GENERATOR PROTECTION SETTING TABLE
52G
Name of Protection & Code No. Menu Text Settings Tripping To
2nd stage under resistance trip delay 64R<1 Trip Dly 1.0 s
Resistance compensation R Compensation Calibration
Current loop input slection CLIO Input 1 Enabled
Current loop input type CL1 Input type 0-20mA
Current loop input name CLIO Inpu Label CLIO Input 1
Current loop input 1 minimum Setting CLI1 Minimum 0
Current loop input 1 maximum Setting CLI1 Maximum 100
Current loop input 1 alarm setting status CLI1 Alarm Disabled
Current loop input 1 trip status CLI1 Trip Disabled
Current loop input 1 under current alarm status CLI1 I<Alarm Enabled
Current loop input 1 under current alarm setting CLI1 I<Alm Set 3.5 mA
Current loop Input 2 Status CLIO Input 2 Disabled
Current loop input 2 under current alarm status CLI2 I<Alarm Disabled
Current loop Input 3 Status CLIO Input 3 Disabled
Current loop input 3 under current alarm status CLI3 I<Alarm Disabled
Current loop Input 4 Status CLIO Input 4 Disabled
Current loop input 4 under current alarm status CLI4 I<Alarm Disabled
Current loop output 1 status CLIO Output 1 Disabled
Current loop output 2 status CLIO Output 2 Disabled
Current loop output 3 status CLIO Output 3 Disabled
Current loop output 4 status CLIO Output 4 Disabled
Page 2 of 8
GENERATOR PROTECTION SETTING TABLE
Tripping charecteristic of 1st stage Over current protection I>1 Function DT (Definite time)
Direction of the 1St stage Over current protection I>1 Direction Non directional
Pick-Up setting for 1st stage over current protection I>1 Current set 0.98 A
Delay for 1st stage over current protection I>1 Time Delay 10 s
Reset time for 1st stage over current protection I>1 tReset 0s
Tripping charecteristic of 2nd stage Over current protection I>2 Function IEC E Inverse
Direction of the 2nd stage Over current protection I>2 Direction Non directional 52G
Pick-Up setting for 2nd stage over current protection I>2 Current set 0.98 A
Time setting multiplier for 2nd stage over current protection I>2 TMS 0.4 s
Reset time for 2nd stage over current protection I>2 tReset 0s
3rd stage over current protection status I>3 Status Disabled
4th stage over current protection status I>4 Status Disabled
Function link for VTS blocking for stage-1, 2, 3, 4 over current
protection I> Function link 1111
Page 3 of 8
52G
GENERATOR PROTECTION SETTING TABLE
Page 4 of 8
OVERALL PROTECTION SETTING TABLE
Name of Protection & Code No. Menu Text Settings Relay Tripping To
Page 5 of 9
GSUT PROTECTION SETTING TABLE
87 pickup 0.15A
Restricted Ground Fault (64REF) Resistance 1347Ω MIB 52 (G & L)
87 Time Delay 0.20 sec
NOTE: For Volts per Hertz direct trip is assigned to 52L (Trip is not through 86C1, 86C2 & 86Com)
Page 6 of 9
UAT PROTECTION SETTING TABLE
87 pickup 0.03A
Restricted Ground Fault (64REF) Resistance 7616Ω MIB 52 (G & L)
87 Time Delay 0.20 sec
Page 7 of 9
CAT PROTECTION SETTING TABLE
87 pickup 0.03A
Restricted Ground Fault (64REF) Resistance 7893Ω MIB 52 (G & L)
87 Time Delay 0.20 sec