469GB

Basic

Multi-Purpose Digital Laser Sensor

LV-N Series Setting Guide


For precautions and operation details, refer to the
instruction manual included with the product.

Sensitivity setting Setting value Current value Fine sensitivity adjustment Mode/Output *2 Preset function

Channel switch *1

*1 This is a power select switch on M8 connector types or monitor output types. Not available for 0-line types.
*2 Press and hold the [MODE] button to make advanced setting changes.

Calibration method

Two-point Calibration Manual adjustment


The value will be automatically set to the mid-point The setting value can be finely adjusted manually.
between when there is no workpiece and when there
is a workpiece. Up Down

1 When there is no workpiece


Press [SET] briefly.

2 When there is a workpiece


Press [SET] briefly.

Workpiece Complete
* When the difference is small., "----" is displayed.

If the setting has become too Initializing the Settings


complicated and you wish to start over...
1 Press and hold the [SET] and [PRESET]
buttons simultaneously for more than
Press and hold three seconds.
3 seconds or more at
2 Use the to select "RST", then press
the same time.
the [MODE] button.
3 Use the to select "iNiT", then press
the [MODE] button.
After initialization is complete, the display
returns to the current value.

LV-N-1
Advanced
Other Calibration Methods

„„Maximum Sensitivity Calibration „„Work-Preset


The value is set slightly higher than the received light intensity when the The current value is corrected to 0.0.
setting was made. Arbitrary two points can be corrected to "100.0" and "0.0" by using this
This is effective when light intensity is decreased due to dust and dirt. function in combination with the Preset function.
In the state shown below, press and hold the [SET] button for three seconds or more. Stop
pushing when "SET" flashes. The sensitivity is set slightly higher than the received light intensity.
Green PST
Thru-Beam Model / Retro-Reflective Model Reflective Model lights up
: with workpiece : without workpiece

* Press and hold [PRESET] to Current value is ""


disable this function.
* Cannot be used in combination
with the Zero-shift function.

FS-N
„„Full Auto Calibration
„„Maximum Sensitivity Preset
The sensitivity can be automatically set while passing the workpiece through.
LV-N
This is effective when the line operation cannot be stopped. This function sets the reference condition to ".0" and correct conditions
with the slightly higher light intensity to "100.0".
Press and hold the [SET] button with no workpiece in place. While "SET" is flashing, pass a
workpiece through. (Continue pressing the [SET] button while the workpiece passes through.) This is useful when you would like to perform detection using the

Common to Thru-Beam Model / Retro-Reflective Model and Reflective Model


background as a reference with reflective models. LR-Z

Thru-Beam Model / Retro-Reflective Model


: with workpiece
LR-T

Press and hold for 3 seconds or more


CZ-V20

Release
GV
„„Positioning Calibration Reflective Model * Press and hold [PRESET] to
disable this function.
: without workpiece
* Cannot be used in combination
This is effective when positioning the workpiece. with the Zero-shift function.
Press the [SET] button with no workpiece. GP-M
Place the workpiece in the location you wish to position it. Press and hold the [SET]
button for at least 3 seconds. Release the button when "SET" flashes.

Common to Thru-Beam Model / Retro-Reflective Model and Reflective Model


PZ-V/M

„„Full Auto Preset PX


Workpiece
The preset can be automatically made while passing the workpiece
through.
This is effective when the line operation cannot be stopped and you
wish to use the preset.

„„Preset Common to
Thru-Beam Model / Retro-Reflective Model

With simple operation, the current value is adjusted to "100.0" at the and Reflective Model
same time as when adjusting sensitivity.
This can remove variation in detected contents or variation due to Press and hold until
"" flashes
individual difference, and is useful in predicting the need for maintenance.

Press [PRESET] button once


While pressing the [PRESET] button,
pass a workpiece through

Green PST lights up


Settings complete
* Press and hold [PRESET] to
disable this function.
* Press and hold [PRESET] to Setting value Current value is * Cannot be used in combination
disable this function. is "" "" with the Zero-shift function.
* Cannot be used in combination
with the Zero-shift function.
LV-N-2
Advanced
Convenient Correction Functions Key Lock

„„Zero Shift „„Setting Key Lock


The current value can be corrected to "0".
This is effective when the light intensity is not set to "0" at the time
1 Press and hold the [MODE] button and (or )
when a reflective model is installed. simultaneously for three seconds or more

2 The screen displays "Loc", disabling key operation.

Green PST lights up


„„Canceling Key Lock
1 Press and hold the [MODE] button and (or )
Current value is "" simultaneously for three seconds or more.
* Press and hold [PRESET] to
disable this function.
* Cannot be used in combination
with the Zero-shift function.

2 The screen displays "unL", enabling key operation.


Display when the LV-S31 is Connected
Keylock with password
When the LV-S31 is connected, the workpiece position is numerically
displayed on the main screen (red display) using the center position as
[5000]. „„Setting the Keylock with password
The display changes as follows according to the workpiece position.
1 While pressing [MODE], press 10 times.
Display Meaning "Loc 0" is displayed.
Near ---- Out of detection range
The detector is nearer to the sensor side
nEAr
than numerical display range
Centering on 5000, the value increases as 2 Press and set any numerical value (up to 4
5000 the workpiece distance increases from the
digits).
sensor
The workpiece is farther from the sensor
FAr
than the numerical display range
Far ---- Out of detection range
3 Press [MODE].
"Loc" is displayed, and button
operation is disabled. Then, the current
Output Switch light intensity is displayed.

Either light-ON (L-on) mode or dark-ON (D-on) mode can be


selected.
„„Canceling the Keylock with password
1 While the current value is displayed, press the
[MODE] button once. 1 While pressing [MODE], press 10 times.
"Loc 0" is displayed.

2 Press to specify a password, and press


2 Use to switch the output (L-on/D-on), then [MODE].
press the [MODE] button again. "unL" is displayed, and button
The output change completes, and the display returns to the operation is enabled.
current value.

LV-N-3
Advanced
Detailed Settings

• To return to the normal screen, press and hold


MODE
while setting each item. „„Display Settings
MODE
• Press the button and the button simultaneously to return to the previous setting.

„„Basic Settings Normal display method


Reverse display

MODE Sub-display off


Press and hold for 3 seconds or more
Extension display

  TURBO mode Bar display

  SUPER mode Excess gain (%) display


ULTRA mode Light intensity hold display *1
 
MEGA mode Excess gain hold (%) display *1
 
  HIGH SPEED mode*1 L-on / D-on display

  FINE mode Enable the saturation of the Preset function *2
Disable the saturation of the Preset function
  Normal sensitivity setting method
Percentage Calibration*2 Settings complete
 
Zero-shift calibration Go to system setup mode
 
Go to detection setup mode
 Settings complete
Return to display setup mode
  Go to detection setup mode
Return to normal display
FS-N
  Go to display setup mode
Go to system setup mode MODE
  *1 Press the button to toggle between Std/P~P_/b~b_/P_b~/P~b_.
MODE
Return to normal display *2 Press the button to set between the range of 100P and 200P.
LV-N
*1 hSP cannot be selected when LV-S31/S62/S63 is connected.
MODE
*2 You can press the button to set between the range of -99P and 99P.
„„System Settings LR-Z

„„Detection Settings Eco feature off


Enable eco feature
LR-T
Reduce power consumption (response time 4 times slower)

Timer OFF
*1 Standard current value display

Off-delay timer *1 Maximum current value display (4 times hysteresis) CZ-V20


On-delay timer *1 Normal operation
One-shot timer *1 Twice the number of interference-prevention units as STD
(response time 2 times slower)
Normal (light intensity) detection mode
DATUM1 mode *2 *3
*2 Disable common key operations GV
Enable common key operations
DATUM2 mode *2 *3
Area detection mode Standard sensitivity
Rising Edge Detection Mode *3 High resolution sensitivity
Falling Edge Detection Mode *3
Settings complete
GP-M
*6 External input off
Go to detection setup mode
External calibration input
Go to display setup mode
Preset input
Return to system setup mode
Zero shift input PZ-V/M
Reset input Return to normal display
Light transmission OFF input
*1 Not displayed when LV-S31 is connected.
Pause mode transition input *4
*2 Main unit only.
Sleep mode transition input PX
*7 Analog scaling *5
Alternate
display

Settings complete
Go to display setup mode
„„2-output Settings*1
Go to system setup mode
Return to detection setup mode Light intensity detection mode
*2
Return to normal display Limit setting output mode *2
Warning output mode
MODE Counter output mode *3
*1 Press the button to set between the range of 1 and 9999(ms).
MODE
*2 Press the button to set the adjustment sensitivity to a range of between Timer OFF
LEu1 and LEu3 and set the warning output level to a range of between OP and Off-delay timer *4
100P. On-delay timer *4
*3 Cannot be selected when LV-S31 is connected. One-shot timer *4
MODE
*4 Press the button to toggle between oFF/oN/KEEP.
Settings complete
*5 The analog output upper limit can be set between 50 and 65535. Refer to the
"LV-N10 Series User's Manual" for the operation method of analog output in
Return to normal display
respect to the preset display.
*6 Not available for zero line types. *1 Only 2 output types (LV-N11x / N12x).
MODE
*7 Monitor output type only (LV-N11MN). *2 Press the button to select the USEr (user reset) or Auto (auto reset)
resetting methods.
*3 Select the count method from oUr1, oUr2 or Auto. When Auto is selected, the
one-shot time can be set between 1 and 9999 (ms).
MODE
*4 Press the button to set between the range of 1 and 9999(ms).

KEYENCE AMERICA PHONE: 888-539-3623


201277E 1056-2 469GB
LV-N-4