Beruflich Dokumente
Kultur Dokumente
Kathmandu Municipality
Ministry Building Design
SUBMITTED BY:
June 2019
Contents
List of Tables iv
List of Figuresv
Page ii
6.1 Introduction .............................................................................................................................................. 16
6.2 Analysis Results ....................................................................................................................................... 16
6.2.1 Base Shear .................................................................................................................................. 16
6.2.2 Story Drift ..................................................................................................................................... 16
6.2.3 Deformation ................................................................................................................................. 16
6.3 Concrete Column Design ......................................................................................................................... 16
6.4 Slab and Staircase Design ....................................................................................................................... 16
6.5 Concrete cover ......................................................................................................................................... 16
6.6 Serviceability Requirements ..................................................................................................................... 17
6.7 Ductile Detailing ....................................................................................................................................... 17
6.8 Foundation Design ................................................................................................................................... 18
Page iii
List of Tables
Table 1: Typical Structural Member and Components ................................................................................... 1
Table 7: Limit State Load Combinations used in Code-based Design (IS) ................................................ 10
Page iv
List of Figures
Figure 1: Overall Design Procedure .................................................................................................................... 5
Figure 2: Response Spectra for Earthquakes with Different Return Periods for Soil Type ......................... 10
Page v
Chapter 1 : Introduction
1.1 Introduction
The structure of Ministry Building located at Birendranagar, Surkhet, engaged the
services of Earthquake Resistant Technology Consultancy Pvt Ltd, to carry out the
design for the spatial requirements in accordance with purpose of the building
taking into account the aesthetic aspect and provision for various services and
systems necessary for the operation of the Building. M/s Earthquake Resistant
Technology Consultancy Pvt Ltd was engaged by the main consultant to carry out
the structural analysis and design in close coordination with the client. In order to
fulfill such requirements, the structural materials and the structural system have
been determined taking into account the availability of materials, cost efficiency
and structural integrity, i.e. stability, strength and serviceability; the three main
factors to be incorporated in the design of all structures. The building is a system
consisting of six storey Special RC moment-resisting frames (SMRF) steel truss at the
top.
The design have been carried out using IS 1893 (part 1): 2016, “Criteria for
Earthquake Resistant Design of Structures and finite element software ETABS
(Version 17), developed by Research Engineers International, USA.
Foundation RC sections
Column RC sections
Lintels RC beam
Page 1
1.4 Codes, Standards and References
The design is based primarily on the current IS 1893 (part 1): 2016, “Criteria for
Earthquake Resistant Design of Structures” which is adopted for the structural
analysis and design of this building, while the relevant codes of British
Standards, European Standards are referred to consider for the areas/provisions
that are not addressed in the Indian Standards or as required for the purpose of
design.
The basic building codes referred are listed below which are followed for
structural design, also indicating their area of application.
Table2: Codes and Standards
11 IS 800: 2007 Code of Practice for General Construction in Steel (Third Revision)
12 NBC:201:1994 Mandatory Rules of Thumbs - Reinforced Concrete Building with
Masonry Infill.
13 IS: 1905-1987 Code of Practice for Structural Use of Un-reinforced Masonry.
14 NBC:109-1994 Masonry: Unreinforced.
15 NBC:110-1994 Plain and Reinforced Concrete.
16 IS:8009-1976 Calculation of settlement of shallow foundations.
17 BS:8110-1985 Structural Use of Concrete.
18 NBC:105-1994 Seismic Design of Buildings in Nepal.
Page 2
The structural elements of reinforced concrete were designed to Limit State Theory.
The major structural elements were automatically designed in the inbuilt program
to IS 456 for reinforced concrete structures elements.
The frame system is designed for gravity loads (Dead and Live/Imposed), seismic
loads
Page 3
Chapter 2 :Design Philosophy and Approach
2.1 Introduction
This chapter presents the design philosophy and approach used in structural
design of the aforesaid building.
According to Indian Standard IS: 1893:2016, the horizontal seismic shear force
acting at the base of the structure, in the direction being considered, shall be:
Vb = AhΣWi
Where, Ah is basic seismic coefficient.
Ah=zISa/2Rg
T = 0.075 h 0.75
Where
h = Height of building
R = 5 as per IS 1893
Site Type:
It is the type of soil considered for the site of Type II medium soil. The combined
effect of Time period and soil type defines the value of spectral acceleration
Sa/g
Page 4
Zone Factor (z):
It is a factor that depends on the local damage expected in the area under
consideration. The location of the building states the value as 0.36.
Step 6: Preparation of
structural drawings
Page 5
Chapter 3 :Basic Materials
3.1 Introduction
This chapter presents the strength of materials used in the design of structural
components.
3.2 Concrete
The minimum compressive, used in different types of structural components are
shown in the following table.
Table 3: Compressive Strength of concrete
IS 456:2000 Slab 30 30
IS 456:2000 Column 35 35
IS 456:2000 Foundation 25 25
fy (Nominal) fy (Expected)
Diameter
(MPa) (MPa)
10mm and below (for Stirrup) 500 550
Page 6
Chapter 4 :Modeling and Analysis
4.1 Introduction
This chapter presents the finite element modeling of the building, including
modeling assumptions of materials, sections, and components properties. The
structural system adopted in the building is the system consisting of Special
moment resisting frame. The structural system is believed to perform best under
seismic loading. To ensure the ductile response of the building during seismic
event the overall structure has been detailed according to the latest code
provision (e.g., IS 13920). One of the fundamental attributes required for the
proper seismic response of a building during earthquake motions is that its
lateral load resisting members should be tied together to act as a single unit.
This provision is intended to provide continuous lateral load system that ties all
parts of the structures together. It also provides for proper connection between
the members of the system to transmit additional seismic forces safely.
A vertical lateral force-resisting system shall be continuous and should run from
the foundation to the top of the building. The flow of seismic forces in the
structure should be such that these forces are delivered through structural
connections to horizontal diaphragms; the diaphragms then distribute these
forces to the vertical lateral force resisting elements such as frames; these
vertical elements transfer the forces into foundation; and foundation transfers
the forces into the soil. The presence of discontinuity in a load path makes a
building inadequate of carrying seismic forces. Therefore the design
professional should identify any gaps in the load paths and then take necessary
mitigation measures to complete the load path. A continuous load path has
been maintained in this building. The provision of redundancy is recommended
because of the uncertainties involved in the magnitude of both seismic loads
and member capacities. If any member of a lateral force resisting system fails,
the redundancy of the structure will help ensure that there is another member
present in the lateral force resisting system that will contribute lateral resistance
to the structure. Redundancy also provides multiple locations for potential
yielding, possibly distributing inelastic activity within the structure and improving
the ductility and energy dissipation.
Page 7
limitation of program are manually carried out in accordance with the r elevant
latest standards. The following matrix shows general architectural configuration
and geotechnical investigation information
4.2.1 Beams
Frame elements are used in modeling of beams, which includes the effects of
bending, torsion, axial deformation, and shear deformations. Insertion points
and end offsets are applied to account for the finite size of beam and column
intersections, if required.
4.2.2 Columns
Frame elements are used in modeling of columns, which includes the effects of
biaxial bending, torsion, axial deformation, and biaxial shear deformations.
4.2.3 Damping
Constant modal damping of 5% was used in seismic analysis.
Page 8
Chapter 5 :Loads
5.1 Introduction
This chapter presents the design loads considered in the structural design,
including gravity loads and seismic loads.
Parameter Value
IS 1893:2016
Zone factor, Z 0.36
Page 9
Figure 2: Response Spectra for Earthquakes with Different Return Periods for Soil Type
Limit State Method design load combinations used in code-based design are
shown in the following table.(Ref: IS 1893:2016)
Table 7: Limit State Load Combinations used in Code-based Design (IS)
1 1.5(DL+LL)
2 1.2(DL+LL±ELx± 0.3ELy)
3 1.5(DL±ELx± 0.3ELy)
5 1.2(DL+LL±ELy± 0.3ELx)
6 1.5(DL±ELy± 0.3ELx)
Page 10
LL = Live load
EL = Earthquake load
Linear static analysis and Response Spectrum analysis are carried out for gravity
and earthquake loadings.
Page 11
Structural Component Design Code
System Approach/Consideration Reference
RC connections Moment connections IS 456:2000
Shear connections
For our case stiffness modifier for beam & columns are taken 0.35 and 0.7 respectively
The stiffness of the frame must be sufficient to control the drift of the building at each story
within the limits specified by the building code. Drift limits in ASCE 7 are a function of both
occupancy category (IBC 1604.5) and the redundancy factor, ρ, (ASCE 7 - 12.3.4) as
shown in Table 2-1.
Referring to Table 2-1, the drift of the commercial complex structure is calculated using
the redundancy factor 1.3 and occupancy category III which is equal to 0.012xH
Page 12
5.8 Soft Storey
It is one in which the lateral stiffness should be less that in the storey above (as per
IS1893:2016). The storey lateral stiffness is the total stiffness of all seismic force resisting
elements resisting lateral earthquake shaking effects in the considered direction.
Page 13
5.10 Mass Irregularity
Mass irregularity shall be considered to exist, when the seismic weight of any floor is
more than 1.5 times of that of floor below. In the buildings with mass irregularity and
located in seismic zone III, IV and V, the earthquake effects shall be estimated by
Dynamic analysis method (IS 1893:2016)
Page 14
5.13 Eccentricity
Eccentricity ratio in all diaphragms is considered for 5% during analysis.
Eccentricity percentage is increase if necessary as per required in relation with
center of mass and center of rigidity.
Page 15
Chapter 6 : Structural Design Results
6.1 Introduction
This chapter presents the analysis and design results of the building. The
structural components were designed to resist the elastic demand forces
considering R factor using seismic coefficient analysis and response spectrum
method.
6.2.3 Deformation
Maximum deformation of the building for static earthquake load condition for X
and Y direction is read form ETABS model. Deformed value of the structure is
tabulated in Table 10.
The concrete column was designed using various sections with reference to IS
456. The minimum size of reinforcement bars of column was designed
considering the ductile detailing with reference to IS 13920.
The concrete column was designed using various sections with reference to IS
456. The minimum size of reinforcement bars of column was designed
considering the ductile detailing with reference to IS 13920.
Page 16
reinforcement bars are 500MPa complying with minimum elongation of 14.5 %
as per IS: 1786 – 2008.
The structural design shall satisfy the following requirements of limit state of
serviceability:
IS: 456-2000 limits final deflection of slab or beam from as cast level to L/250, L
being the effective span of the member. The deflection after erection of
partitions and completion of finishes is limited to lesser of L/325 and 20 mm.
IS: 456-2000 limits the inter-story drift to 0.004 times the story height with partial
load factor of 1.
NBC-105 limits horizontal sway of a floor level relative to adjacent floor levels to
0.01h, h being the story height, and the upper limit to this relative sway is 60
mm. The displacements obtained from the analysis results were scaled up 5/K
times as per clause 9.1, and then compared with the limitations.
Special confinement zone adjacent to each beam column joint is defined, for
beams the length is equal to twice the beam effective depth and for columns
it is largest of:
450 mm
Spacing of ties shall not exceed 100 mm, shall not exceed one fourth of
smallest column sectional dimension and need not be less than 75.
Page 17
Laps in columns shall be permitted only within a specific zone near mid
story height. Tie spacing in the lap splice zones shall not be less than 150
mm
Stirrup spacing shall not exceed one fourth the effective depth.
Shear strength shall be at least the gravity load shear plus 1.4 times ratio
of sum of moments of resistance (top tension for one end and bottom
tension for the other end) to the span of beam.
a) a joint
Page 18
Chapter 7 : Results and Output
7.1 Introduction
This chapter presents the finite element modeling of the building as mentioned
in section chapter 2, including modeling assumptions of materials, sections,
components properties and design and result of the building. The building is
divided into two blocks namely 1& 2.
The area of proposed six storey structure for block 1 & five storey structure for block
2 for the building is designed as frame structure with RC slab. Thickness of wall is as
per drawing and positions of structural member are taken as per architectural
drawing for analysis.
Page 19
Table 10: General and Configuration Information
Geometrical Configuration of
B
Building:
B.1 No. of Block: 1
(1 Basement +5 storey)
B.2 No. of Storey: 8
B.3 Story Height:
Basement 2.9 m
Typical 3.3 m
B.4 No. of column: 15 (Ground floor Column)
B.5 No. of Lift: -
B.6 No. of staircase: -
B.7 Total height of structure: 19.10 m
Total height for Fundamental time
B.8 16.20 m
period caculation
Lx= 22.0 m
B.9 Height to width ratio of building: 1.246
Ly= 13.0 m
B.10 Length to width ratio of building: 1.692
B.11 Seismic joint 325mm
B.12 Floor wise Stiffness: X Y
5th Floor 140950.253 107023.855
4th Floor 143357.244 114085.627
3rd floor 144080.893 115946.164
2nd Floor 155519.685 124896
1st Floor 244696.209 178092.583
Ground Floor 12939519.45 1478736.31
B.13 Floor wise Mass: Mass (kg)
5th Floor 380905.31
4th Floor 433738.51
3rd floor 430019.12
2nd Floor 435802.83
1st Floor 441972.11
Ground Floor 471116.56
Page 20
B.14 Centre of Mass X Y
1st Floor 10.9787 6.9249 m
C Geological Investigation
Geological Investigation
i) Conducted
If Yes
C.1 Soil Investigation Report: Yes
G.S. Soil &
Materials
Soil Investigation Done By:
Engineers
C.2 Pvt.Ltd.
C.3 Allowable Bearing Capacity: 163 kN/m2
C.4 N- value: 50+
C.5 Type of Soil: II
C.6 Water Table: No
C.7 Liquefaction Potential: No
C.8 Calculated Maximum Pressure in
Foundation: 127.05 kN/m2
If No
C.9 Adopted Value as per NBC 205
Table 3.1
Site Consideration as per NBC
C.10 108?
Page 21
Software:(ETABS V 17)
D.2 Structural System: SMRF
D.3 Foundation System: Mat foundation
D.4 Loading Parameters:
As per IS 875
i. Dead Load:
(Part 1)-1987
As per IS 875
ii. Live Load:
(Part 2)-1987
iii. Other Load if any
Beam, Slab M30, Column M35,
D.5 Concrete Grade Used : 25 MPa
Foundation M25.
D.6 Reinforcement Grade Used: HYSD 500 MPa
Reinforcement Grade Used for
HYSD 500 MPa
shear:
Mechanical Properties of other
D.7
construction materials used:
i. Brick Masonry 19.2 KN/m3
ii. Steel Section 76.9 KN/m3
iii. Other
Page 22
Mode 3 0.6749 0.7007
D.9.5 Scale factor in x-dir 2.953
Scale factor in y-dir 3.195
D.9.6 Total Deflection of Building: EQx EQy
i. Along X-direction: 62.414 mm
ii. Along Y-Direction: 81.217 mm
D.9.7 Inter Story Deflection (Drift): EQx EQy
5th Floor 0.002488 0.003462
4th Floor 0.003901 0.005189
3rd floor 0.004814 0.00632
2nd Floor 0.00486 0.006321
1st Floor 0.003232 0.004368
Ground Floor 0.000102 0.000964
Block 2
Page 23
Table 11: Modal Participation mass ratios
Block 2
7.2.2 Base reaction due to linear static and response spectrum method
Analysis was done by linear static and response spectrum method. Scale factor
for the analysis of response spectrum method for x and y direction for block 1 is
& that for block 2 is 2.953 and 3.195 respectively.
Table 12: Auto Seismic
Block 2
Page 24
0.3 1. 0.3 2524.076
EX X - Ecc. Y 5 II 0.606 0.121268 20814.0059
6 5 6 3
0.3 1. 0.3 2524.076
EY Y II 0.606 0.121268 20814.0059
6 5 6 3
Y + Ecc. 0.3 1. 0.3 2524.076
EY 5 II 0.606 0.121268 20814.0059
X 6 5 6 3
0.3 1. 0.3 2524.076
EY Y - Ecc. X 5 II 0.606 0.121268 20814.0059
6 5 6 3
Block 2
Block 2
TABLE: Story
Stiffness
Stiffness X Stiffness Y
Story
kN/m kN/m
5th Floor 140950.253 OK 107023.855 OK
4th Floor 143357.244 OK 114085.627 OK
3rd floor 144080.893 OK 115946.164 OK
2nd Floor 155519.685 OK 124896 OK
1st Floor 244696.209 OK 178092.583 OK
Ground Floor 12939519.45 - 1478736.31 -
Page 25
7.2.4 Torsion
The ratio of maximum and minimum joint displacement at two ends along x
and y direction is less than 1.5. (IS 1893:2016)
Block 2
Xmax 62.756 mm
Xmin 62.071 mm
Xmax/Xmin 1.011 < 1.5; OK
Ymax 82.860 mm
Ymin 79.781 mm
Ymax/Ymin 1.038 < 1.5; OK
Block 2
Page 26
7.2.6 Mass Irregularity
Ratio of storey mass of above and lower floor is maintained to be less than 1.5
as per IS 1893:2016.
Block 2
Seismic Weight
Check
Storey (kN)
kN Wi+1 <1.5Wi
5th Floor 471116.56 ok
4th Floor 441972.11 ok
3rd floor 435802.83 ok
2nd Floor 430019.12 ok
1st Floor 433738.51 ok
Ground Floor 380905.31 -
Block 2
Page 27
Stability index In Y direction
Lateral Storey
Axial Load Height
StoreyDrift,Δu
Storey Load,Pu Classification
Hu Hs
KN (mm) KN (mm)
5th Floor 9098.4862 9.763 1044.8751 3000 0.028337843 non-sway
4th Floor 13866.9633 16.083 1834.8134 3300 0.036833466 non-sway
3rd floor 15363.9822 18.624 2275.3434 3300 0.038107975 non-sway
2nd Floor 22138.001 14.626 2493.7679 3300 0.039345403 non-sway
1st Floor 27484.8901 12.068 2524.0763 3300 0.039821066 non-sway
Block 2
Page 28
7.2.9 Foundation Design:
Foundation was designed as a mat foundation based on 163 kN/m2 bearing
capacity for soil type II (N>50+). The soil subgrade reaction was taken as 20897
kN/m2/m (safety factor =3; settlement criteria=23.4mm). The modeling of
foundation has been done using SAFE version 16 and designed accordingly by
the software. The thickness was checked for punching shear to be less than 1
and soil pressure to be less than 163kN/m 2 for service load and designed with
the help of SAFE 16.
Page 29
Page 30
Figure 4: Punching Check (block 2)
Page 31
Chapter 8 : Summary
8.1 Summary
Design was carried out for the building for which structural system of frame and
steel truss was adopted as SMRF. The footings were checked for mat and
purposed for pile where necessary. Foundation design is carried out considering
soil bearing capacity of 163kN/m2. This building was designed on the basis of IS
1893 (part-1):2016.The proposed design satisfies the key requirement of the
building codes.
Page 32