1 A 2
CW R temp detector Pipe 1 A 2
Motorised Valve Pipe 1 D 3
Motorised Valve prove open Pipe 1 D 2

X-G-P-03 X-G-P-03
Chiller C-P CW Pump Enable C C-P 1 D 2 AT 200 2 4 120 75kW CW Shunt Pump
Pump Starter Status MCC 2 D 3 3
Pump Pressure Switch 1 Pipe 1 D 2
Pump Pressure Switch 2 Pipe 1 D 2
CW F temp detector Pipe 1 A 2
CW R temp detector Pipe 1 A 2
Motorised Valve Pipe 1 D 3
Motorised Valve prove open Pipe 1 D 2

X-G-P-04 X-G-P-04
Chiller C-P CW Pump Enable C C-P 1 D 2 AT 200 2 4 120 75kW CW Shunt Pump
Pump Starter Status MCC 2 D 3 4
Pump Pressure Switch 1 Pipe 1 D 2
Pump Pressure Switch 2 Pipe 1 D 2
CW F temp detector Pipe 1 A 2
CW R temp detector Pipe 1 A 2
Motorised Valve Pipe 1 D 3
Motorised Valve prove open Pipe 1 D 2

X-G-CT-01
X-G-CT-01 SD 125 2 12 70 30kW Cooling Tower fan 1
Tower fan 1 starter low speed enable MCC 1 D 2 5
Tower fan 1 starter high speed enable MCC 1 D 2 SD 125 2 12 70 30kW Cooling Tower fan 2
Tower fan 1 starter low speed status MCC 2 D 3
Tower fan 1 starter high speed status MCC 2 D 3
Tower fan 1 isolator Field 1 D 2
Tower fan 2 starter low speed enable MCC 1 D 2
Tower fan 2 starter high speed enable MCC 1 D 2
Tower fan 2 starter low speed status MCC 2 D 3
Tower fan 2 starter high speed status MCC 2 D 3
Tower fan 2 isolator Field 1 D 2
Tower CW Motorised Valve enable Field 1 D 2
Tower CW Motorised Valve status Field 1 D 2
Low level alarm Tower 1 D 2

X-G-CT-02
X-G-CT-02 SD 125 2 12 70 30kW Cooling Tower fan 1
Tower fan 1 starter low speed enable MCC 1 D 2 6
Tower fan 1 starter high speed enable MCC 1 D 2 SD 125 2 12 70 30kW Cooling Tower fan 2
Tower fan 1 starter low speed status MCC 2 D 3
Tower fan 1 starter high speed status MCC 2 D 3
Tower fan 1 isolator Field 1 D 2
Tower fan 2 starter low speed enable MCC 1 D 2
Tower fan 2 starter high speed enable MCC 1 D 2
Tower fan 2 starter low speed status MCC 2 D 3
Tower fan 2 starter high speed status MCC 2 D 3

RE6309/D001240 Rev 0/2002 15910/1 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
CHILLER HALL MCC #01

Starting Gear Rating A

Load Item Power kW


Cable Size mm2 Cu.
Control Cable Cores

Starting Gear Type


Analouge or Digital

Compartment #

Core Cables
Nr of Points

Cable Type

Load Item
Location
Device

Tower fan 2 isolator Field 1 D 2


Tower CW Motorised Valve enable Field 1 D 2
Tower CW Motorised Valve status Field 1 D 2
Low level alarm Tower 1 D 2

X-G-CT-03
X-G-CT-03 SD 125 2 12 70 30kW Cooling Tower fan 1
Tower fan 1 starter low speed enable MCC 1 D 2 7
Tower fan 1 starter high speed enable MCC 1 D 2 SD 125 2 12 70 30kW Cooling Tower fan 2
Tower fan 1 starter low speed status MCC 2 D 3
Tower fan 1 starter high speed status MCC 2 D 3
Tower fan 1 isolator Field 1 D 2
Tower fan 2 starter low speed enable MCC 1 D 2
Tower fan 2 starter high speed enable MCC 1 D 2
Tower fan 2 starter low speed status MCC 2 D 3
Tower fan 2 starter high speed status MCC 2 D 3
Tower fan 2 isolator Field 1 D 2
Tower CW Motorised Valve enable Field 1 D 2
Tower CW Motorised Valve status Field 1 D 2
Low level alarm Tower 1 D 2

X-G-CT-04
X-G-CT-04 SD 125 2 12 70 30kW Cooling Tower fan 1
Tower fan 1 starter low speed enable MCC 1 D 2 8
Tower fan 1 starter high speed enable MCC 1 D 2 SD 125 2 12 70 30kW Cooling Tower fan 2
Tower fan 1 starter low speed status MCC 2 D 3
Tower fan 1 starter high speed status MCC 2 D 3
Tower fan 1 isolator Field 1 D 2
Tower fan 2 starter low speed enable MCC 1 D 2
Tower fan 2 starter high speed enable MCC 1 D 2
Tower fan 2 starter low speed status MCC 2 D 3
Tower fan 2 starter high speed status MCC 2 D 3
Tower fan 2 isolator Field 1 D 2
Tower CW Motorised Valve enable Field 1 D 2
Tower CW Motorised Valve status Field 1 D 2
Low level alarm Tower 1 D 2

X-G-VS-01
CW Averaging temp detector 1 Field 1 A 2
DOL 32 2 4 10 5.5kW Vortex Separator
CW Averaging temp detector 2 Field 1 A 2
9
Main ChW F temp detector Pipe 1 A 2
Main ChW R temp detector Pipe 1 A 2
Flow header temp detector Pipe 1 A 2
Main ChW Emergency Valve Acutator Pipe 2 D 5
Main ChW Emergency Valve Acutator Pipe 2 D 5
By-pass flow Meter Pipe 1 A 2
BP Meter output to Chiller C-P CC-P 1 A 2
Chillers enable CC-P 1 D 2
Chiller 1 Load feedback CC-P 1 A 2
Chiller 2 Load feedback CC-P 1 A 2
Chiller 3 Load feedback CC-P 1 A 2
Chiller 4 Load feedback CC-P 1 A 2
Chiller 1 Status feedback CC-P 3 D 4
Chiller 2 Status feedback CC-P 3 D 4
Chiller 3 Status feedback CC-P 3 D 4
Chiller 4 Status feedback CC-P 3 D 4
Vortex filter status Pipe 2 D 3
Vortex filter alarm Pipe 1 D 2
Display monitor bus interface unit MCC C 2

1. A = Analogue; D = Digital; C = Communication


2. Starters: DOL = Direct On Line; SD = Star/Delta; AT = Auto Transformer; Inv = Inverter
3 Cable Type :1 = Xlpe/Swa/LSF, Type 2: Xlpe/Swa/Pvc, Type: 3 HEPR cables, Type 4 : PVC/PVC, Type 5: PVC singles
4. Numbers of Points and control cable cores are given for guidance. Tenderer to review against written specified requirements and make due allowance for what is required

RE6309/D001240 Rev 0/2002 15910/2 BEMS Point Schedule + MCC Load Diagram