DIRECTORY OF PAGES SCOPE OF WORK REF.

#
PV-1 PROJECT SUMMARY THIS PROJECT INVOLVES THE INSTALLATION OF A
PHOTOVOLTAIC POWER SYSTEM. SOLAR PANELS WILL BE
PV-2 SITE PLAN RACKED USING A PREENGINEERED RACKING SYSTEM. THE
PV-3 SINGLE-LINE DIAGRAM RACKED MODULES WILL BE ELECTRICALLY CONNECTED WITH
DC TO AC POWER INVERTERS AND INTERCONNECTED TO THE
PV-4 SAFETY LABELS LOCAL UTILITY USING MEANS AND METHODS CONSISTENT
WITH THE RULES ENFORCED BY THE LOCAL UTILITY AND
PV-5.1 ATTACHMENT PLAN 5.1 PERMITTING JURISDICTION.
PV-5.2 ATTACHMENT PLAN 5.2

GRID-TIED SOLAR POWER SYSTEM


PV-6 ATTACHMENT DETAILS THIS DOCUMENT HAS BEEN PREPARED FOR THE PURPOSE OF
DESCRIBING THE DESIGN OF A PROPOSED PV SYSTEM WITH
PV-7 FIRE SAFETY PLAN ENOUGH DETAIL TO DEMONSTRATE COMPLIANCE WITH

ZIP64834
APPLICABLE CODES AND REGULATIONS. THE DOCUMENT
PV-8 SITE IMAGES SHALL NOT BE RELIED UPON AS A SUBSTITUTE FOR
FOLLOWING MANUFACTURER INSTALLATION INSTRUCTIONS.

OAK DR
SMITH RESIDENCE
ADDRESS
MODULE DATASHEET THE SYSTEM SHALL COMPLY WITH ALL MANUFACTURERS
LISTING AND INSTALLATION INSTRUCTIONS, AS WELL AS ALL

STATEMO
OPTIMIZER DATASHEET
APPLICABLE CODES. NOTHING IN THIS DOCUMENT SHALL BE
ARRAY WIRING BOX DATASHEET INTERPRETED IN A WAY THAT OVERRIDES THEM.
CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF ALL

JUNCTION,
APPENDIX

ARRAY WIRING BOX DATASHEET CONDITIONS, DIMENSIONS, AND DETAILS IN THIS DOCUMENT.

BLACK
INVERTER DATASHEETS
SYSTEM DETAILS

STREET
MOUNTING SYSTEM DATASHEET

CARLCITY,
MOUNTING SYSTEM ENGINEERING LETTER NEW GRID-INTERACTIVE
UL 2703 GROUND AND BONDING CERTIFICATION DESCRIPTION PHOTOVOLTAIC SYSTEM WITH NO

137
BATTERY STORAGE
ANCHOR DATASHEET
DC RATING OF SYSTEM 15,050W
AC RATING OF SYSTEM 11,400W
PROJECT DETAILS AC OUTPUT CURRENT 48.0A
PROPERTY OWNER JOHN SMITH
1 X SOLAR EDGE SE3800H-US
INVERTER(S)
137 BLACK OAK DR, CARL JUNCTION, 1 X SOLAR EDGE SE7600H-US
PROPERTY ADDRESS MO 64834 US
MODULE LG LG350Q1C-A5
APN
(1) STRING OF 14 (INV #1)
ZONING RESIDENTIAL ARRAY WIRING (1) STRING OF 15 (INV #1)
(1) STRING OF 14 (INV #2)
USE AND OCCUPANCY ONE- OR TWO-FAMILY DWELLING
CLASSIFICATION GROUP (GROUP R3)
AHJ COUNTY OF JASPER INTERCONNECTION DETAILS
UTILITY COMPANY EMPIRE DISTRICT ELECTRIC CO NEW LOAD-SIDE AC CONNECTION
POINT OF CONNECTION PER NEC 705.12(B) AT MSP
METER SERIAL NUMBER 4598340928
UTILITY SERVICE 120/240V 1Φ
ELECTRICAL CODE 2017 NEC (NFPA 70)
MAIN SERVICE PANEL W/TOP-FED
FIRE CODE 2015 IFC ELECTRICAL PANEL 320A BUSBAR 225A MCB

CONTRACTOR INFORMATION SITE DETAILS PROJECT


COMPANY QUALITY SOLAR ASHRAE EXTREME LOW -18°C (0°F) SUMMARY
LICENSE NUMBER 45983498 (C-46) ASHRAE 2% HIGH 36°C (97°F) DOC ID: 117532-147309-1
ADDRESS 123 MAIN ST., CARL JUNCTION, MO CLIMATE DATA SOURCE JOPLIN MUNICIPAL AP (KJLN) DATE: 7/5/19
PHONE NUMBER (123) 456-7890 WIND SPEED 130 MPH (ASCE7-10) CREATOR: N.P.
CONTRACTOR RISK CATEGORY II REVIEWER:
SIGNATURE
WIND EXPOSURE REVISIONS
CATEGORY
GROUND SNOW LOAD 20 PSF

PV-1
GENERAL NOTES REF. #
EQUIPMENT LIKELY TO BE WORKED UPON WHILE
1 ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT
SATISFY MINIMUM WORKING CLEARANCES PER NEC
110.26.
CONTRACTOR SHALL USE ONLY COMPONENTS LISTED
2 BY A NATIONALLY RECOGNIZED TESTING LABORATORY
FOR THE INTENDED USE.
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL
3

GRID-TIED SOLAR POWER SYSTEM


EQUIPMENT, CABLES, ADDITIONAL CONDUITS,
RACEWAYS, AND OTHER ACCESSORIES NECESSARY
FOR A COMPLETE AND OPERATIONAL PV SYSTEM.

ZIP64834
WHERE DC PV SOURCE OR DC PV OUTPUT CIRCUITS
ARE RUN INSIDE THE BUILDING, THEY SHALL BE
CONTAINED IN METAL RACEWAYS, TYPE MC METAL-

OAK DR
SMITH RESIDENCE
4

ADDRESS
CLAD CABLE, OR METAL ENCLOSURES FROM THE POINT

STATEMO
OF PENETRATION INTO THE BUILDING TO THE FIRST
READILY ACCESSIBLE DISCONNECTING MEANS, PER
NEC 690.31(G).

JUNCTION,
ALL EMT CONDUIT FITTINGS SHALL BE LISTED AS
5 WEATHERPROOF FITTINGS AND INSTALLED TO ENSURE

BLACK
A RAINTIGHT FIT, PER NEC 358.42.

STREET
CARLCITY,
(N) TRANSITION BOX (JB1), OUTDOOR , OUTPUT
CIRCUIT CONDUCTORS SHALL BE RUN IN EMT

137
CONDUIT THROUGH THE INTERIOR OF THE BUILDING
(N) STRING COMBINER (C1), OUTDOOR , OUTPUT
CIRCUIT CONDUCTORS SHALL BE RUN IN EMT
CONDUIT OVER ROOF NO CLOSER THAN 0.5" ABOVE
ROOF SURFACE
(E) GAS METER, OUTDOOR. NO NEW ELECTRICAL
EQUIPMENT SHALL BE INSTALLED WITHIN 36 INCHES
OF CENTER OF GAS METER OR RISER.
(N) INVERTER (I2), OUTDOOR

(N) AC AGGREGATION PANEL (PAN1), OUTDOOR

(N) INVERTER (I1), OUTDOOR

(N) PRODUCTION METER (M1), OUTDOOR

(E) UTILITY METER, OUTDOOR

(N) DISCONNECT (SW1), OUTDOOR


(N) TRANSITION BOX (JB2), OUTDOOR , OUTPUT
CIRCUIT CONDUCTORS SHALL BE RUN IN EMT
CONDUIT THROUGH THE INTERIOR OF THE BUILDING
(N) PROPOSED ROOF-MOUNTED PHOTOVOLTAIC
ARRAY. 6:12 (27°) SLOPED ROOF, 29 PV MODULES SITE PLAN
(BLACK FRAME, CLEAR BACKSHEET), 181° AZIMUTH
(N) PROPOSED ROOF-MOUNTED PHOTOVOLTAIC DOC ID: 117532-147309-1
ARRAY. 6:12 (27°) SLOPED ROOF, 14 PV MODULES
(BLACK FRAME, CLEAR BACKSHEET), 91° AZIMUTH DATE: 7/5/19
CREATOR: N.P.
(E) MAIN SERVICE PANEL (MSP), OUTDOOR
REVIEWER:
ROADWAY
REVISIONS
ALL ARRAY CIRCUITS SHALL BE ROUTED THROUGH
THE INTERIOR OF THE BUILDING, AND WHERE
POSSIBLE, ALONG THE BOTTOM OF LOAD BEARING
MEMBERS. NO CONDUIT SHALL BE INSTALLED ABOVE
THE ROOF.

PV-2
STREET ADDRESS
REF. #

CITY, STATE ZIP


DC RACEWAYS
SEE NOTE NO. 5 (MSP) SEE NOTE NO. 6 (DC RACEWAYS)
EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT (JB1, JB2, C1, I1, I2,
LABELING NOTES REF. #
PAN1)
1 ALL PLAQUES AND SIGNAGE REQUIRED BY 2017 NEC
AND 2015 IFC WILL BE INSTALLED AS REQUIRED.
PHOTOVOLTAIC SYSTEM EQUIPPED ! WARNING ! LABELS, WARNING(S) AND MARKING SHALL COMPLY
JB1 - TRANSITION BOX WITH RAPID SHUTDOWN WARNING ELECTRIC SHOCK HAZARD. TERMINALS ON BOTH WITH ANSI Z535.4, WHICH REQUIRES THAT DANGER,
(SOLADECK 0783-3R-4ER6) WARNING, AND CAUTION SIGNS USED THE STANDARD
PHOTOVOLTAIC POWER SOURCE LINE AND LOAD SIDES MAY BE ENERGIZED IN
TURN RAPID SHUTDOWN
SWITCH TO THE 'OFF'
THE OPEN POSITION. 2 HEADER COLORS, HEADER TEXT, AND SAFETY ALERT
SYMBOL ON EACH LABEL. THE ANSI STANDARD
REQUIRES A HEADING THAT IS AT LEAST 50% TALLER
POSITION TO SHUT DOWN NEC 690.31(G)(3) AND IFC 605.11.1 NEC 690.13(B) THAN THE BODY TEXT, IN ACCORDANCE WITH NEC

GRID-TIED SOLAR POWER SYSTEM


CONDUCTORS OUTSIDE 110.21(B).
JB2 - TRANSITION BOX THE ARRAY.
AC COMBINER PANEL (PAN1) DC DISCONNECT (I1) A PERMANENT PLAQUE OR DIRECTORY SHALL BE

ZIP64834
(SOLADECK 0783-3R-2ER6) CONDUCTORS WITHIN THE
INSTALLED PROVIDING THE LOCATION OF THE SERVICE
ARRAY REMAIN
ENERGIZED IN SUNLIGHT.
3 DISCONNECTING MEANS AND THE PHOTOVOLTAIC
SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME
! WARNING !

OAK DR
SMITH RESIDENCE
ADDRESS
DIRECT-CURRENT PV POWER SOURCE LOCATION IN ACCORDANCE WITH NEC 690.56(B).
THIS EQUIPMENT FED BY MULTIPLE SOURCES. MAXIMUM VOLTAGE: 400V

STATEMO
NEC 690.56(C)(1) TOTAL RATING OF ALL OVERCURRENT DEVICES, WHERE THE INVERTERS ARE REMOTELY LOCATED
C1 - STRING COMBINER MAX CIRCUIT-CURRENT: 37.5A FROM EACH OTHER, A DIRECTORY IN SHALL BE
(MIDNITE SOLAR MNSOB3R-4P) EXCLUDING MAIN OVERCURRENT DEVICE SHALL DC-TO-DC CONVERTER RATED CURRENT: 15.0A
NOT EXCEED AMPACITY OF BUSBAR. INSTALLED AT EACH DC PHOTOVOLTAIC SYSTEM
4

JUNCTION,
DISCONNECTING MEANS, AT EACH AC DISCONNECTING
NEC 705.12(B)(2)(3)(C) NEC 690.53 MEANS, AND AT THE MAIN SERVICE DISCONNECTING

BLACK
MEANS SHOWING THE LOCATION OF ALL AC AND DC
PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IN

STREET
I1 - INVERTER DC DISCONNECT (I2) AC SOLAR DISCONNECT (SW1, CB3 IN MSP) AC DISCONNECT (SW1, CB3 IN MSP) THE BUILDING, IN ACCORDANCE WITH NEC 690.4(H).

CARLCITY,
(SOLAR EDGE SE7600H-US) LABEL(S) WITH MARKING, "TURN RAPID SHUTDOWN
SWITCH TO THE 'OFF' POSITION TO SHUT DOWN

137
DIRECT-CURRENT PV POWER SOURCE CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS
MAXIMUM VOLTAGE: 380V MAXIMUM AC OPERATING CURRENT: 48.0A WITHIN THE ARRAY REMAIN ENERGIZED IN SUNLIGHT,"

I2 - INVERTER
MAX CIRCUIT-CURRENT: 18.8A
DC-TO-DC CONVERTER RATED CURRENT: 15.0A
PV SYSTEM DISCONNECT MAXIMUM AC OPERATING VOLTAGE: 240V 5 SHALL BE LOCATED WITHIN 3 FT OF SERVICE
DISCONNECTING MEANS THE TITLE SHALL UTILIZE
CAPITALIZED LETTERS WITH A MINIMUM HEIGHT OF 3/8”
(SOLAR EDGE SE3800H-US) IN WHITE ON A RED BACKGROUND, AND REMAINING
NEC 690.53 NEC 690.13(B) NEC 690.54 TEXT SHALL BE CAPITALIZED WITH A MINIMUM HEIGHT
OF 3/16” IN BLACK ON WHITE BACKGROUND
ANY AC ELECTRICAL PANEL THAT IS FED BY
AC DISCONNECT (CB1 IN PAN1) AC DISCONNECT (CB2 IN PAN1) BOTH THE UTILITY AND THE PHOTOVOLTAIC LABEL(S) WITH MARKING, "WARNING PHOTOVOLTAIC
SYSTEM (PAN1, MSP) POWER SOURCE," SHALL BE LOCATED AT EVERY 10
PAN1 - AC AGGREGATION PANEL FEET OF EACH DC RACEWAY AND WITHIN ONE FOOT OF
(MODEL NOT SPECIFIED)
6 EVERY TURN OR BEND AND WITHIN ONE FOOT ABOVE
AND BELOW ALL PENETRATIONS OF ROOF/CEILING
MAXIMUM AC OPERATING CURRENT: 32.0A MAXIMUM AC OPERATING CURRENT: 16.0A ! WARNING ! ASSEMBLIES, WALLS AND BARRIERS. THE LABEL SHALL
MAXIMUM AC OPERATING VOLTAGE: 240V MAXIMUM AC OPERATING VOLTAGE: 240V DUAL POWER SOURCE. SECOND SOURCE IS HAVE 3/8” TALL LETTERS AND BE REFLECTIVE WITH
PHOTOVOLTAIC SYSTEM. WHITE TEXT ON A RED BACKGROUND
MSP - MAIN SERVICE PANEL
(SIEMENS) NEC 690.54 NEC 690.54 NEC 705.12(B)(3)

SOLAR BREAKER (MSP)

! WARNING !
SW1 - DISCONNECT
(EATON DG222NRB )
INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE. SAFETY LABELS
NEC 705.12(B)(2)(3)(B) DOC ID: 117532-147309-1
DATE: 7/5/19
CREATOR: N.P.
REVIEWER:

REVISIONS

PV-4.1
POINT-OF-INTERCONNECTION OR AT MAIN SERVICE DISCONNECT (MSP)
REF. #
! CAUTION !
POWER TO THIS BUILDING IS ALSO FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN

GRID-TIED SOLAR POWER SYSTEM

ZIP64834
OAK DR
SMITH RESIDENCE
ADDRESS
STATEMO
JUNCTION,
BLACK
STREET
CARLCITY,
137
NEC 690.56(B)

SAFETY LABELS
DOC ID: 117532-147309-1
DATE: 7/5/19
CREATOR: N.P.
REVIEWER:

REVISIONS

PV-4.2
ROOF PROPERTIES REF. #
ROOF MATERIAL SPANISH BARREL TILE (W-SHAPE)
SLOPE 6/12 (26.6°)
MEAN ROOF HEIGHT 15.9FT
DECK SHEATHING 15/32" OSB
CONSTRUCTION RAFTERS (2X4'S), 24IN OC

GRID-TIED SOLAR POWER SYSTEM


MODULE MECHANICAL PROPERTIES
MODEL LG LG350Q1C-A5

ZIP64834
DIMENSIONS (AREA) 66.9IN X 40.0IN X 1.6IN (18.6 SQ FT)

OAK DR
SMITH RESIDENCE
WEIGHT 40.8LB

ADDRESS
STATEMO
MOUNTING SYSTEM PROPERTIES

JUNCTION,
RAIL MODEL IRONRIDGE XR100

BLACK
QUICK MOUNT PV QMTR-W4
ANCHOR MODEL (FLASHED) W/ (1) TILE REPLACEMENT

STREET
BASE MOUNT, 4.0IN AIR GAP

CARLCITY,
3.0 INCH EMBEDMENT INTO RAFTERS
FASTENING METHOD WITH 2 FASTENERS

137
111.0IN (ZONE 1)
MAX. ALLOW. RAIL SPAN 87.0IN (ZONE 2)
56.0IN (ZONE 3)
72.0IN (ZONE 1)
MAX. MOUNT SPACING 48.0IN (ZONES 2 AND 3)
44.4IN (ZONE 1)
MAX. ALLOW. 34.8IN (ZONE 2)
CANTILEVER 22.4IN (ZONE 3)
GROUNDING AND INTEGRAL GROUNDING CERTIFIED
BONDING TO UL 2703 REQUIREMENTS

DEAD LOAD CALCULATIONS


LOAD QTY LBS TOTAL LBS
MODULES 29 40.8 1182.8
OPTIMIZERS 29 0.6 18.3
LINEAR FEET OF RAIL 196 FT 0.7 133.5 WIND ZONE I WIND ZONE II WIND ZONE III
ANCHORS 51 5.0 253.5
REMOVED TILES 51 -8.5 -433.5
DISTANCE α IS EQUAL TO 10% OF THE BUILDING'S LEAST HORIZONTAL DIMENSION OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET (ACSE 7-
MISC. HARDWARE 11.4 11.4 10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF CORNERS, RAKES, HIPS, EAVES, MANSARDS, AND RIDGES OF ROOF FACES. ATTACHMENT
TOTAL ARRAY WEIGHT 1165.9 LBS α = MAX(MIN(0.4 * MEAN ROOF HEIGHT, 0.1 * LEAST HORIZONTAL DIMENSION), 0.04 * LEAST HORIZONTAL DIMENSION, 3 FT)
PLAN
AREA NAME QTY SQFT TOTAL SQFT 6.1 FT = MAX(MIN(0.4 * 15.9 FT, 0.1 * 61.4 FT), 0.04 * 61.4 FT, 3 FT)
DOC ID: 117532-147309-1
MODULES 29 18.6 539.4 DATE: 7/5/19
POINT LOAD (1165.9 LBS / 51 ATTACHMENTS) 22.9 LBS CREATOR: N.P.
DIST. LOAD (1165.9 LBS / 539.4 SQFT) 2.16 PSF REVIEWER:

REVISIONS
NOTES
RAFTER LOCATIONS ARE APPROXIMATE. ACTUAL
1 LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED
TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THE
MOUNT SPACING EXCEED "MAX. MOUNT SPACING"

PV-5.1
ROOF PROPERTIES REF. #
ROOF MATERIAL SPANISH BARREL TILE (W-SHAPE)
SLOPE 6/12 (26.6°)
MEAN ROOF HEIGHT 13.6FT
DECK SHEATHING 15/32" OSB
CONSTRUCTION RAFTERS (2X4'S), 24IN OC

GRID-TIED SOLAR POWER SYSTEM


MODULE MECHANICAL PROPERTIES
MODEL LG LG350Q1C-A5

ZIP64834
DIMENSIONS (AREA) 66.9IN X 40.0IN X 1.6IN (18.6 SQ FT)

OAK DR
SMITH RESIDENCE
ADDRESS
WEIGHT 40.8LB

STATEMO
MOUNTING SYSTEM PROPERTIES

JUNCTION,
RAIL MODEL IRONRIDGE XR100

BLACK
QUICK MOUNT PV QMTR-W4
ANCHOR MODEL (FLASHED) W/ (1) TILE REPLACEMENT

STREET
BASE MOUNT, 4.0IN AIR GAP

CARL CITY,
3.0 INCH EMBEDMENT INTO RAFTERS
FASTENING METHOD WITH 2 FASTENERS

137
111.0IN (ZONE 1)
MAX. ALLOW. RAIL SPAN 87.0IN (ZONE 2)
56.0IN (ZONE 3)
72.0IN (ZONE 1)
MAX. MOUNT SPACING 48.0IN (ZONES 2 AND 3)
44.4IN (ZONE 1)
MAX. ALLOW. 34.8IN (ZONE 2)
CANTILEVER 22.4IN (ZONE 3)
GROUNDING AND INTEGRAL GROUNDING CERTIFIED
BONDING TO UL 2703 REQUIREMENTS

DEAD LOAD CALCULATIONS


LOAD QTY LBS TOTAL LBS
MODULES 14 40.8 571.0
OPTIMIZERS 14 0.6 8.8
LINEAR FEET OF RAIL 95 FT 0.7 64.4
ANCHORS 27 5.0 134.2
REMOVED TILES 27 -8.5 -229.5
MISC. HARDWARE 5.7 5.7 ATTACHMENT
TOTAL ARRAY WEIGHT 554.7 LBS PLAN
AREA NAME QTY SQFT TOTAL SQFT
DOC ID: 117532-147309-1
MODULES 14 18.6 260.4 DATE: 7/5/19
POINT LOAD (554.7 LBS / 27 ATTACHMENTS) 20.5 LBS CREATOR: N.P.
WIND ZONE I WIND ZONE II WIND ZONE III
DIST. LOAD (554.7 LBS / 260.4 SQFT) 2.13 PSF REVIEWER:

DISTANCE α IS EQUAL TO 10% OF THE BUILDING'S LEAST HORIZONTAL DIMENSION OR 40% OF THE MEAN ROOF HEIGHT, WHICHEVER IS SMALLER, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET (ACSE 7-
REVISIONS
NOTES 10). THESE SETBACKS ARE APPLIED TO THE BUILDING FOOTPRINT AND PROJECTED TO THE PLANES OF ROOF CORNERS, RAKES, HIPS, EAVES, MANSARDS, AND RIDGES OF ROOF FACES.
RAFTER LOCATIONS ARE APPROXIMATE. ACTUAL α = MAX(MIN(0.4 * MEAN ROOF HEIGHT, 0.1 * LEAST HORIZONTAL DIMENSION), 0.04 * LEAST HORIZONTAL DIMENSION, 3 FT)
1 LOCATIONS MAY DIFFER AND CONTRACTOR MAY NEED
TO ADJUST MOUNT LOCATIONS. IN NO CASE SHALL THE 5.5 FT = MAX(MIN(0.4 * 13.6 FT, 0.1 * 61.4 FT), 0.04 * 61.4 FT, 3 FT)
MOUNT SPACING EXCEED "MAX. MOUNT SPACING"

PV-5.2
GRID-TIED SOLAR POWER SYSTEM
REVIEWER:
CREATOR: N.P.

SMITH RESIDENCE
DATE: 7/5/19
DETAILS

PV-6

STREET
137 ADDRESS
BLACK OAK DR
REF. #

REVISIONS
ATTACHMENT

DOC ID: 117532-147309-1

CARLCITY,
JUNCTION,
STATEMO
ZIP64834
GENERAL NOTES REF. #
ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS
THAT DO NOT REQUIRE THE PLACEMENT OF GROUND
LADDERS OVER OPENINGS SUCH AS WINDOWS OR
1 DOORS, AND LOCATED AT STRONG POINTS OF BUILDING
CONSTRUCTION IN LOCATIONS WHERE THE ACCESS
POINT DOES NOT CONFLICT WITH OVERHEAD
OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS.
(IFC 605.11.1.1)
PANELS AND MODULES INSTALLED ON GROUP R-3

GRID-TIED SOLAR POWER SYSTEM


BUILDINGS WITH A SINGLE RIDGE SHALL BE LOCATED IN
2 A MANNER THAT PROVIDES TWO, 3-FOOT-WIDE ACCESS
PATHWAYS FROM THE EAVE TO THE RIDGE ON EACH

ZIP64834
ROOF SLOPE WHERE PANELS AND MODULES ARE
LOCATED. (IFC 605.11.1.2.3)

OAK DR
SMITH RESIDENCE
ADDRESS
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS WITH ROOF HIPS AND VALLEYS SHALL NOT

STATEMO
BE LOCATED CLOSER THAN 18 INCHES TO A HIP OR A
VALLEY WHERE PANELS/MODULES ARE TO BE PLACED
3 ON BOTH SIDES OF A HIP OR VALLEY. WHERE PANELS

JUNCTION,
ARE TO BE LOCATED ON ONLY ONE SIDE OF A HIP OR
VALLEY THAT IS OF EQUAL LENGTH, THE PANELS SHALL

BLACK
BE PERMITTED TO BE PLACED DIRECTLY ADJACENT TO
THE HIP OR VALLEY. (IFC 605.11.1.2.4)

STREET
CARLCITY,
PANELS AND MODULES INSTALLED ON GROUP R-3
BUILDINGS SHALL BE LOCATED NOT LESS THAN 3 FEET
(914 MM) FROM THE RIDGE IN ORDER TO ALLOW FOR

137
FIRE DEPARTMENT SMOKE VENTILATION OPERATIONS,
4 EXCEPT IN SUCH CASES WHERE AN ALTERNATIVE
VENTILATION METHOD APPROVED BY THE FIRE CHIEF
HAS BEEN PROVIDED OR WHERE THE FIRE CHIEF HAS
DETERMINED VERTICAL VENTILATION TECHNIQUES WILL
NOT BE EMPLOYED. (IFC 605.11.1.2.5)

ROOF ACCESS POINT A FOR ROOF F17


1.5 FT. WIDE FIRE ACCESS PATHWAY, PER IFC
605.11.1.2.3 AND IFC 605.11.1.2.4
3.0 FT. WIDE FIRE ACCESS PATHWAY, PER IFC
605.11.1.2.3 AND IFC 605.11.1.2.4
(E) GAS METER, OUTDOOR. NO NEW ELECTRICAL
EQUIPMENT SHALL BE INSTALLED WITHIN 36 INCHES
OF CENTER OF GAS METER OR RISER.
ROOF ACCESS POINT B FOR ROOF F15
3.0 FT. WIDE SMOKE-VENTILATION SETBACK, PER IFC
605.11.1.2.5
PV MODULES INSTALLED ON ROOF WITH IRONRIDGE
ROOF MOUNTING SYSTEM. THE MOUNTING SYSTEM IS
UL 1703 CLASS A FIRE RATED ON A 6/12 SLOPED ROOF
WHEN INSTALLED WITH TYPE 1 OR 2 MODULES. THE FIRE SAFETY
LG LG350Q1C-A5 IS TYPE 1. PLAN
ROOF ACCESS POINT A FOR ROOF F15 DOC ID: 117532-147309-1
3.0 FT. WIDE FIRE ACCESS PATHWAY, PER IFC DATE: 7/5/19
605.11.1.2.3 CREATOR: N.P.
ROADWAY REVIEWER:

ROOF ACCESS POINT B FOR ROOF F17 REVISIONS


TOTAL PLAN VIEW ARRAY AREA IS 711.4 SQ.FT, WHICH
REPRESENTS 21.8% OF TOTAL PLAN VIEW ROOF AREA
(3265.3 SQ.FT)

PV-7
GRID-TIED SOLAR POWER SYSTEM
REVIEWER:
CREATOR: N.P.

SMITH RESIDENCE
DATE: 7/5/19

PV-8

STREET
137 ADDRESS
BLACK OAK DR
REF. #

REVISIONS
SITE IMAGES
DOC ID: 117532-147309-1

CARLCITY,
JUNCTION,
STATEMO
ZIP64834
LG365Q1C-A5 LG360Q1C-A5 LG355Q1C-A5 LG350Q1C-A5

Innovation for
a Better Life Mechanical Properties Electrical Properties (STC *)
Cells 6 x 10 Module 365 360 355 350
Cell Vendor LG Maximum Power (Pmax) 365 360 355 350
Cell Type Monocrystalline / N-type MPP Voltage (Vmpp) 36.7 36.5 36.3 36.1
Cell Dimensions 161.7 x 161.7 mm / 6 inches MPP Current (Impp) 9.95 9.87 9.79 9.70
Dimensions (L x W x H) 1700 x 1016 x 40 mm Open Circuit Voltage (Voc) 42.8 42.7 42.7 42.7
66.93 x 40.0 x 1.57 inch Short Circuit Current (Isc) 10.8 10.79 10.78 10.77
Front Load 6000Pa Module Efficiency 21.1 20.8 20.6 20.3
Rear Load 5400Pa Operating Temperature -40 ~ +90
Weight 18.5 kg Maximum System Voltage 1000
Connector Type MC4 Maximum Series Fuse Rating 20
Junction Box IP68 with 3 Bypass Diodes Power Tolerance (%) 0 ~ +3
Length of Cables 1000 mm x 2 ea * STC (Standard Test Condition): Irradiance 1,000 W/m², Ambient Temperature 25 °C, AM 1.5
Glass Tempered Glass with AR Coating * The nameplate power output is measured and determined by LG Electronics at its sole and absolute discretion.
* The typical change in module efficiency at 200 W/m² in relation to 1000 W/m² is -2.0%.
Frame Anodized Aluminium

Electrical Properties (NOCT*)


Certifications and Warranty
Module 365 360 355 350
IEC 61215, IEC 61730-1/-2 Maximum Power (Pmax) 275 271 267 263
UL 1703 MPP Voltage (Vmpp) 36.6 36.4 36.2 36.0
LG365Q1C-A5 LG360Q1C-A5 LG355Q1C-A5 LG350Q1C-A5 IEC 61701 (Salt mist corrosion test) MPP Current (Impp) 7.51 7.45 7.39 7.32
IEC 62716 (Ammonia corrosion test) Open Circuit Voltage (Voc) 40.2 40.2 40.2 40.1
ISO 9001 Short Circuit Current (Isc) 8.70 8.69 8.68 8.67
Module Fire Performance (USA) Type 1 * NOCT (Nominal Operating Cell Temperature): Irradiance 800 W/m2, ambient temperature 20 °C, wind speed 1 m/s
Fire Resistance Class (CANADA) Class C (ULC / ORD C1703)
Product Warranty 25 years
The LG NeON® R is a powerful solar module that provides world-class
performance. A new cell structure that eliminates electrodes on the Output Warranty of Pmax Linear warranty**
Dimensions (mm/in)

60 cell front maximizes the utilization of light and enhances reliability. The **1) First 5 years : 95%, 2) After 5th year : 0.4% annual degradation, 3) 25 years : 88.4%
4.0/0.2
LG NeON® R is a result of LG’s efforts to increase customer value TM Ø 8.2
/0
Ø 4
.3/0
.2 5.5/0.2

Temperature Characteristics .3

40.0/1.6
40.0/1.6
7.5/0.3

4.0/0.2
beyond basic efficiency. The NeON® R features enhanced durability KM 564573 BS EN 61215 Photovoltaic Modules
R1
.5

and performance under real-world conditions, an enhanced warranty NOCT 44 ± 3 °C


Detail X Detail Y Detail Z Detail D 29.0/1.1 29.0/1.1

and an aesthetic design suitable for roofs. Pmpp -0.30 %/°C


Voc -0.24 %/°C
4-4.0*5.5/0.2*0.2 1016.0/40.0
(Size of Short Side)

Isc 0.04 %/°C Drain Holes


[D view]
976.0/38.4
4-4.0*7.5/0.2*0.3 (Distance between Grounding & Mounting Holes)
40.0/1.6
Drain Holes
[Z view]

Enhanced Performance Warranty High Power Output Characteristic Curves 4-Ø4.3/0.2


Grounding Holes
[Y view] (-) (+)
8-Ø8.2/0.3
LG offers a 25-year product warranty for LG NeON® R, The LG NeON® R has been designed to 1000W Mounting Holes Junction Box

Current (A)
10.00 [X view]

including labor, in addition to an enhanced performance significantly enhance its output, making it efficient 800W
warranty. After 25 years, LG NeON® R is guaranteed to even in limited space. 8.00

produce at least 88.4% of its initial power output. 6.00


600W
1000.0/39.4
Cable Length
400W
4.00
Roof Aesthetics Outstanding Durability 200W
2.00
LG NeON® R has been designed with aesthetics in mind: With its newly reinforced frame design, LG

(Distance between Mounting Holes)

(Distance between Mounting Holes)

1700.0/66.9
1100.0/43.3

1300.0/51.2

(Size of Long Side)


the lack of any electrodes on the front creates an NeON® R can endure a front load up to 6000 Pa, Voltage (V)
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00
improved, modern aesthetic. and a rear load up to 5400 Pa.
140
Isc, Voc, Pmax (%)

120
Isc

Better Performance on a Sunny Day Near Zero LID (Light Induced 100
Voc

LG NeON® R now performs better on sunny Degradation) 80 Pmax

60
days, thanks to its improved temperature coefficient. The n-type cells used in LG NeON® R have

200.0/7.9

105.0/4.1
40
almost no boron. This leads to less LID (Light
Induced Degradation) right after installation. 20

0 Temperature (°C)
-40 -25 0 25 50 75 90 * The distance between the center of the mounting/grounding holes.

North America Solar Business Team


LG Electronics U.S.A. Inc DS-T1-72-W-G-P-EN-60630
About LG Electronics 1000 Sylvan Ave, Englewood Cliffs, NJ 07632
Copyright © 2017 LG Electronics. All rights reserved. Innovation for a Better Life
LG Electronics is a global player who has been committed to expanding its capacity, based on solar energy business as its future growth engine. We embarked on a solar energy source research program in 1985, Contact: lg.solar@lge.com 01/01/2017
supported by LG Group’s rich experience in semi-conductor, LCD, chemistry, and materials industry. We successfully released first Mono X® series to the market in 2010, which were exported to 32 countries in www.lgsolarusa.com
the following 2 years, thereafter. In 2013, NeON™ (previously known as Mono X® NeON) & 2015 NeON2 with CELLO technology won “Intersolar Award”, which proved LG is the leader of innovation in the
industry.
Power Optimizer
For North America

POWER OPTIMIZER
Power Optimizer P320 / P340 / P370 / P400 / P405 / P505
P370
For North America Optimizer model
(typical module
P320
(for 60-cell
P340
(for high-
(for higher-
power
P400
(for 72 & 96-
P405
(for thin film
P505
(for higher
power 60-cell cell current
P320 / P340 / P370 / P400 / P405 / P505 compatibility) modules)
modules)
60 and 72-cell
modules)
modules)
modules)
modules)

INPUT
Rated Input DC Power(1) 320 340 370 400 405 505 W
Absolute Maximum Input

25
Voltage 48 60 80 125(2) 83(2) Vdc
(Voc at lowest temperature)
MPPT Operating Range 8 - 48 8 - 60 8 - 80 12.5 - 105 12.5 - 83 Vdc
YEAR
WARRANTY Maximum Short Circuit Current
11 10.1 14 Adc
(Isc)
Maximum DC Input Current 13.75 12.63 17.5 Adc
Maximum Efficiency 99.5 %
Weighted Efficiency 98.8 98.6 %
Overvoltage Category II
OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER)
Maximum Output Current 15 Adc
Maximum Output Voltage 60 85 Vdc
OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE
INVERTER OFF)
Safety Output Voltage per
1 ± 0.1 Vdc
Power Optimizer
STANDARD COMPLIANCE
EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3
Safety IEC62109-1 (class II safety), UL1741
RoHS Yes
INSTALLATION SPECIFICATIONS
Maximum Allowed System
1000 Vdc
Voltage
Compatible inverters All SolarEdge Single Phase and Three Phase inverters
128 x 152 x 36 / 128 x 152 x 50 / 128 x 152 x 59 /
Dimensions (W x L x H) 128 x 152 x 28 / 5 x 5.97 x 1.1 mm / in
5 x 5.97 x 1.42 5 x 5.97 x 1.96 5 x 5.97 x 2.32
Weight (including cables) 630 / 1.4 750 / 1.7 845 / 1.9 1064 / 2.3 gr / lb
Input Connector MC4(3)
Output Wire Type / Connector Double Insulated; MC4
Output Wire Length 0.95 / 3.0 1.2 / 3.9 m / ft
Input Wire Length 0.16 / 0.52 m / ft
Operating Temperature Range -40 - +85 / -40 - +185 ˚C / ˚F
PV power optimization at the module-level Protection Rating IP68 / NEMA6P
Relative Humidity 0 - 100 %
(1)
Rated STC power of the module. Module of up to +5% power tolerance allowed
(2)
NEC 2017 requires max input voltage be not more than 80V
Specifically designed to work with SolarEdge Fast installation with a single bolt (3)
For other connector types please contact SolarEdge

inverters
Next generation maintenance with module- PV System Design Using Single Phase
Single phase Three Phase 208V Three Phase 480V
Up to 25% more energy level monitoring a SolarEdge Inverter(4)(5) HD-Wave
P320, P340, P370,
Minimum String Length 8 10 18
P400
(Power Optimizers)
Superior efficiency (99.5%) Meets NEC requirements for arc fault P405 / P505 6 8 14
protection (AFCI) and Photovoltaic Rapid Maximum String Length
25 25 50(6)
(Power Optimizers)
Mitigates all types of module mismatch losses, Shutdown System (PVRSS) 5700 (6000 with
from manufacturing tolerance to partial Maximum Power per String SE7600-US - SE11400- 5250 6000(7) 12750(8) W
US)
shading Module-level voltage shutdown for installer Parallel Strings of Different Lengths
Yes
and firefighter safety or Orientations
Flexible system design for maximum space (4)
For detailed string sizing information refer to: http://www.solaredge.com/sites/default/files/string_sizing_na.pdf
(5)
It is not allowed to mix P405/P505 with P320/P340/P370/P400 in one string
utilization (6)
A string with more than 30 optimizers does not meet NEC rapid shutdown requirements; safety voltage will be above the 30V requirement
(7)
For SE14.4KUS/SE43.2KUS: It is allowed to install up to 6,500W per string when 3 strings are connected to the inverter (3 strings per unit for SE43.2KUS) and when
the maximum power difference between the strings is up to 1,000W
(8)
For SE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS: It is allowed to install up to 15,000W per string when 3 strings are connected to the inverter (3 strings per unit for SE66.6KUS/SE100KUS)
and when the maximum power difference between the strings is up to 2,000W

solaredge.com © SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 12/2018/V01/ENG NAM. Subject to change without notice.
Basic Features
• Stamped Seamless Construction
• 18 Gauge Galvanized Steel
• Powder Coated Surfaces
• Flashes into the roof deck
• 3 Roof deck knockouts .5", .75", 1"
• 5 Centering dimples for entry/exit
fittings or conduit
• 2 Position Ground lug installed
• Mounting Hardware Included
SolaDeck Model SD 0783

SolaDeck UL50 Type 3R Enclosures


Available Models:
Model SD 0783 - (3” fixed Din Rail)
Model SD 0786 - (6” slotted Din Rail)

SolaDeck UL 1741 Combiner/Enclosures


Models SD 0783-41 and SD 0786-41 are labeled and ETL listed UL STD 1741
according to the UL STD 1741 for photovoltaic combiner enclosures.
Max Rated - 600VDC, 120AMPS

Model SD 0783-41 3” Fixed Din Rail fastened using Norlock System


**Typical System Configuration
4- Din Rail Mounted Fuse Holders 600VDC 30 AMP
1- Power Distribution Block 600VDC 175AMP
1- Bus Bar with UL lug
Model SD 0786-41 6” Slotted Din Rail fastened using steel studs
**Typical System Configuration
4- Din Rail Mounted Fuse Holders 600VDC 30 AMP
4- Din Rail Mounted Terminal Blocks
Bus Bars with UL lug

**Fuse holders and terminal blocks


added in the field must be UL listed or
recognized and meet 600 VDC 30 AMP
110C for fuse holders, 600V 50 AMP
90C for rail mounted terminal blocks
and 600 V 175 AMP 90C for Power
Distribution Blocks. Use Copper Wire
Conductors.
Cover is trimmed to allow Model SD 0783-41, wired with Model SD 0786-41, wired with
conduit or fittings, base is Din Rail mounted fuse holders, Din Rail mounted fuse holders,
center dimpled for fitting bus bar and power distribution terminal blocks and bus bars.
locations. block.

RSTC Enterprises, Inc • 2219 Heimstead Road • Eau Cliare, WI 54703


For product information call 1(866) 367-7782
Single Phase Inverter
with HD-Wave Technology for North America

INVERTERS
SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US/
Single Phase Inverter SE7600H-US / SE10000H-US / SE11400H-US
SE3000H-US SE3800H-US SE5000H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US

with HD-Wave Technology


OUTPUT
3800 @ 240V 6000 @ 240V 11400 @ 240V
Rated AC Power Output 3000 5000 7600 10000 VA
3300 @ 208V 5000 @ 208V 10000 @ 208V
3800 @ 240V 6000 @ 240V 11400 @ 240V

for North America


Maximum AC Power Output 3000 5000 7600 10000 VA
3300 @ 208V 5000 @ 208V 10000 @ 208V
AC Output Voltage Min.-Nom.-Max.
Vac
(211 - 240 - 264)
SE3000H-US / SE3800H-US / SE5000H-US / SE6000H-US / AC Output Voltage Min.-Nom.-Max.
- - - - Vac
(183 - 208 - 229)
SE7600H-US / SE10000H-US / SE11400H-US AC Frequency (Nominal) 59.3 - 60 - 60.5(1) Hz

12-25 Maximum Continuous Output


Current @240V
12.5 16 21 25 32 42 47.5 A
YEAR Maximum Continuous Output
WARRANTY - 16 - 24 - - 48.5 A
Current @208V
GFDI Threshold 1 A
Utility Monitoring, Islanding
Protection, Country Configurable Yes
Thresholds
INPUT
Maximum DC Power @240V 4650 5900 7750 9300 11800 15500 17650 W
Maximum DC Power @208V - 5100 - 7750 - - 15500 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage 480 Vdc
Nominal DC Input Voltage 380 400 Vdc
Maximum Input Current @240V(2) 8.5 10.5 13.5 16.5 20 27 30.5 Adc
Maximum Input Current @208V(2) - 9 - 13.5 - - 27 Adc
Max. Input Short Circuit Current 45 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 600k Sensitivity
Maximum Inverter Efficiency 99 99.2 %
99 @ 240V
CEC Weighted Efficiency 99 %
98.5 @ 208V
Nighttime Power Consumption < 2.5 W

ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, ZigBee (optional), Cellular (optional)
Revenue Grade Data, ANSI C12.20 Optional(3)
Rapid Shutdown - NEC 2014 and
Optimized installation with HD-Wave technology
Automatic Rapid Shutdown upon AC Grid Disconnect
2017 690.12
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, CSA C22.2, Canadian AFCI according to T.I.L. M-07
Specifically designed to work with Extremely small Grid Connection Standards IEEE1547, Rule 21, Rule 14 (HI)
power optimizers Emissions FCC Part 15 Class B

Built-in module-level monitoring INSTALLATION SPECIFICATIONS


Record-breaking efficiency
AC Output Conduit Size / AWG
3/4” minimum / 14-6 AWG 3/4” minimum /14-4 AWG
Range
Fixed voltage inverter for longer strings Outdoor and indoor installation DC Input Conduit Size / # of Strings /
3/4” minimum / 1-2 strings / 14-6 AWG 3/4” minimum / 1-3 strings / 14-6 AWG
AWG Range
Dimensions with Safety Switch in /
17.7 x 14.6 x 6.8 / 450 x 370 x 174 21.3 x 14.6 x 7.3 / 540 x 370 x 185
Integrated arc fault protection and rapid shutdown for Optional: Revenue grade data, ANSI C12.20 (HxWxD) mm
NEC 2014 and 2017, per article 690.11 and 690.12 Class 0.5 (0.5% accuracy) Weight with Safety Switch 22 / 10 25.1 / 11.4 26.2 / 11.9 38.8 / 17.6 lb / kg
Noise < 25 <50 dBA
UL1741 SA certified, for CPUC Rule 21 grid Cooling Natural Convection
compliance Operating Temperature Range -40 to +140 / -25 to +60(4) (-40˚F / -40˚C option)(5) ˚F / ˚C
Protection Rating NEMA 4X (Inverter with Safety Switch)
(1)
For other regional settings please contact SolarEdge support
(2)
A higher current source may be used; the inverter will limit its input current to the values stated
(3)
Revenue grade inverter P/N: SExxxxH-US000NNC2
solaredge.com (4)
For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf
(5)
-40 version P/N: SExxxxH-US000NNU4
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All
other trademarks mentioned herein are trademarks of their respective owners. Date: 12/2018/V01/ENG NAM. Subject to change without notice.
Datasheet Datasheet

XR Rails
Flush Mount System
XR10 Rail XR100 Rail XR1000 Rail Bonded Splices

A low-profile mounting rail The ultimate residential A heavyweight mounting All rails use internal splices
for regions with light snow. solar mounting rail. rail for commercial projects. for seamless connections.
• 6’ spanning capability • 8’ spanning capability • 12’ spanning capability • Self-drilling screws
• Moderate load capability • Heavy load capability • Extreme load capability • Varying versions for rails
• Clear and black finish • Clear and black finish • Clear anodized finish • Forms secure bonding

Clamps & Grounding

UFOs Stopper Sleeves CAMO Grounding Lugs

Universal Fastening Objects Snap onto the UFO to turn Bond modules to rails while Connect arrays to
bond modules to rails. into a bonded end clamp. staying completely hidden. equipment ground.
• Fully assembled & lubed • Bonds modules to rails • Universal end-cam clamp • Low profile
• Single, universal size • Sized to match modules • Tool-less installation • Single tool installation
• Clear and black finish • Clear and black finish • Fully assembled • Mounts in any direction
Built for solar’s toughest roofs.
Attachments
IronRidge builds the strongest mounting system for pitched roofs in solar. Every component has been tested to
the limit and proven in extreme environments. FlashFoot2 Conduit Mount Slotted L-Feet Bonding Hardware
Our rigorous approach has led to unique structural features, such as curved rails and reinforced flashings, and
is also why our products are fully certified, code compliant and backed by a 25-year warranty.

Strength Tested PE Certified


All components evaluated for superior Pre-stamped engineering letters Flash and mount XR Rails Flash and mount conduit, Drop-in design for rapid rail Bond and attach XR Rails
structural performance. available in most states. with superior waterproofing. strut, or junction boxes. attachment. to roof attachments.
• Twist-on Cap eases install • Twist-on Cap eases install • Secure rail connections • T & Square Bolt options
• Wind-driven rain tested • Wind-driven rain tested • Slot for vertical adjusting • Nut uses 7/16” socket
Class A Fire Rating Design Assistant • Mill and black finish • Secures ¾” or 1” conduit • Clear and black finish • Assembled and lubricated
Certified to maintain the fire resistance Online software makes it simple to
rating of the existing roof. create, share, and price projects. Resources

Design Assistant ERED PROVI


NABCEP Certified Training
IST

UL 2703 Listed System 25-Year Warranty

DE
REG
Go from rough layout to fully Earn free continuing education credits,

R
engineered system. For free. while learning more about our systems.
Entire system and components meet Products guaranteed to be free NT

ON
CO
IN U TI
I NG E DUC A
Go to IronRidge.com/design Go to IronRidge.com/training
newest effective UL 2703 standard. of impairing defects.

© 2019 IronRidge, Inc. All rights reserved. U.S. Patents: #8,695,290; #9,819,303; #9,865,938; Others Pending. Version 1.70
1495 Zephyr Avenue
Hayward, CA 94544
1-800-227-9523
IronRidge.com

Attn: David F. Taggart, VP Products, IronRidge Inc.


Date: March 30th, 2017

Re: Structural Certification and Span Tables for IronRidge Flush Mount System

This letter addresses the structural performance and code compliance of IronRidge’s Flush Mount System. The Flush
Mount System is a proprietary rooftop mounting system used to support photovoltaic (PV) modules installed in portrait or
landscape orientation and set parallel to the underlying roof surface. PV modules are supported by extruded aluminum
XR Rails and secured to the rails with IronRidge mounting clamps. The XR Rails are side mounted to a selected roof
attachment with 3/8” stainless steel bonding hardware and then attached directly to the roof structure or to a stanchion
that is fastened to the underlying roof structure. Assembly details of a typical Flush Mount installation and its core
components are shown in Exhibit EX-0015.

The IronRidge Flush Mount System is designed and certified to the structural requirements of the following reference
standards for the load conditions and configurations tabulated in the attached span tables:

• ASCE/SEI 7-05 Minimum Design Loads for Buildings and Other Structures (ASCE 7-05)
• ASCE/SEI 7-10 Minimum Design Loads for Buildings and Other Structures (ASCE 7-10)
• 2009 International Building Code (IBC-2009)
• 2012 International Building Code (IBC-2012)
• 2010 Aluminum Design Manual (ADM-2010)

The tables included in this letter provide the maximum allowable spans of XR Rails in the Flush Mount System for the
respective loads and configurations listed, covering wind exposure categories B, C, & D, roof zones 1, 2 & 3, and roof
slopes from 0º to 45º. The span tables are applicable provided that the following conditions are met:

1. Span is the distance between two adjacent roof attachment points (measured at the center of the attachment
fastener)

2. The underlying roof pitch, measured between roof surface and horizontal plane, is 45º or less.

3. The mean roof height, defined as the average of the roof eave height and the roof ridge height measured from
grade, does not exceed 30 feet.

4. Module length shall not exceed the listed maximum dimension provided for the respective span table and module
width shall not exceed 40”.

5. All Flush Mount components shall be installed in a professional workmanlike manner per IronRidge’s Flush Mount
installation manual and other applicable standards for general roof construction practice.

© 2017 IronRidge, Inc. MO Flush Mount System Certification Letter - 1


MODULe COMPATIBILITY MODULe COMPATIBILITY
The Flush Mount System may be used to ground and/or mount a PV module complying with UL 1703 only when the MAKe MODeLS
specific module has been evaluated for grounding and/or mounting in compliance with the included instructions. Unless Modules with 46mm frames and model identifier PV-MYYxxxZZ; where "YY" is LE or JE; and "ZZ"
otherwise noted, “xxx” refers to the module power rating and both black and silver frames are included in the certification. Mitsubishi
is either HD, HD2, or FB.
Motech IM and XS series modules with 40, 45, or 50mm frames.
MAKe MODeLS
Modules with 35mm frames and model identifier D6YxxxZZaa; where "Y" can be M or P; "ZZ" can
Modules with 35, 40, or 45mm frames and model identifier aaSM66yyPzz-xxx; where “aa” is CH Neo Solar Power
be B3A, B4A, E3A, E4A, H3A, H4A; and "aa" can be blank, (TF), ME or ME (TF).
Astronergy Solar or A; “yy” is either 10 or 12; and “zz” is blank or (BL). Frameless modules with model identifier
CHSM6610P(DG)-xxx. Modules with 35 or 40mm frames and model identifier VBHNxxxYYzz; where "YY" is SA or KA; and
Panasonic
"zz" is 01, 02, 03, 04, 06, 06B, 11, 11B, 15, 15B, 16, 16B, 17, or 18.
Modules with 35 or 40mm frames and model identifier AC-xxxY/aa-ZZ; where “Y” is M or P; “aa” is 125
Axitec Modules with 35, 40, or 45mm frames and model identifier PSxxxY-ZZ/A; where "Y" is M or P; "ZZ"
or 156; and “ZZ” is 54S, 60S or 72S. Phono Solar
is 20 or 24; and "A" is F, T or U.
Modules with 35 and 40mm frames and model identifier CSbY-xxxZ; where "b" can be 1, 3 or 6; "Y" can
be K, P, U, V, or X; and "Z" can be M, P, AG, MS, PX , M-SD, P-AG, P-FG or P-SD, MS-AG, MS-FG, or Prism Solar Frameless modules with model identifier BiYY-xxxBSTC; where "YY" is 48 or 60.
Canadian Solar
MS-SD. Frameless modules with model identifier CSbY-xxx-FG; where "b" can be 3 or 6; "Y" is K, X, or Modules with 30, 38 and 45mm frames and model identifier RECxxxYYZZ; where “YY” is M, PE,
REC Solar
P; and "Z" can be M-FG or P-FG. TP, or TP2S; and “ZZ” is blank, BLK, SLV, or 72.
Modules with 35, 40, or 50mm frames and model identifier ET-Y6ZZxxxAA; where "Y" is P, L, or M; "ZZ" Modules with 35, 40 or 50mm frames and model identifier JCxxxY-ZZ; where "Y" is F, M or S; and
ET Solar Renesola
is 60 or 72; and "AA" is WB, WW, BB, WBG, WWG, WBAC, WBCO, WWCO, WWBCO or BBAC. "ZZ" is Ab, Ab-b, Abh, Abh-b, Abv, Abv-b, Bb, Bb-b, Bbh, Bbh-b, Bbv, Bbv-b, Db, or Db-b.
Modules with 35, 40, or 50mm frames and model identifier FXS-xxxYY-ZZ; where "xxx" is the module Renogy Modules with 40 or 50mm frames and model identifier RNG-xxxY; where “Y” is D or P.
Flex power rating; "YY" is BB or BC; and "ZZ" is MAA1B, MAA1W, MAB1W, SAA1B, SAA1W, SAC1B, Modules with 40mm frames and model identifier SNxxxY-ZZ; where "Y" is M or P; and "ZZ" is 10, or
SAC1W, SAD1W, SBA1B, SBA1W, SBC1B, or SBC1W. S-Energy
15.
Modules with 35 and 40mm frames and and model identifier GCL-a6/YY xxx; where "a" can be M or P; Modules with 40mm frames and model identifier SEG-6YY-xxxZZ; where "YY" can be MA, MB, PA,
GCL Seraphim Energy Group
and "YY" can be 60, 72, or 72H. PB; and "ZZ" can be BB, WB, or WW.
GigaWatt Solar Modules with 40mm frames and model identifier GWxxxYY; where “YY” is either PB or MB. Modules with 40 and 50mm frames and model identifier SRP-xxx-6YY; where "YY" can be MA, MB,
Seraphim USA
Modules with 40, 45, or 50mm frames and model identifier HSLaaP6-YY-1-xxxZ; where "aa" is either 60 PA, PB, QA-XX-XX, and QB-XX-XX.
Hanwha Solar
or 72; "YY" is PA or PB; and "Z" is blank or B. Sharp Modules with 35 or 40mm frames and model identifier NUYYxxx; where “YY” is SA or SC.
Modules with 32, 35, 40, and 42mm frames and model identifier aaYY-ZZ-xxx; where "aa" can be Q. or Modules with 38mm frames and model identifier SYY-Z-xxx; where “YY” is SA or LA; SG or LG; and
B.; "YY" can be PLUS, PRO, PEAK, LINE PRO, LINE PLUS, or PEAK DUO; and "ZZ" can be G3, G3.1, Silfab
“Z” is M, P, or X.
G4, G4.1, L-G2, L-G2.3, L-G3, L-G3.1, L-G3y, L-G4, L-G4.2, L-G4y, LG4.2/TAA, BFR-G3, BLK-G3,
Hanwha Q CELLS Modules with 40mm frames and model identifier PowerXT xxxY-ZZ; where "Y" can be R or C; and
BFR-G3.1, BLK-G3.1, BFR-G4, BFR-G4.1, BFR G4.3, BLK-G4.1, G4/SC, G4.1/SC, G4.1/TAA, G4.1/ Solaria
"ZZ" is BX, BY, PX, PZ, WX or WZ.
MAX, BFR G4.1/TAA, BFR G4.1/MAX, BLK G4.1/TAA, BLK G4.1/SC, EC-G4.4, G5, BLK-G5, L-G5.2, or
L-G5.2/H. SolarTech Modules with 42mm frames and model identifier STU-xxxYY; where "YY" can be PERC or HJT.
Modules with 40mm frames and model identifier YYZZxxx; where "YY" is 36, 60, 72, or 96; and "ZZ" is Sunmodule Plus, Protect, XL, Bisun, Bisun XL, may be followed by mono, poly or duo and/or black
Heliene SolarWorld
M, P, or MBLK. or bk; modules with 31, 33 or 46mm frames and model identifier SW-xxx.
Modules with 35, 40 and 50mm frames and model identifier HiS-YxxxZZ; where "Y" can be M or S; and Thin film modules with 35mm frames and model identifier STO-xxx or STO-xxxA. Thin film
Hyundai Stion
"ZZ" can be MI, MF, MG, SG, RI, RG(BF), RG(BK), TI, or TG. frameless modules with model identifier STL-xxx or STL-xxxA.
Modules with 40 or 50mm frames and model identifier IT-xxx-YY; where "YY" is blank, HE, or SE, or Modules with 35, 40, or 50mm frames and model identifier SE-YxxxZABCDE; where "Y" is B, F, H,
Itek
SE72. SunEdison P, R, or Z; "Z" is 0 or 4; "A" is B, C, D, E, H, I, J, K, L, M, or N; "B" is B or W; "C" is A or C; "D" is 3,
7, 8, or 9; and "E" is 0, 1 or 2.
Modules with 35, 40 and 45mm frames and model identifier JAyyzz-bb-xxx/aa; where “yy” can be M, P,
M6 or P6; “zz” can be blank, (K), (L), (R), (V), (BK), (FA), (TG), (FA)(R), (L)(BK), (L)(TG), (R)(BK), (R) Modules with 35, 38, 40, 46, or 50mm frames and model identifiers OPTxxx-AA-B-YYY-Z
JA Solar Suniva or MVXxxx-AA-B-YYY-Z; where "AA" is either 60 or 72; "B" is either 4 or 5; "YYY" is either
(TG), (V)(BK), (BK)(TG), or (L)(BK)(TG); “bb” can be 48, 60, 72, 60S01 or 72S01; and “aa” can be MP,
SI, SC, PR, RE, 3BB, 4BB, 4BB/RE, 5BB. 100,101,700,1B0, or 1B1; and "Z" is blank or B.
Modules with 40mm frames and model identifier JKMYxxxZZ-aa; where "Y" is blank or S; "ZZ" is P, Modules with model identifier Ab-xxx-YY and standard (G3) or InvisiMount (G5) 46mm frame;
Jinko PP, M; and "aa" is 60, 60B, 60-J4, 60B-J4, 60(Plus), 60-V, 72, or 72-V. Frameless modules with model Sunpower where "A" is either E, P or X; “b” can be 17, 18, 19, 20, 21, or 22; and “YY” can be blank, NE, BLK,
identifier JKMxxxPP-DV. COM, C-AC, D-AC, BLK-C-AC, or BLK-D-AC.
Modules with 46mm frames and model identifier KYxxxZZ-AA; where “Y” is D or U; “ZZ” is blank, GX, or Sunpreme Frameless modules with model identifier GXB-xxxYY; where "YY" is blank or SL.
Kyocera SX; and “AA” is LPU, LFU, UPU, LPS, LPB, LFB, LFBS, LFB2, LPB2, 3AC, 3BC, 3FC, 4AC, 4BC, 4FC, Suntech Vd, Vem, Wdb, Wde, and Wd series modules with 35, 40, or 50mm frames.
4UC, 5AC, 5BC, 5FC, 5UC, 6BC, 6FC, 8BC, 6MCA, or 6MPA. Modules with 35, 40 or 46mm frames and model identifier TSM-xxxYYZZ; where “YY” is PA05,
Modules with 35, 40, and 46mm frames and model identifier LGxxxYaZ-bb; where "Y" is A, E, N, Q, S; PC05, PD05, PA14, PC14, PD14, PE14, or DD05; and “ZZ” is blank, A, A.05, A.08, A.10, A.18, .05,
LG Trina .08, .10, .18, .08D, .18D, 0.82, A.082(II), .002, .00S, 05S, 08S, A(II), A.08(II), A.05(II), A.10(II), or
"a" is 1 or 2; "Z" is C, K, T, or W; and "bb" is A3, A5, B3, G3, G4, or K4.
A.18(II). Frameless modules with model identifier TSM-xxxYY; and “YY” is either PEG5, PEG5.07,
Longi Modules with 40mm frames and model identifier LR6-YY-xxxM; where "YY" can be 60, 72, or 72HV. PEG14, DEG5(II), DEG5.07(II), or DEG14(II).
Modules with 35 or 40mm frames and model identifier Wsy-xxxz6; where "y" is either P or T; and
Modules with 40mm frames and model identifier MSExxxZZaa; where "ZZ" can be MM, SE, SO or SQ; Winaico
Mission Solar ""z"" is either M or P.
and "aa" can be 1J, 4J, 4S, 5K, 5T, 6J, 6S, or 6W.
Yingli Panda, YGE, and YGE-U series modules with 35, 40, or 50 mm frames.
© 2018 IRONRIDGE, INC. VERSION 1.60 FLUSH MOUNT INSTALLATION MANUAL - 9 © 2018 IRONRIDGE, INC. VERSION 1.60 FLUSH MOUNT INSTALLATION MANUAL - 10
ITEM DESCRIPTION QTY.

REV
QTY.
NO.

SHEET 1 OF 1
3
1

1
1

QMTR-W4: TILE REPLACEMENT,


1 FLASHING, .040" X 12" X 7.5", SHEET, 5052- 1
4 H32, MILL

AVAILABLE IN MILL, AND BLACK FINISHES


TILE REPLACEMENT BASE, 8.125", 6061-T6,
2 MILL 1

CAP SCREW, SERRATED FLANGE, HEX HEAD,

CAP SCREW, HEX HEAD, 5/16"-18 X 1" UNC-


FLASHING, REPLACEMENT TILE, W-TILE, .625"

WASHER, FENDER, 5/16" ID X 1" OD, 18-8 SS


POST, 1.25" OD X 4", 6063-T5/6063-T6, MILL
WASHER, SEALING, 5/16" ID X 3/4" OD,

WASHER, SEALING, 5/16" ID X 1-1/4" OD,

COLLAR, COUNTER FLASHING, 1-1/4" ID


3 2

RAD
EPDM BONDED SS

WASHER, SPLIT-LOCK, 5/16" ID, 18-8 SS


5/16"-18 X 1" UNC-2A, GRADE 8, ZINC

6/9/2017
LAG SCREW, GRK RSS WASHER HEAD, 5/16"
4 2

1
X 4", T-30, STEEL, CLIMATEK COATED

WEIGHT: 2.93
W-TILE, 4" POST
DRAWN BY:
CONE, ALUMINUM, MILL
EPDM BONDED SS
3

DATE:
DESCRIPTION

2A, 18-8 SS

SCALE: 1:5
EPDM

SIZE
A
UNLESS OTHERWISE SPECIFIED:

THREE PLACE DECIMAL .094


.19
DIMENSIONS ARE IN INCHES

TWO PLACE DECIMAL


FRACTIONAL 1/8

2
TOLERANCES:
TITLE:
ITEM
NO.

8
4

7
1

DO NOT SCALE DRAWING


1

THIS EDGE TOWARDS


RACKING NOT INCLUDED
TITLE:
2 QMTR-BM: TILE REPLACEMENT,

ROOF RIDGE
BASE MOUNT
UNLESS OTHERWISE SPECIFIED:
SIZE DRAWN BY: RAD REV
DIMENSIONS ARE IN INCHES
TOLERANCES:
A 4

3
FRACTIONAL 1/8 DATE: 9/23/2016
PROPRIETARY AND CONFIDENTIAL TWO PLACE DECIMAL .19
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF QUICK MOUNT PV. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE DO NOT SCALE DRAWING
WRITTEN PERMISSION OF QUICK MOUNT PV IS PROHIBITED. COPYRIGHT © 2016 QUICK MOUNT PV THREE PLACE DECIMAL .094 SCALE: 1:2 WEIGHT: 2.07 SHEET 1 OF 2

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF QUICK MOUNT PV. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE
5 4 3 2 1
THIS EDGE TOWARDS ROOF RIDGE

1
7.50 2.438 3.44
RACKING NOT
INCLUDED

COPYRIGHT © 2016 QUICK MOUNT PV

4
8.13
12.00
1.94
WEST ORIENTATION EAST ORIENTATION

BASE MOUNT ASSEMBLY SOLD


TILE REPLACEMENT FLASHING,POST,
AND HARDWARE

SEPARATELY (QMTR-BM)
SOLD SEPARATELY
QMTR-F3.25, QMTR-W4, QMTR-S3.25

4
SCALE 1:5

WRITTEN PERMISSION OF QUICK MOUNT PV IS PROHIBITED.


3.25 MIN SLIDE POST ALONG CHANNEL
TO DESIRED LOCATION
4.50 MAX

5
PROPRIETARY AND CONFIDENTIAL
2.956
TITLE:
1.375 6.125 QMTR-BM: TILE REPLACEMENT,
BASE MOUNT
UNLESS OTHERWISE SPECIFIED:
SIZE DRAWN BY: RAD REV
DIMENSIONS ARE IN INCHES

PROPRIETARY AND CONFIDENTIAL


TOLERANCES:
FRACTIONAL 1/8 A DATE: 9/23/2016 4
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF QUICK MOUNT PV. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE DO NOT SCALE DRAWING TWO PLACE DECIMAL .19
WRITTEN PERMISSION OF QUICK MOUNT PV IS PROHIBITED. COPYRIGHT © 2016 QUICK MOUNT PV THREE PLACE DECIMAL .094 SCALE: 1:4 WEIGHT: 2.07 SHEET 2 OF 2

5 4 3 2 1
BI 7.2.3-40 Jul-2017, Rev 7 BI 7.2.3-40 Jul-2017, Rev 7