1-16mmØ VERT.

BARS CHB WALL 2-12mmØ TOP &


BOTTOM BARS
CONSTRUCTION NOTES 200 (min.) 200 (min.)
(DOWEL)

FOR SIZE AND SPACING


A. GENERAL
400

FOR SIZE AND SPACING


OF HOR. & VERT. BARS
STIFFENER COLUMN SC-1 OF HOR. & VERT. BARS
1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO 10mmØ STIRRUPS (SEE CONSTRUCTION NOTES)
MEET SPECIAL CONDITIONS. (SEE DETAIL) CHB WALL (SEE CONSTRUCTION NOTES)
@ 150mm O.C.
2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEEL, MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE
SUBMITTED FOR ENGINEER'S APPROVAL BEFORE FABRICATION.
OPENING OR END WALL

(DOWEL)
1-16mmØ VERT.

400
CHB WALL BARS (TYP.)
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN, CHECK WITH MECHANICAL AND ELECTRICAL CONTRACTORS FOR CONDUITS,
PIPE SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE. 12mm THK. EXPANSION JOINT
(DOWEL)

STIFFENER COLUMN SC-1 WITH MASTIC FILLER


400

4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORINGS AND BRACINGS OF THE STRUCTURE FOR ALL LOADS THAT MAYBE OPENING
IMPOSED DURING CONSTRUCTION.
FOR SIZE AND SPACING CHB WALL 2-12mmØ TOP BARS
FOR SIZE AND SPACING
OF HOR. & VERT. BARS DOWEL BARS TO MATCH
B. CONCRETE AND REINFORCEMENT OF HOR. & VERT. BARS
CHB VERTICAL CHB

200
(SEE CONSTRUCTION NOTES) (SEE CONSTRUCTION NOTES) 400 10mmØ STIRR. 1 @ 50mm,
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDING CODE OR AMERICAN CONCRETE INSTITUTE (ACI-318). (DOWEL)
REST @ 150mm O.C.
R.C. COLUMN OR WALL FIN. FLR. LVL.
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF TWENTY (28)DAYS WITH CORRESPONDING MAXIMUM SIZE
AGGREGATE AND SLUMPS AS FOLLOWS: 2-12mmØ BOTTOM BAR
CORNER WALL INTERSECTING WALL INTERSECTING R.C. COLUMN OR WALL ELEVATION SECTION
SLAB MAXIMUM SIZE MAXIMUM
LOCATION 28 DAYS STRENGTH AGGREGATE SLUMP
TYPICAL CONNECTION DETAIL OF MASONRY WALL TYPICAL DETAIL OF LINTEL BEAM AT CHB WALL OPENING
CURBS & SLAB ON GRADE 3000 PSI (Class - B+) 1.0 IN. (25mm) 4 IN. (100mm)
EXCEPT FOUNDATION
4-16mmØ VERT. BARS MAIN REINFORCEMENTS
FOR SIZE AND SPACING TO BE CONTINUOUS
OF HOR. & VERT. BARS 25
FOUNDATION 3000 PSI (Class - A) 3/4 IN. (19mm) 4 IN. (100mm)

(DOWEL)
(SEE CONSTRUCTION NOTES)
DOWEL BARS TO MATCH WHERE DEPRESSED DOWEL BARS TO

200

t/3 t/3
FFL CHB VERT. BARS SLAB OCCURS MATCH VERT. BARS
3/4 IN. (19mm)

t/3
ALL OTHERS INCLUDING BEAMS,

t
550
Fineness modulus of sand = 2.6
VARIES

SUSPENDED SLAB,COLUMN & 3000 PSI (Class - A) 4 IN. (100mm)


Moisture absorption = 3% for coarse

VERIFY ARCHITECTURAL
RETAINING WALL
aggregate and 2% for fine aggregate
1. ALL JOINTS AND CELLS CONTAINING SLAB 1000 X 10mmØ LONG
REINFORCING BARS SHALL BE FILLED SP. @ 300mm O.C.
NGL
WITH CONCRETE GROUT.
3. ALL REINFORCING BARS SHALL CONFORM TO ASTM A215 GRADE 33 FOR DIA. 12 AND SMALLER BARS AND GRADE 40 FOR DIA. 16 AND LARGER BARS.

(DOWEL)

(DOWEL)
DOWEL BARS TO MATCH 550 MAIN REINFORCEMENTS

400

400
COLUMN HOOPS AREA ALL GRADE 33 BARS. CHB VERT. BARS 2. FOR REINFORCEMENTS
300 300 TO BE CONTINUOUS (TOP & BOT. BARS)
(SEE CONSTRUCTION NOTES)
600 (MIN.)

(TYP.) (TYP.) 30 BAR DIA. 40 30 BAR DIA.


4. IN GENERAL, THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE DETAILING REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO,
UNLESS OTHERWISE SHOWN OR NOTED. 1-16mmØ VERT. BARS (MIN.) (MIN.)

250

250

D/3
5. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS:
250

(DOWEL)
1-16mmØ CONT. HOR. BARS

400

D/3

D
SUSPENDED SLABS - 3/4 IN. (19mm) 3-12mmØ BOTTOM BARS FOR FLOOR SLAB ONLY
3-12mmØ BARS

D/3
SLAB ON GRADE - 1 1/2 IN. (38mm) (AS SHOWN)
WALLS ABOVE GRADE - 1 IN. (25mm) 12mmØ BOT. BARS 600 12mmØ BOT. BARS
600 550 BEAM WHERE JOINT IS AT POINT OF STRESS, PROVIDE
600 SHEAR RODS WITH ENGINEER'S APPROVAL
BEAM STIRRUPS AND COLUMN TIES - 1 1/2 IN. (38mm) @ 300mm O.C. @ 300mm O.C.
WHERE CONCRETE IS EXPOSED TO EARTH - 2 IN. (50mm)
BUT POURED AGAINST FORMS TYPICAL CHB FOOTING DETAILS TYPICAL SECTION OF TYPICAL CONNECTION TYPICAL SLAB AND BEAM
WHERE CONCRETE IS DEPOSITED
DIRECTLY AGAINST EARTH
- 3 IN. (75mm)
(WHERE APPLICABLE) MASONRY PARTITION DETAIL OF R.C. CONSTRUCTION JOINT DETAIL
6. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL LAP OR EXTEND IN ACCORDANCE WITH TABLE 1 (TABLE OF LAP SPLICE AND ANCHORAGE LENGTH)
REINFORCEMENTS WALL AT CORNERS
MAIN REINFORCEMENT
UNLESS OTHERWISE SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE. NOTES: 4-12mmØ @ 1800 LONG TOP BARS BEND
DOWN INTO EDGE BEAM. EXTENDED BARS
1. YIELD STRESS OF HOOPS = 60 KSI
6. ALL ANCHOR BOLTS, DOWELS AND OTHER INSERTS, SHALL BE PROPERLY POSITIONED AND SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. MIN. OF 1200 (4'-0") INTO BARS.
2. D = USE MAX. COLUMN DIMENSION,
1/6 CLEAR HEIGHT OR 18" (450mm) 30 BAR DIA. 30 BAR DIA.

t
7. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, EQUIPMENTS AND MECHANICAL BASES THAT AREA REQUIRED BY THE

1 or 14 D
WHICHEVER IS GREATER. (MIN.) (MIN.)
ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS. 3. NUMBER OF HOOP TIES SAME AS PER COLUMN TIES SCHEDULE.

D=FOR BEAMS
60

DEPRESSION
0
4. ALL CONCRETE REINFORCEMENT DETAIL SHOULD BE DONE IN

VERIFY
t=FOR SLAB

D
8. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN (7) CONSECUTIVE DAYS IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP, FOG ACCORDANCE W/ ACI DETAILING MANUAL 1980 PUB SP-66.
SPRAYING, CURING COMPOUNDS OR OTHER APPROVED METHODS.
H
9. STRIPPING OF FORMS AND SHORES:

0
60
350mm MAX.

0
60
FOUNDATION - 24 HOURS
10 D=FOR BEAMS PROVIDE 2-10mmØ EXTRA SLEEVES FOR UTILITY
SUSPENDED SLAB EXCEPT WHEN ADDITIONAL LOADS AREA IMPOSED - 8 DAYS d 4-12mmØ BOTTOM BARS STIRR. EACH SIDE OF SLEEVES PIPES MAX., 1/5 D
M 2t=FOR SLAB
IN

H
WALLS - 18 HOURS . 30 BAR DIA.
BEAMS -14 DAYS CROSS-TIE (MIN.)
TYPICAL DETAIL FOR SLEEVES
C. MASONRY AND CONCRETE BLOCKS THRU CONCRETE BEAM

CONF. REINF.
@ 100mm
1. ALL NON-LOAD BEARING TYPE CONCRETE BLOCKS SHALL HAVE A UNIT WEIGHT NOT TO EXCEED 80 PCF. FOR LOAD BEARING TYPE CONCRETE BLOCKS, A
TYPICAL CORNER TYPICAL DETAIL FOR BEAM

D
MINIMUM COMPRESSIVE STRENGTH 80 PCF. FOR LOAD BEARING TYPE CONCRETE BLOCKS, A MINIMUM COMPRESSIVE STRENGTH OF 6.90 MPA. SHALL BE NOTES:
DEVELOPED. SLAB DETAIL OR SLAB CHANGE SOFFIT PROVIDE THESE ADDITIONAL BARS FOR ALL OPENINGS PLUS BARS

@ 100mm
D JOINT REINF.
2. PROVIDE 1-16mmØ VERTICAL BARS AT CORNERS,INTERSECTIONS,END OF WALLS AND EACH SIDE OF OPENINGS (NOT SHOWN) PARALLEL TO SIDE OF OPENING EQUAL TO THE
12mmØ X 1000mm LONG NUMBER OF TERMINATED BARS AT OPENING.

30 BAR DIA.
3. LINTEL BEAMS SHALL BEAR AT LEAST 8 INCHES (200mm) ON EACH SIDE OF MASONRY WALL OPENING. @MID-DEPTH OF SLAB
LAP SPLICE LENGTH: SEE ARCHITECTURAL & MECHANICAL PLANS FOR SLAB OPENING

CONF. REINF. PER SCHEDULE CONF. REINF.


AT EACH CORNER

@ 100mm

H (CLEAR HEIGHT OF COLUMN)


4. WALL REINFORCEMENTS SHALL BE AS FOLLOWS: LOCATION.

30 BAR DIA.
WALL THICKNESS VERTICAL REINFORCEMENT HORIZONTAL REINFORCEMENT 40 X BAR DIAMETER OF
MAIN BAR (MIN. SPLICE)

COLUMN TIES AS
8 IN. (200mm) Ø12mm @ 400mm Ø10mm @ 600mm 12mmØ X 1000mm LONG MID -DEPTH
FOR COL. BAR SPLICES L
6 IN. (150mm) Ø10mm @ 400mm Ø12mm @ 400mm OF SLAB AT EACH CORNER
SEE TABLE OF MIN. LAP

600mm
4 IN. (100mm) Ø10mm @ 400mm Ø12mm @ 400mm L/4
SPLICE LENGTH OF COL.

CONF. REINF. TIES LAT. TIES


REINFORCEMENT. TOP BARS @ SUPPORT (CONT.)
5. REINFORCING BARS SHALL BE LAPPED A MINIMUM OF 30 BAR DIAMETERS WHERE SPLICED, DOWELS FROM CONCRETE FOOTINGS OR SLAB SHALL EXTEND

400
INTO THE BLOCK WALL A MINIMUM OF 30 DIA. AND DOWELS TO MATCH VERTICAL REINFORCEMENTS OF WALL. REQ'D. BOT. BARS @ SUPPORT 1-12mmØ TOP & BOT. BARS
WINDOW DOOR

@ 100mm
1-16mmØ EACH OPENING

JT. OF REINF.
6. ALL CELLS CONTAINING REINFORCING BARS OR INSERTS SHALL BE SOLIDLY FILLED WITH CONCRETE GROUT. (REFER TO SPECIFICATIONS). OPENING
FACE (TYP.)

D JOINT REINF. D
OMIT TRIMMER BARS
D. FOUNDATION WHERE OPENING IS

@ 100mm
FRAMED BY BEAMS
1. FOUNDATION IS DESIGN FOR AN ALLOWABLE SOIL BEARING CAPACITY OF 2000 PSF (95.76 MPa) TO BE VERIFIED BY ACTUAL SOIL TESTING. 0.165L EXTRA TOP BARS @ SUPPORT

CONF. REINF.
@ 100mm
2. FOUNDATION SHALL REST ON NATURAL SOIL. UNLESS OTHERWISE NOTED BY THE ENGINEER. NO PART OF THE FOUNDATION SHALL REST ON FILL. BOT. BARS @ MIDSPAN
0.22L

400
3. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AFTER FOOTING EXCAVATION HAVE BEEN COMPLETED AND PRIOR TO CONCRETING TO CONFIRM THE 40 X BAR DIAMETER OF IN TWO WAY SLAB EXTEND
DESIGN SOIL BEARING CAPACITY. MAIN BAR (MIN. SPLICE) BARS UP TO BEAM SUPPORT
TYPICAL COLUMN ELEV. SHOWING TYP. DETAIL OF COL. LAP SPLICE TYPICAL EXTERIOR WINDOW
DOWELS AND TIES SPACING & EXT. GIRDER TO COL. CONNECTION & DOOR OPENING TYPICAL SLAB OPENING DETAIL
DESIGNER: CIVIL ENGINEER:
PROJECT TITLE OWNER: SHEET CONTENT SHEET NO.
CULAGBANG, FRANZ A.
PROPOSED TWO-STOREY
BSCE 3
RESIDENTIAL BUILDING CONSTRACTION NOTES S-01
PRC No. ######## DATE: APRIL 02,2019
PTR No. ########TIN: ###-###-###-###