Beruflich Dokumente
Kultur Dokumente
Chapter Six
Composite Strength of Prestressed Steel-
Concrete Beams
6.1 Introduction
crushing of concrete (ii) yielding of steel beam web, (iii) shear failure, (iv) rupture of
steel tendons. Out of these four failure modes, the fourth mode can be eliminated by
providing special steel anchorages at the ends of and steel deviators along the tendons
sufficient shear studs on the steel beam, to be encased in concrete. The other two
failure modes, namely, compression crushing of concrete and yielding of steel beam
web is the main focus of this study. The tendon profile and amount of prestressing
force in the prestressing tendon are of particular interest since yielding of the steel
This chapter studies the effects of the various tendon profiles of the prestressed
steel tendons for use between the steel beam and the concrete flange. The prestressing
programme involved 2-point and 4-point loading of the composite beams, each with a
different tendon profile but with the same prestressing force. The effects of different
profiles of the prestressing tendons on the ultimate load and deflection of the
89
Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
9m. The first simply-supported composite beam, Beam SS4PT, having straight tendon
profile was tested under a 4-point load to simulate a uniform loading condition while
the other two beams, with trapezoidal (Beam SSTRAP) and triangular tendon profiles
(Beam SSTRIC), were both tested under a two-point load while simply-supported.
The continuous composite beam, Beam CTBD, had a point-load on each of its 4.5m
span, while resting on three supports. The three simply-supported composite beams
were subjected to positive moments at the sagging regions between the two external
supports, while Beam CTBD experienced hogging moments in the middle support.
The prestressing tendons were placed in steel brackets welded to the bottom flanges of
all the beams and maintained at a constant eccentricity using specially-designed steel
deviators. The deviators also served to maintain the profile of the steel tendons
throughout the duration of testing and act as stiffeners for the steel web. All other
components of the composite beams used in the test programme, such as the size of
steel sections, the strength of the concrete, the amount of prestressing force applied in
each tendon and the width of the concrete flange are all kept constant for these three
beams. Results from previous experiments (Wong, 1998) involving Beam CTB
(similar in configuration to CTBD except for the deviators) and Beam CT (without
bottom prestressing tendons) will also be used for discussion and comparision.
90
Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
Beam SS4PT, of length 6.3m, consists of a rolled section UC 203 X 152 X 52,
grade 43 complying with BS4360. The beam had two rows of shear studs, 19mm
diameter and 100mm nominal height, welded to the top flange between the two
the supports spaced 6.0m apart from each other. Rockers were placed on one of the
91
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s
Deviator
6300.0
72 Shear Studs, 2 per group @ 180mm, except the pair near both ends @156mm
Load Load Load Load
150.0
20.0 203.0
32.0
26.0
D16
Chamfer R8
203.0 20.0
32.0
26.0
D16
Chamfer R8
Grade 43 Steel
152.0 152.0
Beam I
FIG 6.2 Configuration of Beam SS4PT
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s
6300.0
72 Shear Studs, 2 per group @ 180mm, except the pair near both ends @156mm
Load Load
2000.0
24.0 24.0
156 180 180 156
C
150.0 150.0
20.0 22.5
36 39.4
30.538.5
D36 D18
R8.0
R8.0
D36
20.0 203.0
93
20.0
Left Deviator Right Deviator 250.0
(Dwg 3) (Dwg 4) C
35.0
2000.0 2000.0
6000.0
A
J203 x 152 x 52
Shear Studs Diameter = 19 mm, Height = 75mm
50.0 50.0 50.0 50.0 50.0 50.0
39.0
Inner D18
Outer Chamfer D36
49.0 38.5
30.5 22.5
Inner D18
Outer Chamfer D36
B
28.0
D16
Grade 43 Steel
26.0 26.0 26.0
Section C-C
152.0
Section B-B
152.0
B Section A-A
152.0
Beam II
FIG 6.3 Configuration of Beam SSTRAP
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s
Centre Deviator
6300.0
72 Shear Studs, 2 per group @ 180mm, except the pair near both ends @156mm
Load Load
20.0 22.5
36 35.8
30.5
38.5
D36 D18
R8.0
R8.0
D36
20.0 203.0
20.0
250.0
94
3000.0 3000.0 C
35.0
6000.0
203.0
35.0
20.0
26.0
49.0 39.0
203.0
31.0 22.0
20.0
26.0
203.0
28.0
20.0
26.0 Grade 43 Steel
A
152.0 152.0 152.0
62 shear studs, 2 per group, @110mm 8 shear studs, 1 per group 62 shear studs, 2 per group, @110mm
Steel Reinforcement
A Concrete B
24.5 Top Bracket 75.5 224.5 300 300 300 251 300 300 300 224.5 75.5 24.5
130
206.2
Grade 43 Steel
BEAM 3
Section B- Section A-
Top Elevation
J203x152x52
20 72.0 72.0
42 15 42
42 15 42
39 128.0 156.0
50
50 43 50.0
R8
8
20 28 35 28.0
R8 R59.0 14.0
26.0 26.0
152.0
Front Elevation
Side Elevation
Top Elevation
42.0
15.0
Deviator Design Used in Beam I and III 42.0
(All Round Welding, Weld Thickness = 10mm) 15.0
42.0
15.0
42.0
J203x152x52
20.0 72.0 72.0
128.0
50.0 50.0 156.0
28.0 28.0
R139.0 14.0
26.0 26.0
152.0
Front Elevation
Side Elevation
Top Elevation
J203x152x52
20 72.0 72.0
42 15 42
42 15 42
39 156.0 128.0
50
43 50 50.0
R8
8
35 28 20 28.0
R59.0 R8
14.0
26.0 26.0
152.0
Front Elevation
Side Elevation
96
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
97
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
98
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
The concrete flange was 1500mm wide and 130mm thick, with two rows of
The cover distance for these two rows of rebars was 20mm for top and bottom surface.
end plates welded to the both ends of the beam using barrel and chuck anchorages.
The two tendons were each prestressed in alternative sequence until the desired
prestressing force of 100kN was reached in each tendon. Four sets of deviators were
welded to the web of the steel beam to maintain the profile of the prestressing tendon.
Two pairs of stiffeners 20mm thick and 25mm wide are welded to the steel
beam at the end supports. This was to guard against the buckling of the steel web
under the applied loads, as the theoretical buckling capacity was not sufficient to
99
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
Two 2.4m long twin spreader beams were used to provide the desired four-
point loads on the composite Beam SS4PT in conjunction with a 4.5m long spreader
beam on top as shown in FIG 6.16. As the spreader beam was huge, it was not
advisable to rest it on rockers sitting on the composite beam as this would cause
punching shear failure at the region below the rocker. Hence, the rockers were placed
100
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
_________________________________________________________________________________________________
___________________________________________________________________________________
_________________________________________________________________________________________________
___________________________________________________________________________________
UC203x152x52
Prestressed Tendons
FIG. 6.13 Front and Side View of Test Setup for Beam SS4PT
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
_________________________________________________________________________________________________
___________________________________________________________________________________
2 .0 m S p re a d e r B e a m
UC203x152x52
Prestressed Tendons
FIG. 6.14 Front and Side View of Test Setup for Beam SSTRAP
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
_________________________________________________________________________________________________
___________________________________________________________________________________
2 .0 m S p re a d e r B e a m
Rocker Support
UC203x152x52
Prestressed Tendons
FIG. 6.15 Front and Side View of Test Setup for Beam SSTRIC
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
_________________________________________________________________________________________________
___________________________________________________________________________________
Prestressed Tendons
FIG. 6.16 Front and Side View of Test Setup for Beam CTBD
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
Beam SSTRAP, of length 6.3m, consisted of a rolled section UC 203 X 152 X 52,
grade 43 complying with BS4360. As shown in FIG 6.3, the basic configuration of the
beam is the same as Beam SS4PT except for the end supports, the tendon profile and
the deviator positions. Beam SSTRAP uses a trapezoidal profile for its prestressing
tendons, hence only two deviators were required to maintain its profile. (FIG.6.14) The
anchorage end plates for the tendons at the supports were adjusted to ensure maximum
contact between the chuck and the tendons. The simply-supported Beam SSTRAP is
105
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
106
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
107
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
Beam SSTRIC, of length 6.3m, also consisted of a rolled section UC 203 X 152 X 52,
grade 43 complying with BS4360. As shown in FIG 6.4, the basic configuration of the
beam is the same is the Beam SSTRAP except for the tendon profile and the deviator
position. Beam SSTRIC is using a triangular profile for its prestressing tendons, hence
only one deviator was required to maintain its profile on each side of the web.
(FIG.6.15) The anchorage end plates used to hold the tendons at the supports were
adjusted as for Beam SSTRAP to ensure maximum contact between the chuck and the
tendons. The simply-supported beam is also subjected to a 2-point load. (FIG 6.22)
108
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
109
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
110
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
111
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
6.2.4. Beam CTBD
Beam CTBD, of length 9.3m, consisted of a rolled section UC 203 X 203 X 52, grade
43A complying with BS4360. As shown in FIG.6.1, the beam had two rows of shear
studs, 19mm diameter and 100mm nominal height welded to the top flange between
the external support and the top bracket at a spacing of 110mm. Between the two top
brackets, a single row of shear studs of the same characteristics was welded to the
flange at a distance of 300mm from each other.(FIG.6.31). The beam had three
supports, spaced 4.5m apart from each other. Rockers were placed on the two external
supports while the middle support rested on a load cell to measure the load acting on it.
(FIG.6.35)
112
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
The concrete flange was 1500mm wide and 130mm thick, with two rows of
The cover distance for these two rows of rebars was 20mm for top and bottom surface.
Six 7-wire high strength tendons, of diameter 12.7mm, were anchored to the 3
brackets attached to the top and bottom flanges of the beam using barrel and chuck
anchorages. The top two tendons were each prestressed to 100kN while the bottom
two tendons each had a prestressing force of 50kN. The steel brackets were designed
designated location (FIG. 6.29 and FIG. 6.30), and intermediate deviators were also
spaced evenly throughout the two beam spans to maintain the eccentricity of the
tendons during loading. FIG. 6.33 For Beam CTBD, the bottom tendons were
Two pairs of stiffeners 20mm thick and 25mm wide are welded to the steel
beam at the supports and one pair at the middle support. This was to prevent the
buckling of the steel web under the applied load, as the calculated buckling capacity
113
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
114
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
115
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
116
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
6.3. Material Properties
6.3.1 Concrete
The concrete used for the composite flange had a compressive strength of 40
MPa. The concrete was batched in a ready mix plant and transported to the laboratory
for casting.
gain. Eight 100 mm cubes were prepared along with the beam specimens. The beam
specimens were moist cured for three days under wet gunny sacks covered with
polythene sheets after which they were kept in the laboratory under ambient indoor
laboratory conditions. Testing was carried out after 28 days after casting. The target
strength, compressive cube strength at 28 days and during the tests were consistent
High-yield deformed T16 steel bars were prepared in the laboratory and used as
internal transverse reinforcement for the concrete flange to prevent cracking of the
The four steel sections, together with the steel anchorages, shear studs and
deviators, were all fabricated by a structural steel fabricator. The deviators also served
as stiffeners. For Beams I and II, the deviators sit directly below the loading points.
6.3.4 Instrumentation
The strain in the concrete and steel were monitored using strain gauges. For
steel, the base length of the strain gauge used is 5mm, type YFRA-5 while for the
117
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
concrete is the 60mm type PL60-11 were used. The strain gauges were mounted onto
the steel-concrete beams at locations shown in FIG. 6.37, 6.38, 6.39 and 6.40.
After the strain gauges are mounted, the formwork for the concrete flange was
assembled. The composite beams were then moved into the testing frame after the
After the formwork was assembled, the two rows of transverse rebars were
placed in the formwork and spot welded into place (FIG. 6.9). Next, the two tendons
on each side of the beam were prestressed alternatively in steps until the required
100kN prestressing force was reached in each tendon. Strain gauges wrere fixed on all
the prestressing tendons (FIG. 6.11). Using the data logger, the increase in the
prestressing force in the tendons during and after jacking could be monitored.
After preparation of the formwork, the casting of the concrete flange was
carried out with a curing period of 3 days using gunny sacks. Lastly, strain gauges are
fixed onto the concrete surfaces before the specimens are ready for testing.
118
hapter 6 Composite Strength
_________________________________________________________________________________________________
4
3
Legend
2
Type PL60-
11
1
Type YFRA-
0
26 25 24 23
14 7 Tendons
119
15 8
31
22
Suppor
21 20
27
5 11
12 18
29 28
30
9 10
16 17
FIG. 6.37 Strain Gauges and Transducers Layout for Beam SS4PT
hapter 6 Composite Strength
_________________________________________________________________________________________________
4
3
Legend
2
Type PL60-11
1
Type YFRA-5
0
26 23
25 24
15 19
120
22 31
21
Support
20 20
27
5 11
12 18
29 28
30
9 10
16 17
FIG. 6.38 Strain Gauges and Transducers Layout for Beam SSTRAP
hapter 6 Composite Strength
_________________________________________________________________________________________________
4
3
Legend
2
Type PL60-
11
1
Type YFRA 0
22 21
20 31
121
Suppo 19
27
5 11
12 18
29 28
30
9 10
16 17
FIG. 6.39 Strain Gauges and Transducers Layout for Beam SSTRIC
hapter 6 Composite Strength
_________________________________________________________________________________________________
Legend 61
Tendons 56 51
Type PL60-11 52
62 46 46 46 57
Type YFRA-5 53
58
63 45 45 45
54
64 59
65 60 55
41 74 67
42 75 68
Support
83 82 81 80
Load
13 Cell
45 40
78 73 71 66
84
80
80
Tendons Tendons
85
46 44
79 77 72 70
37 36 32 31 30 25 24 21 20 14 12 11 8 7
39 38 27 26 23 22 10 9
29 34 33 17 16 15
FIG. 6.40 Strain Gauges and Transducers Layout for Beam CTBD
hapter 6 Composite Strength Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
6.3.5 Design Criteria
2. To prevent the punching failure of concrete due to the high stress concentration at
4. To prevent flexure of the composite beam due to loss of composite action and
excessive slip.
6. To prevent local failure in concrete slab due to high stress concentration or local
7. To achieve yielding of prestressing tendons after the steel section has yielded and
8. To achieve a ductile behaviour for the composite beam after the concrete had
123