GUIDE SPECIFICATION
Model 93E 15 - 80 kVA
PART 1 GENERAL
1.1 SUMMARY
A. The Contractor shall furnish and install a three-phase continuous duty, on-line,
double conversion, solid-state uninterruptible power system, hereafter referred to as
the UPS. The UPS shall operate in conjunction with the existing building electrical
system to provide power conditioning, back-up and distribution for critical electrical
loads. The UPS shall consist of, as required by the project, the UPS module,
battery cabinet(s), and accessory or “option” cabinet(s) for transformers, parallel tie,
and distribution applications, and other features as described in this specification.
A. Components:
1. Rectifier
2. Inverter
3. Sealed Lead Acid Batteries
4. Battery Charger
5. Automatic Bypass
6. Internal Maintenance Bypass Switch
7. Input breaker
8. User Interface Panel
9. Serial (RS-232)/USB Communication Interface
10. Communication Card Slots (2)
11. Remote Emergency Power Off Contacts
12. Environmental (Building Alarm) Inputs (3)
13. Hardwired Input, Output
14. Standard dust filter
15. Optional Internal Battery(for 15-40kVA)
16. Optional bypass breaker
17. Optional Back-feed contactor
18. Optional I/O transformer
19. Optional IP21
20. External Battery Cabinets (or racks)
433204975.DOC 1
21. Communications Options
a. SNMP/Web adapter
b. RS-232 and relay contact interface(Standard for China)
c. Modbus RTU interface
d. Industrial Relay Card
1.4 REFERENCES
A. The UPS and all components shall be designed, manufactured and tested in
accordance with the latest applicable standards as follows. Where a conflict arises
between these documents and statements made herein, the statements in this
specification shall govern.
Safety
a. IEC 62040 or EN 62040
b. EN 60950
B. Markings
CE-mark
433204975.DOC 2
1.5 SUBMITTALS – FOR REVIEW/APPROVAL
A. Submit one copy of a concise operation and maintenance manual.
1.7 QUALIFICATIONS
A. The manufacturer of the unit shall have a minimum of forty years’ experience in the
design, manufacture and testing of Uninterruptible Power Supplies.
B. For the equipment specified herein, the manufacturer shall be ISO 9001 certified for
engineering/R&D and manufacturing facilities.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Eaton Corporation
2.2 RATINGS
A. System Input
1. Input Voltage Operation Range
a. Nominal 400/230 (or 380/220 or 415/240 adjustable) VAC, 4-wire plus
ground
b. +20% to –15% from nominal at 100% load
c. +20% to –50% from nominal at 50% load
2. Input Frequency:40 to 72 Hz
3. Input Power Factor: 0.99
4. Input Current Distortion: 5% THD maximum at full rated linear load
433204975.DOC 3
5. Inrush Current: <5x nominal rating
433204975.DOC 4
9. Bypass:
a. Automatic bypass shall provide an alternate path to power in the case of
overload, inverter failure or other UPS failure
b. Internal Maintenance Bypass can be utilised with the UPS to allow servicing
of the UPS
c. Transfer time to and from any internal bypass shall be no-break, when UPS
and Utility are in sync
d. Unit shall be able to detect bypass module failure.
10. Efficiency:
a. In Normal Mode, 100% linear load, with nominal line condition: up to 94%
b. In Normal Mode, 50% linear load, with nominal line condition: 20-80kVA,
92.5%; 15kVA, 92%
c. In High Efficiency mode: ≥ 98% at 100% linear load; 97.5% at 50% linear
load
2.3 CONSTRUCTION
A. The UPS system is initially provided as a single-module, non-redundant
system. The UPS shall be field-upgradeable with additional parallel capacity up to
3+0 modules, or for redundant operation, up to 3+1 modules. The system can be
configured with numerous options, including:
1. Internal(for 15-40kVA)/External(15-80kVA) Matching Battery Cabinets (EBCs)
2. Several plug-in Connectivity Options
3. Accessory Cabinet, or Tie Cabinet with:
433204975.DOC 5
a. External Maintenance Bypass Switch
b. Breaker panel and/or Sub-feed breaker(s)
c. Two, (or four)-Module paralleling tie, with or without a Maintenance Bypass
Switch
B. Converter (rectifier): Incoming power shall be filtered and converted to DC by a sine-
wave rectifier. The rectifier utilises IGBT technology to correct the input power factor
to 0.99 and draws sinusoidal current (with less than 5% THD) from the utility. In the
event of utility failure, the DC-DC converter shall supply power without interruption
from the external batteries.
C. Inverter: The inverter utilises IGBT technology and Digital Signal Processing to
convert the DC power from the rectifier or converter to regulated AC power for
output to critical loads.
1. Output Voltage: The inverter output voltage is specified in section 2.02.B.
2. Voltage Regulation: The inverter steady state voltage regulation is +/- 1% phase
to neutral, 2% phase to phase. Dynamic regulation meets Class 1 performance
of IEC62040-3.
3. Frequency Control: The inverter steady state frequency regulation is +/-0.1 Hz,
free running in steady state. UPS is synchronized to the Utility bypass in normal
operation.
D. Mechanical Design
1. All materials and components of the UPS shall be new, of current manufacture,
and shall not have been in prior service except as required during factory
testing. The UPS shall be constructed of replaceable subassemblies. All active
electronic devices shall be solid-state.
2. The UPS unit is comprised of an input rectifier, battery charger, inverter, bypass,
maintenance bypass and internal battery or external battery consisting of the
appropriate number of sealed battery modules, and shall be housed in a single
freestanding enclosure. The UPS cabinet shall be cleaned, primed, and painted
with the manufacturer's standard colour. Wheels and leveling feet shall be
provided as standard.
3. The UPS shall be designed for forced-air cooling. Air inlets shall be on the front
of the unit and shall be fitted with washable dust filters. Air outlets shall be at the
rear. A minimum of 150mm rear clearance for ventilation shall be provided for 15-
40kVA systems and a minimum of 200mm for 60-80kVA systems.
4. Cable access shall be through the bottom or rear of the UPS cabinet.
5. Dimensions of standard UPS cabinets:
433204975.DOC 6
2.4 UPS IN PARALLEL CONFIGURATIONS
A. UPS modules shall be capable of being paralleled to increase system power levels
or to provide redundant power. The UPS shall be field-upgradeable with additional
parallel capacity up to 3+0 modules, or for redundant operation, up to 3+1 modules.
The parallel system shall have intelligence to automatically recognise the need for
capacity and/or redundancy. Parallel systems shall utilise autonomous UPS power
modules that do not rely on any control interconnections for synchronized operation.
The individual modules shall operate in a peer-to-peer manner to provide automatic
load sharing, synchronization, and selective tripping capabilities. “Master-slave”
configurations are not acceptable.
B. The parallel system shall utilise a communications network to provide system
information and status, such as operating mode and meter data. This network shall
provide individual module information as well as total system information, and
individual module information shall be available from any module’s front panel
display. The loss of this system information network shall not cause the parallel
units to transfer to bypass or drop the critical load.
433204975.DOC 7
1. Graphical LCD display: Includes basic language (English and local selectable
language), display of unit function and operating parameters. It shall be used to
signify the operating state of the UPS, for indicating alarms, for changing
operations control parameters and set points.
2. Four status LED’s, which indicate:
1 a. Alarms, with a red LED
1 b. On Battery, with a yellow LED
2 c. On Bypass, with a yellow LED
3 d. Power On, with a green LED
3. Six-Key Multifunction Keypad: UPS shall have keypad to allow user to adjust
UPS parameters, view alarm and inverter logs, change UPS operational modes,
and turn the UPS on and off. Keys will be marked as UP, DOWN, LEFT, RIGHT,
ESC and ENTER
4. Meters: When selected, the front display shall show individual screens of input
parameters, output parameters or bypass parameters including; voltage, current,
frequency, true power, apparent power and power factor. The display shall also
show DC Voltage and current.
4
B. Power Management Software Package: The UPS shall offer optional
communications interface that provides the following communication capabilities:
1. Monitor and graphically display input and output voltage and other operating
characteristics
2. Notify end-users in the event of a power anomaly via network or E-mail.
3. Communication Ports:
a. Communication Card Slots: The UPS shall provide (2) communication mini-
slots in the front of the UPS allowing for additional connectivity options,
including SNMP/Web interface, 4x relay contacts, and RS-232 capabilities.
b. Serial communications (via RS-232 or USB) with manufacturer’s service
software package
2.7 BATTERIES
A. Battery Type: Valve Regulated Lead Acid (VRLA), minimum two-year warranted float
service life at 25 degrees C.
B. Same brand with UPS preferred;
C. Holdover Time (Runtime): Each UPS system shall have the option of capability for
matching battery cabinets to increase the holdover time. Please refer to datasheet
for a list of runtimes. The battery times listed there are approximate and may vary
depending on load configuration, temperature, battery age, and state of battery
charge.
D. Battery Cells:192~240 Cells per string. (LCD battery configure interface will support
numbers count by cells)
1
433204975.DOC 8
E. Battery Recharge Time:
1. UPS system will have a typical recharge time of 10 times the length of the
outage 90% usable capacity @ nominal line.
1
F. Bus Voltage: Nominal bus voltage is 432 VDC, adjustable to 384VDC.
2
G. Battery Protection:
1. Short Circuit Protection: Over-current protection shall protect the batteries from
all short circuit fault conditions
2. Battery Module Protection: Internal battery fuse/relay shall be provided
3. Under-voltage Protection:
a. Inverter cut-off voltage: Battery operation shall be terminated when the
battery voltage drops to the 1.67 VPC set point
4. Over-voltage Protection: If the UPS system’s battery bus voltage exceeds the
predetermined set point then the UPS will disable the charger and alarm a
“check battery” condition
1
H. Advanced Battery Management:
1. Battery recharge: After recharging batteries to full capacity, the charger will enter
the rest mode to increase the battery lifetime according the ABM cycle. Hence,
continuous float charging of the battery shall not be required if the ABM feature
is selected. The active battery charger states are constant-current (charge
mode), constant-voltage (float mode) and no-charge (rest mode). The ABM
feature is user (or service) selectable. If ABM is not utilised, the UPS operates as
a conventional float charger.
2. Battery Runtime Monitoring: UPS shall monitor batteries and provide status to
end user of battery remaining capacity via front panel icon, remote
communications, or both. Runtime calculations to be based on load demand and
analysis of battery health.
3. Battery Health Monitoring: UPS shall periodically test and monitor battery health
and provide warnings visually, audibly and/or remotely when battery capacity
falls below 80% of original capacity. Battery testing may also be user initiated via
front panel or serial communications.
2.8 NAMEPLATES
A. Provide a printed nameplate for each UPS.
433204975.DOC 9
2. 30-40 kVA: Less than 62 dBA (A weighted) at one (1) metre from all sides in
normal mode at less than or equal to 75% load.
3. 60-80 kVA: Less than 65 dBA (A weighted) at one (1) metre from all sides in
normal mode at less than or equal to 75% load.
C. Ambient Temperature
1. Operating: UPS: 0 °C to +40 °C, (preferred temperature for batteries: +15 °C to
+25 °C.
2. Storage: UPS -25 °C to +55 °C.
3. Transportation: -25 °C to +60 °C
D. Relative Humidity
1. Operating: 5 to 95% non-condensing.
2. Storage: 5 to 95% non-condensing.
3. Transportation: 5 to 95% non-condensing
E. Altitude
1. Operating: To 1000 metres, de-rating or reducing operating temperature range
may be required for higher altitudes
2. Transit: To 10,000 metres
F. Electrostatic Discharge: The UPS shall be able to withstand a minimum 6 kV without
damage and without affecting the critical load
PART 3 EXECUTION
3.2 INSTALLATION
A. The Contractors shall install all equipment per the manufacturer’s recommendations.
3.3 WARRANTY
All components of the UPS system (UPS module, batteries, and optinal cabinet) shall
be covered by a standard 1-year warranty.
Manufacturer shall also offer, as an option, 7x24 on-site service support with
guaranteed response times. Additional preventive maintenance visits shall be available
as an option for both UPS and battery components.
433204975.DOC 10
Manufacturer shall also include Start-up services consisting of: 5x8 Start-up service of
UPS and batteries, On-site user training, Site Audit, installation and commissioning of
monitoring service.