Menu Loop (Button : Menu)

No Displayed Default R134a/R407C Data /Setting


1. dd/mm/yy day hh:mm
Unit Status
Cooling Staging XXX% XXX %
Stp Source : Local Local
2. Water Temperatures
o
Entering Evap = C
Leaving Evap = oC
3. Evap Press bar gauge ---- U1 ---- U2
o
Evap Temp C ------ ------
Cond Press bar gauge
o
Cond Temp C
o
4. Suction Temp C U1 U2
o
Suction Sup Heat C
o
Delivery Sup Heat C
Valve Position
5. Staging Up U1 U2
Staging Down
Staging Fixed
Compressor Off

Maintenance Loop (Button : Tool) ; Maintenance Password Orange + Print + Blue


No Displayed Default R134a/R407C Data /Setting
Hour Counter
Pump Evap 001
1. Comp C1 C2
Hour Counter 01 00
Number of Start 05 07
2. Last Comp Start C1 C2
20/10/06 20:08 20/10/06 20:06
Last Comp Stop
20/10/06 20:09 20/10/06 20:09
3. EXV Driver State C1 C2
Battery Resist 0.5 0.4
Battery Voltage 19.1 18.9
4. Colling PID Errors
o
Prop 20.9 C
Int 3276.0 oC x sec
Der 0.0 oC/ min
5. Colling PID Act 1000
Proportional 1000
Integral 0000
Derivative 180
Maintenance Loop (Button : Tool) ; Maintenance Password Orange + Print + Blue
6. Colling Reg
Disable Stop N
Increase Stop N
7. Global PID Request
Load Y
Unload N
Standby N
Digital Maintenance
8. Evap pump H. count
Treshold 10 x 100
Reset N
Adjust 01
9. Comp Hour. count C:1 C:2
Treshold 10 x 100 10 x 100
Reset N N
Adjust 01 02
10. Comp Start C:1 C:2
Reset N N
Adjust 05 07
11. Regul Band 3.0 C
Neutral Band 0.2 oC
o
Max Pull Down Rate 1.2 C/min
12. Start Up DT 2.6 oC
Shut Down DT 1.7 oC
13. High ChLwt Start
LWT 25.0 oC
Max Compressor Stage 70%
14. ChLW Temp
Set point Limit
o
Low 4.0 C
o
High 10.0 C
15. Probes Enable
B1 - B10 : Y
16. Exp Probes Enable
B1 : N
Exp Probes Offs
B1 Offs : oC
17. Inputs Probes Offset
B1 - B10 : 0.0
18. Time To Download
Compressor
30s
Digital Maintenance
19. DT To Reload and Re Unload
Compressor
0.7 oC

IN/OUT Loop (Button : I/O)


No Displayed Default R134a/R407C Data /Setting
1. McQuay SPA
Cechina(RM) Italy
Code : Mc Air
V : 21.302 07/07/06
2. I/O exp E
D01 : Economizer #1N
D02 : Economizer #2N
3. Digital Inputs
OOOOCCCOCCCOOCCOCC
Digital Outputs
OOOOOOOOOOOOOOOOO.
4. Analog Input
B1 : Oil Pr.1 3.5 bar
B2 : Oil Pr.2 3.5 bar
5 Analog Input
B3 : 0.1 mA
B4 : Del Temp. 1 033.2oC
B5 : Del Temp. 2 034.4oC
6 B6 : Cond Press 1. 3.5 bar
B7 : Cond Press 2. 2.6 bar
B8 : 0.1 mA
7 Analog Input
B9 : In Water 28.1 oC
B10 : Out Water 27.9 oC
8 Analog Output
Y1: 0.0 V Y4: 0.0 V
Y2: 0.0 V Y5: 0.0 V
9 Bios Version 3.64
Bios Date 18/05/05
Boot Version 03.01
Boot Date 15/04/02
10 Driver Firmware : C1
Version
H.W. 033
S.W. 160
11 Driver Firmware : C2
Version
H.W. 033
S.W. 160
User Loop (Button : Program) ; User Password : 003
No Displayed Default R134a/R407C Data /Setting
1. LWT Setpoint Reset
None
2. Enable Double Setpoint
None
3. Enable Soft Load N
4. Unit Limiting
None
5. Compressor Sequencing
Auto
6. Time Between Main
Pump/fan and compressor
Start 30 s
7. Delay On Switching
the main pump off
180 s
8. Supervisory remote
On/OFF
N
9. Auto Restart After Power
Failure
Y
10. Switch Off Unit
On External Alarm
N
Reset Type Auto
11. Enable Time
Scheduling N
12. Communication
Supervisor
13. Protocol : Carel
Supervisor Com.speed
19200 (RS485 Only)
Identifical No : 001
14. Choose Language
English

Manufacturer Loop (Button : Menu +Program) ; Digit Manufacturer Password : Blue + Print + Down
EXV Setting Password : 013
No Displayed Default R134a/R407C Data /Setting
1. EXV Gas Type
2. En Economizer N
Economizer On 90%
Economizer Off 75%
3. Economizer Motor Protection
o
Setp 60 C
o
Diff 5 C
4. Temperatur Regulation
Integral Time 200s
Derivative Time 60s
Manufacturer Loop (Button : Menu +Program) ; Digit Manufacturer Password : Blue + Print + Down
EXV Setting Password : 013
5. Compressor Configuration
N Of Comp 2
6. Min time between same
Comp Start 600s
Min time between diff
Comp Start 120s
7. Min time Compressor
On 120s
Min time Compressor
Off 180s
8. Interstage time 210s
Double pulse under
35%
9. Cond P. Hold 17.5 bar
Cond P. Down 18.5 bar
Evap P. Hold 1.9 bar
Evap P. Down 1.8 bar
10. Discharge temp. alarm
setpoint 110oC
11. Evaporator Flow alarm
Delay
Startup delay 20 s
Run delay 5s
12. Anti freeze alarm
set point 2.0oC
Diff 1.0oC
Number of pulse to load
13.
compressor 15
Number of pulse
to unload comp 15
14. Unloading
pulse time 0.3s
Min pulse period 01 ssecond
Max pulse period 90 ssecond
15. Loading
pulse time 0.3s
Min pulse period 05 ssecond
Max pulse period 90 second
16. Pump Down Config
Enable Y
Max Time 30s
Min Press 1.2 barg
17. Condensation
Enable press
Type step
Fan steps 4
18. Condensation
Fan step N. 1
Setpt 8.5 bar diff 1.5 bar
Manufacturer Loop (Button : Menu +Program) ; Digit Manufacturer Password : Blue + Print + Down
EXV Setting Password : 013
19. Fan no. 2
Setpoint 10 bar
Diff 2.5 bar
20. Fan no. 3
Setpoint 12 bar
Diff 2.0 bar
21. Fan no. 4
Setpoint 14. bar
Diff 2.0 bar
22. Enable oil heating
control Y
23. Transducer High
press alarm
setpoint : 20.5 bar
diff : 5.0 ar
24. Transducer Low
press alarm
setpoint : 1.6 bar
diff : 0.1 bar
25. Low press alarm delay
Startup delay 120 s
Run delay 60 s
26. Pressure ratio alarm
Min load setpoint 1.4
Max load setpoint 1.8
27. Pressure ratio alarm
Startup delay 180 s
Run delay 90 s
28. Oil High Press diff alarm
setpoint 2.5 bar
delay 20 second
29. Liquid Injection
o
set point 85 C
Diff 10.0oC
30. EXV Setting
EXV Preopening 50%
31. RS 485 net
time check 000
Refresh N
EXV Setting Password : 013
1. EXV Setting 1
No Warning
2. EXV Setting 2
No Warning
3. EXV Setting EXV Setting 1 EXV Setting 2
Actual Position 0000 0000
Manual Position 0500 0500
En. EXV Manual Auto Auto
EXV Setting Password : 013
4. EXV Setting
Valve Type
Alco EX8
Gas Type R134A
5. Opening Extras Y
Closing Extras Y
Time Extras 0 sec
o
6. Sheat Setp 6C
o
Dead Zone 0C
7. Prop Factor 80
Int Factor 30 second
Diff Factor 0.5 second
8. Lw Sheat Protection
Low Limit 1oC
Int Time 1 second
9. LOP Protection
o
Low Limit -30. C
Int Time 40 second
9. MOP Protection
Low Limit 12oC
Int Time 4 second
10. MOP Protection
Start Up delay 90 sec
11. Hit Cond Protection
Hit Cond Limit 90oC
Int Time 4 second
12. Suction Temp High Limit
O
60 C
13. Press Probe
Min Value -0.5 barg
Max Value 7 barg
14. EXV Settings EXV Settings 1 EXV Settings 2
Battery Present Y Y
Plant Present N N