Beruflich Dokumente
Kultur Dokumente
A) Academic Units –
B) Residential Units –
------------------------------------------------------------------------------------------------------------------------ - 1 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
C) Other units –
Foundation system for all structures to be open isolated foundation with soil bearing
capacities as follows (as per soil report dated 07.05.2014) –
1) SBC value 15 T/sq.m at 1.5m below NGL for Academic Block , Faculty housing,
commercial complex, school , Estate office etc.
2) SBC value 30 T/sq.m at 2.5m below NGL for Auditorium, Admin Block, library,
Hostels, Mess hall, sports complex, non faculty apartments etc.
2. DESIGN LOADS
The imposed loads that are envisaged to act permanently (wherever applicable) are
considered for analysis and design. These load values are based on IS: 875 (part-1)-1987
and general construction practice.
Imposed load intensities –
------------------------------------------------------------------------------------------------------------------------ - 2 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
B) Live Loads
The live load is assessed based on the occupancy classifications as per IS:875 (Part-2)-
1987 and are listed as below.
Name of Structure Occupancy Classification UDL (KN/m2)
Academic Units Class room & Lecture room 3.00
Seminar room /Auditorium/projector
Academic Units 5.00
room/ stage
Academic Units Store room/ server room 5.00
------------------------------------------------------------------------------------------------------------------------ - 3 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
3. WIND LOADS
The wind pressure has been calculated based on the data furnished below and other
provisions laid in IS: 875 (Part 3)-1987
Basic Wind Speed Vb = 47 m/sec
Risk Coefficient K1 = 1.04 (Probable Design life of structure is
assumed as 75 years)
Terrain Category = 3
Structure Class = Class B / C …. as per individual unit
Factor K2 = 0.82 to 1.00 ….. as per individual unit
Topography factor K3 = 1.0
Design Wind Speed and wind pressure can be calculated for individual units as per base
dimensions and height of structure with reference to IS: 875 (part 3)-1987.
For Preliminary analysis/design, the wind pressure has been calculated based on the data
furnished below and other provisions laid in IS: 875 (Part 3)-1987
Vz = Vb .k1.k2.k3
= 47 x 1.04 x 0.87 x 1
= 42.52 m/s
Pz = 0.6 x Vz2
= 0.6 x 42.52 x 42.52
= 1084.77 N/sq. m
------------------------------------------------------------------------------------------------------------------------ - 4 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
4. EARTHQUAKE LOAD
The loading due to earthquake is assessed based on the provisions of IS: 1893 (Part-
1):2002
Table Showing Seismic Zone , Importance Factor and Ductile detailing applications for
individual building units -
Ductile
Importance
Sr. No. Building Detail Seismic Zone Detailing as
Factor
per IS13920
1 Auditorium III 1.50 Yes
2 Library III 1.50 Yes
3 Administrative Block III 1.50 Yes
4 Academic unit III 1.50 Yes
5 MDP ( Academic) III 1.50 Yes
6 Sports complex III 1.00 No
7 Dispensary III 1.00 No
8 Entrance gate III 1.00 No
9 Community market III 1.00 No
10 Estate office III 1.00 No
11 Daycare III 1.00 No
12 Canteen III 1.00 No
13 MDP ( Residential) III 1.00 No
14 Students Hostel III 1.00 No
15 Married student hostel III 1.00 No
16 Staff Housing III 1.00 No
17 Faculty Housing III 1.00 No
18 Director’s Bungalow III 1.00 No
19 Hostel Mess III 1.00 No
20 Handicapped Housing III 1.00 No
Fundamental Natural Period (T) is calculated for individual units as per base dimensions
and height of structure with reference to IS: 1893-2002.
------------------------------------------------------------------------------------------------------------------------ - 5 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
The loading due to earthquake is assessed based on the provisions of IS: 1893(Part-
1):2002
= 0.0952
------------------------------------------------------------------------------------------------------------------------ - 6 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
The various loads are combined in accordance with the stipulations in IS:875 (Part 5)-
1987. Wherever imposed load is combined with earthquake load the appropriate part of
the imposed load as specified in IS:1893-2002 is adopted both for evaluating earthquake
effect and for combined load effects, used in such combination.
Type Load Case LOAD COMBINATIONS
Primary 1 DEAD LOAD (DL)
Primary 2 WALL LOAD (WL)
Primary 3 SLAB DEAD LOAD (SDL)
Primary 4 LIVE LOAD (LL)
Primary 5 WIND LOAD X (+) WLX
Primary 6 WIND LOAD Z (+) WLZ
Primary 7 SIESMIC LOAD ALONG-X SLX
Primary 8 SIESMIC LOAD ALONG-Z SLZ
Combination 10 DL + WL + SDL + LL
Combination 11 DL + WL + SDL + LL + WLX
Combination 12 DL + WL + SDL + LL + WLZ
Combination 13 DL + WL + SDL + LL - WLX
Combination 14 DL + WL + SDL + LL - WLZ
Combination 15 DL + WL + SDL + LL + SLX
Combination 16 DL + WL + SDL + LL + SLZ
Combination 17 DL + WL + SDL + LL - SLX
Combination 18 DL + WL + SDL + LL - SLZ
Combination 19 DL + WL + SDL + WLX
Combination 20 DL + WL + SDL + WLZ
Combination 21 DL + WL + SDL - WLX
Combination 22 DL + WL + SDL - WLZ
Combination 23 DL + WL + SDL + SLX
Combination 24 DL + WL + SDL + SLZ
Combination 25 DL + WL + SDL - SLX
Combination 26 DL + WL + SDL - SLZ
------------------------------------------------------------------------------------------------------------------------ - 7 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
7 ANALYSIS METHOD
The overall individual structure is analyzed for Static and Lateral loads due to
Earthquake/Wind loads and its combinations.
The analysis is conducted using standard software such as STAAD, Etabs and SAFE.
8. DESIGN ASSUMPTIONS
A) The design life of the structure is assumed as 50 years. This requirement is not
applicable to replaceable materials.
B) All R.C.C. structures will be designed according to the Limit State method as
specified in IS: 456-2000.
C) The R.C.C. structure is idealized as 3D space frame and analyzed using ETABS,
software for both vertical and lateral loads.
D) Forces and moments from the analysis output for the worst combinations are used for
the design of the structure.
E) Design of structural steel members as per IS: 800-1984
F) Expansion joint/strip to be provide at 45.0m (maximum) to control temperature effect.
G) Following buildings analyzed and designed with consideration of 1 typical floor
provision as per client’s request –
1) All Academic blocks,
2) Commercial complex,
3) Dispensary,
4) Faculty club,
5) Canteen,
6) Student Mess,
7) Estate Office.
------------------------------------------------------------------------------------------------------------------------ - 8 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
9. CONSTRUCTION DETAILS
1) All units except Auditorium, sports complex etc. have RCC floor slab with RCC beam
and slab system or flat slab system.
2) Auditorium, sports complex have m. s. sloping roof structure.
3) Library unit has few structural steel columns with infilled concrete for 15.0 m height.
4) Filling load = All filling in class room/seminar room considered as
light weight material filling. (i.e. light weight cinder)
5) Grade of Concrete = M30 For foundation/column/beams/slabs etc.
M40 For Post Tensioned beams
M25 For Grade slab
(Concrete design Mix as per IS 456-2000)
M15 (For P.C.C. )
6) Aggregate = 20mm and down size, mechanically crushed
aggregate
7) Reinforcements = Grade Fe500 as per IS 1786. (To be tested before use)
8) Cement = Grade 43
9) Minimum column width –
Single / two storey building = 230mm
More than two storey building = 300 mm
10 ) Minimum beam width = 230 mm
11) Masonry work = Aercon AAC Block. (100mm/200mm thk.)
12) Expansion Joint = Provide Expansion joint for Acadamic unit, Admin
Unit, Type A, Type B, Married student hostel.
13) Temperature Analysis = Temperature analysis required for library unit.
( for 250C temperature difference)
14) Structural steel = All the structural steel shall before fabrication
conform to IS:2062.( yield strength = 250 N/sq. m.)
14) Electrode = Covered electrode shall conform to IS 814 or IS
1395 as appropriate. (Make of electrode to be
mention in tender document)
16) Welding = All welding connection as per IS 814,IS 1395,IS 819.
------------------------------------------------------------------------------------------------------------------------ - 9 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
12. MATERIAL
The self-weight of the various elements are computed based on the built weight of
materials as given below –
(based on IS: 875 (part 1)-1987 and general construction practice)
------------------------------------------------------------------------------------------------------------------------ - 10 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
Exposure Condition –
All external exposed structural members should design with consideration of Moderate
exposure and all internal members design with Mild exposure condition.
Foundation system for all structures to be open isolated foundation with soil bearing
capacities as follows (as per soil report dated 07.05.2014) –
3) SBC value 15 T/sq.m at 1.5m below NGL for Academic Block , Faculty housing,
commercial complex, school , Estate office etc.
4) SBC value 30 T/sq.m at 2.5m below NGL for Auditorium, Admin Block, library,
Hostels, Mess hall, sports complex, non faculty apartments etc.
------------------------------------------------------------------------------------------------------------------------ - 11 -
MAHIMTURA CONSULTANTS PVT. LTD. , PROJECT: INDIAN INSTITUTE OF MANAGEMENT
3rd floor , Unique House, S.A. Brelvi Road, AT TIRUCHIRAPPALLI
Fort, Mumbai -01.
All analysis and designs are conforming to the relevant Indian Standards.
List of relevant Indian Standard codes refer for analysis & design-
CODE DESCRIPTION
IS:875 (Part-1)-1987 Code of Practice for Design Loads (Other than Earthquake)for
Building and Structures-Unit Weights of Buildings Materials and
Stored Material.
IS:875 (Part-2)-1987 Code of Practice for Design Loads (Other than Earthquake) for
Building and Structures-Imposed loads
IS:875 (Part-3)-1987 Code of Practice for Design Loads (Other than Earthquake) for
Buildings and Structures –Wind Load.
IS:875 (Part-5)-1987 Code of Practice for Design Loads (Other than Earthquake ) for
Buildings and Structures - Special Loads and Load Combinations
IS:3370 ( Part 1 to 4) Code of Practice for Concrete Structures for storage of Liquids
------------------------------------------------------------------------------------------------------------------------ - 12 -