The controller can handle 2 air compressors for guaranteed rational, cost-effective management and energy saving by

avoiding unnecessary stop/restart cycles.

General information
The Twin-Start controller may only be used as specified in this manual. Keep the manual in good condition in a known, accessible
place for the whole operational life of the equipment.
• The User must appoint an operator who will be charge of the controller. This person shall be responsible for controller inspection
and maintenance or shall delegate another person to do so. When the operator in charge is to be replaced temporarily or permanently,
his/her substitute shall read the operating and maintenance instructions and any records of past servicing and/or maintenance
carefully.
• When requesting servicing, always state MODEL and SERIAL NO.

Safety rules
The controller is tested at the factory before shipment. The controller has been designed for the intended purpose specified in this
manual. It is forbidden to use the controller for any purpose other than specified in this manual and the manufacturer shall not be
liable for any damage to property and/or persons resulting from such use. Have the equipment installed and calibrated by SPECIALIZED
PERSONNEL in compliance with the instructions provided in this manual so as to ensure proper operation.
Use original spare parts only. Using non-original spare parts may shorten the useful life of the equipment and shall invalidate the
warranty effective immediately.
NOTE: Always power off the controller and the compressors connected to it before servicing any inner components.

Warranty conditions
• All controllers are duly tested at the factory and are covered by twelve (12)-month warranty. Warranty period begins upon
delivery date.
• Warranty operates when all contract provisions and administrative regulations have been complied with and on condition that
machine is installed and operated in compliance with the instructions given in this manual.
• Any originally damaged or defective parts will be repaired or replaced free of charge.
• Labor cost is not covered under this warranty and will be charged to User.
• Warranty does not cover: all wear parts, transport costs and any servicing or repair work done by our engineers on site (on-site
inspection, disassembly and re-assembly) due to malfunction not arising from defects of manufacture.
• The decisions made by the engineers of our “AUTHORIZED SERVICE” organization shall be treated as final decisions.
• This warranty does not cover liability for direct or indirect injury to people and/or damage to property arising from improper use.
Warranty is limited to defects of manufacture only.
• Making even minor changes to or anyway altering the equipment, or using non-original spare parts shall make the warranty null
and void.

Installation
• The controller is compatible with power mains providing 230V±10% 50/60Hz single-phase alternated current. If you need to
adapt equipment to the mains rating in use in your country, contact a specialized technician.
• Connect connector (A) to factory compressed air using a hose with 6-mm diameter. Make sure the measuring point of line
pressure is as close as possible to tank pressure value. If possible, connect directly to tank.
• This manual includes the wiring and hook-up diagrams relating to the different machines in the FINI range, including the Rotar
and Pulsar machines. Look up these diagrams carefully in addition to those relevant to the individual compressor before performing
any connection. If your compressor is not included in the attached diagrams, contact the authorized service center nearest you to
obtain the necessary information.

Have all connections performed by a specialized technician.

Twin-Start

M1 M2 M1 M2 M1+M2

START ON AIR ESS M1 M2 OFF STOP

M1 M2
A

6 - English
Controls and set-ups

START Power-On key


STOP Power-Off key
ON Green LED – machine on
OFF Red LED – machine off
AIR System pressure (LED off = optimal pressure, LED on = low pressure)
M1 M1 unit on
M2 M2 unit on
ESS Dryer output on

M1-M2 M1 and M2 units operate alternately


M1 only M1unit operates
M2 only M2 unit operates
M1+M2 both units operate at the same time

Twin-Start

M1 M2 M1 M2 M1+M2

START ON AIR ESS M1 M2 OFF STOP

1 2 3 4 (SW) 1 2 3 4 5 6 7 8 9 10 11 1 2
OFF
ON

230 V ± 10%
50/60 Hz 4 VA

AIR M2 M1 ESS

1234

1 2 3 4 6 7 9 10 11 L1 L2

Set-ups
Switches on the rear of controller

SW1 ON – Enables compressor automatic restart after a mains failure event


OFF – Compressor will only restart when you press the START key
SW2 ON – Compressor restarts after pressure has remained too low for 3 minutes
OFF – Compressor restarts after pressure has remained too low for 1 minute
SW3 ON – Delayed stop. When you press the STOP key, the compressor will only stop after reaching line pressure. The red
LED OFF flashing indicates power-off cycle. This feature is useful when you wish to avoid restarting the compressor
when head is under pressure. As a matter of fact, once line pressure has been reached, the pressure switch with
overload cutout will discharge any exceeding air.
OFF – When you press the STOP key, the compressor will stop without delay. Not recommended unless head is
equipped with a drain valve.
SW4 ON – Activates dryer condensate drainage. A drainage cycle of 5 secs. will be run every 5 minutes.
OFF – Where two dryers are connected together, setting switch to OFF will operate them alternately at 5-minute
intervals.
7 - English
Additional settings
Before operating the compressors, make sure the pressure switch incorporated into the controller is properly set.
Factory setting is as follows:
maximum pressure: 9 bar, range (difference between minimum and maximum pressure): 2 bar.
In the event the compressors connected to the controller feature different maximum pressures, or if you wish to change the
pressure range (difference between stop and start pressure values), turn the two screws placed on pressure switch head. Read the
pressure value on the graduated scales located on pressure switch body.

2 15
6 50 8 120
10 100 6 80
150 40
14 4
200
18 2 15

bar psi bar psi

Start-up procedure
Press the START key to start the compressor. The ON LED will turn on (LED on = selected operation cycle has been activated,
LED flashing = system under pressure). The pressure switch will turn on the AIR pressure indication to show system condition (LED
on = low pressure, LED off = optimal pressure). The LED ESS comes on when dryer starts operating, whereas LED’s M1 and M2
show the condition of the two pump units.

Selecting mode of operation


Keep the STOP key depressed for at least 4 seconds to select mode of operation. The controller will cycle through the different
modes at ½ second intervals, as the green LED’s relating to the different modes turn on. To select a mode, release the STOP key
while the green LED for that mode is on. Mode selection will be retained after a power-off.

• M1-M2 mode: the two pump units operate alternately.


Note that feature SW2 will only operate when this mode is selected. Consider your air consumption and set this switch to ON (low
consumption) or OFF (high consumption) accordingly. When line pressure is reached, both pump units will stop and will only start
pumping again when pressure drops.
• M1 mode: only pump unit M1 operates.
• M2 mode: only pump unit M2 operates.
NOTE: If you are using one pump unit at a time, be sure to make use of the two units equally, otherwise either of the two will wear
earlier.
• M1+M2 mode: both units operate at the same time.
Unit M1 starts up first, while unit M2 starts about 10 seconds later. When line pressure is reached, both units stop and resume
operation as soon as pressure drops.
NOTE: Please consider that operating both units at the same time is rather costly. Simultaneous operation is only worth the cost
when one needs to meet large compressed air requirements. When this is the case, expect consumption to spike especially during
start-up.

Seek advice from your installation engineer to determine which mode of operation best suits your needs. Compare your compressed
air requirement and air delivery rating stated on the CE plate of the compressor.

Specifications
Relay outputs with switching contact: 12A resistive load, 5A inductive load
Power supply voltage: 230V ±10% 50-60 Hz
Operating temperature: -15÷+45°C
Storage temperature: -20÷+70 °C
Controller software: TWI-WD4 Rev.1.01

8 - English
Wiring diagrams

K1 6 221 21 K2 3 222 22

11 0221 91 4 0222 92
D
1 2 3 4 5 6 7 8 9 10 11 1 2

S
P

F AP

PE N1 L2 11 10 9 221 0221 91 21 222 0222 22 92

Predisposizione
Neutro - Neutral

per elettrovalvola
F Fuse 5×20 4A scarico condensa
Linea - Line
Terra - Heart

S Pressure switch Pre-set for


K1-K2 Auxiliary relays Solenoid valve
AP Relay board for draining
condensate
D Controller M1 M2

1. TWIN-START connection 2. TWIN-START connection


PULSAR OIL CONTROL with selayed stop PULSAR AND PULSAR CONCEPT with OIL CONTROL with
1) Remove the jumper across terminals no. 7 and no. 07 of no delayed stop
the compressor terminal board. 1) Remove the jumper across terminals no. 7 and no. 07 of
2) Disconnect the wires of pressure switch PS from terminals the compressor terminal board.
no. 9 and no. 10 of the terminal board and connect them to 2) Disconnect the wires of pressure switch PS (S1) from
terminals no. 7 and no. 07 (now free). terminals no. 9 and no. 10 of the terminal board and connect
3) Connect terminals no. 9 and no. 10 – still free – to the them to terminals no. 7 and no. 07 (now free).
controller as shown in the diagram. 3) Connect terminals no. 9 and no. 10 – still free – to the
4) Disconnect the wires of pressure switch PT from terminals controller as shown in the diagram.
no. 9 and no. 11 of the compressor terminal board and connect 4) Put power to the controller only and set up as outlined earlier
the free terminals to the controller as shown in the diagram. in this manual.
5) Put power to the controller only and set up as outlined earlier 5) Power on and start up the compressors pressing the start
in this manual. buttons to activate the selected sequence.
6) Power on and start up the compressors pressing the start We recommend setting the pressure switch PS of each
buttons to activate the selected sequence. compressor to maximum allowed pressure + 0.5 bar.
We recommend setting the pressure switch PS of each
compressor to maximum allowed pressure + 0.5 bar.

PE N1 L2 11 10 9 221 0221 91 21 222 0222 22 92 PE N1 L2 11 10 9 221 0221 91 21 222 0222 22 92


To the connector no.10

To the connector no.11

To the connector no.10

To the connector no.11

To the connector no.10

To the connector no.10


To the connector no.9

To the connector no.9

To the connector no.9

To the connector no.9

To the connector no.9

To the connector no.9


Al morsetto n˚10

Al morsetto n˚10
Al morsetto n˚11

Al morsetto n˚10

Al morsetto n˚11

Al morsetto n˚10
Al morsetto n˚9

Al morsetto n˚9

Al morsetto n˚9

Al morsetto n˚9

Al morsetto n˚9

Al morsetto n˚9
Neutro - Neutral

Neutro - Neutral
Terra - Heart

Terra - Heart
Linea - Line

Linea - Line

M1 M2 M1 M2
9 - English
3. TWIN-START connection 4. TWIN-START connection
KSC, BSC and ROTAR PLUS. ROTAR 50÷100 “E”
1) Remove the jumper across terminals no. 13 and no. 16 of 1) Connect terminals no. 15 and no. 22 to the controller as
the compressor terminal board. shown in the diagram.
2) Connect the controller as shown in the diagram. 2) Put power to the controller only and set up as outlined earlier
3) Put power to the controller only and set up as outlined earlier in this manual.
in this manual. 3) Put power to the compressors and select function “EST”
4) Power on and start up the compressors pressing the start under “pressure control” on the electronic controller.
buttons to activate the selected sequence. 4) Power on and start up the compressors pressing the start
We recommend setting the pressure switch PS (S1) of each buttons to activate the selected sequence.
compressor to maximum allowed pressure + 0.5 bar. NOTE: The pressure transducers of the compressors are pre-
set for the “safety lock-out” feature in the event air delivery cocks
are closed.

PE N1 L2 11 10 9 221 0221 91 21 222 0222 22 92 PE N1 L2 11 10 9 221 0221 91 21 222 0222 22 92

To the connector no.15

To the connector no.22

To the connector no.15


To the connector no.22
To the connector no.13

To the connector no.16

To the connector no.13


To the connector no.16

Al morsetto n˚22
Al morsetto n˚15

Al morsetto n˚15
Al morsetto n˚22
Al morsetto n˚13

Al morsetto n˚16

Al morsetto n˚13
Al morsetto n˚16

Neutro - Neutral
Neutro - Neutral

Terra - Heart
Terra - Heart

Linea - Line
Linea - Line

M1 M2 M1 M2

5. TWIN-START connection
ROTAR 7÷40 “C”
1) Disconnect wire no. 22 from pressure switch PS of the
compressor and connect it to the controller as shown in the
diagram.
2) Connect the controller to pressure switch PS at the terminal
formerly used for wire 22 as shown in the diagram.
3) Disconnect the wires no. 2 and no. 9 of compressor pressure
switch PT and connect them to the controller as shown in the
diagram.
4) Put power to the controller only and set up as outlined earlier
in this manual.
5) Power on and start up the compressors pressing the start
buttons to activate the selected sequence.
We recommend setting the pressure switch PS of each
compressor to maximum allowed pressure + 0.5 bar.

PE N1 L2 11 10 9 221 0221 91 21 222 0222 22 92


To the pressure switch PS

To the pressure switch PS


Cable no.22 from PS

Cable no.22 from PS


Cable no.9 from PT

Cable no.2 from PT

Cable no.9 from PT

Cable no.2 from PT


Cavetto n˚22 da PS

Cavetto n˚22 da PS
Cavetto n˚9 da PT

Cavetto n˚2 da PT

Cavetto n˚9 da PT

Cavetto n˚2 da PT
Al pressostato PS

Al pressostato PS
Neutro - Neutral
Terra - Heart

Linea - Line

M1 M2

10 - English