Sie sind auf Seite 1von 4

OPERATING INSTRUCTIONS Annunciator - Programmable

Reset Action - Programmable; automatic or latched


! CAUTION:
1. The equipment shall not be installed in environmental
TERMINAL CONNECTIONS
mV/TC/RTD
PIC 1000N Standby Mode - Programmable; enable or disable
8. SENSOR SUPPLY
conditions other than those mentioned in this manual.
2. Fuse Protection: The equipment does not have a built-in-
+ - FOR
PT100
ANALOG
OUTPUT
24VDC supply to power the sensors type fuse. Installation of external fuse of rating 275VAC/ A B B’ + -
9. LINEAR DC OUTPUT (optional) 1Amp for electrical circuitry is highly recommended.
3. Thermal dissipation of equipment is met through ventilation 1 2 3 4 5 6 7 8 9 10
Re-transmission: 4 to 20 mA or 0 to 5 V or 0 to 10 V holes provided on chassis of equipment. Such ventilation
Update rate: 100msec holes shall not be obstructed else it can lead to a safety 22 24

RS485
-
mA+ V+ mA / V-
10. SERIAL COMMUNICATIONS (optional) hazard. sensor supply

+
Type - RS485 4. The output terminals shall be strictly loaded to the 21
-
23

+
Protocol - MODBUS manufacturer specified values/range.
Data Format - 8 bit for Modbus Mechanical Installation: 11 12 13 14 15 16 17 18 N L
48X96 Start bit - programmable; Stop bit: programmable For installing the controller NO1 NO2 NO3 NO4 COM GND +24V
SPECIFICATIONS Parity - programmable 1. Prepare the panel cutout with proper dimensions as shown - +
1. DISPLAY Node Address - 1 to 99, max of 32 units per line DIMENSIONS (in mm)
11. ENVIRONMENTAL CONDITIONS
TERMINAL DESCRIPTION TERMINAL
4-digit (7 segment LED) 0.5" height
Operating Range: 0 to 50oC Live & Neutral L&N
Display Messages: 50 45 46 Panel Cutout
“Or” - a) Appears when measurement exceeds Storage Range: -20 to 75oC +ve mA 2
display scaling range(9999) for signal inputs Humidity: 95% max. 97.5
12. ISOLATION BREAKDOWN RATINGS 88 92 +ve V 3
b) When open sensor is detected. 10
(Applicable for TC/RTD/-5 to 56mV) AC line with respect to all inputs and 2. Remove the clamp from the controller and push the +ve mV / TC+ / RTD 1 4
“rE” - a) Appears when measurement is below outputs: 2000 Volts controller into the panel cutout. Secure the controller in its
All other inputs and outputs with respect to -ve mV / TC- / RTD 2 / -ve mA / -ve V 5
display scaling range (-1999) for signal inputs. place by pushing the clamp on the rear side.
b) Sensor reverse condition occurs. Relay contacts: 2000 VAC 3. For proper sealing, tighten the screws evenly with required +ve analog output 8
(Applicable for TC/RTD/mV) 13. CONNECTION Wire clamping screw terminals torque. -ve analog output 9
Display alternating between PV and ALrM with LED 14. WEIGHT 300 grams ! CAUTION:
of respective alarm flashing. (Programmable The equipment in its installed state must not come in close NO for relay1 12
SAFETY SUMMARY proximity to any heating sources, caustic vapors, oils, steam, or
annunciator option) All safety related codifications; symbols and NO for relay2 13
other unwanted process by-products.
LED Status Annunciators - Alarm ON (4nos) instructions that appear in this operating manual or on the
2. POWER EMC Guidelines: NO for relay3 14
equipment must be strictly followed to ensure the safety of the
AC Versions- 85 to 270 VAC, 50 or 60 Hz, 5 VA 1. Use proper input power cables with shortest connections and NO for relay4 15
operating personnel as well as the instrument.
DC Versions (Optional) - 24 VDC If the equipment is not handled in a manner specified by twisted type. COM for relay1 16
3. SETTINGS the manufacturer it might impair the protection provided by the 2. Layout of connecting cables shall be away from any internal GND / -ve sensor supply
Via three keys on front panel. EMI source.
17
equipment. +24 V / +ve sensor supply 18
4. MEMORY ! CAUTION: Read complete instructions prior to installation LOAD CONNECTIONS
Nonvolatile EEPROM retains all programmable KEYS DESCRIPTION
and operation of the unit.
parameters and values. WARNING: Risk of electric shock. 1. For load current less than 0.5A selec PIC1000
5. MAIN SENSOR INPUT (Universal) ALM

Thermocouple inputs WIRING GUIDELINES L N


1
2
3

J : -200 to 750oC WARNING: 4

1. To prevent the risk of electric shock power supply to the TC


K : -200 to 1350oC TC
equipment must be kept OFF while doing the wiring
T : -200 to 400oC arrangement. LOAD
C NO Functions Key press
R : 0 to 1750oC 2. Wiring shall be done strictly according to the terminal layout
S : 0 to 1750oC with shortest connections. Confirm that all connections are R C To enter or exit program mode + together for 3 seconds
C : 0 to 2300oC correct. MOV or till Level is displayed.
3. Use lugged terminals to meet M3 screws. Snubber To change levels + / to increase or
E : -200 to 750oC 4. To eliminate electromagnetic interference use of short wire
B : +150 to 1820oC decrease the level number.
with adequate ratings and twists of the same in equal size 2. For bigger loads, use interposing relay / contactor
N : -200 to 1300oC shall be made. L N To view function on the same or key once to view the
L : -200 to 600oC 5. Cable used for connection to power source, must have a TC level and to display the
next/previous function.
U : -200 to 900oC 2
cross section of 1mm or greater. These wires shall have TC Contactor current option.
W : 0 to 2300oC insulation capacity made of at least 1.5KV. + to increase and
Platinel II: 0 to 1390oC
C NO To increase or decrease the
MAINTENANCE R C
value of a particular function.
+ to decrease the
RTD inputs (2 wire or 3 wire) 1. The equipment should be cleaned regularly to avoid value of particular function.
MOV
PT100: -100 to 850oC blockage of ventilating parts. Snubber
NOTE: The unit will autoexit program mode after 60 seconds of inactivity.
PT1000: -200 to 300oC 2. Clean the equipment with a clean soft cloth. Do not use C
LOAD
Signal inputs Isopropyl alcohol or any other cleaning agent. To enter or exit program mode:
mV (linear) : -5mV to 56mV
mV (linear) : 0mV to 100mV
INSTALLATION GUIDELINES 1) Snubber Part No.: APRC - 01. Press & together for 3 seconds
! CAUTION: 2) MOV Part No.: AP-MOV - 03.
Voltage : 0 - 10 VDC Note: For inductive loads, use of snubber and
Current : 0 - 20mA DC
1. This equipment, being built-in-type, normally becomes a part
of main control panel and in such case the terminals do not MOV, as shown above, is recommended. PROGRAMMING OF LEVELS
6. INDICATION ACCURACY remain accessible to the end user after installation and PROGRAMMING OF LEVEL 0
ELECTRICAL PRECAUTIONS DURING USE
Temperature:0.25% of Span ±1oC(20min. Warmup) internal wiring.
Signal input: 0.05 % ±1 digit 2. Conductors must not come in contact with the internal Electrical noise generated by switching of inductive loads can KEY PRESS DISPLAY DESCRIPTION
7. ALARM OUTPUTS circuitry of the equipment or else it may lead to a safety create momentary disruption, erratic display, latch up, data loss
hazard that may in turn endanger life or cause electrical or permanent damage to the instrument. To reduce noise: Press + Key
4 nos : Relay output: 5A @ 250VAC or 24VDC shock to the operator. a) Use of MOV across supply of temperature controller & snub Parameters in this level
Alarm modes - Alarm High, Alarm Low, Band, 3. Circuit breaker or mains switch must be installed between power Ber circuits across loads are recommended Press + Key
Fault output and Fault diagnosis source and supply terminals to facilitate power 'ON' or 'OFF' b) Use separate shielded wires for inputs. can be set.
Hysteresis Programmable function. However this switch or breaker must be installed in a Document name: Operating/0807/PIC1000N OP-169-V03 Page 1 of 4
convenient position normally accessible to the operator.
FUNCTIONS MENU KEY PRESS DISPLAY DESCRIPTION KEY PRESS DISPLAY DESCRIPTION
er te g g ng ms Press key to select Reverse scaling
nu
mb da ca
lin g
ca
lin g ali lim
it
lim
it ra Press key to select Resolution
e nit on e t up lin lin sc
Pr
og
Default setting:
am t yp .U luti tim tan lay e as ys ) sca y s h) t sca h) rse igh ow f t Default value: 1
og
r ut
m p s o r
te ns isp rat Bi la t ) la
sp (low npu (low isp (hig npu (hig ev e P.
H
P.
L . o se
Pr Inp Te Re Fil co D PV Di I D I R S. S. No Re NOTE: This parameter is not prompted if input is R, S type thermocouple. NOTE: This parameter is not prompted if TC/RTD input types are selected

Resolution Reverse scaling*


INPUT PARAMETERS ( to scroll through functions press / ) Display for 1sec Display for 1sec

Range: 1 / 0.1 for TC / RTD The display scaling point


er or
it it es
is iat settings can be reversed
mb lim lim ter nc
nu igh ys er de tus nu
r am h low h tim mo sta an Press + 1 / 0.1 / 0.01 / 0.001 for AIN Press + by selecting Reverse
og ar
m
ar
m
ar
m lay ar
m tch ld ar
m
ar
m
Pr Al Al Al De Al La Ho Al Al scaling as
Press key to select Filter time constant
*** Default value: 1sec Press key to select Set point high limit
ALARM MODULE ( ALARM 1) ( to scroll through functions press / ) Filter time Default value: 750oC
Display for 1sec
constant * Set point high limit
+

Display for 1sec


*** Press + / (SPHL)
Range: OFF, 1 to 99 sec
to change value
OR

ALARM MODULE ( ALARM 2) ( to scroll through functions press / )


Press + / Range :SPLL to max.
Press key to select Display update rate to change value range of sensor
Default value: 1.0 sec (for TC/RTD)SPLL to
***
+

DSCH (for AIN)


ALARM MODULE ( ALARM 3) ( to scroll through functions press / ) Display for 1sec Display update rate For AIN display as per decimal point selected.
TO CHANGE LEVELS PRESS

Press + / Press key to select Set point low limit


Range : 0.5 to 6.0 sec
*** to change value Default value: -200oC
ALARM MODULE ( ALARM 4) ( to scroll through functions press / ) Press key to select PV bias Set point low limit
te s s Default value: 0.0 Display
ra es
rity bit for 1sec
Ba
ud
Ad
dr
Pa St
op
PV bias * (SPLL)
Appearance of all shaded menus Display for 1sec Range :min. range of
dependent on selection of other parameters. Press + /
Press + /
Range : -200 to 200 to change value sensor to SPHL
*COMMUNICATION MODULE (To change function / ) Refer programming for futher details
r *- Applicable only for communication models. to change value (fixed 0.1oC for TC/RTD) (for TC/RTD)
t t ro
mi mi er For AIN display as per decimal point selected. DSCL to SPHL (for AIN)
al r li r li or g t% **-Applicable only for analog output models.
nu we pe ns evel alo tpu
Ma Lo Up Se l An ou ***-Looping depends on selection of other Press key to select Display value scaling point1 For AIN display as per decimal point selected.
parameters. Default value: 0 Press key to select No. of Programs
**ANALOG O/P MODULE (To change function / ) NOTE: This parameter is not prompted if TC/RTD input types are selected Default setting: 25
n
ca
tio rd Display value scaling Number of
tifi el
0
el
1
el
2
el
3
el
4
el
5
el
6
rd wo Display for 1sec point Display for 1sec
en ss low (DSCL) *
id
er de ck
lev
ck
lev
c kl
ev
ck
lev
ck
lev
ck
lev
c kl
ev ge wo
an ss w
pa Programs
Us co Lo Lo Lo Lo Lo Lo Lo Ch pa Ne Press + / Range : -1999 to DSCH Press + / Range :01 to 25
to change value For AIN display as per decimal point
to change value
selected.
LOCKOUT MODULE ( to scroll through functions press / )
Press key to select input value scaling point 1 Press key to select Reset
Default value: 0.00 Default setting:
NOTE: This parameter is not prompted if TC/RTD input types are selected Reset
KEY PRESS DISPLAY DESCRIPTION KEY PRESS DISPLAY DESCRIPTION Display for 1sec
Press key to select input sensor type o Input value scaling
Press + W (0 to 2300 C) Display for 1sec point low (ISCL) *
Default setting: J All parameters set to
o
Press + Platinel II: 0 to 1390 C Press + / Range : 0.0mA / -5mV / Press + factory setting
to change value
0.0 V to ISCH NOTE: After altering the value of the input parameters
Input sensor Press + PT100: -100 to 850oC (default value changes as per analog
Display for 1sec input selected)
press or for the change to actually take effect.
selection Press + PT1000: -200 to 300oC NOTE: Programming steps for Level 1 (Alarm 1 module)
J ( -200 to 750oC ) Press key to select Display value scaling point 2 Level 2 (Alarm 2 module), Level 3 (Alarm 3 module),
mV(linear): Default value: 9999 Level 4 (Alarm 4 module) is same.
Press +
Press + K (-200 to 1350oC) -5mV to 56mV NOTE: This parameter is not prompted if TC/RTD input types are selected Programming of level 1 is shown.
o mV(linear): Display value scaling
Press + T (-200 to 400 C) Press + Display for 1sec point
PROGRAMMING OF LEVEL 1
0.0mV to 100mV high (DSCH) *
Press + R (0 to 1750 C) o Press + till Level 1 is displayed
Press + / Range : DSCL to 9999
o
Press + 10VDC to change value For AIN display as per decimal point selected. KEY PRESS DISPLAY DESCRIPTION
Press + S (0 to 1750 C)
Press + 20mA DC Press key to select Input value scaling point 2 Parameters in this level
Press + C (0 to 2300oC) Default value: 20.0mA can be set.
Press key to select Temperature unit NOTE: This parameter is not prompted if TC/RTD input types are selected Press key to select Program number
Press + E (-200 to 750oC) Default setting: OC
Input value scaling Default setting: 1
NOTE: This parameter is not prompted if analog input is selected.
Press + B (+150 to 1820oC) Display for 1sec
point high (ISCH) * NOTE: This parameter is not prompted if alarm mode is /
/
N (-200 to 1300 C ) o Temperature Press + / Range: ISCL to 20.00mA
Press + Display for 1sec
Unit to change value Program number
o
/ 56mV / 10.00V Display for 1sec
Press + L (-200 to 600 C) Value displayed in OC (default value changes as per analog input selected)

Note: * mark explained in the user guide. Press + / Range: 01 to number


Press + U (-200 to 900oC) Press + Value displayed in OF to change value of Programs
AIN - Analog Input
Document name: Operating/0807/PIC1000N OP-169-V03 Page 2 of 4
PROGRAMMING OF LEVEL 1 KEY PRESS DISPLAY DESCRIPTION KEY PRESS DISPLAY DESCRIPTION PROGRAMMING OF LEVEL 7
KEY PRESS DISPLAY DESCRIPTION Press key to select Alarm hold status. Press key to select Stop bits. Press + till Level 7 is displayed
Press key to select Alarm high limit Default setting: Default value: 1
Default value: 750oC NOTE: This parameter is not prompted if alarm mode is Stop bits KEY PRESS DISPLAY DESCRIPTION
Display for 1sec
NOTE: This parameter is not prompted if alarm mode is / Hold Alarm* Parameters in this level
Display for 1sec Selectable between
/ / can be set.
Alarm high limit Used to avoid alarm at 1&2 Press key to select user Identification Code
Display for 1sec Press + (Stop bit 2 is not valid only if Parity
power ON. Alarm is is other than NONE)
Default setting: 0
Range: LA to SPHL Press + enabled only after the
Press + / (BAND mode) NOTE: Applicable only if Analog output is available. Display
User Identification
for 1sec
to change value process value has Code
SPLL to SPHL(HA mode) PROGRAMMING OF LEVEL 6
( display as per resolution selected.) reached the set point. Press + / Range: 0000 to 9999
KEY PRESS DISPLAY DESCRIPTION to change value
Press key to select Alarm low limit Press key to select Relay status for alarm1.
Default value: -200oC Default setting: Press + till Level 6 is displayed Press key to select Lock level 0
NOTE: This parameter is not prompted if alarm mode is
Default setting:
NOTE: This parameter is not prompted if alarm mode is /
/ / Parameters in this level
Relay status for Display for 1sec Lock level 0
Display for 1sec can be set.
Display for 1sec Alarm low limit Alarm1 full access to level 0 parameters
Relay Energized. Press key to select Manual Mode.
Range: SPHL to HA Default setting: Press + level 0 parameters can be read
Press + / (BAND mode) Relay De - energized
Press +
to change value
SPLL to SPHL (LA mode) Manual Mode Press + No access to level 0 parameters
Display for 1sec
For AIN display as per decimal point selected. Press key to select Alarm annunciator.
Press key to select Lock level 1
Default setting: Used to set manual Default setting:
Press key to select Alarm hysteresis.
NOTE: This parameter is not prompted if alarm mode is
Default value: 1.0 Press + output On / Off.
Display for 1sec Lock level 1
NOTE: This parameter is not prompted if alarm mode is / Display for 1sec Alarm annunciator*
/ Press key to select Analog low scaling point full access to level 1 parameters
No annunciator Default value: -1999
Display for 1sec Alarm hysteresis LED of alarm1 blinks at Press + level 1 parameters can be read
NOTE:This parameter is prompted only if manual =
Press + the rate of 0.2sec
Range: 0.1 to 99.9 oC Press + No access to level 1 parameters
Press + / LED blinking; display
(for TC/RTD) Press + Low scaling point
to change value flashing b/w PV and Display for 1sec Press key to select Lock level 2
1 to 999 (for analog input) message (ALRM) at 1sec Default setting:
For AIN display as per decimal point selected. Press + / Programmable from
Press key to select Delay timer PROGRAMMING OF LEVEL 5 to change value -1999 to 9999. Display for 1sec Lock level 2
Default value: 0.00 Press + till Level 5 is displayed Fixed 1oC resolution for TC / RTD. full access to level 2 parameters
For AIN display as per decimal point selected
NOTE: This parameter is not prompted if alarm mode is / KEY PRESS DISPLAY DESCRIPTION level 2 parameters can be read
/
Press +
Parameters in this level Press key to select Analog high scaling point
Press + No access to level 2 parameters
Display for 1sec Delay timer can be set. Default value: 9999
Press key to select Baudrate. NOTE:This parameter is prompted only if manual = Press key to select Lock level 3
Press + / Range: 0.0 to 99.59 Default value:9600 Default setting:
to change value min.sec Baud rate Display High scaling point
for 1sec Display Lock level 3
Display for 1sec for 1sec
Press key to select Alarm mode.
Press + /
Programmable for 300, Press + / Programmable from full access to level 3 parameters
Default setting: for level 1 & 3 600, 1200, 2400, 4800, to change value
Default setting: for level 2 & 4. to change value -1999 to 9999 level 3 parameters can be read
9600 bps. o
Fixed 1 C resolution for TC / RTD.
Press +
Display for 1sec Alarm mode * Press key to select Address. For AIN display as per decimal point selected
Press + No access to level 3 parameters
Default value:01
Alarm off Press key to select Sensor error level Press key to select Lock level 4
Address
Display for 1sec Default setting: Default setting:
Press + High Alarm
Press + / Range: 01 to 99 Display for 1sec Lock level 4
Press + Low Alarm to change value Display for 1sec Sensor error level
full access to level 4 parameters
Press + Band Alarm Press key to select Parity. Incase of sensor failure
Default setting: the output can be set to Press + level 4 parameters can be read
Press + Fault Diagnosis Alarm
Display
Parity Press + high or low value of Press + No access to level 4 parameters
Fail Output Alarm for 1sec
Press + range.
None Press key to select Lock level 5
Press key to select Alarm latch status. Default setting:
Default setting: Press key to select Analog output %.
Press + Even NOTE: This parameter is not prompted if Level 5 is not present.
NOTE: This parameter is not prompted if alarm mode is
Default setting:
Press + Odd NOTE: This parameter is prompted only if manual =. Display for 1sec Lock level 5
Display
Latch alarm*
for 1sec Press + Mark full access to level 5 parameters
Display for 1sec Analog output %
When latch is ON Alarm Press + Space level 5 parameters can be read
Programmable from Press +
status will be preserved Press + /
Press + at any process condition. Note: * mark explained in the user guide. to change value 0.0 to 100.0 Press + No access to level 5 parameters
Document name: Operating/0807/PIC1000N OP-169-V03 Page 3 of 4
KEY PRESS DISPLAY DESCRIPTION Alarm display options: KEY PRESS DISPLAY DESCRIPTION CALIBRATION CERTIFICATE
Press key to select Lock level 6 (1) Press the key to view the status of alarms (Selection for Date:
and then display
Default setting: (2) Press + to view the status of next alarm retransmission mode)
NOTE: This parameter is not prompted if Level 6 is not present. (after alarm 4 it rolls over to alarm 1). Press Model No:
Lock level 6 Only the alarms that are active can be viewed. Sr. No.:
Display for 1sec Alarm status ( e.g : of alarm 1) will be displayed as follows: Press + / Adjust the display to 0
full access to level 6 parameters LA-1 for low alarm for alarm1, Press
Claimed Accuracy: ± 0.25 % of full scale ± 1
HA-1 for high alarm for alarm 1, Press + / digit (After 20min warmup time)
Press + level 6 parameters can be read FO-1 for Fail output alarm for alarm 1, Adjust the display to 400
Press key
No access to level 6 parameters FD-1 for fault diagonosis for alarm1.
Press +
(3) Press + to acknowledge the particular alarm Eg. : 2) For analog Input :- Sources calibrated against:
Press key to select change password Hinditron Multimeter, Model 86, Sr.No.:1094
(Alarm will be acknowledged only if latch ON). Retransmission output : 4 - 20 mA
Default setting: Desired output : 4mA at 0V, 20mA at 10V Multimeter calibration report no:
SCALING FOR ANALOG INPUT: Input scaling : 0V - 0; 10V - 400 ERTL (W), Mumbai, INDIA
Display for 1sec Change password To scale the controller, two scaling points are necessary. Settings:
Each scaling point has a coordinate pair of Display Values The calibration of this unit has been verified at the
and Input Values. It is recommended that the two scaling Press + following values:
Press + points be at the low and high ends of the input signal being Press + CALIBRATION DISPLAY
Press key to select new password measured. Process value scaling will be linear between and SENSOR TEMP.(OC) VALUE
Press
Default value: 0 continue past the entered points to the limits of the input ( 0.1 Resolution) (OC)
This parameter is prompted only if - range. (Factory settings example will display 0.0 at 0 mA Select the Input type as
Using + / voltage
input and display 9999 at 20.00 mA input.)
35.0 35.0
Display for 1secNew password
Reverse acting indication can be accomplished by setting Press until Is displayed K 700.0 700.0
Press + / Range : 0000 to 9999
to change value reverse scaling parameter as DISPLAY
Using + / Adjust the display to 0 1350 1350
YES. In this case referring the 0.0 0.0
Press
USER GUIDE : above eg. for 0.00 mA input 9999
PT100 500.0 500.0
the display will show 9999 and Press + / Adjust the display to 0 800.0 800.0
ALARM MODES
High Alarm: 20.00 mA input the display will 0.0
0.0 0.0
Press
The alarm is turned ON when PV rises above a preset value. show 0.0. 0.00mA 20.00mA
INPUT

NOTE : This change will not be Press + / Adjust the display to 400 PT1000 100.0 100.0
Low Alarm: ISC.L = 0.00 ISC.H = 20.00
visible in the programming menu. DSC.L = 0.0 DSC.H = 9999 250.0 250.0
The alarm is turned ON when PV falls below a preset value. RSCL = no Press
Band Alarm:
Press + / Adjust the display to 10 CALIBRATION DISPLAY
The alarm is turned ON when PV rises above or falls below a KEY PRESS DISPLAY DESCRIPTION INPUT VALUE VALUE
preset value. Note : By default the display will be 10.00 for 0-10V Input ( 0.1 Resolution)
Fault Diagnosis Alarm: Setting for Manual output mode :- Press Key
Eg. For 4-20 mA if constant 12mA output current is desired then Voltage 0.0 0.0
The alarm is turned ON in case a hardware failure occurs. Setting for Retransmission :
Fail Output Alarm: Setting for manual output : (VDC)
Press + till 10.0 10.0
The alarm is turned ON in case of : Press +
a) measurement value exceeds range Press key displays momentarily
Press key display momentarily Current 0.0 0.0
B) Sensor reverse condition(applicable for TC/RTD/0- 56mV). and then display (mA)
Latch Alarm: Press + / (Selection for 20.0 20.0
manual output mode) Press
This function is used to latch the alarm. When activated, the
Press 0.0 0.0
alarm is latched until it is acknowledged manually, even Press + / Adjust the display to 0
though the alarm condition may have disappeared. Press + / Adjust display to 50.0% to 0-100mV
get 12mA at output Press 100.0 100.0
FILTER TIME CONSTANT: Press key
Press + / Adjust the display to 400
The filter is an adaptive digital filter that discriminates Setting for Retransmission mode The actual results versus the input given falls
Press key within specified accuracy of 0.25% & hence the
between measurement noise and actual process changes. Eg. :1) For Temperature Input :-
If the signal is varying too greatly due to measurement noise, unit is certified & passed.
Input : RTD Input Connection with 2-wire Transmitter
increase the filter value. If the fastest controller response is Connection with Internal 24VDC supply :
needed, decrease the filter value.
Retransmission output : 4 - 20 mA
Desired output : 4mA at 00C Eg: To give 0-20mA DC analog input CHECKED BY:
20mA at 4000C -
Two-wire
BIAS: Settings : Transmitter
This value offsets the controller's PV display value by the +
Press +
entered amount. This is useful in applications in which the + -
sensor cannot provide the actual temperature signal due to Press + (Specifications subject to change as development
1 2 3 4 5 6 7 8 9 10
mounting constraints, inaccuracy etc. Press key is a continuous process).
22 24

RS485
-
Using + / Select the Input type as RTD
mA+ V+ mA / V-
Selec Controls Pvt. Ltd., India,
ALARM ANNUNCIATOR: GND +24V

+
21 23
When alarm annunciator is ON, during alarm condition, visual - +
annunciation is given by the upper display altering between AL-NO Press till is displayed Tel:91-22-28476443/1882, Fax:91-22-28471733,
11 12 13 14 15 16 17 18 N L
and process temperature where NO is the alarm number. The Press + till is display Toll free: 1800 227 353, Website: www.selec.com
annunciator may be disabled by selecting function ANN as OFF. NO1 NO2 NO3 NO4 COM
- + E- mail: sales@selec.com.
Press key display momentarily Document name: Operating/0807/PIC1000N OP-169-V03 Page 4 of 4

Das könnte Ihnen auch gefallen