Beruflich Dokumente
Kultur Dokumente
Department of Engineering
Objectives
• To determine the parameters of the equivalent circuit, efficiency and voltage regulation of
the given transformer by open circuit test and short circuit test.
• Apparatus
Components
• Connection wires
EEE3405/LAB03 Page 1 of 8
PART A: BACKGROUND
I 1 V2 N 2
= =
I 2 V1 N 1
To determine the efficiency of the given transformer, the methods commonly used are the
Open circuit test and Short circuit test.
EEE3405/LAB03 Page 2 of 8
The connection diagram and the equivalent circuit for the open circuit test are shown in
Figure 1 and Figure 2 respectively.
Open circuit test is used to find the magnetizing branch of the equivalent circuit of the given
transformer.
For supply voltage = Voc
supply current = Ioc
Supply power = Poc
then
Poc
the power factor of the open circuit test is : cos φ =
Voc × I oc
and
I p = I oc × cos φ
I m = I oc × sin φ
V oc
Hence, R p = (magnetizing resistance accounted for iron loss)
Ip
Voc
and X m = (magnetizing resistance)
Im
EEE3405/LAB03 Page 3 of 8
Short Circuit Test
The connection diagram and the equivalent circuit for the short circuit test are shown in
Figure 3 and Figure 4 respectively.
Short circuit test is used to find the leakage branch of the equivalent circuit of the given
transformer.
For supply voltage = Vsc
supply current = Isc
Supply power = Psc
then
Psc
the power factor of the open circuit test is : cos φ =
V sc × I sc
Hence
V sc
Ze =
I sc
Psc
Re = 2
I sc
X e = Z e − Re
2 2
EEE3405/LAB03 Page 4 of 8
After we carried out the open circuit test and short circuit test of the given transformer, we
can find out the parameters of the equivalent circuit, which is
The voltage regulation of the given transformer can also be known at any given value of
power factor, lagging or leading.
V1 − V2
V . R. = ( per unit value) or
V2
I 1 ( Re cos φ ± X e sin φ )
V . R. = ( per unit value)
V2
where
+ for lagging power factor
- for leading power factor
φ is the power factor angle of the load
EEE3405/LAB03 Page 5 of 8
PART B: PROCEDURE
5. Set the output of the variac to zero before switching on the supply.
6. Increase the output of the variac to 70V and take the wattmeter, ammeter and voltage
readings.
7. Repeat step (6) at an interval of 10V each up to 150V with all meter readings being
taken.
80
90
100
110
120
150
8. Decrease the input voltage of the variac to zero and switch off the power supply.
9. Connect the circuit as shown in Figure 3 (step down connection). Do not switch on the
power supply.
10 Short circuit of the secondary terminals of the transformer will cause a large current
flow in the short circuit link, so ensure the short circuit link is installed securely.
EEE3405/LAB03 Page 6 of 8
13 Set the output of the variac to zero before switching on the supply.
14 Increase the output voltage at the variac slowly until the full-load current is seen at the
ammeter. Take the readings of the wattmeter, ammeter and voltmeter immediately.
Wattmeter =
Ammeter -=
Voltmeter =
15 Decrease the input voltage of the variac slowly to zero and switch off the power
supply.
1. From the open circuit test results, calculate the parameters Ip, Im, Rp and Xm, at rated
voltage.
.2. From the short circuit test results, calculate the parameters Re and Xe, referred to the
high voltage side or low – voltage side.
EEE3405/LAB03 Page 7 of 8
3. Plot the graph of Ioc and Poc against the applied voltage. and comment it
EEE3405/LAB03 Page 8 of 8