Pulse (Rate) Meter

▣Features
l13 kinds of various operation modes (A)
Counter
: Revolution/Speed/Frequency, Absolute rate,
Passing time, Error rate, Cycle, Density, Passing speed,
Error ratio, Time width, Time interval, Interval, Integration,
Length measurement(Except MP5M having 11 models) (B)
lVarious output function Timer

: Relay output, NPN/PNP open collector output,


Low speed Serial output, BCD output, 4-20mA output,
RS485 communication output (C)
Temp.
lVarious functions
controlle
: Prescale function, Data monitoring function,
Hysterisis width setting function, Max./Min. value
mornitoring function, Delay function, Auto zero time
(D)
setting function, Lock setting function Power
controlle
lMax. display range : -19 999 to 99999 (MP5M:0~99999)
lVarious display units : rpm, rps, Hz, kHz, sec, min, m, mm, mm/s, m/s,
m/min, m/h, ℓ/s, ℓ/min, ℓ/h, %, counts, etc.
(E)
lSelectable voltage input(PNP) or No voltage input(NPN)
Panel
l50kHz High speed response function meter

Please read "Caution for your safety" in


! op eration manu albefore usin g. (F)
Tacho/
▣Ordering information Speed/
Pulse
meter
MP 5 S 4 N
Main output(Comparative value output) Sub output(Display value output) (G)
S Type Display
N Indication type X unit

N Indication type X
1 NPN open collector five-stage output X
(H)
Y Type 2 PNP open collector five-stage output X Sensor
controlle
3 X BCD Dynamic
4 X PV transmission(4-20mADC)
5 X RS485 communication output
(I)
Proximit
N Indication type X sensor
Output A Relay five-stage(HH, H, GO, L, LL) X
1 Relay three-stage(H, GO, L) X
(J)
2 NPN open collector five-stage output BCD Dynamic
Photo
3 PNP open collector five-stage output BCD Dynamic electri c
W Type sensor
4 NPN open collector five-stage output PV transmission(4-20mADC)
5 PNP open collector five-stage output PV transmission(4-20mADC)
6 NPN open collector five-stage output Low speed serial output (K)
Pressur
7 PNP open collector five-stage output Low speed serial output sensor
8 NPN open collector five-stage output RS485 communication output
9 PNP open collector five-stage output RS485 communication output
(L)
N Indication type X Rotary
Relay single(High-limit)output encoder
M Type 1 X
+ NPN open collector output
Relay double(High/Low-limit) output (M)
2 + NPN open collector output X 5-Phase
stepping
Power supply motor &
4 100-240VAC 50/60Hz Driver &
Controlle
S DIN Size W48×H48mm
Size Y DIN Size W72×H36mm
W DIN Size W96×H48mm
M DIN Size W72×H72mm
Digit
5 5digit(99999)
Series
MP Pulse meter
※PNP open collector output : Option

F-4
MP5S/MP5Y/MP5W/MP5M Series
▣Specifications (MP5S/ MP5Y/ MP5W Series)
Series MP5S MP5Y MP5W
Display method 7 Segment LED(Zero blanking)
Character size W4 × H8mm W6.8 × H13.8mm
Max. indication 5digits(-19999 ~ 99999)
Power supply 100-240VAC 50/60Hz
Allowable operation
Allowable operation voltage: 90 ~ 110%
voltage
Power consumption Approx. Min. 7.5VA(240VAC) Approx. Min. 3.5VA(240VAC) Approx. Min. 6VA
Power for external sensor 12VDC ±10%, 80mA
U Non-contact input : Max. 50kHz(Pulse width:Each over 10㎲)
Input frequency U Contact input : Max. 45Hz( Pulse width:Over 11ms)
[Voltage input] High : 4.5-24VDC, Low : 0-1.0VDC, Input impedance : 4.5kΩ
Input level [No-voltage input] Impedance at short-circuit : Max. 200Ω, Residual voltage : Max. 1V
Impedance at open-circuit : Min. 100kΩ
U Mode F1, F4, F7, F8, F9, F10 : 0.0005Hz ~ 50kHz U Mode F3 : 0.02s ~ 3,200s
Measuring range
U Mode F2, F5, F6 : 0.01s ~ 3,200s U Mode F11, F12, F13 : 0 to 4 ×10 9 Count
Measuring accuracy U Mode F1, F4, F7, F8, F9, F10 : F.S. ±0.05% rdg ±1Digit
(23 ±5℃) U Mode F2, F3, F5, F6 : F.S. ±0.01% rdg ±1Digit
Display accuracy 0.05 / 0.5 / 1 / 2 / 4 / 8sec.(The same as update output cycle)
Number of revolution/Speed/Frequency(F1), Passing time(F2), Cycle(F3), Passing speed(F4),
Time width(F5), Time interval(F6), Absolute rate(F7), Error ratio(F8), Density(F9), Error rate(F10),
Operation mode
Length measurement(F11), Interval(F12), Integration(F13)
※Please see the operating mode(F-18~21 page).
Prescale function Direct input method(0.0001×10-9 to 9.9999×10 9 )
Hysterisis (Note1) 0 to 9999
U Lock setting function
U Monitoring delay function
U Lock setting function U Auto-Zero time setting function
U Auto-Zero time setting function U Current output range selection(Current output type only)
U Time unit selection function U Comparative output function(HH, H, GO, L, LL)
Other function U Monitoring function : U Time unit selection function
Memorize max. value U Deviation memory function(F output mode applied only)
U Memory retention function U Monitoring function : Memorize max. value or min. value
(Mode F13 applied only) U Remote/Local switching function(Communication output type only)
U Data Bank switching function (Note2)
U Memory retention function(Mode F13 applied only)
Relay three-stage 250VAC 3A resistive load 3a
Relay five-stage 250VAC 3A resistive load 5a
NPN Open collector
five-stage
12-24VDC 30mA Max. 12-24VDC 20mA Max.
PNP Open collector
five-stage
NPN Open collector
BCD Dynamic NPN Open collector
12-24VDC 20mA Max.
12-24VDC 20mA Max.
Low speed serial output
PV transmission 4-20mADC Load 600Ω Max. 4-20mADC Load 600Ω Max.
RS485 communication 32 chennel, Mutual direction comunication function
Memory Non-volatile memory(Input times : Min. 100,000 times)
Insulation resistance Min. 100MΩ(at 500VDC) Between charge part and non-charge part
2000VAC 60Hz 1minute
Dielectric stength
(Between terminals of AC power and case, Between terminals of AC power and measuring terminals)
Impulse noise stength ±2000VAC the square wave noise(pulse width:1㎲)by the noise simulator, Repeat frequency 60Hz
Mechanical 0.75mm amplitude at frequency of 10 ~55Hz in each of X, Y, Z directions for 2 hour
Vibration
Malfunction 0.5mm amplitude at frequency of 10 ~ 55Hz in each of X, Y, Z directions for 10 minutes
Mechanical 300m/s²(30G) in X, Y, Z directions for 3 times
Shock
Malfunction 100m/s²(10G) in X, Y, Z directions for 3 times
Relay Malfunction Min. 10,000,000 times
life cycleMechanical Min. 100,000 times(250VAC 3A Load current)
Ambient temperature -10 ~ +50℃(at non-freezing status)
Storage temperature -20 ~ +60℃(at non-freezing status)
Ambient humidity 35 ~ 85%RH
Weight Approx. 130g Approx. 135g Approx. 230g
※(Note1) The hysteresis setting range is different by the place of decimal point set.
※(Note2) Data Bank switching function MP5W series only.

F-5
Pulse (Rate) Meter
▣Specifications (MP5M Series)
(A)
MP5M MP5M-41 MP5M-42
Model Counter
Indication type High-limit setting type High/Low-limit setting type
Display method 7 Segment LED(Zero Blanking), Letter size : W4 X H8mm
Max. indication 5digits(0.0001 ~ 99999)
Power supply 100-240VAC 50/60Hz (B)
Timer
Allowable operation
Allowable operation voltage: 90 ~ 110%
voltage
Power consumption Approx. 7.5VA(240VAC) Approx. 8VA(240VAC)
Power for external (C)
12VDC ±10%, 80mA Temp.
sensor
controlle
U Non-contact input : Max. 50kHz(pulse width:over 10㎲)
Input frequency U Contact input : Max. 45Hz(pulse width:over 11ms)
[Voltage input] High : 4.5-24VDC, Low : 0-1.0VDC, Input impedance : 4.5kΩ
Input level [No-voltage input] Impedance at short-circuit : Max. 300Ω, Residual voltage : Max. 1V (D)
Impedance at open-circuit : Min. 100kΩ Power
controlle
U Mode F1, F4, F7, F8 : 0.0005Hz ~ 50kHz U Mode F3 : 0.02s ~ 3,200s
Measuring range
U Mode F2, F5, F6 : 0.01s ~ 3,200s U Mode F9, F10, F11 : 0 ~ 4 ×10 9 Count
Measuring accuracy U Mode F1, F4, F7, F8 : F.S. ±0.05% rdg ±1Digit
(E)
(23 ±5℃) U Mode F2, F3, F5, F6 : F.S. ±0.01% rdg ±1Digit Panel
Display accuracy 0.05 / 0.5 / 1 / 2 / 4 / 8sec.(The same as update output cycle) meter

Number of revolution/Speed/Frequency(F1), Passing time(F2), Cycle(F3), Passing speed(F4),


Operation mode Time width(F5), Time interval(F6), Absolute rate(F7), Density(F8), Length measurement(F9),
(F)
Interval(F10), Integration(F11) ※Please see the operating mode(F-18~21page). Tacho/
Prescale function Direct input method(0.0001×10 ~ 9.9999×10 ) -9 9 Speed/
Pulse
Hysterisis (Note1) 0 ~ 9999 meter
U Lock setting function
U Monitoring delay function
U Lock setting function U Auto-Zero time setting function (G)
U Lock setting function U Monitoring delay function U Time unit selection function Display
U Auto-Zero time setting function U Auto-Zero time setting function U Displa y value monitoring function unit
U Time unit selection function U Time unit selection function U Memory retention function
Other function U Display value monitoring function U Display value monitoring function (Mode F11 applied only)
U Memory retention function U Memory retention function U Comparative output function(H, L)
(Mode F11 applied only) U Output mode selection fuction (H)
(Mode F11 applied only) Sensor
(S, H, L , B, I, F)
U High-limit output function(H) controlle
U Deviation m emory function
(F output m ode applied only)
Relay output 250VAC 3A resistive load 1a 1b 250VAC 3A resistive load 1a×2
Main (I)
output NPN Open 30VDC 100mA Max. 30VDC 100mA Max. ×2 Proximit
Collector sensor
Memory retention Non-volatile memory(Input times : Min. 100,000 times)
Weight Approx. 275g Approx. 310g Approx. 330g
※Function part is same as MP5S, MP5Y, MP5W series. (J)
Photo
※(Note1) The hysteresis setting range is different by the place of decimal point set.(See F-24 Page, hysteresis function.) electri c
sensor
▣Connections
◎MP5M Series
(K)
lMP5M-4N(Indication type) lMP5M-41(High-limit setting type) lMP5M-42(High/Low-limit setting type) Pressur
sensor

(L)
Black Black Brown Blue
HOLD/ Black Black Brown Blue
HOLD/ Black Black Brown Blue HOLD/ Rotary
I NA INB + 12V 0V RESET IN A INB + 12V 0V R ESET High I NA IN B + 12V 0V R ESET High Low encoder

8 9 10 11 12 13 14 8 9 10 11 12 13 14 8 9 10 11 12 13 14
(M)
5-Phase
stepping
motor &
15 17 15 17 15 17 Driver &
Controlle

16 18 16 18 16 18
H H L

1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7
CONTACT OUT: CONTACT OUT:
250VAC 3A 250VAC 3A !
! !
S OURCE RESISTIVE LOAD SOURCE RE SISTIVE LOAD SOURCE
100-240VAC 100-240VAC 100-240VAC

F-6
MP5S/MP5Y/MP5W/MP5M Series
▣Connections
◎MP5S Series
lMP5S-4N(Indication type)

Black Black Brown Blue HOLD/


INA INB +12V 0V RESET

6 7 8 9 10

11 12

1 2 3 4 5

~
! SOURCE
100-240VAC

◎MP5Y Series
lMP5Y-4N(Indication type) lMAIN Output / SUB Output

2 4 6 8 10

Black Black Blue Brown

1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 3 5 7 9
INA INB 0V +12V ※Hirose Connector:
~ HIF3BD-10PA -2.54DS
HOLD/RESET SOURCE
100-240VAC
(★ 1) 50/60Hz
※ (★ 1)It is used for RESET terminal when an operation mode is F13.
(S ee the "Operating mode" F-21 page)

◈Main output(Connector) ◈Sub output(Connector)


lMP5Y-41(NPN Open Collector output) lMP5Y-43(BCD Dynamic output)
MAIN OUT BCD OUT
(NPN OPEN COLLE CTOR) (NPN OPEN COLLECTOR)
12-24VDC Max. 30mA 12-24VDC Max. 30mA
A C D0 D2 D4
2 4 6 8 10 2 4 6 8 10

HH GO LL

H L
COM 1
1 3 5 7 9 1 3 5 7 9
COM B D D1 D3
lMP5Y-42(PNP Open Collector output) lMP5Y-44(PV transmission output)
MAIN OUT +
(P NP OPE N COLLECTOR) 2 4 6 8 +
10
12-24VDC Max. 30mA
2 4 6 8 10
4-20mADC
Load 600Ω Max.
HH GO LL

-
1 3 5 7 9
H L
COM
lMP5Y-45(RS485 communication output)
1 3 5 7 9
B(-)
※Main output type & sub output type : option 2 4 6 8 10

RS485

A(+)
1 3 5 7 9

F-7
Pulse (Rate) Meter
◎MP5W Series
lMP5W-4N(Indication type) lMP5W-4A(RELAY Five-stage output)
(A)
Counter

CONTACT OUT:
10 11 12 13 14 15 250VA C 3A 1a
HH H GO L LL COM RE SIS TIVE LOAD
(B)
Black Black Blue Brown Timer

1 2 3 4 5 6 7 8 9

(C)
lMP5W-41(Three-stage output) Temp.
controlle
1 2 3 4 5 6 7 8 9 CONTACT OUT:
10 11 12 13 14 15 250VA C 3A 1a
INA INB 0V (★1) 0V +12V RE SIS TIVE LOAD
~
HO LD/RES ET 80mA ! SOURCE (D)
H GO L
100-240VAC Power
controlle
BANK (★2) 50/60Hz 6VA 1 2 3 4 5 6 7 8 9

※(★ 1)It is used for RE SET terminal when an operation mode is F13. (S ee the "Operating mode" F-21 page)
※(★ 2)Please see F-24 page for BA NK function. (E)
※M ain output type & sub output type : opt ion Panel
meter

◈Main output+Sub output(Connector)


2 4 6 8 10 12 14 16 18 20 (F)
Tacho/
Speed/
Pulse
meter
1 2 3 4 5 6 7 8 9
1 3 5 7 9 11 13 15 17 19
※Hirose Connetor:HIF3BA-20PA-2.54DS (G)
Display
lMP5W-42/ MP5W-43(NPN/PNP Open Collector output + BCD output) unit

2 4 6 8 10 12 14 16 18 20 2 4 6
+24VDC B D D1 D3 DOT COM2
HH GO LL 30mA Max. HH GO LL
MAIN OUT BCD OUT MAIN OUT (H)
(NPN OPEN COLLECTOR (NPN OPEN COLLECTOR) (PNP OPEN COLLECTOR Sensor
:12-24VDC Max. 20mA) 12-24VD C Max. 20mA :12-24VDC Max. 20mA) controlle
H L COM 1
COM 0V A C D0 D2 D4 ※POL H L

1 3 5 7 9 11 13 15 17 19 1 3 5

(I)
※P OL signal is on when it is - dis play value
Proximit
sensor
lMP5W-44/ MP5W-45(NPN/PNP Open Collector output + PV transmission output(4-20mADC) output)

2 4 6 8 10 12 14 16 18 20 2 4 6
(J)
HH GO LL
+24V DC + HH GO LL Photo
30mA Max.
MAIN OUT MAIN OUT electri c
4-20 mADC
(NPN OPEN COLLECTOR (PNP OPEN COLLECTOR sensor
Lo ad 600Ω Max.
:12-24VDC Max. 20mA) :12-24VDC Max. 20mA)
H L COM L
H
COM 1 0V -
1 3 5 7 9 11 13 15 17 19 1 3 5
(K)
Pressur
sensor
lMP5W-46/ MP5W-47(NPN/PNP Open Collector output + Low speed serial output)

2 4 6 8 10 12 14 16 18 20 2 4 6
+24V DC ※POL CLOCK LATCH (L)
HH GO LL 30mA Max. HH GO LL
MAIN OUT SERI AL OUT MAIN OUT Rotary
(NPN OPEN COLLECTOR) (PNP OPEN COLLECTOR encoder
(NPN OPEN COLLECTOR
:12-24VDC Max. 20mA) 12-24VD C Max. 20mA :12-24VDC Max. 20mA)
H L COM1 H L
COM1 0V COM2 DATA
(M)
1 3 5 7 9 11 13 15 17 19 1 3 5 5-Phase
stepping
※ POL signal is on when it is - display value motor &
Driver &
Controlle
lMP5W-48/ MP5W-49(NPN/PNP Open Collector output + RS485 communication output)

2 4 6 8 10 12 14 16 18 20 2 4 6
+24VDC B(-)
HH GO LL 30mA Max. HH GO LL
MAIN OUT MAIN OUT
(NPN OPEN COLLECTOR RS 485 (PNP OPEN COLLECTOR
:12-24VDC Max. 20mA) :12-24VDC Max. 20mA)
H L COM
COM 0V A(+) H L
1 3 5 7 9 11 13 15 17 19 1 3 5

F-8
MP5S/MP5Y/MP5W/MP5M Series
▣Dimensions
lMP5S Series
lPanel cut-out
100 Min.55
48
10 78 12
+0.6
45 -0
PUL SE M ETER

M in.62
45 +0.6
-0

MD

Unit:mm

lMP5Y Series
lPanel cut-out
85 108
※ There is no M in.91
72 6 89.5 14 terminal block in
indication type.

PU LSE METER 33 +0.6


-0

Min.40
68 +0.7
-0

MD
MP 5Y

※Hirose Connetor :HIF3BD-10PA-2.54DS Unit:mm

lMP5W Series
[Terminal type]
109 106

96 10.5 Sub Terminal


4 91.5
lPanel cut-out

Min.116
PULS E METER

45+0.6
-0

P
Min.52
92 +0.8
-0

※There is no t erminal block in Main Terminal


Indication type.

Unit:mm
[Connector type]
110.4
※Hirose connetor
6 91.5 14.9
HIF3BA-20PA-2.54DS

lMP5M Series
86 lPanel cut-out
126
72 Min.91
13 102 11

+0.7
68 -0

_ _ _ _ _ MD
Min.91 +0.7
HIG H 7 7 7 7 7 68-0
r r r r r

_ _ _ _ _

LOW 7 7 7 7 7
r r r r r

M P5M
Unit:mm

F-9
Pulse (Rate) Meter
▣Input specifications
◎Input signal (A)
Counter
lNon-contact input
Min. 10㎲
U Input frequency: 50kHz Max.
Standard duty rate of input signal is 1:1, ON/OFF ON
pulse width should be over 10㎲.
OFF (B)
U Input voltage Level : ON voltage → 4.5-24V, OFF voltage → 0-1.0V Timer
ON OFF *T : 1cycle of input signal

lRelay contact input T


U Input frequency : 45Hz Max.
(C)
ON/OFF pulse width should be over 11ms. Temp.
U Relay contact specification : Please use a relay contact that can carry controlle
the load current(min. 12VDC 2mA).
◎Input type
MP5W has NPN input and PNP input and you are able to select in Parameter 1 group. (D)
Power
1)When it is NPN input type controlle

①Contact ②NPN voltage ③NPN OU C output


output type sensor type sensor MP5W
+12V (E)
Panel
4.5kΩ meter
IN

(F)
0V(COM) Tacho/
Speed/
Pulse
meter
2)When it is PNP input type
①Contact ②PNP voltage ③PNP OU C output
output type sensor type sensor MP5W (G)
+12V Display
unit

IN

(H)
4.5kΩ Sensor
0V(COM) controlle

※OU C is Open collector output.


(I)
Proximit
▣Output specification(MP5Y/ MP5W Series) sensor

◎BCD Dynamic output Ex)When BCD Dynamic output is 125.89


lOutput : Display value (J)
10 4 Digit 10 0 Digit
lOutput signal Photo
BCD Data(A, B, C, D, DOT) ← A : Lowest bit PV Display 1 2 5. 8 9 electric
sensor
Dot : Highest bit
Digit Data(D0, D1, D2, D3, D4) ← D0 : Lowest digit A H L H L H L H
D4 : Highest digit (K)
Pressur
※There is no Dot data output in MP5Y-43, B H H L H H H H
sensor
therefore decimal point should be mark in
first display plate. BCD C H H H L H H H
Data
lOutput type : NPN Open collector (L)
lRated load voltage : 12-24VDC D H H H H L L H Rotary
encoder
lMax. load current : 30mA(MP5Y)/20mA(MP5W)
DOT H H H L H H H
(M)
5-Phase
H H
stepping
D0 motor &
H 0.1ms Dr iver &
Controlle
D1
H
Digit D2
H
D3
H
D4
5ms 7.8ms

39ms

F-10
MP5S/MP5Y/MP5W/MP5M Series
◎Low speed serial output
lOutput : Display value
lOutput signal : CLK, Data, Latch
lCLK cycle : 50Hz
lOutput CLK bit : 25 bit
lOutput Data bit : 25 bit
lOutput form: NPN Open Collector
lRated load voltag : 12-24VDC
lMax. load current : 30mA(MP5Y)/20mA(MP5W)

lSerial transmission time diagram


C1 C2 C3 C23 C24 C25 C1 C2 C3 C4
CLK

20ms

Data D1 D2 D3 D23 D24 D25 D1 D2 D3 D4


20㎲
5ms

Latch

lData output sequence when it is serial transmission


Start

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
CLK
ordering Shift

Decimal Data Decimal Data Decimal Data Decimal Data Decimal Data
point(5digit ) (5digit) point (4digit) (4digit) point(3digit) (3digit) point(2digit) (2digit) point(1digit) (1digit)

10 4 Digit 10 3 Digit 10 2 Digit 10 1 Digit 10 0 Digit

◎PV transmission output(4-20mADC)


lApplication : Transmit the measured value
lFunction : This function is to transmit 4-2mADC
Display
converted from measured display value value
between High limit output(FS-H) and
FS-H
Low limit(FS-L).
lRange of High/Low limit output setting If set FS-L and FS-H in certain FS-L
U High limit setting range(FS-H) section, the output will be
: From min. to max within range of measurment 4-20mADC. ▶
U Low limit setting range(FS-L)
: From min. to max within range of measurment When the resolution is 8,000 division 20mA
lResistive load : Max. 600Ω from FS-L to FS-H, the resolution
lResolution : 8000 division will be lower when the display value 4mA
is narrower than 8,000 division. ▶

◎RS485 communication output


lAddress : 0 ~ 99 address(32 channels)
lTransmission speed(Baud rate) : 2400/4800/9600 bps
lTransmission code : ASCII
lParity Bit : No
lData Bit : 8 Bit
lStop Bit : 1 Bit
lCommunication items
U MP5W ← PC : Comparative value of each bank data, Prescale value and Peak value, RESET control
U MP5W → PC : Comparative value of each bank data, Prescale value and Peak value, Display value
※See page F-25 for communication data.

F-11
Pulse (Rate) Meter
▣Operation mode by each Parameter group chart
lParameter display are different according to each operation mode, see "▣Parameter" site. (A)
Counter
l" " : When select the operation mode, the parameter will be displayed.
"X" : When select the operation mode, the parameter will not be displayed.
l"◎" : It is only able to set or for sensor made in F11, F12, F13 of operation mode.
Parameter display F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 (B)
F1
Timer

(C)
Temp.
Parameter
controlle
0 grou p

X
(D)
X Power
controlle

(E)
Panel
X X X X ◎ ◎ ◎ meter

X
Parameter X (F)
X X X X X X X Tacho/
1 grou p
Speed/
X Pulse
meter
X
X X X X X X X
(G)
X X X X X X Display
X X X
unit
X X X X X X X X X X X X

(H)
Sensor
X X X X controlle
X X X X X X X X X

(I)
Proximit
sensor

Parameter
2 g roup
(J)
Photo
X X X electri c
sensor
X X X
X X X X X X X X X
(K)
X X X X X X X X X Pressur
sensor
X X X X X X X X

When it is PV retransmission output, it operates in all mode. (L)


Rotary
encoder

Parameter
3 grou p (M)
When it is RS485 communication output, it operates in all modes. 5-Phase
stepping
motor &
Driver &
Controlle

▣ Operation mode by each Series


Operation mode Number of
r evolution/ Passing Passing Time Time Absolute Err or Length
Cycle Density Error Int erval Integration
S peed/ speed time width interval rate ratio measurement
Series name Frequency
MP5S/MP5Y/MP5W F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13
MP5M F1 F2 F3 F4 F5 F6 F7 X F8 X F9 F10 F11

F-12
MP5S/MP5Y/MP5W/MP5M Series
▣Model by each Parameter group chart
lThe parameter has different modes according to each model, therefore see parameter group chart and
operation chart for each mode.
l : When select the operation mode, the parameter will be displayed.
X : When select the operation mode, the parameter will not be displayed.

Model name MP5S-4N


MP5Y-4N MP5Y-41 MP 5W-4A
MP 5W-44 MP5W-46 MP 5W-48
MP5W-4N MP5Y-42 MP5Y-43 MP5Y-44 MP 5Y- 45 MP 5W- 41 MP 5W-42 MP 5W-45 MP5W-47 MP 5W-49 MP 5M- 41 MP5M-42
Parameter MP5M-4N MP 5W-43

※ : Data bank( )setting is available in only MP5W-4N.

▣Monitoring delay operation function chart by each output mode

Comparative output
X X X
adjustment function
Starting correction timer function

F-13
Pulse (Rate) Meter
▣Parameter
(A)
lParameter 0 group Counter

Run
(B)
MD Key Touch If prssing MD key in RUN mode, it will enter into Parameter into Parameter 0 group. Timer

Set HH comparativevalue.
See the "setting range of comparative value by operating mode" for a setting range.
( ◀ : Move the setting digit , : Change the setting value) (C)
Temp.
MD MD
controlle

lSetting range of comparative value


Set H comparativevalue. by operating mode (D)
Power
( ◀ : Move the setting digit
Operating mode controlle
, : Change the setting value) Setting range
MD MD
F1, F2, F7, F9,
0 ~ 99999
(★1) F11, F12, F13
(E)
Set L comparativevalue. 0 ~ Setting Panel
F3, F4, F5, F6 meter
( ◀ : Move the setting digit time range
, : Change the setting value)
MD MD F8, F10 -19999 ~ 99999 (F)
Tacho/
※The setting range differs by Speed/
setting position of decimal point. Pulse
Set LL comparativevalue. meter

( ◀ : Move the setting digit


MD MD
, : Change the setting value) (G)
Display
unit

Display High Peak value among measuring values.


If press ◀ Key for 2 sec, The Peak value will be reset and (H)
it displays a current measuring value Sensor
MD MD controlle

Display Low Peak value among measuring values. (I)


Proximit
If press ◀ Key for 2 sec, The Peak value will be reset and sensor

MD MD
it displays a current measuring value

(J)
Photo
electri c
※If pressing MD key in RUN mode, it will enter into Parameter 0 group. sensor
※When entering into Parameter 0 group, parameter and set dara value flash as 1 sec. cycle.
※(★1)U The parameter shown in dotted line is displayed only for comparative value setting type.
(K)
U If selecting F mode among output modes, it is to set H and L deviation only, therefore [ ]and [ ] Pressur
parameter will not appear. sensor

※After changing set data value in each parameter, data will be saved by pessing MD key for 2sec and return to RUN
mode, but if you do not touch any key for 60sec while change data, if will return to RUN mode whit previous set value.
(L)
If no comparing value setting function type, [ ] Parameter will appear when entering parameter 0 group. Rotary
encoder

(M)
5-Phase
stepping
motor &
Driver &
Controlle

F-14
MP5S/MP5Y/MP5W/MP5M Series
lParameter 1 group

Run
MD key Press for 3sec
This is parameter 1 group.
Display for 2 sec and move to .
MD

Select operation mode.


~

MD MD ( , : Change the operation mode)

Set the sensor type of input A.


lInput sensor
NPN input type
MD MD
( , : Change the)
U Transistor input :
U Contact input :
Set the sensor type of input B.
PNP input type
U Transistor input :
MD MD ( , : Change the sensor type) U Contact input :

Select the output mode.

MD MD ( , : Change the output mode)

Set the hysteresis for the output .


Setting range : ~ (The hysteresis range differs by the setting position
of desimal point. See F-24 page)
MD MD
( , : Change the setting value)

Select starting time correction function ( ) or


(★ 1) ▲ comparative output (L,LL) limit function( )

( , : Change the setting value)
MD MD

The retention time is set at the thetimer furction of starting operation( )


setting range : ~ sec
( ◀ : Move the digit , : Change the setting value)

MD

Set the Auto-Zero time of INA input.


Setting range : ~ sec
MD
( ◀ : Move the digit , : Change the setting value)
MD

Set the Auto-Zero time of INB input.


Setting range : ~ sec

MD MD ( ◀ : Move the digit , : Change the setting value)

It sets the memory retention.


(★ 2) ( : Memory retention, : No memory retention)
MD MD ( , : Change the setting value)

※If pressing MD key for 3 sec. in RUN mode, it will enter into Parameter 1 group.
※When entering into Parameter 1 group, parameter and set data value flash as 1 sec. cycle.
※The parameter shown in dotted line is not displayed by operating mode.
(See F-15page, "Setting range of comparative value by operating mode".)
※(★1)The parameter is displayed in case of comparative value setting type only.
(But, only MP5M-42 is available among MP5M Series.)
※(★2)The Selecting function of memory retention is displayed when the mode is F13(Integration mode).
(But, F11 mode for MP5M-42)
※After changing set data value in each Parameter, data will be saved by MD pressing key for 2sec and return to RUN mode,
but if you do not touch any key for 60sec while changing data, it return to RUN mode with previous set value.

F-15
Pulse (Rate) Meter
lParameter 2 group
Run (A)
Counter
MD key Press for 4sec.
Display for 2 sec. and move to [ ] parameter automatically.
This is Parameter 2 group.
MD (B)
Select Data Bank. Timer
( , : Change the setting value)
MD MD Only MP5W type has the Data bank parameter.

(C)
Set the decimal point position of display value. Temp.
controlle
(★ 1) ◀ ◀ ◀ ◀ ◀

MD
(D)
It will be displayed in F3, F4, F5, F6 operation mode and set the time unit. Power
▲ controlle
( , : Change the setting value)
▼ lTime range by time unit
MD MD SE C MIN
It will be displayed in F3, F4, F5, F6 operation mode (E)
999.99sec. 999.99min.
and set the time range. Panel
9999.9 sec. 9999.9min. meter
( , :Change the 99min59.9sec. 99hour59.9min.
(sec.)
(min.) setting value) 9hour59min59sec. 999hour59min.
(F)
MD MD 99999sec. 99999min. Tacho/
Set the comparative value HH. Speed/
lSetting range of comparative Pulse
See "Setting range of comparative value by operating
value by operation mode meter
mode" for setting range
MD MD ( ◀ :M ove the setting digit , :Change the setting value) Operating mode S etting r ange
F1, F2, F7, F9, (G)
Set the comparative value H. 0 ~ 99999
F11, F12, F13 Display
See "Setting range of comparative value by operating unit
mode" for setting range F3, F4, F5, F6 0 ~ Set ting time
MD MD ( ◀ :M ove the setting digit , :Change the setting value) range
(★ 2)
-19999 ~
Set the comparative value L. F8, F10
99999 (H)
See "Setting range of comparative value by operating
※The setting range differs by Sensor
mode" for setting range controlle
MD MD ( ◀ :M ove the setting digit , :Change the setting value) setting position of decimal point.

Set the comparative value LL.


See "setting range of comparative value by operating
(I)
mode" for setting range Proximit
MD MD ( ◀ :M ove the setting digit , :Change the setting value) sensor

Set the prescale value of input A mantissa(X).


Setting range : ~
(J)
MD MD ( ◀ :M ove the setting digit , :Change the setting value) Photo
electri c
Set the prescalevalue of input A an exponent(y). sensor
Setting range : ~ (10 - 9 ~ 10 9 )
( ◀ :M ove the setting digit , :Change the setting value)
MD MD
(K)
Set the prescale value of input B mantissa(X). Pressur
sensor
Setting range : ~
( ◀ :Change t he digit , :Change the setting value)
MD MD
(★ 3)
Set the prescalevalue of input A an exponent(y). (L)
Setting range : ~ (10 - 9 ~ 10 9 ) Rotary
encoder
( ◀ :Change t he digit , :Change the setting value)
MD MD

Select the display cycle. (M)


5-Phase
(Unit:sec) stepping
motor &
MD MD ( , :Change t he setting value) Driver &
Controlle
※If pressing MD key for 4sec.in RUN mode, [ ]will be displayed after [ ]. If releasing MD key, it is entering into
Parameter 2 group.
※When entering into Parameter 2 group, parameter and set data value flash by 1sec cycle.
※(★1)It will be displayed only in F3, F4, F5, F6 modes.
※(★2)If selecting F mode among output modes, it is set H and L deviation only, therefore [ ] and [ ] parameter will
not appear.
※(★3)It will be displayed only in F7, F8, F9, F10 modes. But in case of MP5M typw, it is displayed only in F7, F8 modes.
※After changing the setting value in each Parameters, if pressing MD key for 2sec., data will be saved then return to RUN.
If no keys are touched for 60sec.,previous data will be saved and return to RUN.

F-16
MP5S/MP5Y/MP5W/MP5M Series
lParameter 3 group
Run
M D k ey Press fo r 5sec.
This is Parameter 3 group.
Display for 2 sec. and move to [ ] parameter automatically.
MD
Set the High-limit value of PV retransmission output.
See "setting range of comparative value by operating mode"
for setting range
MD MD ( ◀ :Move the setting digit , :Change the setting value)
(★1)

Set the Low-limit value of PV retransmission output.


( ◀ :Move the setting digit , :Change the setting value)
MD MD
lSetting range of comparative
Set the communication Address. value by operation mode
setting range : ~ (32channel) Operating mode Sett ing range
( ◀ :Move the setting digit F1, F2, F7, F9,
0 ~ 99999
MD MD , :Change the setting value) F11, F12, F13
0 ~ S etting
F3, F4, F5, F6
Set the communication Speed. time r ange
(★ 2) -19999 ~
F8, F10
99999
MD
( ◀ :Move the setting digit
MD
, :Change the setting value) ※The setting range differs by
sett ing position of decimal
Select the Remote and the Local. point.

( : using, : non-using)
MD MD ( ◀ :Move the setting digit , :Change the setting value)

Enable to lock the key for each parameter group


: Lock cancel
MD MD
: P0 ~ 3 Lock
( ◀ :Move the setting digit : P1 ~ 3 Lock
, :Change the setting value) : P2 ~ 3 Lock
: P3 Lock only
※If pressing M D key for 5sec. in RUN mode, [ ] and [ ]will be displayed after [ ].
If releasing M D key, it is entering into Parameter 3 group.
※When entering into Parameter 3 group, parameter and data value flash as 1sec. cycle.
※(★1)The parameter is displayed in case of PV transmission output type only.
※(★2)The parameter is displayed in case of RS485 transmission output type only. When selecting Remote[ ], you
cannot operate front keys.
※After changing set data value in each parameters, data will be saved by pressing MD key for 2sec and return to RUN
mode, but if you do not touch any key for 60sec while changing data, it will return to RUN move with previous set value.

▣Factory defalts
lParameter 1 group lParameter 2 group lParameter 3 group
Mode Setting range Mode Setting range Mode Setting range

※Setting specification may not be displayed because of operation mode or output specification.

F-17
Pulse (Rate) Meter
▣Operation mode
lSelect operation mode from (mode) of Parameter 1 group. (A)
Counter
lThere are 13 kinds of operation mode in this unit.
There are 11 kinds of operation mode in MP5M series.

lMode F1(Frequency/Number of revolution/Speed) (B)


Timer
: This mode is to display calculated frequency lDisplay value and display unit
or number of revolutions or speed by Display value Display unit α(Prescale value)
measuring frequency of Input A. Hz 1 MP5 S eries
Frequency
1)Frequency(Hz) = f × [α= 1(sec) ] kHz 0.001 (C)
Temp.
Number of RPS 1
controlle
revolut ion rpm 60
2)Number of revolution(rpm)
= f × [α= 60(sec) ] mm / sec 1,000L
cm / sec 100L
1 (D)
Several targets α=60× Speed m / sec L
N Power
m / min 60L controlle
3)Speed(m/min) = f × [α= 60 × L(m) ] Encoder
km / hour 3.6L
MP5 Ser ies
πD ※Display unit of default:rpm
Several targets α=60×
1000N lTime chart (E)
Panel
Input A meter
※L = The length of conveyor moved for t1 t2 t3 t4 t5 t6

1 pulse cycle[m] Hold


N : Detection target per 1 revolution input (F)
Tacho/
α: Prescale value display (1/t1) ×α (1/t3) × α (1/t6) × α Speed/
Pulse
※α: Prescale value meter

lMode F2(Passing speed) lDisplay value and display unit


MP5 Series (G)
: Display the passing speed between ON of Dis play value Display unit α (Prescale value) Display
unit
input A and ON of input B. mm / sec 1,000L
cm / sec 100L
Passing
Passing speed(V) = f × [ = L(m) ] m / sec L
speed
m / min 60L (H)
Sensor
km / hour 3.6L
※f : This is reciprocal number of the time controlle
※Display unit of factory default:m/sec
between ON of input A and ON of
input B. lTime chart Sensor A Sensor B
L : The distance between input A and (I)
Input A Proximit
input B[m] sensor
※α: Prescale value Input B
ta
Hold
input (J)
t1 t2 t3 t4 t5 t6 t7
Photo
electri c
1 1 1 1 sensor
Display ×α ×α ×α ×α
t1 t2 t4 t7
ta : It requires min. 20ms for return time
(K)
Pressur
lMode F3(Cycle) lDisplay value and display unit sensor

Display value Display unit


Display the time from when input A is
SE C MIN
ON to the next ON. (L)
999.99sec. 999.99min.
Rotary
9999.9sec. 9999.9min. encoder
Cycle(T) = t Cycle 99min. 59.9sec. 99hour 59.9min.
9hour 59min.
999hour 59min. MP 5 (M)
※t : Measurement time [sec] 59sec. Photoelectric
Series 5-Phase
99999sec. 99999min. sensor stepping
motor &
※Set the display unit at the (Time unit) of Parameter 2. Driver &
※Display unit of factory default:999.99sec. Controlle

lTime chart

Input A
t1 t2 t3 t4 t5 t6

Hold
input
※ is not displayed in MP5M-4N,
MP5M-41, MP5M-42. Display t1 t3 t6

※t1, t2, t3, t4, t5, t6 should be over 20ms then able to measure.

F-18
MP5S/MP5Y/MP5W/MP5M Series
lMode F4(Passing time)
lDisplay value and display unit
It displays the pass time of certain distance Dis play unit
Display value
to measure the time between ON and the SEC MIN
next ON of Input A. 999.99sec. 999.99min.

Passing 9999.9sec. 9999.9min.


Passing time(sec) = t ×
time 99min. 59.9sec. 99hour 59.9min.
9hour 59min.
L(m)
[ =
Moving distance within 1pulse cycle[m] ] 59sec.
99999sec.
999hour 59min.

99999min.
M P5
Series
※Set the display unit at the (Time unit) of Parameter 2.
※t : Measurement time[sec] ※Display unit of factory default:999.99sec.
L : Certain distance[m] lTime char t
※α: Presale value
Input A
t1 t2 t3 t4 t5 t6

※ is not displayed in MP5M-4N, Hold


MP5M-41, MP5M-42. input

Display t1 × α t 3 ×α t6 × α

lMode F5(Time width) lDisplay value and display unit


Display value Display unit MP 5 Series
It displays the ON time of input A.
SE C MIN ※Display unit of factory
specification
999.99sec. 999.99min.
Time width(T) = t : 999.99sec.
9999.9sec. 9999.9min.
Time width 99min. 59.9sec. 99hour 59.9min.
※t : ON measurement time of input A[sec]
9hour 59min. 999hour 59min.
59sec.
99999sec. 99999min. Motor
Stamp
※Set the display unit at the (Time unit) of Parameter 2.
※Display unit of factory default:999.99sec.
lTime chart

Input A
t1 ta t2 ta t3
※ is not displayed in MP5M-4N,
MP5M-41, MP5M-42. Hold
input

Display t1 t3
ta : It requires min. 20ms for return time

lMode F6(Time interval) lDis play value and display unit M P5 Series
Display value Display unit
It displays the time from input A is ON to
SEC MIN
input B is ON.
999.99sec. 999.99min.
9999.9sec. 9999.9min.
Time difference(T) = t(Ta~Tb) Time interval 99min. 59.9sec. 99hour 59.9min.

9hour 59min. 999hour 59min.


※t(Ta ~ Tb) : The measured time from input 59sec.
A is ON to input B is ON[sec] 99999sec. 99999min. Sensor A Sensor B
※Set the display unit at the (Time unit) of Parameter 2.
※Display unit of factory default:999.99sec.

lTime chart

Input A

Input B
ta

Hold
input t1 t2 t3 t4 t5 t6 t7
※ is not displayed in MP5M-4N,
MP5M-41, MP5M-42.
Display t1 t2 t4 t7
ta : It requires min. 20ms for return time

F-19
Pulse (Rate) Meter
lMode F7(Absolute rate)
It displays how many percentage fast or late, lDisplay value and display unit (A)
Counter
speed, value etc. of input B against input A Display value Display unit
Absolute rate %

Absolute rate = (Input B / Input A) × 100% A Flow meter B Flow meter


(B)
Frequency of input B[Hz]×Bα Timer
Absolute rate = × 100[%]
Frequency of input A[Hz]×Aα Liquid

MP5 Series
※Aα: Prescale value of input A lTime char t (C)
Temp.
Bα: Prescale value of input A Input A controlle
fA
Frequency of input B[Hz]×Bα
Display = ×100[%]
Frequency of input A[Hz]×Aα
Input B (D)
Power
※There is no error mode in MP5M-4N, fB controlle
MP5M-41, MP5M-42 models.
※Hold : Hold signal is ON, the display value will be held until Hold signal is OFF.

(E)
lMode F8(Error ratio) Panel
meter
It displays how many percentage(%) fast or
lDisplay value and display unit Conveyer A
late of input B against input A.
Conveyer B (F)
Display value Display unit Tacho/
Error ratio % Speed/
Pulse
Input B-Input A ※Aα : Prescale value of input A meter
Error ratio= ×100[%]
Input A Bα: Prescale value of input B

(G)
lTime chart MP5 S eries Display
(Frequency of input B[Hz]×Bα) unit
-(Frequency of input A[Hz]×Aα)
Error ratio= ×100[%] Input A
Frequency of input A[Hz]×Aα fA
(H)
Sensor
Input B controlle
fB

※There is no error ratio mode in MP5M-4N, (I)


(Frequency of input B[Hz]×Bα)-(Frequency of input A[Hz]×Aα)
Display= ×100[%] Proximit
MP5M-41, MP5M-42 models. Frequency of input A[Hz]×Aα sensor

※Hold : Hold signal is ON, the display value will be held until Hold signal is OFF.
(J)
lMode F9(Density) Photo
electri c
lDisplay value and display unit
sensor
It displays the density rate of input B against
Display value Display unit
total sum of input A and input B. Density %
※ Aα :Prescale value of input A (K)
Input B Pressur
Bα :Prescale value of input B A Flow meter B Flow meter
Density= ×100[%] sensor
Input A + Input B

Frequency of input B[Hz]×Bα lTime chart Liquid (L)


Density= ×100[%] Rotary
(Frequency of input A[Hz]×Aα)
Input A MP5 Series encoder
+(Frequency of input B[Hz]×Bα) fA

(M)
5-Phase
Input B stepping
fB motor &
Driver &
Controlle

Frequency of input B[Hz]× Bα


Display= × 100[%]
(Frequency of input A[Hz]×Aα)+(Frequency of input B[Hz]×Bα)

※Hold : Hold signal is ON, the display value will be held until Hold signal is OFF.
※F8 mode is applied to MP5M-4N, MP5M-41,
MP5M-42 models.

F-20
MP5S/MP5Y/MP5W/MP5M Series
lMode F10(Error rate)
It displays the error between standard input A lDisplay value and display unit Conveyer A
Display value Display unit Conveyer B
and comparing input B.
Error END User setting unit
※Aα : Prescale value of input A
Error = Input B - Input A
Bα: Prescale value of input B
Error = (Frequency of input B[Hz] × Bα) MP5 Series
- (Frequency of input A[Hz] × Aα) lTime chart

Input A Input B
※There is no error mode in MP5M-4N, fA fB
MP5M-41, MP5M-42 models.
※Hold : Hold signal is ON, the display value will be held until Hold signal is OFF.

lMode F11(Length measurment) lDis play value and display unit


It displays the number of input A pulses while Display value Display unit
input B is ON. A
Quantity[EA]
mm
Length B
measurement cm Photoelectric
Length measurment = P × α sensor
m
※P : Number of input A pulse,
※ Factory default(Unit):Quantity[E A] MP5 Series
α: Prescale value
lTime char t
1 2 3 4 5 6 1 2 1 2 3 4

Input A

Input B
※F9 mode is applied to MP5M-4N, ta tb

MP5M-41, MP5M-42 models. Hold


input
Display 6× α 4× α
※ ta, tb : It requires min. 20ms for return time

lMode F12(Interval) lDis play value and display unit MP5 Series
It displays the number of input A pulse from Display value Display unit
input B is ON to the time input B is ON next. Quantity[EA]
mm
Interval
Interval = P × α cm
m
A
※P : Number of input A pulse, ※Factory default(Unit):Quantit y[EA ]
α: Prescale value Photoelectric sensor
B
lTime chart
1 2 3 4 1 2 1 2 3
Input A

Input B
ta tb
Hold
※F10 mode is applied to MP5M-4N, input
MP5M-41, MP5M-42 models. Display 4 ×α 3 ×α

※ta : It requires min. 20ms for return time

lMode F13(Integration) lDisplay value and display unit

It displays the counting value against pulses Display value Display unit
Integration Quantity[EA ] MP5
of input A. Series

lOperation and Time chart


Integration = P ×α ① It is count ing the number of Input pulse.
② Input B is an Enable input signal, when this is ON, it stops the display value
and counting Input A . When it is OFF, input A is counting again.
※P : Pulse number of input A,
1 2 3 4 5 6 1 2 3 4
α : Prescale value
Input A

Input B
RESET
※F11 mode is applied to MP5M-4N, input
MP5M-41, MP5M-42 models. Display 0 1 2 3 4 5 6 0 1 2 3 4

※α =1 display value

F-21
Pulse (Rate) Meter
▣Output mode
lSelect output mode in (output type) of Parameter1 group. (A)
Counter
lMP5 series are 6 kinds of output mode. There is no output mode in indicator type, MP5Y-43/44/45, MP5M-41 models.
☞ S(Standard) output mode, H(High) output mode, L(Low) output mode, B(Block) output mode, I(One shot)output mode,
F(Deviation)output mode.
lB output mode : Comparative setting value condotion is that B output mode should be LL<L<H<HH, F output mode (B)
should be L<H, other S, H, L, I output modes operate individually regardless to value size of comparative setting value. Timer
(There is no GO, HH, LL, OUTPUT in MP5M-42)
◎S(Standard) output mode[ ] ◎I(One Shot) output mode[ ]
HH HH (C)
Comparative H Comparative H Temp.
value L value controlle
L
LL LL
Hys
HH
Hys HH
H H (D)
Power
Output GO Output GO controlle
Hys 0.3s
L L
Hys
LL LL
Display value ≥ Comparative value HH ☞ HH output ON Display value ≥Comparative value HH ☞ HH output ON (E)
Display value ≥ Comparative value H ☞ H output ON Comparative value HH >Display value ≥ Comparative value H ☞ H output O N Panel
Display value ≤ Comparative value L ☞ L output ON Comparative value H >Display value ≥Comparative value L ☞ L output ON meter
Display value ≤ Comparative value LL ☞ LL output ON Comparative value L > Display value ≥Comparative value LL ☞ LL output O N
GO output : When there are no HH, H, L, LL output,
it will be ON. ※There is no GO output in output I mode.
※One Shot( ) output time has been fixed 0.3sec. (F)
◎H(High) output mode[ ] ※There is no Hyster esis in I(One shot) compar ative output mode. Tacho/
HH Speed/
Pulse
Comparative H ◎F(Deflection) output mode[ ]
meter
value L
This function is to memorize the setting value and it outputs
LL
when exceed the deviation of H, L.
Hys
HH lThe setting value memory : Memorize the cu rrent display (G)
Hys Display
H value as the setting value with pressin g( M + ▲ ) key in
unit
Output Hys front.
L lDisplay the setting value : Check the memorized the setting
Hys
LL value by ( ▲ ) key. (Display the memorized setting value for
pressing ▲ key continuously.) (H)
GO
Display value ≥ Comparative value HH ☞ HH output ON lDevi ati on setting : Set H[ ], L[ ] deviatio n by Sensor
Display value ≥ Comparative value H ☞ H output ON setting value. (The set deviation will be memorized until set controlle
Display value ≥ Comparative value L ☞ L output ON the next deviation again when power off.)
Display value ≥ Comparative value LL ☞ LL output ON
lDeviation setting range : 0.0001 to 99999(The setting range
GO output : When there are no HH, H, L, LL output,
it will be ON. will be changed by decimal point setting parameter. (I)
If set decimal point as 0000.0, the setting range will be 0.1 Proximit
◎L(Low) output mode[ ] sensor
to 9999.9.)
HH
Comparative lOperation : Display value ≤ L Comparative value ☞
H
value L L Comparative output ON,
LL Display value ≥ H Comparative value ☞ (J)
Photo
H Comparative output ON electri c
Hys
HH Press ( M + ▲ ) Key for sensor
Hys memorizing the setting
H value at the same time
Out put Hys
L (High-limit)H deviation
(K)
Hys Setting value Pressur
LL
sensor
GO (Low-limit)L deviation
Display value ≤ Comparative value HH ☞ HH output ON
Display value ≤ Comparative value H ☞ H output ON
Display value ≤ Comparative value L ☞ L output ON
(L)
Display value ≤ Comparative value LL ☞ LL output ON ON
Power Rotary
GO output : When there are no HH, H, L, LL output, encoder
OFF
it will be ON.
◎B(Block) output mode[ ] Setting value ON
memory OFF (M)
HH
Comparative 5-Phase
H
value L deviation ON stepping
L motor &
output OFF
LL Driver &
(★ 1) Controlle
Hys
HH H deviation ON
Hys output
H OFF
(★2)
Output GO
L Hys ※(★1)Wh en select the com parat ive ou tput adjustme nt
Hys function, output will not be come.
LL
※(★2)Output position may be different from above graph.
Display value ≥Comparative value HH ☞ HH output ON
Comparative value HH > Display value ≥Comparative value H ☞ H output ON ※There are no HH, GO, LL outputs in F output mode.
Comparative value LL >Display value ≥Comparative value L ☞ L output ON ※Even thought set the deviation as "0(Zero)", it will work as
Display value ≤ Comparative value LL ☞ LL output ON setting "1".
GO output : When there are no HH, H, L, LL output, it will be ON.

F-22
MP5S/MP5Y/MP5W/MP5M Series
▣Function
◎Display sampling time
This model is cycle measurement calculation type. There are the starting correction timer function and
It displays reciprocal number of measuring time comparative output limit function in the monitoring
that detecting time of target. Measuring accuracy delay function.
may be dropped by short of cycle measuring time if (Select it in mode of Parameter 1)
the target is revolving with high speed. ①The starting correction timer function(
This function is to change the display cycle in range mode of Parameter 1 group). This function is to
of (0.05/0.5/1/2/4/8sec.) and displays the average make the output not come for the setting time.
value of measuring value then able to prevent (Time setting range 0.0 to 99.9sec.)
measuring accuracy drop when revolving with high Applicable output mode : S, H, L, B, I, F mode
speed. When t he measuring tim e is iong, the M onitoring delay time
response of preset output type is delayed. Comparative
Theref or e, plea se adjust the measuring tim e setting value
L, LL
properly.
Input
Sampling No ouput
Output L, LL
②Comparative output limit function( mode of
Inner Counting
Parameter1 group)This function is to limit the
※Select display sampling time in parameter 2.
LL, L output before H or HH output.
◎Prescale function Applicable output mode : S, B, F mode
This prescale function allows you to multiply the
lThe output mode is S output mode
number of pulse or pulse length by a variable(X ×
HH
10 y ) then display specification of measurement.
Comparative H
It will display frequency or RPM from prescale value L
value by measuring the input A frequency, For LL
example, the prescale value when need to display
HH
the RPM as below.
H
For example, when need to display rpm, what is
Output GO
αvalue of prescale ?
RPM = f×α L

MP5
= f×60×(1/ N) LL
Series = f×60×(1 / 4) This point where the comparative
= f×60×0.25 output limit function is released.

※ f : Input pulse(Frequency) per sec. = f×15 ※L, LL comparative output( ) does not come on
※α: Prescale value after supply ing power.
※N : Pulse number per 1 revolution ※When the output mode is S output mo de, the
lPrescale value(α=15) setting setting value of H H, H , L, LL are not effected
Set Prescale value(α) as (X and y) separately in by each other. T herefore HH value may be equal
, ( , ) of Parameter 2group. or lower than LL value.
Set Prescale(α=15) as (X):1,5000, y:10 1 lThe output mode is B output mode
Also you are able to get the same display value HH
even though set as X=0.1500, y=10 2 Comparative H
X setting range : 0.0001~9.9999 value L
Y setting range : 10 -9 ~10 9 LL

◎Display peak value monitoring function HH


H
This function is to save High Peak value or
Output GO
Low Peak value against display value.
L
lThis function is to save the High Peak( ) value
or Low Peak( )value against the display value. LL
This point where the comparative
lSee Parameter 0 for Reset. output limit function is released.

◎Monitoring delay time function ※L, LL comparative output( ) does not come on
This function is for the stable control to limit L, LL after supply ing power.
output until certain output is come or to limit all ※Each setting value of HH, H, LL, L does not effect
output during the equipment will reach to be stable on each other. Therefore HH value may be equal
status against various change of input such as the or smaller than LL value.
staring current when the motor is running after Setting value should be LL<L<H<HH in sequence.
power on.

F-23
Pulse (Rate) Meter
◎Lock setting function
lThe output mode is F output mode This function is to set the enable or disable of each (A)
Parameter. Counter
H deviation
Comparative lOff : No lock function
Setting value
value lLoC 0 : P0 ~ P3 Lock(Lock Parameter 0 ~ 3)
L deviation
lLoC 1 : P1 ~ P3 Lock(Lock Parameter 1 ~ 3) (B)

Output
H lLoC 2 : P2 ~ P3 Lock(Lock Parameter 2 ~ 3) Timer

L lLoC 3 : P3 Lock(Lock Parameter 3 only)


This point where the comparative
output limit function is released. ※Set lock function in paramert 3 group.
(C)
※Initial L comparative output( ) does not come ◎Inner hardware Lock setting function Temp.
controlle
on after supplying power. This function is to lock in Parameter 3 group by
※The output mode is F output mode, the comparative Inner hardware Lock function in order to prevent
output limit function will be released at the setting wrong setting.
(D)
value(Standard setting). lh0(Hardware Lock0) Power
controlle
※H and L deviation does not effect on each other. It is able to check and change mode in Para-
Therefore, H deviation setting value may be equal meter 3 group.
or smaller than L deviation setting value. lh1(Hardware Lock1)
(E)
It is able to check and change mode in Para- Panel
◎Hysteresis function meter 3 group but, unable to change. meter

Set the Hysteresis value(A) for comparative setting lh2(Hardware Lock2)


value in order to prevent unstable operation due to It is unable to check and change mode in Para (F)
Tacho/
output going ON/OFF frequently. -meter 3 group Speed/
Comparative lIt is possible to lock or unlock after supplied Pulse
A:Hyster isis value meter
setting value power in inner hardware Lock setting.
H, HH A
Comparative lMP5S, MP5Y, MP5W Series
A (G)
setting value Display
L, LL unit

Output H, HH

Output L, LL
h0 mode h1 mode h2 mode
(H)
(Factory default setting)
Sensor
DOT position Setting range controlle
※Inner hardware lock setting pin is on inner PCB.
00000 0000 ~ 9999
0000.0 000.0 ~ 999.9 lMP5M Series
000.00 00.00 ~ 99.99 1 2 1 2 1 2 1 2 (I)
ON ON ON ON Proximit
00.000 0.000 ~ 9.999 OFF OFF OFF sensor
OFF
0.0000 0.000 ~ 0.999 h0 mode h1 mode
h2 mode
※You are able to set "0" but when set "0", the (Factory default setting)
(J)
actual operation will be as "1". ※The position of inner hardware lock setting switch. Photo
electri c
※The initial setting value is 0001. sensor
※You are able to set in " " mode of Parameter 1
1 2
group. ON
(K)
Pressur
◎Auto-Zero time setting function sensor
◎Data bank switching function
When you know the interval of input signal, Auto- This function is to program 2 sets of comparative
zero time should be set as a little bit longer than setting value and 2 kinds of prescale value(Data (L)
that interval of input signal. If there is no pulse bank 1, Data bank 2) then able to select. Rotary
input within setting time(A uto-zero time), it encoder
lWhen the 3 and 5 terminals are open circuited,
regards as the input signal is cut off then make the the comparative value and prescale of Data bank
(M)
value as "00000" forcibly. Note that the Auto-zero 1 will be used. 5-Phase
time setting should be longer than the narrowest lWhen the 3 and 5 terminals are short-circuited, stepping
motor &
interval of input pulse. the comparative value and prescale of Data bank Driver &
Controlle
Otherwise it may be difficult to make the display 2 will be used.
value as "00000". lTo save comparing value and prescale value at
lAuto-zero time setting range(0.1 to 9999.9sec) each data bank, select data bank to be saved at
lWhen the display value is "00000", each output mode of parameter2, then when setting
will respond to how it was programmed for "0". comparing value and prescale value, it will save in
lSet the time in " " mode of parameter1 group. related data bank.
※This function is only for MP5W series.

F-24
MP5S/MP5Y/MP5W/MP5M Series
◎Time unit selection function ◎Communication Command and Block
Enable to display PV value in various time ranges. Format of Command and Response
lTime unit selection functioncan be set in parameter STX 10
1
10
0
R/W X/D ETX CRC
2 group.
lApplicable mode : Mode F3 to F6 St art Address Header Text END CRC
Code Code Code Code Code
SEC MIN
Calculation range of CRC Check Sum
999.99 sec. 999.99 min.
9999.9 sec. 9999.9min. ①Start Code
It shows the first of BLOCK
99min59.9 sec. 99hour59.9 min.
STX → [02H], in case of Response, ACK/NAK
9ho ur59min59 sec. 999hour59 min.
will be added.
99999 sec. 99999 min.
②Address Code
※There is no " " setting mode when set the time This code is upper system can discern MP5
unit display function. series and able to set within range of 00 to 99.
※Time range of( ) part is not displayed in MP5M (BCD ASCII)
series. ③Header Code
It shows Command as 2 alphabets as below.
▣Communication output RX(Read request) → R[52H], X[58H]
◎System ordering RD(Read response) → R[52H], D[44H]
Vert ical resistance WX(Write request) → W[57H], X[58H]
N
WD(Write response) → W[57H], D[44H]
TRXD+ TRXD+
Upper MP5 ④Text
series
TRXD- TRXD- It indicates the detail contents of Comm and
/Response.(See Command)
⑤END Code
TRXD- TRXD+ TRXD- TRXD+ It indicates the end of BLOCK. ETX → [03H]
MP5 series MP5 series ⑥CRC
1 (N-1) CRC is Cyclic Redundancy Check and called
◎Communication control ordering polynominal code. CRC is f or more r eliable
1. The communication control ordering of MP5 transmit/receive to check the error between
series is protocol(Not compatible with other transmitter and reciever.
system). There are CRC-8, CRC-16 and CRC-32, CRC-
2. After 4sec. being suppli ed the power in to 8 has been adopted in MP5 series according to
upper system, then able to start communicating. CCITT-8 Polynomial regulation. (See CRC table)
3. Initial communication will be started by upper Result value is HEX 1 Byte.
system. When Command signal come out from <CRC Table >
upper system then MP5 series will response. 0 1 2 3 4 5 6 7 8 9 A B C D E F
If there is no response after 3times of the 0 0x00 0x5E 0xBC 0xE2 0x61 0x3F 0xDD0x83 0xC2 0x9C 0x7E 0x20 0xA3 0xFD 0x1F 0x41
command signal from upper system, error will be 1 0x9D0xC3 0x21 0x7F 0xFC 0xA2 0x40 0x1E 0x5F 0x01 0xE3 0xBD 0x3E 0x60 0x82 0xDC
2 0x23 0x7D 0x9F 0xC1 0x42 0x1C 0xFE 0xA0 0xE1 0xBF 0x5D 0x03 0x80 0xDE0x3C 0x62
occurred.
3 0xBE 0xE0 0x02 0x5C0xDF 0x81 0x63 0x3D 0x7C 0x22 0xC0 0x9E 0x1D 0x44 0xA1 0xFF
S A C T E C S A C T E C 4 0x46 0x18 0xFA 0xA4 0x27 0x79 0x9B 0xC5 0x84 0xDA 0x38 0x66 0xE5 0xBB 0x59 0x07
T DM X T R T D M X T R 5 0xDB 0x85 0x67 0x39 0xBA 0xE4 0x06 0x58 0x19 0x47 0xA5 0xFB 0x78 0x26 0xC4 0x9A
X R D T X C X R D T X C 6 0x65 0x3B 0xD9 0x87 0x04 0x5A 0xB8 0xE6 0xA7 0xF9 0x1B 0x45 0xC6 0x98 0x7A 0x24
Upper
7 0xF8 0xA6 0x44 0x1A 0x99 0xC7 0x25 0x7B 0x3A 0x64 0x86 0xD8 0x5B 0x05 0xE7 0xB9
8 0x8C0xD2 0x30 0x6E 0xED 0xB3 0x51 0x0F 0x4E 0x10 0xF2 0xAC 0x2F 0x71 0x93 0xCD
MP5W A S A C T E C 9 0x11 0x4F 0xAD 0xF3 0x70 0x2E 0xCC0x92 0xD3 0xBD 0x6F 0x31 0xB2 0xEC0x0E 0x50
C T D M X T R A 0xAF 0xF1 0x13 0x4D 0xCE 0x90 0x72 0x2C 0x6D 0x33 0xD1 0xBF 0x0C 0x52 0xB0 0xEE
K X R D T X C B 0x32 0x6C 0x8E 0xD0 0x53 0x0D 0xEF0xB1 0xF0 0xAE 0x4C 0x12 0x91 0xCF 0x2D 0x73
C 0xCA 0x94 0x76 0x28 0xAB 0xF5 0x17 0x49 0x08 0x56 0xB4 0xEA 0x69 0x37 0xD5 0x8B
A B C D 0x57 0x09 0xEB 0xB5 0x36 0x68 0x8A0xD4 0x95 0xCB 0x29 0x77 0xF4 0xAA 0x48 0x16
E 0xE9 0xB7 0x55 0x0B 0x88 0xDB 0x34 0x6A 0x2B 0x75 0x97 0xC9 0x4A 0x14 0xF6 0xA8
※A → Min. 4sec, B → Max. 300msec, F 0x74 0x2A 0xC8 0x96 0x15 0x4B 0xA9 0xF7 0xB6 0xE8 0x0A 0x54 0xD7 0x89 0x6B 0x35

C → Min. 20msec

F-25
Pulse (Rate) Meter
◎Communication Command

lThe Charictaristic(Number) at " " is ASCII. STX 0 1 W X 0 C 0 + 0 0 1 2 3 4 5 ETX CRC


(A)
Counter
5 3
Sort ACK STX Addr Command Bank Code +/- 10 10 4 10 10 2 10 1 10 0 DP ETX CRC Dec-
Check
Start Address C o mm an d Bank C om ma n d Symbol 10 10 10 10 10 10 ima l End sum
5 4 3 2 1 0

point
02H "R" "X" "0" "0" "0" "0" "0" "0" "0" 03H CRC
02H 30H 31H 57H 58H 30H 43H 30H 2BH 30H 30H 31H 32H 33H 34H 33H 03H 5DH
(B)
06H 02H "R" "D" 03H CRC
Timer
2. Response(MP5 series)
02H "W" "X" 03H CRC When complete the operation after normal receive.
ACK STX 0 1 W D 0 C 0 + 0 0 1 2 3 4 3 ETX CRC
06H 02H "W" "D" 03H CRC (C)
Dec - Temp.
ACK Start Address Co mma nd Bank Co mman d Symbol 10 5 10 4 10 3 10 2 10 1 10 0 im al End Check
sum controlle
point
P 0 Process Value
C 0 Comparative Value HH 06H 02H 30H 31H 57H 44H 30H 43H 30H 2BH 30H 30H 31H 32H 33H 34H 35H 03H 3CH

C 1 Comparative Value H
3. CRC error : Transmit NAK[15H] only. (D)
C 2 Comparative Value L Power
(Need to transmit again) controlle
C 3 Comparative Value LL
4. Other : No response of ACK/NAK
K 0 Peak Value Max .
①After receiving STX, the address are not the
K 1 Peak Value Min.
same (E)
X 0 Prescaling Value X.Ain Panel
②When receive buffer overflow is occurred. meter
X 1 Prescaling Value X.Bin
③When the baud rate or other communication
Y 0 Prescaling Value Y.Ain
setting value are not the same.
Y 1 Prescaling Value Y.Bin (F)
5. When there are no ACK/NAK response Tacho/
Reset control of maximum/minimum Speed/
R 0
values ①Check the status of lines Pulse
②Check the communication condition meter
lRead[RX] of measurement/setting value :
(Setting value)
Address 01, Command RX
③When assume the problem is due to noise, try (G)
1. Command(Upper) to operate communi-cation 3 times more until Display
①Command unit
recovery
②Application : Address(01), Header code(RX), ④When occurred communication failure frequently,
Current value(P0) of Bank(0),
please adjust the communicating speed.
CRC Check sum(B5H) (H)
Sensor
STX 0 1 R X 0 P 0 + 0 0 0 0 0 0 0 ETX CRC ▣Precaution for communicating with controlle

Start Address Command Bank Command Symbol 10 5 10 4 10 3 10 2 10 1 10 0 D ecima l END Chec k


point sum MP5 series
02H 30H 31H 52H 58H 30H 50H 30H 2BH 30H 30H 30H 30H 30H 30H 30H 03H B5H 1. It is not possible to modify Parameter(Baud rate, (I)
Proximit
2. Response Address etc)related to communication of MP5 sensor
①Normal receive : Adding ACK[06H] to current series on line with upper systems such as PC,
value of Data transmission PLC etc. (Error will be occurred)
Bank(0) is +1.234. 2. Firstly make communication Parameter of MP5 (J)
Photo
series and upper system at one. electri c
ACK STX 0 1 R D 0 P 0 + 0 0 1 2 3 4 3 ETX CRC
3. It is not allow to set overlapping communication sensor
Check De c-
3 2 1 0
ACK Start Address Comman d Bank Co mmand Symbol 10 5 10 4 10 10 10 10 imal End sum number at the same communication line.
point
(Error will be occurred) (K)
06H 02H 30H 31H 52H 44H 30H 50H 30H 2BH 30H 30H 31H 32H 33H 34H 33H 03H 23H
4. Please use Twist pair wire for RS485 commu- Pressur
sensor
②Normal : Adding ACK[06H] to current value of nication.
Data transmission Bank(0)is -56.7. 5. The total length of communication is 800m and
ACK STX 0 1 R D 0 P 0 - 0 0 1 5 6 7 1 ETX CRC over 32 equipment can be connected.
(L)
D ec-
6. When connect communication cable between Rotary
3 2 1 0 Check encoder
ACK Start Address Com mand Bank Co mmand Symbol 10 10 10 10 10 10 imal End sum MP5 series and upper systems, the vertical
5 4

point
resistance(100 ~ 200Ω) must be installed at
06H 02H 30H 31H 52H 44H 30H 50H 30H 2DH 30H 30H 31H 35H 36H 37H 31H 03H 42H
(M)
between both communication lines. 5-Phase
lWrite[WX] of measurement / Setting value : 7. Please check Parameter related to communi- stepping
motor &
Address 01, Command WX cation Driver &
Controlle
1. COMMAND(Upper) ①Start bit : 1(Fix)
①Command ②Stop bit : 1(Fix)
②Application : Address(01), Head Code(WX), ③Parity bit : Non(Fix)
The setting value into SV-HH(C0) ④Data bit : 8(Fix)
of BANK(0) is +1.234. ⑤Baud rate : 2400, 4800, 9600(Setable)
⑥Address : 00 ~ 99(Setable)

F-26