Removable AC Metal-enclosed Switchgear

12kV ET1
Automotive
Powering
business
worldwide
Aerospace

Eaton delivers the power inside hundreds of products that


are answering the demands of today’s fast changing world.
We help our customers worldwide manage the power
they need for buildings, aircraft, trucks, cars, machinery
and entire businesses. And we do it in a way that
consumes fewer resources.

Next generation Powering Greener Buildings


Truck transportation and Businesses
Eaton is driving the Eaton’s Electrical Group is a
development of new leading provider of power
technologies – from hybrid quality, distribution and control
drivetrains and emission control solutions that increase energy
systems to advanced engine efficiency and improve power
components – that reduce fuel quality, safety and reliability.
consumption and emissions in Our solutions offer a growing
trucks and cars. portfolio of “green” products
and services, such as energy
Higher expectations audits and real-time energy
consumption monitoring.
We continue to expand our
Eaton’s Uninterruptible Power
aerospace solutions and
Hydraulics services to meet the needs of
Supplies (UPS), variable-speed
drives and lighting controls help
new aviation platforms,
conserve energy and increase
including the high-flying light jet
efficiency.
and very light jet markets.

Building on our strengths


Our hydraulics business
combines localised service and
support with an innovative
portfolio of fluid power
solutions to answer the needs
of global infrastructure projects,
including locks, canals and
Electrical dams.

1
MV switchgear technology
is in our DNA

Eaton Corporation is a worldwide leader in the


design, manufacture, and sale of safe, reliable
and high-performance medium voltage power
distribution equipment in accordance with IEC,
ANSI and GB / DL standards

Complete Global Medium Voltage Switchgear Solutions


Eaton, a premier leader in designing and manufacturing power
distribution and protection equipment in the electrical industry,
offers a comprehensive range of medium voltage (MV) solutions
to meet the needs of virtually every application. From products
that feature cutting-edge design that allow for easy access,
maintenance and space savings, to arc-resistant products that
enhance safety, Eaton’s medium voltage solutions provide a
variety of products for every need. Additionally, Eaton’s global
service network provides maximum customer support in all
regions of the world.
As one of the few completely vertically integrated and diversified
industrial manufacturers in the world, Eaton designs not only MV
assemblies, but also the key components that comprise the MV
solutions – from steel housing and circuit breaker compartments
to vacuum interrupters, circuit breakers, bus systems and fuses.
Eaton’s MV heritage, strengthened by acquisitions such as
Westinghouse DCBU, Cutler Hammer, MEM and Holec, has
resulted in breakthrough MV technologies and numerous
Eaton’s range of international patents over the years.
SF6 free switchgear Part of Eaton’s complete electrical PowerChain Solutions
– which help businesses minimize risks while realizing greater
for Medium Voltage reliability, cost efficiencies, capital utilization and safety –
Eaton’s medium voltage equipment meets all applicable
standards and certifications such as IEC, NEMA / ANSI, GB / DL,
UL, IEEE, KEMA and CSA.
When it comes to medium voltage solutions, you can trust the
one name with a long history of proven performance: Eaton.

2
12kV ET1 Removable AC Metal-enclosed Switchgear

12kV ET1 Removable AC Metal-enclosed Switchgear

The following features allow • All the operations on the


users to have maintenance-free device can and also should
or least-maintenance be conducted on the
equipments: condition of completely
closed door, including
• The vacuum interrupter opening/closing of circuit
applies ceramic shell with
breaker, racking in/out of
vacuity ≤10-6Pa, guaranteeing
circuit breaker’s trolley,
25-year operation life
opening/closing of earthing
• The spring operating switch
mechanism requires only
• Easily view circuit breaker’s
minimum maintenance
position, its opening/closing
• After the switchgear’s back and energy charged status,
door is opened, cable via front door observation
terminal and current window
transformer can be repaired
• Enlarged pressure relief
12kV ET1 Removable Metal-enclosed Switchgear
• Standard components are channel for the circuit
used, with stocks available, breaker improves heat
to meet user’s requirements dissipation efficiency with
General modular design, the front increased safety
cubicle of the switchgear is • Front maintenance or rear
ET1 removable metal-enclosed composed of low-voltage ET1 safe and reliable maintenance mode can be
switchgear (hereafter called as compartment, circuit breaker switchgear selected easily, due to
the switchgear) is the latest compartment and maintenance customer’s requirements
generation of indoor complete compartment, while its rear • Completely metal-clad and
power distribution equipment totally enclosed • In accordance with IEC
cubicle includes busbar
developed by Eaton, with three 60928 and GB3903&DL404,
compartment and cable • Each compartment in the
phase AC 50Hz, 7.2-12kV single the switchgear passes each
compartment. They can be switchgear is separated and
busbar section system. It is type test by National Center
assembled separately, easy for independent from each other
mainly used in power plant, for Quality Supervision &
batch production and
substation, industrial and • Quick-closing earthing switch Testing of High voltage
maintenance. This complete
is used for earthing and Apparatus
mining factories, as well as equipment can meet
manual short circuit
high-rise buildings, for power requirements of China Grid • Higher level of technical
reception and power towards medium-voltage • Reliable Five-Prevention performance with long
distribution, with functions of switchgears, and also meet interlock can effectively creepage distance and
controlling, protecting and special requirements of prevent from mal-operation compound insulation
detecting electric circuits. “Five-Prevention”, completely and entrance into energized
closed door operation and the compartments
The switchgear can be fitted
with Eaton’s W-VACi, E-VAC working condition of totally
and VCP-W withdrawable enclosed, complete isolation,
vacuum circuit breakers. With complete insulation.

W-VACi circuit breaker E-VAC circuit breaker VCP-W circuit breaker


Figure 1. circuit breaker

3
12kV ET1 Removable AC Metal-enclosed Switchgear

ET1 highly practicable • Wiring for secondary circuit ET1 widely applicable Standards applied
switchgear is in sufficient sized ducts, switchgear
stylish looking and easy to • IEC62271-200
• Tightly enclosure can prevent check • Equipped with standard • IEC63371-100
dirt and small animals from • Sufficient space is provided, transformers
entrance • GB3906
easy for cable connection • Various cable termination can
• Operation on completely be used • GB/T11022
• Earthing switch can be
closed door condition • DL402
operated either automatically • Multiple cables can be
maximizes personal safety or manually. Both ways are connected parallel ( up to 6 • DL404
for operating staff independent from each other cables per phase)
• DL593
• Trolley for vacuum circuit • The turnover supporter and • Adaptable to incoming and
breaker is maintenance free, meter mounting board in the outgoing of cable or busbar,
with the matched operating meter box facilitates or mixed incoming and
mechanism requiring secondary wiring and outgoing of cable and busbar
minimum maintenance repairing
• The switchgear can adapt to
• Vacuum circuit breaker’s • The uniform lifted earthing several primary schemes
compartment door is fitted busbar is easy for field with uniform interface sizes
with emergency opening connection
device to conduct
emergency opening • With modular design for
operation without opening cubicles, the whole cubicle
the compartment door can be removed separately
after removing the
• Trolley for vacuum circuit split-board, avoiding gripping
breakers has good between cubicles and
interchangeability, providing facilitating maintenance
easy replacement of circuit operations such as removing
breakers and replacing cubicles in a
fast and direct way

Switchgear design report

Technical parameters

Table 1. Technical parameters of the switchgear

Type ET1
Rated voltage kV 12
Rated power frequency withstand voltage(1min) kV 42
Rated lightning impulse withstand voltage(BIL) kV 75
Rated frequency Hz 50/60
4s thermal withstand current (RMS) kA 20,25,31.5,40,50,63/3s**
Rated peak withstand current (Peak) kA 50,63,80,100,125,160**
Main busbar rated current A 4000,6300**
Branch busbar rated current A 630,1250,1600,2000,2500,3150,4000*,4000/6300FC**
Cubicle width (W) mm 800,1000
Cubicle depth (D) mm 1500(1650)
Cubicle height (H) mm 2200
Protection degree IP4X for metal enclosure(IP2X for opened compartment door of circuit breaker)
Weight kg 700-1000(trolley included)

* The switchgear requires forced cooling


** Special cubicle type, with W*D*H (1100*1900*2400). For more details, please contact Eaton representatives.

4
12kV ET1 Removable AC Metal-enclosed Switchgear

Table 2. Key technical data for W-VACi, E-VAC, VCP-W63W type vacuum circuit breakers

Type Unit W-VACi E-VAC E-VAC


Rated voltage kV 12 12 12
Rated power frequency withstand voltage(1min) kV 42 42 42
Rated lightning impulse withstand voltage(BIL) kV 75 75 75
Rated frequency Hz 50/60 50/60 50/60
Rated current A 630,1250,1600,2000,2500,3150,4000* 4000,6300*
Rated short circuit breaking current(RMS) kA 25,31.5,40 25,31.5,40,50 63
Rated short circuit making current (Peak) kA 63,80,100 63,80,100,125 160
4s thermal withstand current (RMS) kA 25,31.5,40 25,31.5,40,50 63/3s
Arcing time maximum ms <15 <15 -
Mechanical life time 30000 20000 10000
Automatic reclosing operation sequence - O-0.3s-CO-180s-CO,O-180s-CO-180s-CO O-180s-CO-180s-CO
Energy charging motor power W 90 65 440
Energy charging motor voltage (DC/AC) V 110/ 220 110/ 220 110/ 220
Energy charging time of motor S 15 15 15
Opening/closing coil voltage (DC/AC) V 110/ 220 110/ 220 110/ 220

* Forced cooling is required

Features of W-VACi circuit Features of VCP-W63W


breakers circuit breakers
• In accordance with standards • Totally imported circuit
including IEC, GB and DL breakers
• Using the latest EATON • Conforming to ANSL, IEC,
encapsulated vacuum GB and DL standards
interrupter, with chopping
• Very high rated current with
current below 3A natural cooling up to 4000A,
• The latest EATON spring and forced cooling up to
Figure 4. Outline of
operating mechanism with 6300A
VCP-W63W vacuum circuit
impact construction
Figure 2. Outline of W-VACi breaker (4000A/63KA) • Rated short circuit breaking
Vacuum circuit breaker • Ideal switching resistance current is 63kA, while rated
(1250A/31.5KA) load, inductive load and short circuit making current
capacitive load is 160kA
• Light weight
• Motor operation for both DC Surface treatment
and AC applications
• Maintenance free Door and terminal blanking
plates apply epoxy resin power
spray coating, while the
Features of E-VAC circuit cubicles of the switchgear use
zinc-aluminum-magnesium
breakers
steel sheet or aluminum-zinc
• In accordance with standards coating steel sheet. The above
Figure 3. Outline of E-VAC including IEC, GB and DL adopted treatment methods
vacuum circuit breaker and materials ensure a very
(1250A/31.5KA) • Using the latest EATON strong anti-corrosion capacity
vacuum interrupter, with for the switchgear housing.
chopping current below 3A
In consideration of requirement
• The mature spring operating for temperature rise, the related
mechanism with impact busbar compartment parts
construction need to be sprayed with matt
• Ideal switching resistance black paint.
load, inductive load and
capacitive load
• Economical choice
• Motor operation for both DC
and AC applications
• Maintenance free
5
12kV ET1 Removable AC Metal-enclosed Switchgear

Frame Busbar and auxiliary wire Circuit breaker trolley • Manual energy charging
spring unit
• Design is based on IEC Busbar • Circuit breaker trolley is a
• Local closing button
62271 standard central type with its design
• Designed in accordance with conforming to IEC60056, • Local tripping button
• Main materials for cubicles IEC60695 standard. Busbar
use 2.0mm GB1984 standard.
materials inside the cubicle
zinc-aluminum-magnesium are all of high quality • The circuit breaker with
steel sheet or aluminum-zinc same type and rated capacity Circuit breaker
electro-refined copper compartment
coating steel sheet, and rate is fully exchangeable.
adopt double-bender • The maximum dimension for
busbar of each phase is • The mechanical interlock unit A special guide rail is installed
technology with features of for mal-operation is installed
three pieces of 120*10mm2 inside the circuit breaker
high strength, good between circuit breaker
busbar with maximum compartment for circuit breaker
anti-corrosion and good trolley and the switchgear.
continuous current of 4000A. trolley to slide and work on it. In
anti-oxygenic property. No When circuit breaker is
The selected busbar section the compartment, the trolley
need for surface treatment. closing, trolley can not push
can meet the requirements has” SERVICE", "TEST" and
Parts assembling uses high in or draw out. Only when
of system peak withstand "REMOVED" positions. When
strength bolts or rivet the trolley is in SERVICE or
current 125kA and 4s trolley is moving from "TEST"
connection with features of TEST position, circuit breaker
thermal withstand current position to "SERVICE " position,
high precision and good can be closing.
50kA. In the case of shutter is opened automatically;
rigidity for fitting
abnormal environmental • The moving contact is tulip when trolley is moving in a
• Enclosing and isolation of climate, the section can type using compressed negative direction, then the
low voltage compartment, ensure system to work spring or band spring with shutter is closed automatically
VCB compartment, busbar normally silver plating surface. Flexible to completely isolate primary
compartment and cable connection permits higher contact. (See figure 5).
compartment adopts steel • For the special cubicle with
rated current of 6300A, tolerance allowance. The The door of the circuit breaker
sheet separation. good contact causes the
Independent pressure please contact EATON compartment is fitted with the
smaller resistance of main emergency opening button
releasing channel is provided • Selection of busbar materials circuit and low temperature
in all compartments except (unique design from EATON). In
shall be based on IEC60431 rise.
for low-voltage compartment case of emergency, without
• Busbar is pre-drilled with four • Mechanical life (CO cycle): opening trolley compartment
• No welding points for the sides as R5mm rounded W-VACi as 30000 times, door, the manual opening may
frame. Special fixture are corners before delivery. As E-VAC as 20000 times, be conducted, to ensure safety
used in assembling, ensuring rated current is 4000A, the VCP-W63W as 10000 times. of operators. (See figure 6)
very high assembling connection plate of branch
precision bus shall be silver plating • Allowable breaking times
under rated current: W-VACi
• VCB compartment is • Fixing bolts of busbar use 8.8 as 30000 times, E-VAC as
designed with metal or SMC class high strength 20000 times, VCP-W63W as
automatically shutter to meet steeliness bolts, allowing 10000 times.
requirements of busbar to mount in an easy,
simultaneously automatic smooth and very solid way • The operation mechanism is
isolation between circuit the energy charging spring
breaker and busbar side • Earthing busbar size is type. At the moment when
commonly 60*5mm2. This the circuit breaker is
• VCB compartment is fitted section can bear 40kA/1s opening, the spring
with special guide rail to short time current. Earthing recharges energy.
facilitate trolley to push in or busbar is pre-drilled before
draw out easily delivery • The expected life of vacuum
interrupter is 25 years. And
• Each functional unit is fitted the chopping current of the
with doors possessing lock Auxiliary circuit vacuum interrupter is limited Figure 5
and hinge. Distance between to ≤ 3A.
hinges ≤ 330mm • Conductor section
specification: • Operation times of circuit
• The frame is tidy, firm and • current circuit 2.5mm2 breaker can be displayed by
aesthetically looking after • voltage circuit 1.5mm2 the counter on the panel.
processing and assembling
• Insulation degree: • The circuit breaker is fitted
• The protection degree for the • 2000V with display and controller
switchgear shell can reach shown as follows:
IP4X after enclosed • Connection mode:
• fixed terminal block • Mechanical display of
groups the amount of opening and closing
terminal block groups status
shall satisfy user’s
• Energy charging display
demand, reserving 10%
of energy charging
as backup and with
motor
linking plates available
Figure 6

6
12kV ET1 Removable AC Metal-enclosed Switchgear

Cable compartment Low voltage compartment


The cable compartment can be Panel and inner space of low
fitted with current transformer, voltage compartment can be
earthing switch and surge equipped with relay protective
arrester. ET1 switchgear components, meters, air
provides customers with rear switch, energized display,
panel mounting and simulation bus and various
maintenance mode. The design secondary components.
of the cable compartment and
The modular grid plate is used
the switchgear can satisfy
for mounting indoor secondary
various cables in and out
equipment. It can flexibly
modes, for example, bottom in
allocate every secondary
bottom out or top in top out Figure 7
component and facilitate
mode.
secondary connection.
The cable connection can
Fitted with advanced
connect 3 400mm2 three -core
microprocessor-based relay,
cables in parallel, easy for
additional communication
connection. (See figure 7).
interface can be incorporated
Height of cable mounting is ≥
into substation integrated
750mm.
automation.
Microprocessor-based relay
Busbar compartment provides protective function
and possesses multiple
Based on Chinese customer’s functions such as displaying,
requirements, adjacent busbar recording and alarming of
compartments adopt metal substation’s key information.
baffle plate and bushing Fitted with standard RS232 or
isolation to prevent possible RS485 serial interface, it can be
accident from spreading out; connected with substation
larger busbar compartment monitoring system.
busbar mounting and
maintenance window; window Low voltage compartment has
periphery adopts edge fold following control and display
processing, to reduce injuries to units: Figure 8
operators; busbar supporter • Local/ remote selector
adopt epoxy resin Insulators, switch
supporting insulator to adopt
long creepage distance (≥ • Signal indicator:
opening/closing status, and
240mm). When the distance indication of circuit breaker
between phases and to earth is service trolley operating,
larger than 125mm, busbar testing position and the
within the cubicle usually adopt earthing switch in closing
air insulation method. position
Otherwise, it will adopt
compound Insulation method. • High voltage voltage
Then, the whole bus is covered indicator (connected with
with thermal shrinkage capacitor voltage divider of
insulated sleeve. The busbar cable compartment)
lapping area is protected by
insulation hood. (See figure 8)

Figure 9

7
12kV ET1 Removable AC Metal-enclosed Switchgear

Mounting foundation diagram

H
80mm C
G
Channel steel B
A D±1

25
30
A

1~3mm

J
1560(1710)
4Xn-ø13 A-A

780
120

1500(1650)

1060
780
200 120 8-14*24
50
Secondary

30 90 220

385
1200
placement 4-16*26
Of concrete

25
385
Primary
placement
A E Of concrete Front cubicle
Front cubicle F Schematic diagram for mounting foundation of switchgear Schematic diagram for mounting dimensions of switchgear

Figure 10. Schematic diagrams for switchgear construction

Cubicle width (mm) A B C D E F G H J


800 530 630 800 800 630 700 (n-1)*700 (n-1)*800+790 450
1000 730 830 1000 1000 830 900 (n-1)*1000 (n-1)*1000+990 450
Note:
1. n is the number of cubicles with same width
2. Value in the bracket is the value of depth as1710mm.

8
12kV ET1 Removable AC Metal-enclosed Switchgear

Safety and maintenance Safe operation


Design of the switchgear can In order to ensure that the
ensure safety of operators and switchgear and the trolley
equipment itself with operate in correct sequence,
convenient maintenance for the switchgear is equipped with
China’s users. reliable mechanical or electrical
interlock. For key measures,
please see Table 3.

Table 3. Interlock
Five-prevention requirement Detailed measures
Prevent from incorrectly switching If the circuit breaker is already in closing status, the interlocking rod moves backward. At this moment, movement of closing
spring release plate can not raise the lever to release the lock latch.
Prevent operating trolley in load Operations on completely closed door condition fully ensure the safety of operators. There is a mechanical interlock
condition between circuit breaker trolley and the switchgear. Only when the circuit breaker trolley in TEST and SERVICE positions, the
closing can be conducted. When the circuit breaker is in closing status, the circuit breaker will automatically trip when the
circuit breaker trolley is drawn by mistake.
Prevent switching-on earthing Circuit breaker trolley is in SERVICE position, when the cable compartment is energized, earthing switch can not operate
switch in live condition with mechanical interlock.
Prevent earthing switch energizing When earthing switch is closed, then with mechanical interlock, the circuit breaker, the entering operating hole can not be
in earthing position opened in the circuit breaker trolley, and the trolley can not enter into SERVICE position. Then the primary circuit can not be
connected. Only when earthing switch is in opening position, the trolley can rack from TEST position to SERVICE position.
Prevent from entering into The bus compartment, trolley compartment and cable compartment are separated to each other. When the trolley is moved
energized separation to TEST position or DISCONNECTED position, the shutter will automatically close and primary stationary contact is isolated
completely. When the cable compartment is fitted with voltage indicator or mechanical interlock, the back door can open
only after earthing switch is closed. If the back door is not closed, earthing switch can not open.
Secondary plug When the trolley is in central position and SERVICE position, the secondary plug is locked and can not be removed.

Interlock/protection for • If the trolley is in TEST or • When and only when • Switchgear cubicle and all
mal-operation SERVICE position without earthing switch is closed, the metal separation plates are
control voltage, the circuit cable compartment back earthing with set-up special
Fitted with a series of breaker can not close. It can door can be opened earthing terminal for
Five-Prevention interlock only be manually opened (mechanical interlock). If connection, providing good
devices, to prevent danger and (mechanical interlock) back door is not closed, the earthing continuity
corresponding mal-operation earthing switch can not open
• If the trolley is in SERVICE
with serious consequences. position, the control plug is • In order to further satisfy
Therefore, it prevents locked and can not be pulled requirement from specific Maintenance
effectively operating staff and out customers, switchgear cable
the switchgear. The interlock Below features provide users
compartment door can be
device has following functions: • When the earthing switch is with maintenance free or
closed, the trolley can not equipped with energized
minimum maintenance
• When circuit breaker and move from TEST/isolation compulsory locking unit
earthing switch are in • Vacuum interrupter is
position to SERVICE position;
opening position, the trolley ceramic housing, with
when the trolley is in
can move from Safety of operating staff vacuity 10-6 Pa and the
SERVICE position, the
TEST/isolation position to guarantee of 25-year
earthing switch can not be
SERVICE position. If the • The switchgear is operation life
closed (mechanical interlock)
circuit breaker is in closing metal-enclosed and already
• Spring operating mechanism
condition and is racked, the • Additional interlock device passed Type Test for internal only needs least
trolley will trip automatically such as lockout arcing fault maintenance
when moving from electromagnet can be
• Only when cubicle doors are • After opening switchgear’s
TEST/isolation position to mounted on the trolley
completely closed or live back door, the cable terminal
SERVICE position. Reverse and/or earthing switch
parts can not be accessed, box and current transformer
movement has the same operation mechanism.
operation of circuit breakers can be repaired
result (mechanical interlock) Customers shall make a
is allowed
request in ordering • Standard components are
• Only when the trolley is • When the cubicle door is
completely engaged in TEST • After the trolley is in adopted with available
closed, it is possible to check stocks, meeting user’s
or SERVICE position, the REMOVED position, the
for energizing condition in needs
circuit breaker can close shutter can be locked out
the cubicle without
(mechanical interlock) with padlock
accessing live parts

9
12kV ET1 Removable AC Metal-enclosed Switchgear

Switchgear earthing unit The form of the primary and the Installation of busbar Spare parts and accessories
secondary cable chute of
• Connecting each cubicles switchgear depend on The main busbar is supported To supply based on customer’s
with prepared connecting switchgear’s installing position by insulator. Coupling method request and requirements, with
plates and construction condition. is adopted between main buses supply decisions made by both
and between main busbar and sides.
• Connecting all necessary The error per m2 for installing
earthing lead in the branch busbar.
foundation surface of the
switchgear switchgear is lower than 1mm. Wipe the busbar with clean dry
• Connecting the foundation The total error for its length is soft cloth. Check busbar for any
frame wit the earthing bar. If not over 3mm. damage. Cover the connection
the cubicles in line exceed area with conductive paste or
According to engineering neutral Vaseline.
10 sets, then two earthing demand and instructions on the
bar connecting points is drawing, the switchgear is After installation, the fixing
required. transport to specific location. In bolts are tightened with torque
case of a long row of wrench.
switchgears (above 10 sets), it Cover the connection area well
General requirement for is recommended start the with insulation hood.
switchgear installing split-assembling process from
the middle switchgear.
The installing foundation of
switchgear shall meet the Special transportation tools Attached documents,
related stipulations of such as crane, fork truck are spare parts as well as
“Technical code for erection used. Roller and crowbar is accessories
and acceptance for power strictly forbidden to use. The
construction”. The installing circuit breaker trolley can be List of attached documents
foundation of switchgear drawn out from the switchgear
generally needs two concrete and be kept in another place for • Quality certificate
grouting procedures. The first is safekeeping. • Packing list
for embedded installing parts of When installing, the first cubicle • Delivery inspection report
switchgear and for laying shall be adjusted first, or the
foundation channels. The • Installation & operation
first section shall meet
second grouting is for floor instruction
horizontal and vertical
supplemental layer. Its height is requirements. The installation • Transportation and storage
usually 60mm. The height for plainness of the switchgear instruction
floor supplemental concrete shall not exceed 2mm. • List of spare parts and
layer shall be lower than the
After adjusting the first cubicle, accessories
channel level for 3-6mm.
other cubicles are mounted. • Secondary connection
Pay attention to have the side diagram
cutout aligning to the mounted
• Other related data
section.

Climate and environment


12KV ET1 switchgear is designed to fully consider factors such as
customer’s local climate and environmental conditions, and meet
other special requirements as well.

Table 4. Climate and environment

Climate and environment condition Normal applicable conditions Auxiliary measures


Altitude (m) ≤ 1000 With auxiliary measures, ≤ 2500
Temperature max. (℃ ) 40 Technical parameter selection can meet > 40
Temperature min. (℃ ) -15 Heater is equipped
Daily average relative humidity 95% Hearer anti-condensing is equipped
Monthly average relative humidity 90% Hearer anti-condensing is equipped
Seismic earth acceleration Horizontal acceleration does not exceed 0.2g Passed seismic test
Vertical acceleration does not exceed 0.1g Passed seismic test
Safety factor > 1.67 Passed seismic test
Coastal effect (light see wind with salt) IP4X Housing applies coating aluminum-zinc steel sheet or epoxy powder spray coating

10
12kV ET1 Removable AC Metal-enclosed Switchgear

Selection of switchgear Ordering notes


For technical parameter and Please contact us before
connection scheme in details, ordering.
please see switchgear technical
parameter table and main
connection scheme table (See
attached Table 5).
If a customer has special
requirement, please contact
and consult with our Eaton’s
related representative.

Table 5. Single Line Diagram

Scheme No. 001 002 003 004


Main schematic diagram

Main equipment
Application Cable incoming and outgoing Cable incoming and outgoing Cable incoming and outgoing Cable incoming and outgoing
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1 1 1
LZZB8-10A3 2 2 3 3
JDZ2/JDZX
H.V.fuse
Earthing switch 1 1
Surge arrester
Voltage indicator Optional Optional Optional Optional

Scheme No. 005 006 007 008


Main schematic diagram

Main equipment
Application Right coupling left coupling Right coupling left coupling
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1 1 1
LZZB8-10A3 2 2 3 3
JDZ2/JDZX
H.V.fuse
Earthing switch
Surge arrester
Voltage indicator Optional Optional Optional Optional

11
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 009 010 011 012


Main schematic diagram

Main equipment
Application Right coupling left coupling Right coupling left coupling
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1 1 1
LZZB8-10A3 2 2 3 3
JDZ2/JDZX
H.V.fuse
Earthing switch 1 1 1 1
Surge arrester
Voltage indicator Optional Optional Optional Optional

Scheme No. 013 014 015 016


Main schematic diagram

Main equipment
Application Busbar coupling
Rated current 630~4000
W-VAC/VAC 1
LZZB8-10A3
JDZ2/JDZX
H.V.fuse
Earthing switch
Surge arrester
Voltage indicator Optional

12
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 017 018 019 020


Main schematic diagram

Main equipment
Application Voltage measuring Voltage measuring Voltage measuring Protection Voltage measuring Protection
Rated current
W-VAC/VAC
LZZB8-10A3
JDZ2/JDZX 2JDZ2-10 3JDZX-10 2JDZ2-10 3JDZX-10
H.V.fuse 3 3
Earthing switch
Surge arrester 3 3
Voltage indicator

Scheme No. 021 022 023 024


Main schematic diagram

Main equipment
Application Voltage Left and Right coupling Voltage Left and Right coupling Voltage measuring Protection Voltage measuring Protection
Rated current
W-VAC/VAC
LZZB8-10A3
JDZ2/JDZX 2JDZ2-10 3JDZX-10 2JDZ2-10 3JDZX-10
H.V.fuse 3 3 3 3
Earthing switch
Surge arrester 3 3
Voltage indicator

13
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 025 026 027 028


Main schematic diagram

Main equipment
Application Voltage measuring Protection Voltage measuring Protection Voltage measuring Protection Voltage measuring Protection
Rated current
W-VAC/VAC
LZZB8-10A3
JDZ2/JDZX 2JDZ2-10 3JDZX-10 2JDZ2-10 3JDZX-10
H.V.fuse 3 3 3 3
Earthing switch
Surge arrester 3 3 3 3
Voltage indicator

Scheme No. 029 030 031 032


Main schematic diagram

Main equipment
Application Left and right incoming Cable incoming and outgoing Cable incoming and outgoing
Rated current 630~4000 630~4000 630~4000
W-VAC/VAC
LZZB8-10A3
JDZ2/JDZX
H.V.fuse
Earthing switch 1
Surge arrester
Voltage indicator Optional Optional Optional

14
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 033 034 035 036


Main schematic diagram

Main equipment
Application Cable overhead incoming overhead incoming overhead incoming overhead incoming
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1
LZZB8-10A3 2 2
JDZ2/JDZX
H.V.fuse
Earthing switch
Surge arrester
Voltage indicator Optional Optional Optional Optional

Scheme No. 037 038 039 040


Main schematic diagram

Main equipment
Application Cable overhead incoming Cable overhead incoming Cable overhead incoming Cable overhead incoming
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1 1 1
LZZB8-10A3 3 3 3 3
JDZ2/JDZX
H.V.fuse
Earthing switch 1 1
Surge arrester
Voltage indicator Optional Optional Optional Optional

15
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 041 042 043 044


Main schematic diagram

Main equipment
Application Overhead incoming and outgoing Overhead incoming and outgoing Overhead incoming and outgoing Overhead incoming and outgoing
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1 1 1
LZZB8-10A3 2 2 3 3
JDZ2/JDZX
H.V.fuse
Earthing switch 1 1
Surge arrester
Voltage indicator Optional Optional Optional Optional

Scheme No. 045 046 047 048


Main schematic diagram

Main equipment
Application Self feeding tra.
Rated current
W-VAC/VAC
LZZB8-10A3
JDZ2/JDZX
H.V.fuse 3
Earthing switch 1(30/50KVA)
Surge arrester
Voltage indicator Optional

16
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 049 050 051 052


Main schematic diagram

Main equipment
Application Metering Metering Isolated incoming and outgoing Isolated incoming and outgoing
Rated current 630~4000 630~4000
W-VAC/VAC
LZZB8-10A3 2 2
JDZ2/JDZX 2JDZ2-10 2JDZ2-10
H.V.fuse 3 3
Earthing switch
Surge arrester
Voltage indicator Optional Optional

Scheme No. 055 056


Main schematic diagram

Main equipment
Application Metering
Rated current
W-VAC/VAC
LZZB8-10A3 2
JDZ2/JDZX 2JDZ2-10
H.V.fuse 3
Earthing switch
Surge arrester
Voltage indicator

17
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 057 058 059 060


Main schematic diagram

Main equipment
Application Cable overhead incoming Cable overhead incoming Cable overhead incoming Cable overhead incoming
Rated current 630~4000 630~4000 630~4000 630~4000
W-VAC/VAC 1 1 1 1
LZZB8-10A3 2 2 3 3
JDZ2/JDZX 2 2 2 2
H.V.fuse 3 3 3 3
Earthing switch 1 1
Surge arrester
Voltage indicator Optional Optional Optional Optional

Scheme No. 061 062 063 064


Main schematic diagram

Main equipment
Application Cable overhead incoming Cable overhead incoming
Rated current 630-4000 630-4000
W-VAC/VAC 1 1
LZZB8-10A3 2 2
JDZ2/JDZX 3 3
H.V.fuse 3 3
Earthing switch 1
Surge arrester
Voltage indicator Optional Optional

18
12kV ET1 Removable AC Metal-enclosed Switchgear

Scheme No. 065 066 067 068


Main schematic diagram

Main equipment
Application Motor feeder Motor feeder Motor feeder
Rated current 400 400 400
W-VAC/VAC 1 1 1
LZZB8-10A3 2 3 2
JDZ2/JDZX
H.V.fuse 3 3 3
Earthing switch 1
Surge arrester 3
Voltage indicator Optional Optional Optional

Scheme No. 069 070 071 072


Main schematic diagram

Main equipment
Application Motor feeder
Rated current 400
W-VAC/VAC 1
LZZB8-10A3 3
JDZ2/JDZX
H.V.fuse 3
Earthing switch 1
Surge arrester 3
Voltage indicator Optional

19
12kV ET1 Removable AC Metal-enclosed Switchgear

043 019 002 007 052 002 019 043

Typical primary scheme (1)

051(Change) 007 056 002 007 052 002 056 008 051(Change)

Typical primary scheme (2)

003 020 004 013 056 020 004 007 034 008 020 004 056 013 004 020 003

Typical primary scheme (3)

20
The power of fusion.

1833 1874 1886 1893 1897 1899 1906 1908 1911 1914 1934 1961 1962 1963 1967 1977 1983 1984 1989

There’s a certain energy at Eaton. It’s the power of uniting some of the
world’s most respected names to build a brand you can trust to meet
your every power management need.

Eaton is dedicated to ensuring that reliable, eff cient and safe power
is available when it’s needed most. Building on over 100 years of
experience in electrical power management, the experts at Eaton
deliver customized, integrated solutions to solve your most critical
challenges. To learn more visit www.eaton.com/electrical.

All of the above are trademarks of Eaton or its affiliates. Eaton has a licenseto use the
Westinghouse brand name in Asia Pacific. ©2013 Eaton.
Eaton is dedicated to ensuring that reliable, efficient and safe
power is available when it’s needed most. With unparalleled
knowledge of electrical power management across industries,
experts at Eaton deliver customized, integrated solutions to solve
our customers’ most critical challenges.

Our focus is on delivering the right solution for the application.


But, decision makers demand more than just innovative products.
They turn to Eaton for an unwavering commitment to personal
support that makes customer success a top priority. For more
information, visit www.eaton.com/electrical.

Eaton Corporation
Asia Pacific Headquarter
No.3, Lane 280, Linhong Road,
Changning District,
Shanghai 200335
www.eaton.com.cn/electrical

© 2013 Eaton Corporation Eaton is a registered trademark


All Rights Reserved of Eaton Corporation.
Printed in China
Publication number: CHICA0101002_EN All trademarks are property of their
Jul. 2013 respective owners.