Sie sind auf Seite 1von 2

AC inverter cable according datasheet or VDE table

AA
Current carrying capacity Current carrying capacity Current carrying capacity
70°C in ground at 20° Ambient in air at 30° Air amb. 90°C in ground at 20° Ambient
0.6/1kV Aluminium coper Aluminium coper 0.6/1kV Aluminium coper
Table 13-44 Table 13-45 Table 13-44
multi core
cross multi core cable as AC cable as AC cross multi core cable as AC
section mm² system system section mm² system
4 - - - - 4 - -
6 - - - - 6 - -
10 - 79 - 59 10 - 88
16 - 102 - 79 16 - 112
25 102 133 82 106 25 112 145
35 123 159 100 129 35 135 174
50 144 188 119 157 50 158 206
70 179 232 152 199 70 196 254
95 215 280 166 246 95 234 305
120 245 318 216 285 120 268 348
150 275 350 246 326 150 300 392
185 313 406 285 374 185 342 444
240 364 473 338 445 240 398 517
300 419 535 400 511 300 457 585
400 484 613 472 597 400 529 671
Current carrying capacity
in air at 30° Air amb.
Aluminium coper
Table 13-45
multi core
cable as AC
system
- -
- -
- 74
- 98
102 133
126 162
149 197
191 250
234 308
273 359
311 412
360 475
427 564
507 649
600 761

Das könnte Ihnen auch gefallen