Sie sind auf Seite 1von 1

450 450

300 300

4-35x41 SLOTS
80mm THICK INTERLOCKING 30 THK.

450

450
PAVERS W/DRY SWEPT JOINTS

300

300
ANCHOR BOLT 4 THK. PLATE
50mm THICK SAND ANCHOR BOLT
TEMPLATE DETAIL-2 4-GUSSET PLATE
SETTING BED
GRANULAR SUB BASE TEMPLATE 160X70X6
50

F.R.L 250mm CLASS C


20 NON SHRINKAGE
GROUT 20mm TEMPLATE DETAILS BASE PLATE DETAILS

150

THREADED
4
100

LENGTH.
100
3 1

380
500

600
T16mm@
20

M33
200mm c/c

400
A
1100

SLEEVE 100mm AS A

900
APPROVED

820
2
OPC-40 N/mm2 BITUMEN PAINT WITH T12mm@
PROTECTION BOARD 200mm c/c
R40
BLINDING CONC.
75 SRC-20

ANCHOR BOLT C/W 2 HEX.


900
900 NUTS & 2 PLAIN WASHERS
75

SEC.B-B ELEVATION

FOUNDATION DETAIL FOR OCTAGONAL LIGHTING


COLUMN WITH SINGLE & DOUBLE ARM BRACKET
(900X900X1100)mm

REINFORCEMENT DETAIL STRUCTURAL NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS.


2. REINFORCEMENT STEEL: Fy 460B DEFORMED BARS
NO BAR DIA QTY. LENGTH(mm) BAR SHAPE 3. FOUNDATION IS DESIGNED FOR NET ALLOWABLE SOIL
75 900 BEARING PRESSURE OF 150 kPa (ASSUMED).
BEFORE CONSTRUCTION IT IS CONTRACTOR'S
450 RESPONSIBILITY TO ENSURE THE BEARING CAPACITY AT
75

900 675
300 SITE IS NOT LESS THAN 150 kPa.
20

1 T16-200 10+10 2100


4. CONCRETE GRADE SHALL BE OF C30.
750 5. MINIMUM CONCRETE COVER SHALL BE 75mm.
20 6. TWO COATS OF BITUMEN PAINT SHALL BE PAINTED ON ALL
750 SIDES OF THE FOUNDATION AND OVER THE BLINDING CONCRETE
7. CONTRACTOR TO OBTAIN APPROVALS FROM ALL RELEVANT
2 2 T12-200 5 3200 AUTHORITIES BEFORE CONSTRUCTION OF THIS FOUNDATION.
750
B B 75 T12mm@ 100
200mm c/c
900

350
450
900

300

1
T16mm@ 3 T12 2 1600 350
200mm c/c 100
LEGEND:
4 T12 20 450 300
150 F.R.L FINISH GROUND LEVEL

SEC.A-A
TOP PLAN
REV. BY APP 'D DATE DESCRIPTION

FOUNDATION DETAILS FOR


OCTAGONAL LIGHTING POLE

DRAWING NO: CSG/HM/FD/19-001

Das könnte Ihnen auch gefallen