PV-1 PROJECT SUMMARY THIS PROJECT INVOLVES THE INSTALLATION OF A
PHOTOVOLTAIC POWER SYSTEM. SOLAR PANELS WILL BE
PV-2 SITE PLAN RACKED USING A PREENGINEERED RACKING SYSTEM. THE
PV-3 SINGLE-LINE DIAGRAM RACKED MODULES WILL BE ELECTRICALLY CONNECTED WITH
DC TO AC POWER INVERTERS AND INTERCONNECTED TO THE
PV-4 SAFETY LABELS LOCAL UTILITY USING MEANS AND METHODS CONSISTENT
WITH THE RULES ENFORCED BY THE LOCAL UTILITY AND
PV-5.1 ATTACHMENT PLAN 5.1 PERMITTING JURISDICTION.
PV-5.2 ATTACHMENT PLAN 5.2
ZIP64834
APPLICABLE CODES AND REGULATIONS. THE DOCUMENT
PV-8 SITE IMAGES SHALL NOT BE RELIED UPON AS A SUBSTITUTE FOR
FOLLOWING MANUFACTURER INSTALLATION INSTRUCTIONS.
OAK DR
SMITH RESIDENCE
ADDRESS
MODULE DATASHEET THE SYSTEM SHALL COMPLY WITH ALL MANUFACTURERS
LISTING AND INSTALLATION INSTRUCTIONS, AS WELL AS ALL
STATEMO
OPTIMIZER DATASHEET
APPLICABLE CODES. NOTHING IN THIS DOCUMENT SHALL BE
ARRAY WIRING BOX DATASHEET INTERPRETED IN A WAY THAT OVERRIDES THEM.
CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL
JUNCTION,
APPENDIX
ARRAY WIRING BOX DATASHEET CONDITIONS, DIMENSIONS, AND DETAILS IN THIS DOCUMENT.
BLACK
INVERTER DATASHEETS
SYSTEM DETAILS
STREET
MOUNTING SYSTEM DATASHEET
CARLCITY,
MOUNTING SYSTEM ENGINEERING LETTER NEW GRID-INTERACTIVE
UL 2703 GROUND AND BONDING CERTIFICATION DESCRIPTION PHOTOVOLTAIC SYSTEM WITH NO
137
BATTERY STORAGE
ANCHOR DATASHEET
DC RATING OF SYSTEM 15,050W
AC RATING OF SYSTEM 11,400W
PROJECT DETAILS AC OUTPUT CURRENT 48.0A
PROPERTY OWNER JOHN SMITH
1 X SOLAR EDGE SE3800H-US
INVERTER(S)
137 BLACK OAK DR, CARL JUNCTION, 1 X SOLAR EDGE SE7600H-US
PROPERTY ADDRESS MO 64834 US
MODULE LG LG350Q1C-A5
APN
(1) STRING OF 14 (INV #1)
ZONING RESIDENTIAL ARRAY WIRING (1) STRING OF 15 (INV #1)
(1) STRING OF 14 (INV #2)
USE AND OCCUPANCY ONE- OR TWO-FAMILY DWELLING
CLASSIFICATION GROUP (GROUP R3)
AHJ COUNTY OF JASPER INTERCONNECTION DETAILS
UTILITY COMPANY EMPIRE DISTRICT ELECTRIC CO NEW LOAD-SIDE AC CONNECTION
POINT OF CONNECTION PER NEC 705.12(B) AT MSP
METER SERIAL NUMBER 4598340928
UTILITY SERVICE 120/240V 1Φ
ELECTRICAL CODE 2017 NEC (NFPA 70)
MAIN SERVICE PANEL W/TOP-FED
FIRE CODE 2015 IFC ELECTRICAL PANEL 320A BUSBAR 225A MCB
PV-1
GENERAL NOTES REF. #
EQUIPMENT LIKELY TO BE WORKED UPON WHILE
1 ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT
SATISFY MINIMUM WORKING CLEARANCES PER NEC
110.26.
CONTRACTOR SHALL USE ONLY COMPONENTS LISTED
2 BY A NATIONALLY RECOGNIZED TESTING LABORATORY
FOR THE INTENDED USE.
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL
3
ZIP64834
WHERE DC PV SOURCE OR DC PV OUTPUT CIRCUITS
ARE RUN INSIDE THE BUILDING, THEY SHALL BE
CONTAINED IN METAL RACEWAYS, TYPE MC METAL-
OAK DR
SMITH RESIDENCE
4
ADDRESS
CLAD CABLE, OR METAL ENCLOSURES FROM THE POINT
STATEMO
OF PENETRATION INTO THE BUILDING TO THE FIRST
READILY ACCESSIBLE DISCONNECTING MEANS, PER
NEC 690.31(G).
JUNCTION,
ALL EMT CONDUIT FITTINGS SHALL BE LISTED AS
5 WEATHERPROOF FITTINGS AND INSTALLED TO ENSURE
BLACK
A RAINTIGHT FIT, PER NEC 358.42.
STREET
CARLCITY,
(N) TRANSITION BOX (JB1), OUTDOOR , OUTPUT
CIRCUIT CONDUCTORS SHALL BE RUN IN EMT
137
CONDUIT THROUGH THE INTERIOR OF THE BUILDING
(N) STRING COMBINER (C1), OUTDOOR , OUTPUT
CIRCUIT CONDUCTORS SHALL BE RUN IN EMT
CONDUIT OVER ROOF NO CLOSER THAN 0.5" ABOVE
ROOF SURFACE
(E) GAS METER, OUTDOOR. NO NEW ELECTRICAL
EQUIPMENT SHALL BE INSTALLED WITHIN 36 INCHES
OF CENTER OF GAS METER OR RISER.
(N) INVERTER (I2), OUTDOOR
PV-2
STREET ADDRESS
REF. #
ZIP64834
(SOLADECK 0783-3R-2ER6) CONDUCTORS WITHIN THE
INSTALLED PROVIDING THE LOCATION OF THE SERVICE
ARRAY REMAIN
ENERGIZED IN SUNLIGHT.
3 DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME
! WARNING !
OAK DR
SMITH RESIDENCE
ADDRESS
DIRECT-CURRENT PV POWER SOURCE LOCATION IN ACCORDANCE WITH NEC 690.56(B).
THIS EQUIPMENT FED BY MULTIPLE SOURCES. MAXIMUM VOLTAGE: 400V
STATEMO
NEC 690.56(C)(1) TOTAL RATING OF ALL OVERCURRENT DEVICES, WHERE THE INVERTERS ARE REMOTELY LOCATED
C1 - STRING COMBINER MAX CIRCUIT-CURRENT: 37.5A FROM EACH OTHER, A DIRECTORY IN SHALL BE
(MIDNITE SOLAR MNSOB3R-4P) EXCLUDING MAIN OVERCURRENT DEVICE SHALL DC-TO-DC CONVERTER RATED CURRENT: 15.0A
NOT EXCEED AMPACITY OF BUSBAR. INSTALLED AT EACH DC PHOTOVOLTAIC SYSTEM
4
JUNCTION,
DISCONNECTING MEANS, AT EACH AC DISCONNECTING
NEC 705.12(B)(2)(3)(C) NEC 690.53 MEANS, AND AT THE MAIN SERVICE DISCONNECTING
BLACK
MEANS SHOWING THE LOCATION OF ALL AC AND DC
PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IN
STREET
I1 - INVERTER DC DISCONNECT (I2) AC SOLAR DISCONNECT (SW1, CB3 IN MSP) AC DISCONNECT (SW1, CB3 IN MSP) THE BUILDING, IN ACCORDANCE WITH NEC 690.4(H).
CARLCITY,
(SOLAR EDGE SE7600H-US) LABEL(S) WITH MARKING, "TURN RAPID SHUTDOWN
SWITCH TO THE 'OFF' POSITION TO SHUT DOWN
137
DIRECT-CURRENT PV POWER SOURCE CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS
MAXIMUM VOLTAGE: 380V MAXIMUM AC OPERATING CURRENT: 48.0A WITHIN THE ARRAY REMAIN ENERGIZED IN SUNLIGHT,"
I2 - INVERTER
MAX CIRCUIT-CURRENT: 18.8A
DC-TO-DC CONVERTER RATED CURRENT: 15.0A
PV SYSTEM DISCONNECT MAXIMUM AC OPERATING VOLTAGE: 240V 5 SHALL BE LOCATED WITHIN 3 FT OF SERVICE
DISCONNECTING MEANS THE TITLE SHALL UTILIZE
CAPITALIZED LETTERS WITH A MINIMUM HEIGHT OF 3/8”
(SOLAR EDGE SE3800H-US) IN WHITE ON A RED BACKGROUND, AND REMAINING
NEC 690.53 NEC 690.13(B) NEC 690.54 TEXT SHALL BE CAPITALIZED WITH A MINIMUM HEIGHT
OF 3/16” IN BLACK ON WHITE BACKGROUND
ANY AC ELECTRICAL PANEL THAT IS FED BY
AC DISCONNECT (CB1 IN PAN1) AC DISCONNECT (CB2 IN PAN1) BOTH THE UTILITY AND THE PHOTOVOLTAIC LABEL(S) WITH MARKING, "WARNING PHOTOVOLTAIC
SYSTEM (PAN1, MSP) POWER SOURCE," SHALL BE LOCATED AT EVERY 10
PAN1 - AC AGGREGATION PANEL FEET OF EACH DC RACEWAY AND WITHIN ONE FOOT OF
(MODEL NOT SPECIFIED)
6 EVERY TURN OR BEND AND WITHIN ONE FOOT ABOVE
AND BELOW ALL PENETRATIONS OF ROOF/CEILING
MAXIMUM AC OPERATING CURRENT: 32.0A MAXIMUM AC OPERATING CURRENT: 16.0A ! WARNING ! ASSEMBLIES, WALLS AND BARRIERS. THE LABEL SHALL
MAXIMUM AC OPERATING VOLTAGE: 240V MAXIMUM AC OPERATING VOLTAGE: 240V DUAL POWER SOURCE. SECOND SOURCE IS HAVE 3/8” TALL LETTERS AND BE REFLECTIVE WITH
PHOTOVOLTAIC SYSTEM. WHITE TEXT ON A RED BACKGROUND
MSP - MAIN SERVICE PANEL
(SIEMENS) NEC 690.54 NEC 690.54 NEC 705.12(B)(3)
! WARNING !
SW1 - DISCONNECT
(EATON DG222NRB )
INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE. SAFETY LABELS
NEC 705.12(B)(2)(3)(B) DOC ID: 117532-147309-1
DATE: 7/5/19
CREATOR: N.P.
REVIEWER:
REVISIONS
PV-4.1
POINT-OF-INTERCONNECTION OR AT MAIN SERVICE DISCONNECT (MSP)
REF. #
! CAUTION !
POWER TO THIS BUILDING IS ALSO FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN
ZIP64834
OAK DR
SMITH RESIDENCE
ADDRESS
STATEMO
JUNCTION,
BLACK
STREET
CARLCITY,
137
NEC 690.56(B)
SAFETY LABELS
DOC ID: 117532-147309-1
DATE: 7/5/19
CREATOR: N.P.
REVIEWER:
REVISIONS
PV-4.2
ROOF PROPERTIES REF. #
ROOF MATERIAL SPANISH BARREL TILE (W-SHAPE)
SLOPE 6/12 (26.6°)
MEAN ROOF HEIGHT 15.9FT
DECK SHEATHING 15/32" OSB
CONSTRUCTION RAFTERS (2X4'S), 24IN OC
ZIP64834
DIMENSIONS (AREA) 66.9IN X 40.0IN X 1.6IN (18.6 SQ FT)
OAK DR
SMITH RESIDENCE
WEIGHT 40.8LB
ADDRESS
STATEMO
MOUNTING SYSTEM PROPERTIES
JUNCTION,
RAIL MODEL IRONRIDGE XR100
BLACK
QUICK MOUNT PV QMTR-W4
ANCHOR MODEL (FLASHED) W/ (1) TILE REPLACEMENT
STREET
BASE MOUNT, 4.0IN AIR GAP
CARLCITY,
3.0 INCH EMBEDMENT INTO RAFTERS
FASTENING METHOD WITH 2 FASTENERS
137
111.0IN (ZONE 1)
MAX. ALLOW. RAIL SPAN 87.0IN (ZONE 2)
56.0IN (ZONE 3)
72.0IN (ZONE 1)
MAX. MOUNT SPACING 48.0IN (ZONES 2 AND 3)
44.4IN (ZONE 1)
MAX. ALLOW. 34.8IN (ZONE 2)
CANTILEVER 22.4IN (ZONE 3)
GROUNDING AND INTEGRAL GROUNDING CERTIFIED
BONDING TO UL 2703 REQUIREMENTS
REVISIONS
NOTES
RAFTER LOCATIONS ARE APPROXIMATE. ACTUAL
1 LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED
TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THE
MOUNT SPACING EXCEED "MAX. MOUNT SPACING"
PV-5.1
ROOF PROPERTIES REF. #
ROOF MATERIAL SPANISH BARREL TILE (W-SHAPE)
SLOPE 6/12 (26.6°)
MEAN ROOF HEIGHT 13.6FT
DECK SHEATHING 15/32" OSB
CONSTRUCTION RAFTERS (2X4'S), 24IN OC
ZIP64834
DIMENSIONS (AREA) 66.9IN X 40.0IN X 1.6IN (18.6 SQ FT)
OAK DR
SMITH RESIDENCE
ADDRESS
WEIGHT 40.8LB
STATEMO
MOUNTING SYSTEM PROPERTIES
JUNCTION,
RAIL MODEL IRONRIDGE XR100
BLACK
QUICK MOUNT PV QMTR-W4
ANCHOR MODEL (FLASHED) W/ (1) TILE REPLACEMENT
STREET
BASE MOUNT, 4.0IN AIR GAP
CARL CITY,
3.0 INCH EMBEDMENT INTO RAFTERS
FASTENING METHOD WITH 2 FASTENERS
137
111.0IN (ZONE 1)
MAX. ALLOW. RAIL SPAN 87.0IN (ZONE 2)
56.0IN (ZONE 3)
72.0IN (ZONE 1)
MAX. MOUNT SPACING 48.0IN (ZONES 2 AND 3)
44.4IN (ZONE 1)
MAX. ALLOW. 34.8IN (ZONE 2)
CANTILEVER 22.4IN (ZONE 3)
GROUNDING AND INTEGRAL GROUNDING CERTIFIED
BONDING TO UL 2703 REQUIREMENTS
DISTANCE α IS EQUAL TO 10% OF THE BUILDING'S LEAST HORIZONTAL DIMENSION OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET (ACSE 7-
REVISIONS
NOTES 10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF CORNERS, RAKES, HIPS, EAVES, MANSARDS, AND RIDGES OF ROOF FACES.
RAFTER LOCATIONS ARE APPROXIMATE. ACTUAL α = MAX(MIN(0.4 * MEAN ROOF HEIGHT, 0.1 * LEAST HORIZONTAL DIMENSION), 0.04 * LEAST HORIZONTAL DIMENSION, 3 FT)
1 LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED
TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THE 5.5 FT = MAX(MIN(0.4 * 13.6 FT, 0.1 * 61.4 FT), 0.04 * 61.4 FT, 3 FT)
MOUNT SPACING EXCEED "MAX. MOUNT SPACING"
PV-5.2
GRID-TIED SOLAR POWER SYSTEM
REVIEWER:
CREATOR: N.P.
SMITH RESIDENCE
DATE: 7/5/19
DETAILS
PV-6
STREET
137 ADDRESS
BLACK OAK DR
REF. #
REVISIONS
ATTACHMENT
CARLCITY,
JUNCTION,
STATEMO
ZIP64834
GENERAL NOTES REF. #
ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS
THAT DO NOT REQUIRE THE PLACEMENT OF GROUND
LADDERS OVER OPENINGS SUCH AS WINDOWS OR
1 DOORS, AND LOCATED AT STRONG POINTS OF BUILDING
CONSTRUCTION IN LOCATIONS WHERE THE ACCESS
POINT DOES NOT CONFLICT WITH OVERHEAD
OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.
(IFC 605.11.1.1)
PANELS AND MODULES INSTALLED ON GROUP R-3
ZIP64834
ROOF SLOPE WHERE PANELS AND MODULES ARE
LOCATED. (IFC 605.11.1.2.3)
OAK DR
SMITH RESIDENCE
ADDRESS
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS WITH ROOF HIPS AND VALLEYS SHALL NOT
STATEMO
BE LOCATED CLOSER THAN 18 INCHES TO A HIP OR A
VALLEY WHERE PANELS/MODULES ARE TO BE PLACED
3 ON BOTH SIDES OF A HIP OR VALLEY. WHERE PANELS
JUNCTION,
ARE TO BE LOCATED ON ONLY ONE SIDE OF A HIP OR
VALLEY THAT IS OF EQUAL LENGTH, THE PANELS SHALL
BLACK
BE PERMITTED TO BE PLACED DIRECTLY ADJACENT TO
THE HIP OR VALLEY. (IFC 605.11.1.2.4)
STREET
CARLCITY,
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS SHALL BE LOCATED NOT LESS THAN 3 FEET
(914 MM) FROM THE RIDGE IN ORDER TO ALLOW FOR
137
FIRE DEPARTMENT SMOKE VENTILATION OPERATIONS,
4 EXCEPT IN SUCH CASES WHERE AN ALTERNATIVE
VENTILATION METHOD APPROVED BY THE FIRE CHIEF
HAS BEEN PROVIDED OR WHERE THE FIRE CHIEF HAS
DETERMINED VERTICAL VENTILATION TECHNIQUES WILL
NOT BE EMPLOYED. (IFC 605.11.1.2.5)
PV-7
GRID-TIED SOLAR POWER SYSTEM
REVIEWER:
CREATOR: N.P.
SMITH RESIDENCE
DATE: 7/5/19
PV-8
STREET
137 ADDRESS
BLACK OAK DR
REF. #
REVISIONS
SITE IMAGES
DOC ID: 117532-147309-1
CARLCITY,
JUNCTION,
STATEMO
ZIP64834
LG365Q1C-A5 LG360Q1C-A5 LG355Q1C-A5 LG350Q1C-A5
Innovation for
a Better Life Mechanical Properties Electrical Properties (STC *)
Cells 6 x 10 Module 365 360 355 350
Cell Vendor LG Maximum Power (Pmax) 365 360 355 350
Cell Type Monocrystalline / N-type MPP Voltage (Vmpp) 36.7 36.5 36.3 36.1
Cell Dimensions 161.7 x 161.7 mm / 6 inches MPP Current (Impp) 9.95 9.87 9.79 9.70
Dimensions (L x W x H) 1700 x 1016 x 40 mm Open Circuit Voltage (Voc) 42.8 42.7 42.7 42.7
66.93 x 40.0 x 1.57 inch Short Circuit Current (Isc) 10.8 10.79 10.78 10.77
Front Load 6000Pa Module Efficiency 21.1 20.8 20.6 20.3
Rear Load 5400Pa Operating Temperature -40 ~ +90
Weight 18.5 kg Maximum System Voltage 1000
Connector Type MC4 Maximum Series Fuse Rating 20
Junction Box IP68 with 3 Bypass Diodes Power Tolerance (%) 0 ~ +3
Length of Cables 1000 mm x 2 ea * STC (Standard Test Condition): Irradiance 1,000 W/m², Ambient Temperature 25 °C, AM 1.5
Glass Tempered Glass with AR Coating * The nameplate power output is measured and determined by LG Electronics at its sole and absolute discretion.
* The typical change in module efficiency at 200 W/m² in relation to 1000 W/m² is -2.0%.
Frame Anodized Aluminium
60 cell front maximizes the utilization of light and enhances reliability. The **1) First 5 years : 95%, 2) After 5th year : 0.4% annual degradation, 3) 25 years : 88.4%
4.0/0.2
LG NeON® R is a result of LG’s efforts to increase customer value TM Ø 8.2
/0
Ø 4
.3/0
.2 5.5/0.2
Temperature Characteristics .3
40.0/1.6
40.0/1.6
7.5/0.3
4.0/0.2
beyond basic efficiency. The NeON® R features enhanced durability KM 564573 BS EN 61215 Photovoltaic Modules
R1
.5
Current (A)
10.00 [X view]
including labor, in addition to an enhanced performance significantly enhance its output, making it efficient 800W
warranty. After 25 years, LG NeON® R is guaranteed to even in limited space. 8.00
1700.0/66.9
1100.0/43.3
1300.0/51.2
120
Isc
Better Performance on a Sunny Day Near Zero LID (Light Induced 100
Voc
60
days, thanks to its improved temperature coefficient. The n-type cells used in LG NeON® R have
200.0/7.9
105.0/4.1
40
almost no boron. This leads to less LID (Light
Induced Degradation) right after installation. 20
0 Temperature (°C)
-40 -25 0 25 50 75 90 * The distance between the center of the mounting/grounding holes.
POWER OPTIMIZER
Power Optimizer P320 / P340 / P370 / P400 / P405 / P505
P370
For North America Optimizer model
(typical module
P320
(for 60-cell
P340
(for high-
(for higher-
power
P400
(for 72 & 96-
P405
(for thin film
P505
(for higher
power 60-cell cell current
P320 / P340 / P370 / P400 / P405 / P505 compatibility) modules)
modules)
60 and 72-cell
modules)
modules)
modules)
modules)
INPUT
Rated Input DC Power(1) 320 340 370 400 405 505 W
Absolute Maximum Input
25
Voltage 48 60 80 125(2) 83(2) Vdc
(Voc at lowest temperature)
MPPT Operating Range 8 - 48 8 - 60 8 - 80 12.5 - 105 12.5 - 83 Vdc
YEAR
WARRANTY Maximum Short Circuit Current
11 10.1 14 Adc
(Isc)
Maximum DC Input Current 13.75 12.63 17.5 Adc
Maximum Efficiency 99.5 %
Weighted Efficiency 98.8 98.6 %
Overvoltage Category II
OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER)
Maximum Output Current 15 Adc
Maximum Output Voltage 60 85 Vdc
OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE
INVERTER OFF)
Safety Output Voltage per
1 ± 0.1 Vdc
Power Optimizer
STANDARD COMPLIANCE
EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3
Safety IEC62109-1 (class II safety), UL1741
RoHS Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System
1000 Vdc
Voltage
Compatible inverters All SolarEdge Single Phase and Three Phase inverters
128 x 152 x 36 / 128 x 152 x 50 / 128 x 152 x 59 /
Dimensions (W x L x H) 128 x 152 x 28 / 5 x 5.97 x 1.1 mm / in
5 x 5.97 x 1.42 5 x 5.97 x 1.96 5 x 5.97 x 2.32
Weight (including cables) 630 / 1.4 750 / 1.7 845 / 1.9 1064 / 2.3 gr / lb
Input Connector MC4(3)
Output Wire Type / Connector Double Insulated; MC4
Output Wire Length 0.95 / 3.0 1.2 / 3.9 m / ft
Input Wire Length 0.16 / 0.52 m / ft
Operating Temperature Range -40 - +85 / -40 - +185 ˚C / ˚F
PV power optimization at the module-level Protection Rating IP68 / NEMA6P
Relative Humidity 0 - 100 %
(1)
Rated STC power of the module. Module of up to +5% power tolerance allowed
(2)
NEC 2017 requires max input voltage be not more than 80V
Specifically designed to work with SolarEdge Fast installation with a single bolt (3)
For other connector types please contact SolarEdge
inverters
Next generation maintenance with module- PV System Design Using Single Phase
Single phase Three Phase 208V Three Phase 480V
Up to 25% more energy level monitoring a SolarEdge Inverter(4)(5) HD-Wave
P320, P340, P370,
Minimum String Length 8 10 18
P400
(Power Optimizers)
Superior efficiency (99.5%) Meets NEC requirements for arc fault P405 / P505 6 8 14
protection (AFCI) and Photovoltaic Rapid Maximum String Length
25 25 50(6)
(Power Optimizers)
Mitigates all types of module mismatch losses, Shutdown System (PVRSS) 5700 (6000 with
from manufacturing tolerance to partial Maximum Power per String SE7600-US - SE11400- 5250 6000(7) 12750(8) W
US)
shading Module-level voltage shutdown for installer Parallel Strings of Different Lengths
Yes
and firefighter safety or Orientations
Flexible system design for maximum space (4)
For detailed string sizing information refer to: http://www.solaredge.com/sites/default/files/string_sizing_na.pdf
(5)
It is not allowed to mix P405/P505 with P320/P340/P370/P400 in one string
utilization (6)
A string with more than 30 optimizers does not meet NEC rapid shutdown requirements; safety voltage will be above the 30V requirement
(7)
For SE14.4KUS/SE43.2KUS: It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter (3 strings per unit for SE43.2KUS) and when
the maximum power difference between the strings is up to 1,000W
(8)
For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS: It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter (3 strings per unit for SE66.6KUS/SE100KUS)
and when the maximum power difference between the strings is up to 2,000W
solaredge.com © SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 12/2018/V01/ENG NAM. Subject to change without notice.
Basic Features
• Stamped Seamless Construction
• 18 Gauge Galvanized Steel
• Powder Coated Surfaces
• Flashes into the roof deck
• 3 Roof deck knockouts .5", .75", 1"
• 5 Centering dimples for entry/exit
fittings or conduit
• 2 Position Ground lug installed
• Mounting Hardware Included
SolaDeck Model SD 0783
INVERTERS
SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/
Single Phase Inverter SE7600H-US / SE10000H-US / SE11400H-US
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional)
Revenue Grade Data, ANSI C12.20 Optional(3)
Rapid Shutdown - NEC 2014 and
Optimized installation with HD-Wave technology
Automatic Rapid Shutdown upon AC Grid Disconnect
2017 690.12
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Specifically designed to work with Extremely small Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
power optimizers Emissions FCC Part 15 Class B
XR Rails
Flush Mount System
XR10 Rail XR100 Rail XR1000 Rail Bonded Splices
A low-profile mounting rail The ultimate residential A heavyweight mounting All rails use internal splices
for regions with light snow. solar mounting rail. rail for commercial projects. for seamless connections.
• 6’ spanning capability • 8’ spanning capability • 12’ spanning capability • Self-drilling screws
• Moderate load capability • Heavy load capability • Extreme load capability • Varying versions for rails
• Clear and black finish • Clear and black finish • Clear anodized finish • Forms secure bonding
Universal Fastening Objects Snap onto the UFO to turn Bond modules to rails while Connect arrays to
bond modules to rails. into a bonded end clamp. staying completely hidden. equipment ground.
• Fully assembled & lubed • Bonds modules to rails • Universal end-cam clamp • Low profile
• Single, universal size • Sized to match modules • Tool-less installation • Single tool installation
• Clear and black finish • Clear and black finish • Fully assembled • Mounts in any direction
Built for solar’s toughest roofs.
Attachments
IronRidge builds the strongest mounting system for pitched roofs in solar. Every component has been tested to
the limit and proven in extreme environments. FlashFoot2 Conduit Mount Slotted L-Feet Bonding Hardware
Our rigorous approach has led to unique structural features, such as curved rails and reinforced flashings, and
is also why our products are fully certified, code compliant and backed by a 25-year warranty.
DE
REG
Go from rough layout to fully Earn free continuing education credits,
R
engineered system. For free. while learning more about our systems.
Entire system and components meet Products guaranteed to be free NT
ON
CO
IN U TI
I NG E DUC A
Go to IronRidge.com/design Go to IronRidge.com/training
newest effective UL 2703 standard. of impairing defects.
© 2019 IronRidge, Inc. All rights reserved. U.S. Patents: #8,695,290; #9,819,303; #9,865,938; Others Pending. Version 1.70
1495 Zephyr Avenue
Hayward, CA 94544
1-800-227-9523
IronRidge.com
Re: Structural Certification and Span Tables for IronRidge Flush Mount System
This letter addresses the structural performance and code compliance of IronRidge’s Flush Mount System. The Flush
Mount System is a proprietary rooftop mounting system used to support photovoltaic (PV) modules installed in portrait or
landscape orientation and set parallel to the underlying roof surface. PV modules are supported by extruded aluminum
XR Rails and secured to the rails with IronRidge mounting clamps. The XR Rails are side mounted to a selected roof
attachment with 3/8” stainless steel bonding hardware and then attached directly to the roof structure or to a stanchion
that is fastened to the underlying roof structure. Assembly details of a typical Flush Mount installation and its core
components are shown in Exhibit EX-0015.
The IronRidge Flush Mount System is designed and certified to the structural requirements of the following reference
standards for the load conditions and configurations tabulated in the attached span tables:
• ASCE/SEI 7-05 Minimum Design Loads for Buildings and Other Structures (ASCE 7-05)
• ASCE/SEI 7-10 Minimum Design Loads for Buildings and Other Structures (ASCE 7-10)
• 2009 International Building Code (IBC-2009)
• 2012 International Building Code (IBC-2012)
• 2010 Aluminum Design Manual (ADM-2010)
The tables included in this letter provide the maximum allowable spans of XR Rails in the Flush Mount System for the
respective loads and configurations listed, covering wind exposure categories B, C, & D, roof zones 1, 2 & 3, and roof
slopes from 0º to 45º. The span tables are applicable provided that the following conditions are met:
1. Span is the distance between two adjacent roof attachment points (measured at the center of the attachment
fastener)
2. The underlying roof pitch, measured between roof surface and horizontal plane, is 45º or less.
3. The mean roof height, defined as the average of the roof eave height and the roof ridge height measured from
grade, does not exceed 30 feet.
4. Module length shall not exceed the listed maximum dimension provided for the respective span table and module
width shall not exceed 40”.
5. All Flush Mount components shall be installed in a professional workmanlike manner per IronRidge’s Flush Mount
installation manual and other applicable standards for general roof construction practice.
REV
QTY.
NO.
SHEET 1 OF 1
3
1
1
1
RAD
EPDM BONDED SS
6/9/2017
LAG SCREW, GRK RSS WASHER HEAD, 5/16"
4 2
1
X 4", T-30, STEEL, CLIMATEK COATED
WEIGHT: 2.93
W-TILE, 4" POST
DRAWN BY:
CONE, ALUMINUM, MILL
EPDM BONDED SS
3
DATE:
DESCRIPTION
2A, 18-8 SS
SCALE: 1:5
EPDM
SIZE
A
UNLESS OTHERWISE SPECIFIED:
2
TOLERANCES:
TITLE:
ITEM
NO.
8
4
7
1
ROOF RIDGE
BASE MOUNT
UNLESS OTHERWISE SPECIFIED:
SIZE DRAWN BY: RAD REV
DIMENSIONS ARE IN INCHES
TOLERANCES:
A 4
3
FRACTIONAL 1/8 DATE: 9/23/2016
PROPRIETARY AND CONFIDENTIAL TWO PLACE DECIMAL .19
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF QUICK MOUNT PV. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE DO NOT SCALE DRAWING
WRITTEN PERMISSION OF QUICK MOUNT PV IS PROHIBITED. COPYRIGHT © 2016 QUICK MOUNT PV THREE PLACE DECIMAL .094 SCALE: 1:2 WEIGHT: 2.07 SHEET 1 OF 2
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF QUICK MOUNT PV. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE
5 4 3 2 1
THIS EDGE TOWARDS ROOF RIDGE
1
7.50 2.438 3.44
RACKING NOT
INCLUDED
4
8.13
12.00
1.94
WEST ORIENTATION EAST ORIENTATION
SEPARATELY (QMTR-BM)
SOLD SEPARATELY
QMTR-F3.25, QMTR-W4, QMTR-S3.25
4
SCALE 1:5
5
PROPRIETARY AND CONFIDENTIAL
2.956
TITLE:
1.375 6.125 QMTR-BM: TILE REPLACEMENT,
BASE MOUNT
UNLESS OTHERWISE SPECIFIED:
SIZE DRAWN BY: RAD REV
DIMENSIONS ARE IN INCHES
5 4 3 2 1
BI 7.2.3-40 Jul-2017, Rev 7 BI 7.2.3-40 Jul-2017, Rev 7
2 4