Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+...

Página 1 de 3

Fechar o SIS

Tela anterior

produtos: NENHUM EQUIPAMENTO SELECIONADO


Modelo: NENHUM EQUIPAMENTO SELECIONADO
Configuração: NENHUM EQUIPAMENTO SELECIONADO

Operação dos Sistemas


Electronic Modular Control Panel II+ (EMCP II+) for EUI Engines
Número de Mídia -RENR1200-01 Data de Publicação -10/01/1999 Data de Atualização -10/09/2001

i01174908

Modes Of Operation
SMCS - 4490; 7451

Table 1

Display Area Functions When In ormal Mode, Alarm Mode Or Shutdown Mode (1)
Item Of Alarm Mode
Display ormal Mode Shutdown Mode
Area
Upper AC Data Shown AC Data Shown (2) Fault Code Shown
Display
Lower Engine Data And Relay Engine Data And Relay Engine Data And Relay
Display Status Shown Status Shown Status Shown
Shutdown All Off All Off Flashing
Indicators
Fault Alarm Off Flashing (2) Off
Indicators
Key Function Normal Mode Alarm Mode Shutdown Mode

Left Most No Function No Function No Function


Key (3)
Selects The AC Phase Selects The AC Phase No Function
Phase Select
That Is Shown On The That Is Shown On The
Key
Upper Display Upper Display
Stops And Starts The Stops And Starts The Stops And Starts The
Engine Meter Scrolling Of Engine Scrolling Of Engine Scrolling Of Engine
Key Conditions On Lower Conditions On Lower Conditions On Lower
Display Display Display
Lamp Test Performs A Lamp Test Performs A Lamp Test Performs A Lamp Test
Key

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 31/08/2010
Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+... Página 2 de 3

Alarms Code No Function Shows The Fault Code No Function


Key On The Upper Display
Exit Key (3) No Function No Function No Function

Service Enters The GSC Into Enters The GSC Into No Function
Mode Key Service Mode Service Mode
(1) For a description of the display area functions when in service mode, see the topic Service Mode.
(2) When an alarm fault is present, the fault code is shown on the upper display when the alarm codes key is pressed.
(3) This key only functions when in service mode, see the topic Service Mode.

Illustration 1 g00474240
Display Area Of Generator Set Control (GSC)

(1) Dedicated Shutdown Indicators

(2) Fault Shutdown Indicator

(3) Fault Alarm Indicator

(4) Upper Display

(5) Lower Display

(6) Keypad

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 31/08/2010
Pesquisa de Mídia - RENR1200 - Electronic Modular Control Panel II+ (EMCP II+... Página 3 de 3

The GSC has four modes of operation. A brief description of each mode follows this paragraph. See
the individual topic for more detailed information.

ormal Mode - The GSC uses normal mode for the normal operation of the generator set. The
operator can identify the normal mode by observing the display area. When the GSC is in the normal
mode, all dedicated shutdown indicators are OFF. The fault shutdown indicator is OFF. The fault
alarm indicator is OFF and "SERV "is NOT SHOWING on the upper display.

Alarm Mode - If there is an alarm fault, the GSC will automatically go into alarm mode in order to
alert the operator. The operator can identify the alarm mode by observing the display area. When the
GSC is in alarm mode, the fault alarm indicator is FLASHING. When the alarm code key is pressed,
the fault code will be shown.

Shutdown Mode - If there is a shutdown fault, the GSC will automatically go into shutdown mode
in order to alert the operator. The operator can identify the shutdown mode by observing the display
area. When the GSC is in shutdown mode, a dedicated shutdown indicator is FLASHING, or the
fault shutdown indicator is FLASHING.

Service Mode - The GSC goes into service mode when the operator presses the service mode key on
the keypad. The operator can use service mode for the following purposes.

 Assist with troubleshooting diagnostic faults.

 Calibrate generator set functions.

 Adjust generator set functions.

 Verify generator set functions.

 Satisfy special applications.

 Satisfy the needs of the customer.

The operator can identify service mode by observing the display area. When the generator set is in
service mode, "SERV" is SHOWN on the upper display.

ote: Service mode can not be entered when the ECS is in the AUTO position.