Sie sind auf Seite 1von 36

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

Chapter Six
Composite Strength of Prestressed Steel-
Concrete Beams

6.1 Introduction

Composite beams strengthened with prestressed tendons display several failure

modes as mentioned in chapter 1. These failure modes include (i) compression

crushing of concrete (ii) yielding of steel beam web, (iii) shear failure, (iv) rupture of

steel tendons. Out of these four failure modes, the fourth mode can be eliminated by

providing special steel anchorages at the ends of and steel deviators along the tendons

to eliminate stress concentrations. Shear failure can be prevented by providing

sufficient shear studs on the steel beam, to be encased in concrete. The other two

failure modes, namely, compression crushing of concrete and yielding of steel beam

web is the main focus of this study. The tendon profile and amount of prestressing

force in the prestressing tendon are of particular interest since yielding of the steel

beam web is highly dependent on it.

This chapter studies the effects of the various tendon profiles of the prestressed

steel tendons for use between the steel beam and the concrete flange. The prestressing

tendon used in the present study is of diameter of 12.7mm. The experimental

programme involved 2-point and 4-point loading of the composite beams, each with a

different tendon profile but with the same prestressing force. The effects of different

profiles of the prestressing tendons on the ultimate load and deflection of the

composite beams were determined.

89
Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

6.2 Test Programme

The experimental programme involved testing three simply-supported,

externally prestressed steel-concrete composite specimens of length 6m and one

continuously-supported 2-span externally-prestressed steel-concrete beam of length

9m. The first simply-supported composite beam, Beam SS4PT, having straight tendon

profile was tested under a 4-point load to simulate a uniform loading condition while

the other two beams, with trapezoidal (Beam SSTRAP) and triangular tendon profiles

(Beam SSTRIC), were both tested under a two-point load while simply-supported.

The continuous composite beam, Beam CTBD, had a point-load on each of its 4.5m

span, while resting on three supports. The three simply-supported composite beams

were subjected to positive moments at the sagging regions between the two external

supports, while Beam CTBD experienced hogging moments in the middle support.

The prestressing tendons were placed in steel brackets welded to the bottom flanges of

all the beams and maintained at a constant eccentricity using specially-designed steel

deviators. The deviators also served to maintain the profile of the steel tendons

throughout the duration of testing and act as stiffeners for the steel web. All other

components of the composite beams used in the test programme, such as the size of

steel sections, the strength of the concrete, the amount of prestressing force applied in

each tendon and the width of the concrete flange are all kept constant for these three

beams. Results from previous experiments (Wong, 1998) involving Beam CTB

(similar in configuration to CTBD except for the deviators) and Beam CT (without

bottom prestressing tendons) will also be used for discussion and comparision.

90
Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

FIG. 6.1 Deviators to maintain the Tendon’s Eccentricity

6.2.1 Beam SS4PT

Beam SS4PT, of length 6.3m, consists of a rolled section UC 203 X 152 X 52,

grade 43 complying with BS4360. The beam had two rows of shear studs, 19mm

diameter and 100mm nominal height, welded to the top flange between the two

external supports at a spacing of 150mm. The Beam SS4PT is simply-supported, with

the supports spaced 6.0m apart from each other. Rockers were placed on one of the

external supports (FIG 6.8) while the other support is fixed.

91
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s

Deviator

Top Plan View

6300.0
72 Shear Studs, 2 per group @ 180mm, except the pair near both ends @156mm
Load Load Load Load

150.0

Chapter Six: Composite Strength of Prestressed Steel-Concrete


B A
92

20.0 203.0

1200.0 1200.0 1200.0 1200.0 1200.0 20.0


B A
30
6000.0

Shear Studs Diameter = 19 mm, Height = 75mm


50.0 50.0 50.0 50.0 J203 x 152 x 52
203.0 20.0

32.0
26.0
D16
Chamfer R8
203.0 20.0

32.0
26.0
D16
Chamfer R8
Grade 43 Steel
152.0 152.0

Section B-B Section A-A

Beam I
FIG 6.2 Configuration of Beam SS4PT
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s

Left Deviators Right Deviators

Top Plan View

6300.0

72 Shear Studs, 2 per group @ 180mm, except the pair near both ends @156mm
Load Load

2000.0
24.0 24.0
156 180 180 156
C
150.0 150.0

Chapter Six: Composite Strength of Prestressed Steel-Concrete


D16

20.0 22.5
36 39.4
30.538.5

D36 D18

R8.0
R8.0
D36

20.0 203.0
93

20.0
Left Deviator Right Deviator 250.0
(Dwg 3) (Dwg 4) C
35.0

2000.0 2000.0

6000.0

A
J203 x 152 x 52
Shear Studs Diameter = 19 mm, Height = 75mm
50.0 50.0 50.0 50.0 50.0 50.0

39.0
Inner D18
Outer Chamfer D36

49.0 38.5
30.5 22.5
Inner D18
Outer Chamfer D36
B
28.0
D16
Grade 43 Steel
26.0 26.0 26.0

203.0 20.0 203.0 20.0 203.0 20.0

Section C-C
152.0

Section B-B
152.0

B Section A-A
152.0

Beam II
FIG 6.3 Configuration of Beam SSTRAP
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s

Centre Deviator

Top Plan View

6300.0
72 Shear Studs, 2 per group @ 180mm, except the pair near both ends @156mm
Load Load

Chapter Six: Composite Strength of Prestressed Steel-Concrete


150.0
24.0
C
D16

20.0 22.5
36 35.8
30.5
38.5
D36 D18

R8.0
R8.0
D36

20.0 203.0

20.0
250.0
94

3000.0 3000.0 C
35.0
6000.0

Shear Studs Diameter = 19 mm, Height = 75mm

50.0 50.0 50.0 50.0


A
50.0 50.0
J203 x 152 x 52
Inner D18
Outer Chamfer D36
Inner D18
Outer Chamfer D36
B D16

203.0
35.0

20.0
26.0
49.0 39.0

203.0
31.0 22.0

20.0
26.0

203.0
28.0

20.0
26.0 Grade 43 Steel
A
152.0 152.0 152.0

Section C-C Section B-B B Section A-A


Beam III
FIG 6.4 Configuration of Beam SSTRIC
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams m
s

3400 2500 3400

62 shear studs, 2 per group, @110mm 8 shear studs, 1 per group 62 shear studs, 2 per group, @110mm

Steel Reinforcement
A Concrete B
24.5 Top Bracket 75.5 224.5 300 300 300 251 300 300 300 224.5 75.5 24.5
130
206.2

150 Bottom Bracket 150


Deviator
650 3500 500 500
A 3500
B 650
9300

Chapter Six: Composite Strength of Prestressed Steel-Concrete


UC 203 x 203 x 52
95

Grade 43 Steel

BEAM 3
Section B- Section A-

UC 203 x 203 x UC 203 x 203 x


Grade 43 Grade 43
Shear Studs Diameter = 19 mm, Height
FIG. 6.5 Configuration of Beam CTBD
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

Top Elevation

26.0 50.0 50.0 26.0

42.0 Chamfer R8.0


15.0
Deviator Design Used in Beam II 42.0
15.0
(All Round Welding, Weld Thickness = 10mm) 43.0 39.0
15.0 15.0
42.0

J203x152x52
20 72.0 72.0

42 15 42
42 15 42

39 128.0 156.0
50
50 43 50.0
R8
8
20 28 35 28.0
R8 R59.0 14.0

26.0 26.0
152.0
Front Elevation
Side Elevation

Right Deviator Design

Top Elevation

26.0 50.0 50.0 26.0

42.0
15.0
Deviator Design Used in Beam I and III 42.0
(All Round Welding, Weld Thickness = 10mm) 15.0
42.0
15.0
42.0

J203x152x52
20.0 72.0 72.0

42.0 15.0 42.0 42.0 15.0 42.0

128.0
50.0 50.0 156.0
28.0 28.0
R139.0 14.0

26.0 26.0
152.0
Front Elevation
Side Elevation

Central Deviator Design

Top Elevation

Deviator Design Used in Beam II


(All Round Welding, Weld Thickness = 10mm) 42.0
15.0 15.0
39.0 43.0
15.0
42.0
15.0
Chamfer R8.0 42.0

26.0 50.0 50.0 26.0

J203x152x52
20 72.0 72.0

42 15 42
42 15 42

39 156.0 128.0
50
43 50 50.0
R8
8
35 28 20 28.0
R59.0 R8
14.0

26.0 26.0
152.0
Front Elevation
Side Elevation

Left Deviator Design

FIG 6.6 Deviators Design used in Beams

96
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.7 Overall View of Beam SS4PT Test Setup

FIG. 6.8 Side View of Beam SS4PT Test Setup

97
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.9 Transverse Reinforcement Layout

FIG. 6.10 Prestressed Steel Tendons with Strain Gauge

98
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
The concrete flange was 1500mm wide and 130mm thick, with two rows of

transverse reinforcement bars spaced evenly throughout it at a distance of 110mm.

The cover distance for these two rows of rebars was 20mm for top and bottom surface.

Two 7-wire prestressing tendons, of diameter 12.7mm, were anchored to the

end plates welded to the both ends of the beam using barrel and chuck anchorages.

The two tendons were each prestressed in alternative sequence until the desired

prestressing force of 100kN was reached in each tendon. Four sets of deviators were

welded to the web of the steel beam to maintain the profile of the prestressing tendon.

FIG. 6.11 Deviator to maintain tendon’s eccentricity

Two pairs of stiffeners 20mm thick and 25mm wide are welded to the steel

beam at the end supports. This was to guard against the buckling of the steel web

under the applied loads, as the theoretical buckling capacity was not sufficient to

withstand the external loads to be applied without the stiffeners.

99
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
Two 2.4m long twin spreader beams were used to provide the desired four-

point loads on the composite Beam SS4PT in conjunction with a 4.5m long spreader

beam on top as shown in FIG 6.16. As the spreader beam was huge, it was not

advisable to rest it on rockers sitting on the composite beam as this would cause

punching shear failure at the region below the rocker. Hence, the rockers were placed

on top of a set of I-beams resting on the composite beam (FIG 6.12).

FIG. 6.12 I-Beams used to Transfer Load to Composite Beam

100
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

_________________________________________________________________________________________________
___________________________________________________________________________________

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

_________________________________________________________________________________________________
___________________________________________________________________________________

Rocker Support 4.5m Spreader Beam

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


2 .0 m S p re a d e r B e a m
101

UC203x152x52
Prestressed Tendons

FIG. 6.13 Front and Side View of Test Setup for Beam SS4PT
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

_________________________________________________________________________________________________
___________________________________________________________________________________

4.5m Spreader Beam

2 .0 m S p re a d e r B e a m

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


Rocker Support
102

UC203x152x52
Prestressed Tendons

FIG. 6.14 Front and Side View of Test Setup for Beam SSTRAP
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

_________________________________________________________________________________________________
___________________________________________________________________________________

4.5m Spreader Beam

2 .0 m S p re a d e r B e a m

Rocker Support

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


103

UC203x152x52
Prestressed Tendons

FIG. 6.15 Front and Side View of Test Setup for Beam SSTRIC
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams

_________________________________________________________________________________________________
___________________________________________________________________________________

Rocker Support 4.5m Spreader Beam

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


Deviator
UC203x203x52
104

Prestressed Tendons

FIG. 6.16 Front and Side View of Test Setup for Beam CTBD
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

6.2.2 Beam SSTRAP

Beam SSTRAP, of length 6.3m, consisted of a rolled section UC 203 X 152 X 52,

grade 43 complying with BS4360. As shown in FIG 6.3, the basic configuration of the

beam is the same as Beam SS4PT except for the end supports, the tendon profile and

the deviator positions. Beam SSTRAP uses a trapezoidal profile for its prestressing

tendons, hence only two deviators were required to maintain its profile. (FIG.6.14) The

anchorage end plates for the tendons at the supports were adjusted to ensure maximum

contact between the chuck and the tendons. The simply-supported Beam SSTRAP is

subjected to a 2-point load as shown in FIG 6.17.

FIG. 6.17 Overall View of Beam SSTRAP Test Setup

105
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.18 Side View of Beam SSTRAP Test Setup

FIG. 6.19 Left Deviator Maintain Trapezoidal Profile

106
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.20 Trapezoidal Tendon Profile with Strain Gauges Attached

FIG. 6.21 Change in Beam Profile During Loading

107
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

6.2.3 Beam SSTRIC

Beam SSTRIC, of length 6.3m, also consisted of a rolled section UC 203 X 152 X 52,

grade 43 complying with BS4360. As shown in FIG 6.4, the basic configuration of the

FIG. 6.22 Overall Test Setup for Beam SSTRIC

beam is the same is the Beam SSTRAP except for the tendon profile and the deviator

position. Beam SSTRIC is using a triangular profile for its prestressing tendons, hence

only one deviator was required to maintain its profile on each side of the web.

(FIG.6.15) The anchorage end plates used to hold the tendons at the supports were

adjusted as for Beam SSTRAP to ensure maximum contact between the chuck and the

tendons. The simply-supported beam is also subjected to a 2-point load. (FIG 6.22)

108
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.23 Front View of Beam SSTRIC Test Setup

FIG. 6.24 Triangular Tendon Profile with Strain Gauges Attached

109
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.25 Central Deviator with Transducer

FIG. 6.26 Transducer to Measure Slippage at Support

110
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.27 I-Beam used to Transfer Load to Beam SSTRIC

FIG. 6.28 Deviator to House Prestressed Tendon

111
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
6.2.4. Beam CTBD

Beam CTBD, of length 9.3m, consisted of a rolled section UC 203 X 203 X 52, grade

43A complying with BS4360. As shown in FIG.6.1, the beam had two rows of shear

studs, 19mm diameter and 100mm nominal height welded to the top flange between

the external support and the top bracket at a spacing of 110mm. Between the two top

brackets, a single row of shear studs of the same characteristics was welded to the

flange at a distance of 300mm from each other.(FIG.6.31). The beam had three

supports, spaced 4.5m apart from each other. Rockers were placed on the two external

supports while the middle support rested on a load cell to measure the load acting on it.

(FIG.6.35)

FIG.6.29. Bottom Bracket Design

112
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
The concrete flange was 1500mm wide and 130mm thick, with two rows of

transverse reinforcement bars spaced evenly throughout it at a distance of 110mm.

The cover distance for these two rows of rebars was 20mm for top and bottom surface.

Six 7-wire high strength tendons, of diameter 12.7mm, were anchored to the 3

brackets attached to the top and bottom flanges of the beam using barrel and chuck

anchorages. The top two tendons were each prestressed to 100kN while the bottom

two tendons each had a prestressing force of 50kN. The steel brackets were designed

and prefabricated by professionals to house the three pairs of tendons at their

designated location (FIG. 6.29 and FIG. 6.30), and intermediate deviators were also

spaced evenly throughout the two beam spans to maintain the eccentricity of the

tendons during loading. FIG. 6.33 For Beam CTBD, the bottom tendons were

prestressed before the top tendons.

Two pairs of stiffeners 20mm thick and 25mm wide are welded to the steel

beam at the supports and one pair at the middle support. This was to prevent the

buckling of the steel web under the applied load, as the calculated buckling capacity

was not sufficient to withstand the external load.(FIG. 6.32)

FIG.6.30. Top Bracket Design

113
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG.6.31 Top Prestressing Tendon

FIG.6.32 Shear Studs Welded on Steel Beam with Reinforcement

114
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.33. Steel Deviator to Hold Prestressing Tendon in Place

FIG. 6.34. Strain Gauges Attached to Bottom Tendon

115
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________

FIG. 6.35 Steel Beam Resting On Load Cell

FIG. 6.36 Scaffolding for the Formwork

116
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
6.3. Material Properties

6.3.1 Concrete

The concrete used for the composite flange had a compressive strength of 40

MPa. The concrete was batched in a ready mix plant and transported to the laboratory

for casting.

An admixture by the tradename Rapidard was used to accelerate the strength

gain. Eight 100 mm cubes were prepared along with the beam specimens. The beam

specimens were moist cured for three days under wet gunny sacks covered with

polythene sheets after which they were kept in the laboratory under ambient indoor

laboratory conditions. Testing was carried out after 28 days after casting. The target

strength, compressive cube strength at 28 days and during the tests were consistent

with the required strength needed for the test program.

6.3.2 Steel Reinforcement

High-yield deformed T16 steel bars were prepared in the laboratory and used as

internal transverse reinforcement for the concrete flange to prevent cracking of the

concrete along the beam.

6.3.3 Steel Beam

The four steel sections, together with the steel anchorages, shear studs and

deviators, were all fabricated by a structural steel fabricator. The deviators also served

as stiffeners. For Beams I and II, the deviators sit directly below the loading points.

6.3.4 Instrumentation

The strain in the concrete and steel were monitored using strain gauges. For

steel, the base length of the strain gauge used is 5mm, type YFRA-5 while for the

117
hapter 6 Composite Strength of Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
concrete is the 60mm type PL60-11 were used. The strain gauges were mounted onto

the steel-concrete beams at locations shown in FIG. 6.37, 6.38, 6.39 and 6.40.

After the strain gauges are mounted, the formwork for the concrete flange was

assembled. The composite beams were then moved into the testing frame after the

concrete had reached the required strength.

After the formwork was assembled, the two rows of transverse rebars were

placed in the formwork and spot welded into place (FIG. 6.9). Next, the two tendons

on each side of the beam were prestressed alternatively in steps until the required

100kN prestressing force was reached in each tendon. Strain gauges wrere fixed on all

the prestressing tendons (FIG. 6.11). Using the data logger, the increase in the

prestressing force in the tendons during and after jacking could be monitored.

After preparation of the formwork, the casting of the concrete flange was

carried out with a curing period of 3 days using gunny sacks. Lastly, strain gauges are

fixed onto the concrete surfaces before the specimens are ready for testing.

118
hapter 6 Composite Strength

_________________________________________________________________________________________________
4

3
Legend
2
Type PL60-
11
1
Type YFRA-
0

26 25 24 23

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


13 6 19

14 7 Tendons
119

15 8

31
22
Suppor
21 20

27
5 11
12 18
29 28

30

9 10
16 17

FIG. 6.37 Strain Gauges and Transducers Layout for Beam SS4PT
hapter 6 Composite Strength

_________________________________________________________________________________________________
4

3
Legend
2
Type PL60-11
1
Type YFRA-5
0

26 23
25 24

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


13 6
7
14 8 Tendo

15 19
120

22 31
21
Support
20 20

27
5 11
12 18
29 28

30

9 10
16 17

FIG. 6.38 Strain Gauges and Transducers Layout for Beam SSTRAP
hapter 6 Composite Strength

_________________________________________________________________________________________________
4

3
Legend
2
Type PL60-
11
1
Type YFRA 0

22 21

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


13 14 6
15
7 Tendon

20 31
121

Suppo 19

27
5 11
12 18
29 28

30

9 10
16 17
FIG. 6.39 Strain Gauges and Transducers Layout for Beam SSTRIC
hapter 6 Composite Strength

_________________________________________________________________________________________________
Legend 61
Tendons 56 51
Type PL60-11 52
62 46 46 46 57
Type YFRA-5 53
58
63 45 45 45
54
64 59

65 60 55

41 74 67

42 75 68

Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams


43 76 69
122

Support
83 82 81 80
Load
13 Cell

45 40
78 73 71 66
84
80
80
Tendons Tendons
85
46 44
79 77 72 70
37 36 32 31 30 25 24 21 20 14 12 11 8 7

39 38 27 26 23 22 10 9
29 34 33 17 16 15

FIG. 6.40 Strain Gauges and Transducers Layout for Beam CTBD
hapter 6 Composite Strength Chapter Six: Composite Strength of Prestressed Steel-Concrete Beams
___________________________________________________________________________________
6.3.5 Design Criteria

The design criteria for all three specimens are as follows:

1. To prevent buckling of the steel section during the prestressing state.

2. To prevent the punching failure of concrete due to the high stress concentration at

the point load positions.

3. To achieve a flexural mode of failure by development of plastic hinges at midspan.

4. To prevent flexure of the composite beam due to loss of composite action and

excessive slip.

5. To prevent failure in vertical shear.

6. To prevent local failure in concrete slab due to high stress concentration or local

failure in steel section due to local buckling.

7. To achieve yielding of prestressing tendons after the steel section has yielded and

before the crushing of concrete.

8. To achieve a ductile behaviour for the composite beam after the concrete had

crushed by further loading the beam beyond failure load.

123

Das könnte Ihnen auch gefallen