DHC-100
Digital High-Resolution Controller
The Peaktronics DHC-100 is a high performance
digital positioner intended to control AC actuators, provid-
ing 450 points of resolution with quarter turn actuators
ranging from 2 sec to 120 sec and rated for 25% duty or
more. The DHC-100 has many automatic advanced fea-
tures that will enhance any actuator while making it easy to
install and set up.
The simple three button control is used to configure
all parameters the unit needs for a wide variety of applica-
tions, and allows the open and closed positions to be easily
set for direct or reversing acting without any rewiring. The
unit can be configured for various command types (4-
20mA, 1-5V, 0-5V, 0-10V, or a digital command) and its
default operation upon loss of command.
Various option modules are easily plugged into the
unit, providing other features such as a position feedback
signal (current or voltage), auxiliary switches, fault relay
contact, or digital communications. A wide range of data is
accessible through a digital communications module, pro-
viding additional control or information.
The unit is of single solid construction and is easily
mounted with two screws. The DHC-100 is interchange- 117VAC DHC-100 DHC-100C (CE ready)
able with the AMC and LRC standard size controllers, and 234VAC DHC-100A DHC-100D
can be used to upgrade performance for those applications. 24VAC DHC-100B DHC-100E (CE ready)
FEATURES
• Positions to ±0.1° with quarter-turn actuators ranging from 2 sec to 120 sec (with or
without a brake).
• Adaptive Control feature continuously adjusts for load and actuator conditions and
eliminates calibration procedures and auto-cal operations.
• Three button control provides easy setup and eliminates the need for instrumentation.
• Polarity Detection feature allows direct or reverse acting operation without re-wiring.
• Electronic Brake feature can eliminate need for a mechanical brake in many applica-
tions, and extends mechanical brake life when used.
• Automatic Duty Cycle Control feature prevents shutdown of a process due to a ther-
mal overload of the actuator motor, and allows actuators rated for 25% duty or more to
be safely used.
OUTLINE
ELECTRICAL
PEAKTRONICS CONNECTIONS
Digital High Resolution
DIGITAL AUTO
4-20mA MANUAL / FB POT CAL to Motor
J1
1-5VDC CLOSE LAST MOTOR 1 OUTPUT 1
0-5VDC OPEN (BOTH OFF) NEUTRAL 2
0-10VDC AUX CLOSE OUTPUT MODE MOTOR 2 OUTPUT 3
AUX OPEN OUTPUT GND 4
COMMAND TYPE WIPER 5
LOSS OF COMMAND +2.5V 6
to Feedback Pot
FAULT AUX POSITION OUT
(FLASHING) CAL (STEADY ON)
to AC Power
J2
L2 NEUTRAL 1
FRONT PANEL L1 LINE 2
EARTH GND 3
J7 SIGNAL GND ( ) 4
4-20mA (+) 5
1-5V, 0-5V, 0-10V (+) 6
*1.32" +5V OUT 7
+15V OUT 8
to Signal
* Add 0.04" when option module installed.
J1 J2 J3
1 2 3 4 5 6 1 2 3 4 5 6 7 8 OPTION MODULE
CONNECTOR
1.36" FUSE
#6 clear hole
(2) places
to Auto/Manual Station
J7
J3
GND 1
1.36" OVERRIDE INPUT 2
BLOCK DIAGRAM
ACTUATOR
7
+5V OUTPUT
POWER / SIGNAL
MOTOR 2 LIMIT SWITCH
6
(+) 1-5, 0-5, 0-10 V INPUT 3 OUTPUT
5 optional
(+) 4-20mA INPUT
4 4 GND brake
SIGNAL GND coil
3 5 WIPER FEEDBACK
EARTH GND
POT
2
L1 LINE
1
L2 NEUTRAL 6 +2.5V
J7 OVERRIDE
2 INPUT
OVERRIDE
AUTO/MANUAL
STATION
1 GND
DESCRIPTION
The DHC-100 is rated for motors with up to 5A unit itself without the need for any instrumentation. The
running currents and comes in three versions to accom- adaptive control feature of the DHC-100 eliminates the
modate different voltage applications. The DHC-100 and need for any calibration steps. In the simplest application,
DHC-100C are rated for 117 VAC ±10%; the DHC-100A only the closed and open positions need to be set and the
and DHC-100D are rated for 234 VAC ±10%, and the unit automatically and continuously sets all other parame-
DHC-100B and DHC-100E are rated for 24 VAC ±10%. ters when placed in the AUTO mode.
The unit is easily mounted with 2 screws and is equipped CAUTION ! These units are intended to be
with removable screw terminals that provide for easy field mounted in an appropriate enclosure to avoid electrical
wiring. The unit's size, mounting, and screw terminals are shocks and exposure to electrostatic charges. High volt-
compatible with the AMC-100, AMC-101 and LRC-101 ages are present on the outside of the unit when power is
series controllers - the DHC-100 can be used as a direct applied. AC power should be disconnected and antistatic
replacement for those units in nearly any application. measures should be taken prior to any wiring of these
The simple three button control (MODE, ▲, and units. A heater and thermostat should be used where con-
▼) allows the user to perform a complete set-up from the densation may occur.
ACTUATOR (J1)
ADJUST UP (▲) and ADJUST DOWN (▼)
The actuator motor and feedback potentiometer
are connected to J1 as shown in the Block Diagram. The The adjust up (▲) and adjust down (▼) buttons
Motor Neutral wire must be connected to pin 2, while one are used to adjust the setting of any given function. When
motor winding is connected to pin 1 and the other winding a function is selected by the MODE button, the adjust but-
to pin 3. The feedback potentiometer wiper must be con- tons will affect that function only. Note, that the AUTO
nected to pin 5, while one end is connected to pin 4 and mode does not have any adjustable settings, and therefore,
the other end to pin 6. The Polarity Detection feature of the adjust up (▲) and adjust down (▼) buttons have no
the DHC-100 automatically determines which motor effect. Also, the adjust buttons are disabled in the
winding to control based on where the open and closed OVERRIDE mode.
positions are set; this feature also eliminates the need to
rewire the unit for direct or reverse acting applications.
When the ▲ and ▼ buttons are used to control OVERRIDE MODE
the actuator, the ▲ button will turn on the motor winding
connected to pin 1, while the ▼ button will turn on the The OVERRIDE mode is not selected by the
motor winding connected to pin 3. See MANUAL/FB MODE button and can be enabled at anytime by connect-
POT CAL for more details. ing a resistance greater than 250 ohms to the Override In-
put (J7 pin 1 and pin 2). While the OVERRIDE mode is
enabled, the MODE button and adjust buttons are dis-
OVERRIDE (J7) abled, and the Manual/Pot Cal indicator will turn on
steady to indicate that the unit is being controlled by the
J7 provides a simple 2-wire connection that can Override Input. Shorting J7 pin 1 to pin 2 returns the unit
override the DHC-100 to perform a variety of external to normal operation and the previously selected mode.
control functions. Using an appropriate interface module, Note that earlier models may not have connector J7, and
commonly used auto/manual station switches are easily therefore do not have the OVERRIDE mode feature.
implemented with low voltage/low current switches. See Controlling the DHC-100 from the Override Input
Special Applications for more details. The factory in- is accomplished by connecting a specific resistance to se-
stalled jumper between pins 1 and 2 enables normal opera- lect a specific operation. The table below defines the op-
LOSS OF COMMAND
AUX CLOSE OUTPUT
When using 1-5V, 4-20mA, or a Digital input type
The AUX CLOSE OUTPUT function is used to for the command signal, the DHC-100 will detect when
set an optional output setting that is associated with the the command signal is lost or out of range. A loss of com-
closed position - an appropriate relay option module is mand condition is detected whenever the input is discon-
required to use this output. The adjust buttons are used to nected, the input becomes less than 0.75V or 3mA, or the
set the actuator to a desired position. Whenever the actua- input becomes greater than 5.25V or 21mA. If the DHC-
tor position falls between the defined closed position and 100 detects a loss of the command signal, the Fault indica-
the Aux Close position, the Aux Close Output indicator tor will flash and the actuator will be moved to one of
will flash. Additionally, the DHC-100 will turn on a relay three preset positions: the open position, the closed posi-
output on the optional relay module - the output can be tion, or the position last attained prior to losing the com-
used to drive an alarm or merely act as an auxiliary limit mand signal. The LOSS OF COMMAND function is used
switch. to set the desired default position.
Upon selecting the AUX CLOSE OUTPUT func- When the LOSS OF COMMAND function is se-
tion, the DHC-100 will begin moving the actuator to the lected, the adjust buttons are used to set the default posi-
previously set position. It is not necessary to make an ad- tion. The DHC-100 indicates the selected default setting
justment if the unit has been previously set to the desired by flashing the Open function indicator for the open de-
position. fault position, or it will flash the Close function indicator
for the closed default position. When neither indicator is
on, then the "last position" default is selected.
AUX OPEN OUTPUT When a 0-5V or 0-10V command signal is used, a
loss of command signal cannot be detected. Therefore, if
The AUX OPEN OUTPUT function is used to set the unit is configured for a 0-5V or 0-10V command sig-
an optional output setting that is associated with the open nal (see COMMAND INPUT), the MODE button will not
position - an appropriate relay option module is required select the LOSS OF COMMAND function.
to use this output. The adjust buttons are used to set the
actuator to a desired position. Whenever the actuator po-
sition falls between the defined open position and the Aux AUX POSITION OUT CAL
Open position, the Aux Open Output indicator will flash.
Additionally, the DHC-100 will turn on a relay output on Note that the AUX POSITION OUT CAL indica-
the optional relay module - the output can be used to drive tor also serves as a Fault indicator. When the indicator is
an alarm or merely act as an auxiliary limit switch. on steady, the AUX POSITION OUT CAL function is
Upon selecting the AUX OPEN OUTPUT func- selected. When the indicator flashes, a Fault condition has
tion, the DHC-100 will begin moving the actuator to the been detected (see FAULT INDICATOR for details). The
FAULT INDICATOR
STALL DETECTION FEATURE
The DHC-100 detects various fault conditions that
prohibit the unit from controlling the actuator. When any The Stall Detection feature of the DHC-100 (see
of these conditions are detected, the Fault indicator will FAULT INDICATOR) essentially performs a similar
flash, and the motor outputs are turned off until all fault function as commonly used torque switches; however, the
conditions have been corrected. If an appropriate relay differences should be considered before eliminating the
option module is installed, the Fault relay output on the torque switches. The DHC-100 feature does not measure
option module will also turn off. A communications op- torque, but rather motion; if the load is sensitive to exces-
tion module can read the specific condition(s) causing the sive torque, the torque switches may be desirable. Since
fault. Note that a fault condition DOES NOT disable the common torque switches are mechanical devices, they can
motor outputs when manually controlling the actuator provide a fail safe feature in the event of electrical failures
with the the adjust buttons; while useful for troubleshoot- (such as shorted wires or damage to the DHC-100).
ing, care should be excercised when operating the motor The Stall Detection feature is useful for detecting
under a fault condition. The OVERRIDE mode can also when any of the motor wires become disconnected. How-
operate the motor when a fault condition exists - see ever, limit switches employed in actuators essentially dis-
OVERRIDE MODE for details. The various fault condi- connect one of the motor windings. The DHC-100 will
tions are described below: detect this as a motor stall. To avoid this condition, the
limit switches must be set outside of the operating range
LOSS OF COMMAND - If the command signal is dis- set by the CLOSE and OPEN functions.
connected or out of range, the fault indicator will remain
on until the signal is reconnected or back in range.
OPTION MODULES
Various option modules can be plugged into the Contact the factory for the latest available modules. Refer
DHC-100 option module connector, J3. Option modules to the diagram below for instructions on installing an op-
provide additional features such as position feedback sig- tion module.
nals, auxiliary switch outputs, or digital communications.
Plug option module into J3, Loosen front panel screws and lift front panel up to
lock module in front panel allow option module to plug in underneath.
slots, and retighten front
panel screws.
Option
Module
J3 DHC Series
Installing an Option Module
SPECIFICATIONS
POWER REQUIREMENTS
DHC-100, DHC-100C: 117VAC ±10%, 50/60 Hz
DHC-100A, DHC-100D: 234VAC ±10%, 50/60 Hz
DHC-100B, DHC-100E: 24VAC ±10%, 50/60 Hz
12 VA typical (not including output load)
Fuse Type: 6.3A TR5 Time Delay (replaceable)
AC MOTOR OUTPUTS
Off-state Leakage Current: <15mA
Maximum Load Current @ 60°C: 5A
ENVIRONMENTAL
Operating Temperature Range: 0 °C to 60 °C
Storage Temperature Range: -40 °C to 85 °C
Relative Humidity Range: 0 to 90 % (noncondensing)
* The unit exhibits a particular sensitivity at 137MHz. Installations suspected of having a strong ex-
posure near the specified limit in the range of 132Mhz to 142Mhz can increase immunity by install-
ing a clamp-on ferrite (250 ohms or more at 100MHz) around the I/O cable(s). A Steward 28A2029-
0A2 ferrite or equivalent is recommended.
WIRING DIAGRAMS
Input Signal Configurations
J2-6
1-5V, 0-5V, 0-10V 1-5V
0-5V
DHC-100 J2-5
DHC-100 or
0-10V
4-20mA Sourcing J2-4 DAC
4-20mA or SIGNAL GND
Sinking
J2-4 output
SIGNAL GND
4-20mA Input using a self powered transmitter 1-5/0-5/0-10V Input using digital-to-analog card
MLT-100A
(includes dial and knob)
XMA-104A
XMA-108
J2-8 RED
J2-8
+15V
+15V OUT OUT
CW
OPEN
4-20mA WHT
4-20mA Transmitter
DHC-100 Transmitter DHC-100 Command
135 ohm Pot
Slide
Wire J2-5 BLK
J2-5
4-20mA
4-20mA
WIRING DIAGRAMS
Special Applications
DHC-100
7 Voltage Output
OTR-100
6 mA Output
OTX-100 mA Feedback Monitor
(Option Module) 5 GND
4 AUX Close Output
3 AUX Open Output
2 Fault Output OTR-100 only NOTE: The Fault Output contact will
open when power is lost or when a
1 Common fault condition exists.
Mechanical
Manual Override
Switch
Manual
Override
J7-2
Normal
DHC Operation
Series
J7-1
WIRING DIAGRAMS
Special Applications (continued)
MECHANICAL USING
MANUAL OVERRIDE
AMM-100
DHC SWITCH MOMENTARY
1 S C O L
Series (optional)
STOP SWITCHES
(optional)
J7-1
AUTO
(optional)
J7-2
OPEN
CLOSE
OFF (optional) Connect for latching function.
STOP
MANUAL Note, one STOP switch will
be required.
MECHANICAL USING
MANUAL OVERRIDE
AMM-100
DHC SWITCH TOGGLE
1 S C O L
Series (optional) SWITCHES
J7-1
OFF
AUTO CLOSE OPEN
J7-2 OFF (optional)
MANUAL
www.peaktronics.com