Beruflich Dokumente
Kultur Dokumente
By
I
II
SYNOPSIS
ducted to several rooms. It can operate under almost all conditions that a
viable option for consumers. This thesis details the design, sizing, costing
III
Jeffrey James Snelgar
13 Market Street
Kensington, Perth WA 6151
rd
3 June 2005
Dear Sir,
Yours faithfully,
_____________________
Jeffrey Snelgar
1204 5239
IV
ACKNOWLEDGEMENTS
I would like to thank Associate Professor William Lawrance for his support
Many thanks go to David Langridge from Solar Focus Pty Ltd for his helpful
Last of all, I would like to thank Zibby Cielma and especially Russell
Wilkinson and for their invaluable assistance with the construction and testing
of the prototype, without which the project would have been far more difficult.
V
TABLE OF CONTENTS
1.0 INTRODUCTION..................................................................................1
1.1 THE ENERGY CRISIS AND AIR CONDITIONING ...........................1
1.1.1 AIR-CONDITIONING DEMAND....................................................1
1.1.2 ALTERNATIVE POWER...............................................................1
1.2 SOLAR-POWERED AIR-CONDITIONING.......................................3
1.3 THESIS ORGANISATION................................................................5
2.0 EVAPORATIVE AIR-CONDITIONING.................................................7
2.1 INTRODUCTION.............................................................................7
2.2 DIRECT EVAPORATIVE AIR-CONDITIONING................................8
2.3 CONSTRUCTION.............................................................................9
2.3.1 INTRODUCTION ..........................................................................9
2.3.2 FAN MOTOR ..............................................................................10
2.3.3 WATER PUMP............................................................................11
2.3.4 COOLING PADS.........................................................................11
2.4 ADVANTAGES...............................................................................12
2.5 DISADVANTAGES.........................................................................12
2.6 SIZING ...........................................................................................13
3.0 MOTORS AND DRIVES....................................................................15
3.1 INTRODUCTION............................................................................15
3.2 PERMANENT MAGNET DC MOTORS ..........................................15
3.3 PULLEYS AND DRIVES.................................................................17
3.3.2 BELT DRIVES.............................................................................18
3.3.3 PRELOAD...................................................................................18
3.3.4 V-BELTS.....................................................................................19
3.3.5 TOOTHED-BELTS......................................................................19
3.3.6 CONSTRUCTION.......................................................................20
4.0 PHOTOVOLTAIC THEORY...............................................................21
4.1 SOLAR RADIATION.......................................................................21
4.2 ENERGY FROM THE SUN.............................................................21
4.3 HISTORY OF SOLAR POWER.......................................................23
4.4 SOLAR CELL OPERATION............................................................24
4.5 SEMICONDUCTORS.....................................................................25
4.5.1 INTRODUCTION ........................................................................25
4.5.2 CRYSTALLINE SILICON............................................................25
4.5.3 BAND STRUCTURE AND DOPING...........................................26
4.5.4 P-N JUNCTIONS........................................................................27
4.5.5 LIGHT ABSORBSION BY A SEMICONDUCTOR.......................29
4.6 SOLAR CELLS...............................................................................31
4.6.1 INTRODUCTION ........................................................................31
4.6.2 EFFECT OF TEMPERATURE....................................................33
4.6.3 EFFECT OF IRRADIANCE.........................................................34
4.6.4 EFFECT OF SHUNT AND SERIES RESISTANCE....................35
5.0 STAND ALONE PHOTOVOLTAIC SYSTEM COMPONENTS..........36
5.1 BATTERIES....................................................................................36
VI
5.1.1 INTRODUCTION ........................................................................36
5.1.2 LEAD-ACID.................................................................................37
5.1.3 NICKEL-CADMIUM.....................................................................42
5.1.4 BATTERY EQUATION................................................................44
5.2 CHARGE REGULATOR.................................................................45
5.3 MAXIMUM POWER POINT TRACKERS........................................47
5.4 OPTIMUM ORIENTATION AND TILT ANGLES..............................48
5.4.1 INTRODUCTION ........................................................................48
5.4.2 FIXED ARRAY TILTING.............................................................49
5.4.3 TRACKERS................................................................................50
6.0 SYSTEM SIZING ...............................................................................52
6.1 INTRODUCTION............................................................................52
6.2 SOLAR RADIATION LEVELS.........................................................52
6.3 SYSTEM LOAD..............................................................................53
6.3.1 INTRODUCTION ........................................................................53
6.3.2 12V SYSTEM..............................................................................53
6.3.3 24V SYSTEM..............................................................................59
7.0 SIMULATION.....................................................................................64
7.1 INTRODUCTION............................................................................64
7.2 ARRAY MODEL..............................................................................64
7.3 EVAPORATIVE AIR-CONDITIONING SYSTEM SIMULATION.....67
7.3.1 INTRODUCTION ........................................................................67
7.3.2 INPUTS.......................................................................................67
7.3.3 BATTERY...................................................................................71
7.3.4 MATHEMATICAL OPERATORS ................................................72
7.3.5 OUTPUTS...................................................................................73
7.4 PRELIMINARY LOAD TESTING ....................................................77
7.4.1 INTRODUCTION ........................................................................77
7.4.2 TEST ONE: 8hrs continuous operation.......................................78
7.4.3 TEST TWO: Failure of one PV....................................................79
7.4.4 TEST THREE: One cloudy day...................................................80
7.4.5 PRELIMINARY SIMULATION CONCLUSIONS..........................82
7.5 12V PROTOTYPE SYSTEM TESTING ..........................................83
7.5.1 INTRODUCTION ........................................................................83
7.5.2 TEST ONE: 8hrs continuous operation.......................................84
7.5.3 TEST TWO: Maximum daily usage.............................................86
7.5.4 TEST THREE: Failure of one PV................................................89
7.5.5 TEST FOUR: One cloudy day.....................................................91
7.5.6 CONCLUSIONS / FINDINGS......................................................94
8.0 PROTOTYPE MODEL.......................................................................95
8.1 INTRODUCTION............................................................................95
8.2 CIRCUIT DIAGRAM .......................................................................95
8.3 SYSTEM COMPONENTS..............................................................96
8.3.1 BREEZAIR EA70 AIR-CONDITIONING UNIT............................96
8.3.2 WATER PUMP............................................................................96
8.3.3 FAN MOTOR ..............................................................................98
8.3.4 BATTERY...................................................................................99
8.3.5 SOLAR MODULES...................................................................100
VII
8.3.6 CHARGE REGULATOR...........................................................100
8.4 BELT DRIVES AND PULLEYS.....................................................101
8.4.1 INTRODUCTION ......................................................................101
8.4.2 PULLEY SELECTION...............................................................102
8.5 PROTOTYPE CONSTRUCTION..................................................104
8.6 FULL PROTOTYPE SYSTEM TESTING.....................................105
8.6.1 INTRODUCTION ......................................................................105
8.6.2 FAN SPEED..............................................................................105
8.6.3 ELECTRICAL PERFORMANCE...............................................106
8.6.4 AIR SPEED AND COOLING PERFORMANCE........................107
9.0 FEASIBILITY STUDY......................................................................109
9.1 INTRODUCTION..........................................................................109
9.2 SYSTEM COMPONENTS............................................................109
9.2.1 INTRODUCTION ......................................................................109
9.2.2 12V SYSTEM............................................................................109
9.2.3 24V SYSTEM............................................................................110
9.3 SYSTEM COSTING......................................................................110
9.3.1 INTRODUCTION ......................................................................110
9.3.2 12V SYSTEM............................................................................110
9.3.3 24V SYSTEM............................................................................111
9.4 PAYBACK PERIOD......................................................................112
9.4.1 INTRODUCTION ......................................................................112
9.4.2 12V SYSTEM............................................................................113
9.4.3 24V SYSTEM............................................................................115
9.5 ECONOMIC ANALYSIS ...............................................................115
9.6 ENVIRONMENTAL ANALYSIS....................................................116
10.0 CONCLUSION.................................................................................118
10.1 INTRODUCTION..........................................................................118
10.2 SYSTEM LIMITATIONS ...............................................................118
10.2.1 INTRODUCTION...................................................................118
10.2.2 BELT DRIVE LIMITATIONS..................................................118
10.2.3 TESTING LIMITATIONS.......................................................119
10.3 ECONOMIC FEASIBILITY............................................................119
10.4 FUTURE DEVELOPMENT...........................................................120
10.4.1 INTRODUCTION...................................................................120
10.4.2 HYBRID SYSTEM.................................................................120
10.4.3 SYSTEM VOLTAGE..............................................................120
10.4.4 BELT DRIVE .........................................................................121
10.4.5 WATER PUMP......................................................................121
10.4.6 FAN MOTOR.........................................................................122
10.4.7 FAN TYPE.............................................................................122
11.0 BIBLIOGRAPHY..............................................................................123
12.0 APPENDICES..................................................................................126
12.1 APPENDIX A................................................................................126
12.2 APPENDIX B................................................................................127
12.3 APPENDIX C................................................................................128
12.4 APPENDIX D................................................................................129
VIII
12.5 APPENDIX E................................................................................130
12.6 APPENDIX F................................................................................131
12.7 APPENDIX G................................................................................132
12.8 APPENDIX H................................................................................137
12.9 APPENDIX I..................................................................................144
IX
LIST OF FIGURES
X
Figure 7.19: Battery capacity over 96 hours .................................................79
Figure 7.20: Battery capacity over 96 hours .................................................80
Figure 7.21: Irradiance graph with initial cloudy day.....................................81
Figure 7.22: Battery Capacity with cloudy day and 150Ah battery................81
Figure 7.23: Battery Capacity with cloudy day and 110Ah battery................82
Figure 7.24: Load current profile over 96 hours............................................84
Figure 7.25: Battery capacity over 96 hours .................................................85
Figure 7.25: Energy balance over 96 hours..................................................85
Figure 7.26: Total energy generated and consumed over 96 hours .............85
Figure 7.27: Equivalent energy costing over 96 hours..................................86
Figure 7.28: Total energy costing over 96 hours...........................................86
Figure 7.29: Battery capacity if run for 11 hours per day..............................87
Figure 7.30: Battery capacity if run for 10 hours per day..............................87
Figure 7.31: Energy balance over 96 hours..................................................88
Figure 7.32: Total energy generated and consumed over 96 hours .............88
Figure 7.33: Equivalent energy costing over 96 hours..................................88
Figure 7.34: Total energy costing over 96 hours...........................................89
Figure 7.35: Array Power over 96 hours.......................................................89
Figure 7.36: Battery capacity over 96 hours .................................................90
Figure 7.37: Energy balance over 96 hours..................................................90
Figure 7.38: Total energy generated and consumed over 96 hours .............90
Figure 7.39: Equivalent energy costing over 96 hours..................................91
Figure 7.40: Total energy costing over 96 hours...........................................91
Figure 7.41: Array power over 96 hours........................................................92
Figure 7.42: Battery capacity over 96 hours .................................................92
Figure 7.43: Energy balance over 96 hours..................................................93
Figure 7.44: Total energy generated and consumed over 96 hours .............93
Figure 7.45: Equivalent energy costing over 96 hours..................................93
Figure 7.46: Total energy costing over 96 hours...........................................93
Figure 8.1: Prototype system configuration...................................................95
Figure 8.2: A similar original evaporative system..........................................96
Figure 8.3: A similar centrifugal fan ..............................................................96
Figure 8.4: The original Tornado AC water pump.........................................97
Figure 8.5: The replacement Flojet 12VDC water pump...............................97
Figure 8.6: The old fan motor.......................................................................98
Figure 8.7: The new DC fan motor................................................................99
Figure 8.8: The 12V 150Ah Gel Cell Battery used in the prototype system..99
Figure 8.9: The BPSX60 60W module array...............................................100
Figure 8.10: Fan and motor pulleys connected by a V-belt drive................101
Figure 8.11: Various size pulleys tested.....................................................102
Figure 8.12: The completed prototype with air duct and “cooling pads”......104
Figure 8.13: The prototype test was run on a partially cloudy day..............105
Figure 8.14: Output air speed at different locations of the output ducting...107
Figure 9.2: Coal and CO2e emissions saved by use of solar system.........117
XI
LIST OF TABLES
XII
1.0 INTRODUCTION
extremely hot summer days. This has caused rolling blackouts across
hot days. Those who do not obey the instructions face a $1000
1
Alternative methods of generating electricity are becoming
causing many power supply issues, whilst the detrimental effect that
resources have now been abused to the extent where action must
Fossil fuel fired generation accounts for over 50% of the annual
fuels, but it is expected that solar power will play an important part in
2
They are durable. Systems are generally designed to last
utility grid.
s u c h a s a s o l a r - p o we r e d a i r - c o n d i t i o n i n g u n i t t o b e
unit costs.
3
whether Western Power has placed a ban on air-conditioning, making it
Whilst the high cost of energy from PV presently limits its applications,
there are still many applications for which PV provides the most
economical power supply solution. PV is also often chosen simply for its
The challenge of this project was to design, simulate and construct a roof
photovoltaic cells. This unit would be ducted to more than one room
between cooling output and power input, such that it was effectively
Matlab simulations were used to help size the system and to verify the
improvements.
4
1.3 THESIS ORGANISATION
Chapter Three briefly explains the theory of motor and drives as they are
This chapter helps explain the basis behind solar technology that will be
Chapter Five describes the types of stand alone components required for
5
similar scenarios. It also includes a brief explanation of the simulation
prototype air-conditioner.
into the setup cost of the system and its effective usability.
Chapter Ten details conclusions that have been derived from the
6
2.0 EVAPORATIVE AIR-CONDITIONING
2.1 INTRODUCTION
western United States, the Indian subcontinent, the Middle East, Eastern
Africa, and northern Mexico. As these locations suggest, EAC works best
for comfort in locations that are hot and dry, and is best suited to arid and
poultry houses (Bom, G., et al, 1999). EAC has significant environmental
and HCFC use, whilst preventing the emission of CO2 and other gases.
EACs also reduce the peak electrical demand since they are more energy
efficient than refrigerative units. Energy savings due to the use of EACs
are in the tens of millions of barrels of oil per year (Bom et al, 1999).
conditioning. These are direct and indirect cooling. Dartnell (2005) states
that with direct cooling, water evaporates directly into the airstream. It
therefore humidifies the air and reduces its dry bulb temperature. Indirect
7
moisture added to the supply air. Only one side of the heat exchanger is
cooled with the evaporating water. Since the unit constructed in this
project utilises direct cooling, only this method will be discussed further.
Direct EAC is the oldest, simplest, and most widespread form of air-
and a fan motor. The performance of an EAC is dependant upon the wet-
is the temperature to which air will cool when water is evaporated into
the location. Both of these are used to compute the relative humidity. The
actual savings will vary with the humidity and dry-bulb temperature of the
8
The system uses a fan to draw hot outside air through a cooling pad
made from a porous material and then into the dwelling. Heat is
cooler air exiting the fan. The efficiency of the unit is heavily reliant on the
materials the cooling pads are constructed from and the fan that is used.
A critical component in EAC is the use of water. The amount of water that
typically consumes between 5 and 100 litres a day (Bom et al, 1999),
which equates to around $20 to $25 worth of water per season (Breezair,
2004).
2.3 CONSTRUCTION
2.3.1 INTRODUCTION
9
Figure 2.3: Section of a typical evaporative air-conditioner
As shown in the figure above, the fan draws warm outside air through
the wetted cooling pad, cooling the air. The water is pumped from the
sump through the distribution system to the top of the pads. It then
trickles down through the cooling pads by means of gravity and back
into the water sump. Since water is lost through evaporation, the water
level in the sump is maintained by use of a float valve. The cooled air
duct distribution system. The cool air flows into the room/s displacing
the hot air. The room temperature can be controlled by adjusting the
fan speed, and hence the airflow into the room (Blanchard, 2003).
10
motors are also becoming more commonly used. They generally
range from 200 to 1000W. These motors should have a drip proof
In the past, the most common type of cooling media was pads made
from "aspen". These were wood fibres packed together loosely that
allow air to pass through them. This was generally packed into 50mm
thick slabs within a cloth mesh and held together with a wire mesh
frame. The cooling efficiency of these pads was only about 50% and is
make cooling pads. This type also has a low efficiency of about 50%.
These types of pads also have a random water flow pattern and only a
short useful life (Premier Industries Inc, 2005). There are now new
synthetic pads in the market that offer efficiencies around 90% and are
longer lasting than their predecessors. The higher the wetting ability
the cooling pad possesses, the higher the possible efficiency of the
air-conditioner.
11
2.4 ADVANTAGES
2.5 DISADVANTAGES
world.
12
Damage can occur to rooftops if proper maintenance is not
overflow water.
health problems.
2.6 SIZING
m3/min. Bom (1999) states that the general rule when sizing a system is
to provide a change in air between one and four times every four minutes.
This rate is dependant on the wet-bulb temperatures. The higher the wet-
varies the air change requirement. A higher efficiency requires less air
room with a large window area, high sun exposure and poor insulation
would require one air change every minute. However a well insulated,
shaded room with a single window which would only require air change
every four minutes. The other cases are obviously in between these
extremes
13
The following are recommended air change rates for different wet-bulb
For wet-bulb temperatures greater than 21C, the EAC may not be able to
provide “comfortable” cooling, but rather “relief” cooling. The air change
14
3.0 MOTORS AND DRIVES
3.1 INTRODUCTION
system will operate have optimum performance. This chapter details the
belt-drives.
Permanent magnet DC motors are most useful where the required size is
less than 0.1 horsepower (74.6W), however they are more suitable for
consume power. They are easily reversed by changing the polarity of the
voltage applied to the terminals. They are capable of high-stall torque and
15
Figure 3.1: DC Motor Torque-Speed Characteristics
Each curve is a theoretical straight line since the permanent magnet field
speed varies inversely with field strength and the stall torque varies
determines the speed, and only torque will determine the current.
The operating speed can be calculated, based on the rated voltage and
16
to the voltage applied to its terminals. For example, a DC motor that is
rated at 30VDC and 2000rpm, but operated at 12V will have an operating
speed of,
Voperating
noperating nrated
Vrated
12V
noperating 2000 800rpm
30V
Pulleys are particularly useful for altering the speed at which the
driven shaft is rotating. The drive shaft speed can either be reduced
equation is,
Speedmotor
Speedload
Ratiopulley
17
by a moment arm. In the case of a pulley, the length of the moment
size of the pulley. If the load remains constant, but the pulley size
machinery. They are useful when the speed of the driven shaft is
different from that of the driver shaft and when there is a distance
3.3.3 PRELOAD
A belt drive requires residual tension in the "loose" span of the belt in
order to operate properly. This can never be allowed to get near zero
otherwise the belt drive will not function properly. To counter this
is unlike chain drives that actually have loose spans. In V-belt drives,
the preload maintains the contact force between the belt and the
surface of the pulley so that friction can transmit the power. In tooth-
belt drives, the preload maintains the correct contact pattern between
the belt teeth and sprocket grooves. This is required to keep the teeth
18
centre-line distance between the pulleys or by using an idler which
imposes a side load on one of the spans. V-belt drives usually require
3.3.4 V-BELTS
between the belt and the pulley. The friction force between the belt
and the pulley depends on the size of the normal force between the
belt and the pulley; the coefficient of friction between the belt and the
pulley; and the arc of contact between the belt and the pulley. The
of the shape of the belt, but the normal force between the belt and
sides of the pulley sheave depends on the angle between the sheave
3.3.5 TOOTHED-BELTS
19
s p r o c k e t , t h e m a xi m u m t o r q u e t o b e t r a n s m i t t e d , a n d t h e
3.3.6 CONSTRUCTION
construction rubber flat belts have better stretch resistance than plied
20
4.0 PHOTOVOLTAIC THEORY
Careful assessment of the solar radiation at the site where the PV system
Irradiance is the total power from a radiant source falling on a unit area.
The average energy that strikes the Earth’s surface perpendicular to the
However, not all of this energy reaches the Earth’s surface due to
(aerosols). The energy that reaches the surface in a direct line from the
diffuse radiation. Some radiation can reach the receiver after it has
reflected from the ground, known as albedo. The total radiation of these
21
Figure 4.1: Solar radiation in the atmosphere (Markvart, 2000)
The amount of radiation that reaches the ground is highly variable due to
An air mass of 1 (AM1) exists when it is a clear day at sea level and the
sun is at zenith. At most times, the sun is at an angle relative to zenith, z,
and will result in an air mass greater than 1. The standard air mass for
22
calibrating photovoltaic modules is AM1.5, since this is a typical solar
Due to the Earth’s rotation around the sun in an elliptic orbit, and its
equator, the motion of the sun can be pictured as following this path
Energy from the sun has been used to generate electricity since 1861,
machine which used sunlight to evaporate water, using the steam to run a
been made in this field resulting in the photovoltaic solar cells produced
today.
23
The discovery of the first photovoltaic effect in a liquid electrolyte was by
1876. However, the first silicon cell was not produced until 1941, followed
by the first cell of similar structure to modern day cells in 1954, which was
6% efficient.
The first application for photovoltaics was as power sources for satellites
sunlight directly into electricity by the use of the photovoltaic effect. This
process involves the incident energy of the light creating mobile charged
24
particles in the semiconductor, which are then separated by the device
There are many different solar cells commercially available, with many
4.5 SEMICONDUCTORS
4.5.1 INTRODUCTION
P h o t o vo lt a i c c e l l s a r e p r o d u c e d f ro m m a t e r i a l s k n o wn a s
that they are somewhere between good conductors like metals, and
such as cadmium telluride and copper indium diselenide are still being
25
processes required (Markvart, 2000). Crystalline cells have a
materials.
each atom has four its four nearest neighbours at the vertices of a
utilises the four outer valence electrons. Each bond contains two
Quantum theory states that the energy of an electron must fall within
certain well-defined bands. The electrons which form the bonds of the
lattice structure are in the energy band known as the valence band
(EV). The next highest band is known as the conduction band (E C).
bandgap (EG).
EG = EC - EV
26
Figure 4.4: Band structure in semiconductors
number of electrons to fill the valence band and the conduction band
is empty. Electrons cannot move from the full valence band because
silicon, which promotes one electron from each impurity atom to the
Electrons in the conduction band are mobile and the crystal becomes
27
The banding is in equilibrium, and there is no current flow through the
junction.
potential barrier between the two junctions. A forward bias results from
the potential barrier and only a tiny current is allowed to flow. This is
28
qV
I I0 exp 1
kT
hc
E ph ()
its wavelength. Only photons with energy greater than the bandgap
promoted from the valence band into the conduction band. A hole is
then left in the valance band and an extra carrier exists in the
decay to states near the edges of the their respective bands. As these
conversion process.
29
Figure 4.7: Current flow in external connection
electron along the connection to the p-side to refill the hole left from
the displaced electron. This results in a net current and voltage to exist
between the two sides of the junction. Neglecting losses, each photon
Il qNA
exposed to light.
V Eg / q
30
4.6 SOLAR CELLS
4.6.1 INTRODUCTION
means of contacts at both the front and back of the cell. At the front
they are spaced widely and are made from very thin strips of metal to
terminals.
current through the p-n junction and the output current is therefore the
qV
I I lIo exp 1
kT
The effect that illumination has on the cell can be seen in the IV
into the negative region of the graph by the illumination current. This
31
Figure 4.8: Cell IV characteristics compared to a diode
For a given irradiance and temperature and cell size, there are two
limiting factors of output. These are the short-circuit current and open-
current and this occur when the voltage is zero. In an ideal cell, when
I=0,
kT Il
VOC ln
O 1
q I
where Vm and Im are the voltage and current at the maximum power
point. The quality of the solar cell can be referred to by the value of
32
the fill factor. The higher the fill factor is, the higher the quality of the
cell.
the effect of the ambient temperature around the cell must be allowed
negligible.
33
Figure 4.10: The effect of temperature
34
4.6.4 EFFECT OF SHUNT AND SERIES RESISTANCE
A series and shunt resistance exists inside solar cells. This resistance
characteristics below.
35
5.0 STAND ALONE PHOTOVOLTAIC SYSTEM COMPONENTS
5.1 BATTERIES
5.1.1 INTRODUCTION
Solar modules are devices that can be utilised to generate power from
only available for part of a day, and so the power output of solar
modules are severely limited. Even during daylight hours, the sun’s
output from the solar cells, such as at night time. Energy storage
can be sized accordingly, and the type of storage can be chosen. The
storage device should be sized such that it will cope with several
Solar systems generally use deep cycle batteries because they are
36
crucial factor when determining the size of a battery required for a
system. The DOD in a deep cycle battery should not fall below 60-
5.1.2 LEAD-ACID
5.1.2.1 INTRODUCTION
the amount of chemical reactions the lead can achieved with the
electrolyte. The positive plate is made from the lead oxide and the
negative from the lead. Two chemical reactions are created which
37
As can it can be seen from the chemical equations, during charge
forms at the anode, pure lead at the cathode and the sulphuric acid
Pure lead plates are used where low discharge is required and
has a long life span; however, they must be handled carefully due
to the soft nature of the plates. They are easily broken if care is
not taken.
Lead calcium plates are used where the battery is not frequently
deeply discharged. The life span of is slightly less than that of pure
lead plates. However, due to the doping of calcium they are not
38
only cheaper, but also much stronger and less susceptible to
damage.
Lead antimony plates are made from lead doped with antimony.
Similar to calcium, this also decreases the cost and adds strength
deeply, and thus require to be almost fully charged all of the time.
These type of batteries are not used in PV systems for this these
reasons.
5.1.2.3 CYCLING
The life span of a lead acid battery is greatly affected by the cycling
and can be a safety hazard. The reason for this is what is known
39
characteristics for charging and discharging are shown in the
figures below.
5.1.2.4 ADVANTAGES
40
When maintained and used properly, are long lasting and
durable.
options.
5.1.2.5 LIMITATIONS
They have a low energy density. They are quite heavy for
with a DOD typically between 30 and 70% and have a life span of
41
for such large discharge characteristics and a deep discharge will
5.1.3 NICKEL-CADMIUM
5.1.3.1 INTRODUCTION
plate is made from the nickel hydrate; the negative is from the
which they are used and the environment which they must operate.
42
overcharged and fully discharged over considerable time without
5.1.3.2 ADVANTAGES
1000 cycles.
storage.
They have a long shelf life since they are not affected by
self discharge.
43
They have a low cost per cycle compared to other batteries.
5.1.3.3 LIMITATIONS
44
Figure 5.6: Typical curve of battery voltage w.r.t Battery
SOC (Lawrance, 2005)
Charge regulators are used for the purpose of regulating current flow from
the solar panels for the purpose of protecting the battery in a system
gassing and loss of electrolyte, and can result in damage to the battery.
The device disconnects the load from the battery if the voltage drops
below a pre-set minimum. The load is not reconnected until the voltage
has risen significantly past the pre-set value. The purpose of this process
is to ensure that the battery has a chance to recharge before the load is
The charge regulator also limits the maximum voltage that is supplied by
is not necessary for most systems unless there is a vast contrast in size
between array and the battery capacity. Therefore the voltage regulation
45
that is required can be achieved by use of either a shunt or series
regulator.
and battery. As the battery is being charged and the battery voltage
voltage and current. Since the voltage across the resistor is only small
in parallel with the battery and PV array. However, this combination may
current from the PV array is diverted through the resistor and less through
the battery. For both types, the variable resistance element is generally a
MOSFET transistor.
46
Figure 5.7: Shunt and Series Regulators
A maximum power point tracker (MPPT) is a device that ensures that the
power output is achieved when the load resistance is matched with the
shown below.
Vout PMAX R
47
Figure 5.8: MPPT system configuration (Lawrance, 2005)
5.4.1 INTRODUCTION
angle and the tilt angle are two variables that need to be considered
when designing a system. The tilt angle is the angle between the
plane of the module and the horizontal. The azimuth angle is the
angle between the plane of the module and the shortest line to the
equator from the position. This is due n orth for the southern
hemisphere and due south for the northern hemisphere. The tilt angle
chosen should provide maximum power output from the system. This
48
is obtained when the array tilt angle is roughly equal to the latitude
the sun’s path across the sky. The tilt angle can be fixed at a certain
system will only be used in summer, the seasonal tilt adjustment of -10
Table 5.1: Seasonal tilt angles and adjustments for 32deg latitude
Site
Season Latitude Adjustment Tilt Angle
Summer 32 deg -10 deg 22 deg
Autumn 32 deg 0 deg 32 deg
Winter 32 deg +15 deg 47 deg
Spring 32 deg 0 deg 32 deg
49
Figure 5.10: Summer tilt adjustment for 32 deg latitude
This is the case the tilt angle of the photovoltaic array is fixed all year
round.
5.4.3 TRACKERS
continually follow the motion of the sun. Most arrays are fixed at a
specific tilt angle, whilst facing the equator. This option is the most
can increase the output of an array by up to 40%. This varies the tilt
angle based on the time of year and the inclination of the Sun’s path
50
across the sky, whilst also tracking it during the day from East to West.
A single-axis tracker only tracks the sun across the sky at a set tilt
the year in order to maintain a high output. This method yields almost
the basis of a gas system. The Sun’s warmth causes the motion of
Freon gas from one vessel to another via a small pipe. This
When the sun rises at dawn, the resultant warmth causes the module
to flip back to its starting position for another day of tracking. These
therefore the benefits of the extra output must be weighed against the
costs. For this reason, fixed arrays are more commonly used for solar
systems.
51
6.0 SYSTEM SIZING
6.1 INTRODUCTION
design. The capital cost of solar system is the largest component when
pricing solar electricity. The capital cost has a direct influence on the
the correct size components are used to minimise the overall capital cost.
follows:
The following details the sizing of the solar evaporative air-conditioner for
system will be sized, due to the recommendations from the result of the
52
The total average irradiation on an inclined plane at plane angle of 20
Therefore the average total daily irradiation for summer will be,
6.3.1 INTRODUCTION
The load is the combination of load currents from the electrical devices
are in parallel with the battery and can therefore be added to yield a
total system load. The load will be run for an average of 8 hours per
day.
53
Table 6.2: 12V System load
PART QTY CURRENT (A) POWER (W)
Flojet water pump 1 1.3 15.6
EMP Fan motor 1 8.7 104.4
Totals: 10.0 120.0
12V,
Furthermore,
So if the system is run for eight hours per day, the total energy
6.3.2.2 PV SIZING
are most suitable to the system. The prototype will be tested using
54
modules are used, they have much higher Vmax voltages, since
DC-DC converter. This would add extra cost to the system, and so
for this system. The data for several modules sizes is shown
below.
BPSX60
as follows.
2
The power produced by 1m of BPSX60 PV module is,
PPV max 60 2
PPV,1m2 120.00W / m
AreaPV 0.500
55
ElectricalPowerOutput
100%
SolarPowerStrikingCell
120.00
100% 12.0%
1000
2
The electrical energy that is produced by 1m of BPSX60 at 12.0%
efficiency is,
3.372 1000 2
EPV 0.937kWhr / m / day
3600
2
Hence 1m of BPSX60 PV modules will produce
2
0.937kWhr/m /day of power. Therefore one panel will produce,
960
No 2.05
468
to power the system. Two modules would limit the system to being
run for slightly less than full 8 hours per day, and would be a more
56
power would be greater than required. The decision is ultimately a
BP380
2
The power produced by 1m of BP380 PV module is,
PPV max 80 2
PPV,1m2 142.22W / m
AreaPV 0.562
ElectricalPowerOutput
100%
SolarPowerStrikingCell
142.22
100% 14.22%
1000
efficiency is,
57
Converted from MJ to kWhr,
3.996 1000 2
EPV 1.110kWhr / m / day
3600
2 2
Hence 1m of BP380 PV modules will produce 1.110kWhr/m /day
960
No 1.54
624
A suitably sized battery must be found that can effectively run the
determined.
Wh / day 960
Ah / day 80.0Ah / day
Vsystem 12
days during the summer months in Perth, and so sizing for only
58
Therefore the amount of ampere-hours the system is required to
store is,
80.0
Capacity 133.33Ah
0.6
A gel cell 12V 150Ah battery has therefore been chosen for the
system.
From this sizing method it can be seen that a 12V evaporative air-
250W 30VDC EMP fan motor, a 150Ah 12V gel cell deep cycle
modules.
than that of the 12V system. Several assumptions are made about
the system:
supply.
59
The 12V Flojet pump could be powered from one of the 12V
assumed to be 24.0V,
Furthermore,
So if the system is run for eight hours per day, the total energy
60
6.3.3.2 PV SIZING
BPSX60
as follows.
produce,
1977.60
No 4.23
468
BP380
produce,
1977.60
No 3.17
624
61
Therefore either 3 or 4 BP380 modules could be used to power the
system. Three modules would limit the system to being run for
slightly less than full 8 hours per day, and would be a more
Two suitably sized batteries must be found that can effectively run
system:
determined.
Wh / day 1977.60
Ah / day 82.4Ah / day
Vsystem 24
days during the summer months in Perth, and so sizing for only
store is,
62
To avoid over draining the batteries, the depth of discharge is
82.4
Capacity 137.33Ah
0.6
Since the batteries are in series, the current will be the same in
From this sizing method it can be seen that a 24V evaporative air-
250W 30VDC EMP fan motor, two 150Ah 12V gel cell deep cycle
modules.
63
7.0 SIMULATION
7.1 INTRODUCTION
Matlab Simulink software was utilised for the simulation of the solar -
suitably sized pump and fan motor. Furthermore, the model could be
components had been sized. The unit could be tested under differing set-
viewed in Appendix F.
A model for a BP280 PV array has been developed for the purpose of
64
The model is broken down into a hierarchical structure that consists of all
the equations that exist in a PV cell. The governing equation for this
model is,
MS MP
Model Inputs Model Outputs
G Tc
Ta PV ARRAY
VPVA IPVA
Level 1
G, Ta , VPVM IPVM, Tc
NS
PV MODULE
NP
Level 2
G, Ta , VPVC IPVC, Tc
RS
PV CELL
RSH
ILG,Tc ID Level 3
G, Ta VPVC, IPVC, Tc
T RS
r Ior
I Calculation of Calculation of Tr
SCR I I
LG D EG
It A
Level 4
G, Ta Tc
NOCT Calculation of
Tc
Level 5
65
The inputs to this equation are also a resultant of other input variables
that are consistent with the BP280 module, and the array formation
Variation of the number of series and parallel cells that form the module
66
7.3 EVAPORATIVE AIR-CONDITIONING SYSTEM SIMULATION
7.3.1 INTRODUCTION
model.
7.3.2 INPUTS
7.3.2.1 INTRODUCTION
Look-up Tables
there were 96 different values for each input. These values were
67
Figure 7.5: Look-up tables used as inputs in simulation
7.3.2.2 IRRADIANCE
G. The values are averaged hourly and are in Watts per square
metre. The data has been used four times to represent four
68
consecutive fine days. As will be seen later, this data was also
[0 0 0 0 0 108 548 752 879 935 976 990 1004 1001 988 947 843
674 208 0 0 0 0 0 0 0 0 0 0 108 548 752 879 935 976 990 1004
1001 988 947 843 674 208 0 0 0 0 0 0 0 0 0 0 108 548 752 879
935 976 990 1004 1001 988 947 843 674 208 0 0 0 0 0 0 0 0 0 0
108 548 752 879 935 976 990 1004 1001 988 947 843 674 208 0
0 0 0 0]
The values are averaged hourly and are in degrees Kelvin. The
data has been used four times to represent four consecutive days
69
Look-up table input data
[294.1 293.4 292.1 290.9 289.6 288.8 288.6 290.1 292.3 295.6
298.8 300.8 302.4 304.0 304.2 303.3 302.1 301.1 300.0 298.9
297.8 296.6 295.7 294.8 294.1 293.4 292.1 290.9 289.6 288.8
288.6 290.1 292.3 295.6 298.8 300.8 302.4 304.0 304.2 303.3
302.1 301.1 300.0 298.9 297.8 296.6 295.7 294.8 294.1 293.4
292.1 290.9 289.6 288.8 288.6 290.1 292.3 295.6 298.8 300.8
302.4 304.0 304.2 303.3 302.1 301.1 300.0 298.9 297.8 296.6
295.7 294.8 294.1 293.4 292.1 290.9 289.6 288.8 288.6 290.1
292.3 295.6 298.8 300.8 302.4 304.0 304.2 303.3 302.1 301.1
300.0 298.9 297.8 296.6 295.7 294.8]
entered that was multiplied with the loading profile to give the
70
Look-up table input data
[0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
111111110000000000000000111111110000
0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 0]
7.3.3 BATTERY
shown in the figure below. This model is however very limited and is
71
understood that this only a very simplistic model and accurate results
Product - The product block is utilised to multiply two inputs and output
the resultant.
Integrator – The integrator block is used to sum inputs over the period
of the simulation and output the total. In the system simulation, this
block was used to simulate a charge regulator for the battery. The
upper limit is set to the maximum battery capacity, whilst the lower
72
limit is set to 20Ah to simulate a charge regulator disconnecting the
Sum – The sum block used to subtract one input from another, and
resultant.
7.3.5 OUTPUTS
7.3.5.1 INTRODUCTION
73
Display – The display block shows the final output in numerical
form.
The cell temperature is a direct output from the array model and
The array current was also a direct output of the array model and
74
7.3.5.4 ARRAY POWER
The array power was output from a product block which had an
The battery voltage is output from the battery voltage equation that
subtracts the load current from the PV current. The resultant is the
charging current of the battery and can be seen in the figure below.
75
7.3.5.7 BATTERY CAPACITY
simulation.
below.
76
equivalent value of energy generated and consumed by the
tariff of 13.94 cents per kWh was multiplied by the energy curves to
for this purpose, and the costs are superimposed over the solar-
7.4.1 INTRODUCTION
allowable load current and power that could be utilised to run both the
77
water pump and the fan motor under various scenarios. As the fan
motor had not been purchased at the time, it was necessary to first
estimate the maximum power that the motor could draw so that a
The maximum draw current possible without full battery discharge was
78
Therefore the maximum current rating for the fan motor would be 19 -
maximum value each day under this loading; however any increase
For this simulation the number of parallel modules simulated was 2.25.
the same as 1 failed 60W PV. Once again, the system was tested to
the point where the battery capacity only just regains a maximum
79
Figure 7.20: Battery capacity over 96 hours
rating for the fan motor would be 14.7 - 1.3 = 13.4A. This corresponds
As can be seen below, the first day’s irradiation levels have been
capacity. Since the battery will be receiving very little input power
during the first day of operation, the system will be running off the
battery for eight hours. The battery level should not fall below a depth
80
Look-up table input data
This simulation showed that 12.7A can still be drawn from the battery
on a cloudy day and the system will still recover and not cause
81
To test the necessity of a battery with such a high amp-hour rating, a
This simulation showed that 9.7A can still be drawn from the battery
on a cloudy day and the system will still recover and not cause
damage to the battery. From this, it can be seen that a higher amp-
conditioning system.
From these three tests, a motor was chosen such that the maximum
output power could be gained, but the total load current was less than
the smallest maximum load current that met all three criteria. These
results have shown that the system should be successful even in the
82
the constant power draw of the fan motor does not exceed 152W, then
Tests revealed that there is very little difference in running the system
than that which is being fed back into the system by the PV array
during the day, then the system will continue to operate. Even if there
is a cloudy day, 12.7A can still be drawn from a 150Ah battery for the
higher than the previous day. However, the system may actually be
loaded higher if the unit is not used on every one of the four days or if
it is used for less than eight on a particular day. If the system has time
will be greater. It is unlikely that the system will be used for 8 hours a
day, for four consecutive days, and therefore higher load currents may
7.5.1 INTRODUCTION
83
permanent magnet DC motor rated at 10A continuous and 2000rpm.
operating current. The approximate total current draw of the fan motor
From the system costing analysis in Section 9.2, the decision was to
The system was simulated for eight hour daily usage and under
average irradiation and temperature. The battery capacity did not fall
84
Figure 7.25: Battery capacity over 96 hours
The energy balance showed that the system has ample generated
than the energy generated over the 96 hour period, and so the net
85
The equivalent energy costing curve indicates that the system energy
will cost $2.23 less to run than a mains-powered unit, and the energy
value of $0.60.
temperature experienced.
86
It was found that the maximum daily usage is ten hours, rounded to
the nearest hour. The following figures show the battery capacity
seen that during 11 hour usage, the battery capacity falls away each
day and the system would not be able to maintain the demand.
change.
87
Since the loading period is at a maximum, the difference between the
very similar. However, since the loading profile is longer than usual,
the cost of the equivalent mains-powered unit also increases and the
88
Figure 7.34: Total energy costing over 96 hours
If one of the PV modules were to fail, and the system only received
half the generated power the system would not be able to maintain
normal loading. The array power would halve due to the loss of the
generated by one module, the battery capacity would drop over the
89
Figure 7.36: Battery capacity over 96 hours
Since the generation of energy has halved, the cost of the energy
remains the same as before since the load has not altered.
90
Figure 7.39: Equivalent energy costing over 96 hours
This simulation has shown that the failure of one PV module will cause a
dramatic effect on the usability of the system. The loading profile will
modules are inherently reliable and low maintenance, this issue should
even in the summer months. For this reason, the system should be
91
Figure 7.41: Array power over 96 hours
The simulations found that the sizing of the battery was substantial
used to power the system during the period of poor irradiation and falls
the following day has good irradiation levels. As can be seen in the
figure below, the system takes several days to recover full battery
The energy balance shows that the energy consumed by the system is
greater than the energy generated for almost all of the 96 hour period;
92
however, the battery supplies the extra energy required by the system,
93
7.5.6 CONCLUSIONS / FINDINGS
consecutive cloudy days are experienced, then the system loading will
94
8.0 PROTOTYPE MODEL
8.1 INTRODUCTION
constructed based on the system sizing that had been conducted. The
This chapter details the construction and testing of the prototype system.
cooling pads and frames being stolen from the university. Due to the
limitation of time and money in this project, this posed a crucial problem.
Replacement pads and frames of affordable cost could not be found and
95
8.3 SYSTEM COMPONENTS
system, with a centrifugal fan and three cooling pads. The objective
such that the output of the system would be comparable with the
original.
Due to monetary constraints, the pump that was used in the original
96
room evaporative air-conditioner was utilised. This was a Flojet 12V
pump was 1.3A and is relatively inefficient, this would simulate a more
efficient pump that can displace more water. The reduced water flow
would only have a small effect on the operation of the system, and
appropriate. There are other pumps in the market that would be more
97
8.3.3 FAN MOTOR
The original fan motor was a Brook Crompton Parkinson 550W single-
fan was connected to the motor by a belt drive and operated at 300-
500rpm (low/high).
The new motor chosen for the system was an EMP 30VDC 250W
12V, it will operate at a fraction of the rated speed. This motor is not
the most ideal for the situation, however due to the 30VDC rating; it
98
Figure 8.7: The new DC fan motor
8.3.4 BATTERY
The prototype system was tested with a 12V 150Ah Gel Cel deep
cycle battery. The loads were connected in parallel with the battery,
Figure 8.8: The 12V 150Ah Gel Cell Battery used in the
prototype system
99
8.3.5 SOLAR MODULES
Four BPSX60 60W solar modules were utilised in the testing of the
run all day since the power output of the array is affected by shading
the prototype system. This charge regulator used a three stage pulse
series with the PV array to control the charge of the battery. However,
it was not used to disconnect the load if the battery capacity fell too
switch.
100
8.4 BELT DRIVES AND PULLEYS
8.4.1 INTRODUCTION
The original system utilised a V-belt drive to link the fan motor and the
speed. The optimum speed that was desired was around 500rpm and
so this was set as the target to achieve. The pulley size on the fan
was fixed as this was too hard to replace, due to its size and the
diameter, and so using this figure, a suitable fan pulley size could be
determined.
Voperating
noperating nrated
Vrated
101
12V
noperating 2000 800rpm
30V
800
Ratio pulley 1.6 :1
500
Since the fan pulley is fixed at 232mm in diameter, the required motor
232
145mm
1.6
This motor pulley size was implemented and tested. However, it was
found that the current drawn by the motor was 16.7A, which is well in
be chosen that would limit the current to less than 10A, whilst
figure below.
102
The pulley variations were tested initially on a 12V system, but also on
yield the desired fan speed. A problem arose whereby the motor
became highly loaded due to the tension of the V-belt. The V-belt was
the motor and therefore a higher load current was experienced. The
24V system was not tested any further since the required fan speed
Table 8.1: The effect of pulley size on load current and speed
Motor Motor Fan
Pulley Pulley Battery Load speed speed
Size Voltage Current
(mm) Ratio (V) (A) (rpm) (rpm)
12V
From these results, an approximate pulley size for a 12V system could
below the rated current. Appendix B shows the graph of these results
and shows the selected pulley size, the theoretical fan speed and the
load current. From this it was clear that a pulley size of 110mm would
A 108mm pulley was selected for the unit as this was the closest size
103
available. This pulley selection proved correct, with the fan speed at
The selected 108mm motor pulley was attached to the fan motor and a
suitable length V-belt was used to connect it to the centrifugal fan. The
motor position was then adjusted to give a suitable tension on the belt.
The water pump was mounted to the side of the fan housing to ensure
that it was in a semi-dry position. Hosing was then attached, with one
end inserted into the water sump and the other to the water distribution
system in the unit’s roof. The electrical wiring was then attached to both
the fan motor and the water pump and ducted out of the unit. Shade cloth
was then used as a replacement for the absent cooling pads, such that
the water would have a surface to flow down and into the water sump.
easily malleable and allows airflow through it. The completed air -
104
8.6 FULL PROTOTYPE SYSTEM TESTING
8.6.1 INTRODUCTION
The system was tested during a partially cloudy day in late April for a
period of two hours. Due to the lack of proper cooling pads, the
system inherently leaked water and could not be tested for any
The desired centrifugal fan speed of 500rpm was not achieved, as the
actual speed ranged from 325-350 rpm. Event thought the system
105
8.6.3 ELECTRICAL PERFORMANCE
The results of the prototype test with four BPSX60 60W PV modules
Appendix D.
The results of the prototype test with three BPSX60 60W PV modules
Appendix C.
sunlight returns.
10A for the entire test, and had a maximum deviation of 0.5A.
106
Battery Charge – The rate of discharge and charge of the
107
Since the output ducting is 0.4m by 0.355m, the cross-sectional area
is,
be able to output this quantity of air per minute. Using the same
500 3
Air output500rpm 37.15 57.15m / min
325
150 3 3
Air outputEquiv 37.15 98.42m / min 100m / min
57.15
108
9.0 FEASIBILITY STUDY
9.1 INTRODUCTION
levels are above 1000W/m2, thus making it an ideal location for a solar
details the cost of setting up such a system in Perth, and analyses its
economic viability.
9.2.1 INTRODUCTION
implemented.
water pump, a 250W 30VDC EMP fan motor, a 150Ah 12V gel cell
deep cycle battery, and either three BPSX60 60W or two BP380 80W
PV modules.
109
9.2.3 24V SYSTEM
water pump, a 250W 30VDC EMP fan motor, two 150Ah 12V gel cell
deep cycle batteries, and either five BPSX60 60W or four BP380 80W
PV modules.
9.3.1 INTRODUCTION
The 12V system is far more economically viable than the 24V system
For the implementation of the 12V system, the capital cost for the
One BPSX60 60 W PV module costs $530, and so the cost per Watt
is:
$530
$8.33 /W
60
110
Therefore 20W of power would have a theoretical value of:
This is much less than the $240 that would otherwise have to be paid
The itemised costing for the 12V system is shown in the table below.
The 24V system has a capital cost of between $4468 and $4518. This
system will operate with greater performance than the 12V system, but
111
This is far more than the $50 that would otherwise have to be paid to
The itemised costing for the 24V system is shown in the table
following.
From this costing analysis, it can be seen that the opt imum 12V
system will cost $2692. The optimum 24V system will cost $4518.
9.4.1 INTRODUCTION
assessing its pay back period. This is the time that is required to pay
back the initial capital cost with the savings that the system produces.
112
9.4.2 12V SYSTEM
T h e p o we r co n su m p t io n o f t h e 1 2 V s yst e m o ve r 4 d a ys is
4.307
1077Whrs / day 1.077kWhrs / day
4
Assuming that the Western Power A1 Tariff, the cost per kWhr of
electricity is 13.94 cents, the cost of the power consumption per day
will be,
2692
17934days
0.1501
Assuming the unit is only used approximately 90 days per year over
17934
199.3years
90
From this analysis, it is clear that the unit will never recover its capital
113
(Bintec Pty Ltd, 2002). A comparison can be achieved by calculating
the average yearly cost of both systems. This will include capital
Therefore the cost per year for operating for 90 days during the
be $50 per year. The operating cost of the solar-powered unit is nil,
114
however it requires replacement of the battery approximately every
five years.
By this cost analysis it can seen that the solar-powered unit becomes
th
cheaper on an average total cost per year basis at the 17 year.
The power savings of the 24V system would be greater than that of
the 12V system; however the capital costs are much higher. The
resultant pay back period would be far greater than the 12V system.
by selling excess energy back into the electricity grid. Since the load
would be zero in months other than summer, this energy is unused. This
energy could be utilised to help pay back the system costs faster.
However, the cost involved in the set up of such a grid connection would
be far too high to make it feasible for a small system such as this one.
targeted at customers who have no grid connection, those who want more
115
reliability in their cooling demand, and/or those who wish to make a
powered unit will show that the solar unit is far superior in an
manufacturing the units, the two units have been compared on several
21kg of CO2e.
The solar powered unit does not require any coal to be burnt and hence
to,
116
360kWh 1.114kg 401.4kg of CO2 gas/year.
The environmental benefits of the solar unit are therefore significant over
the life of the unit. A graph of these values over 20 years can be viewed
in below.
117
10.0 CONCLUSION
10.1 INTRODUCTION
level. Various changes to the design can be made to give the system far
better performance.
The 12V prototype system was capable of outputting sufficient cooling for
two to three rooms. This fell short of the desire to cool an entire
household.
10.2.1 INTRODUCTION
The major limiting factor encountered was that of the belt drive. Since
fan motor, the type of belt and pulley system utilised did not required
to connect the fan motor to the centrifugal fan. V-belt drives are a
118
relatively inefficient means of delivering power to the load. The
loading causes the motor to operate above rated torque and the
The testing of the prototype system was limited due to the absence of
appropriate cooling pads. This meant that the system could not be run
for any extended length of time due to water leakage. It was sufficient
more, compared with $0.1394/kWh for power from the grid. PV systems
are most likely to be cost effective where grid power does not yet reach.
119
prototype unit, whereby an old AC system is converted to DC, then the
scale and a mark-up placed on the system costs, then the unit may not be
10.4.1 INTRODUCTION
for periods of poor solar radiation. The unit could easily be connected
to the grid to top up battery levels if they fall below the required level
because of poor solar power output. Simulations can be run with solar
The system voltage utilised should be 24V rather than the 12V tested
with the prototype. This will allow the fan motor to be used to a higher
120
performance level, and increase the centrifugal fan speed to the
desired 500rpm. The system would require two 12V batteries and as
such would increase system costs. The 24V system would require an
smaller pulley on the fan motor and as such an alternative belt drive
The belt should be a tooth drive rather than a V -drive. This will
decrease the additional load that the drive applies on the fan motor.
Tooth drives are more flexible and do not require much tension to
prevent the belt from slipping. They are therefore more efficient and
The performance of the Flojet water pump was sufficient for the testing
of the prototype system. However, the current draw from the pump
pumps with 4.5L/min rating could be sourced that have about half the
power rating. The water pump in the solar unit should be equivalent in
121
Alternatively, the pump could be driven from the fan motor. This
would decrease the load current and increase the efficiency of the
system.
A fan motor that has an optimised speed at the system voltage will
increase the performance of the unit. The prototype fan motor was
rated at 30VDC, whilst the system voltage was only 40% of this value.
The unit design should be altered such that a large axial fan can be
utilised rather than a centrifugal fan. Axial fans are more efficient
since they are a direct drive from the motor. The efficiency
122
11.0 BIBLIOGRAPHY
Bintec Pty Ltd., 2002, Airconditioners. Retrieved May 17, 2005, from
http://www.thisplace.com.au/priceguide/aircond.htm.
Bom, G., Foster, R., Dijkstra, E., Tummer-s, A., 1999, World bank
technical paper No. 421, Evaporative Air-Conditioning Applications for
Environmentally Friendly Cooling. Retrieved: February 26, 2005, from
www.worldbank.org.
EPI Inc, 2004, Properties of belt drives. Retrieved: May 21, 2005, from
http://www.epi-eng.com/BAS-BeltDrives.htm.
123
Leading Outdoor Technology Supply LLC, 2005, Deep cycle batteries.
Retrieved: April 27, 2005, from
http://www.4lots.com/index.asp?PageAction=VIEWPROD&ProdID=86
5.
Solar Valley Electronics, 2005, Solar panel pricing. Retrieved: April 24,
2005, from http://www.solarvalley.com.au/solarpanelspricing.htm.
124
Sustainable Village, Shurflo water pump prices. Retrieved: April 27,
2005, from
http://www.thesustainablevillage.com/products/catalogs/vol1no1/scree
n/02_SV_2002_Water.pdf.
125
12.0 APPENDICES
12.1 APPENDIX A
126
12.2 APPENDIX B
127
12.3 APPENDIX C
128
12.4 APPENDIX D
129
12.5 APPENDIX E
130
12.6 APPENDIX F
131
12.7 APPENDIX G
Irradiation data
132
Irradiation data
133
Irradiation data
134
Irradiation data
135
Irradiation data
136
12.8 APPENDIX H
8 hrs operation
2 BP380 modules
150Ah battery
Good irradiation
137
138
TEST TWO: Maximum daily usage
10 hrs operation
2 BP380 modules
150Ah battery
Good irradiation
139
140
TEST THREE: Failure of one PV
8 hrs operation
1 BP380 modules
150Ah battery
Good irradiation
141
142
TEST FOUR: One cloudy day
8 hrs operation
2 BP380 modules
150Ah battery
Poor irradiation on the first day
143
12.9 APPENDIX I
144