Sie sind auf Seite 1von 6

2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)

An Interface Protection Relay for Networked


Microgrids with Inverter Based Sources
Anoop V Eluvathingal, K. Shanti Swarup
Department of Electrical Engineering
Indian Institute of Technology Madras, Chennai, India
ee14d001@ee.iitm.ac.in, swarup@ee.iitm.ac.in

Abstract—Large scale integration of distributed generating lays. Hence a protection scheme independent of fault current
sources challenges the conventional protection schemes in the magnitude has to be designed.
distribution networks. The response of inverter interfaced sources Various researches have been carried out to address the
to network faults are different from the conventional generators
and hence need special protection systems. A new protec- protection issues in active distribution networks [3]. The
tion methodology for distribution networks with inverter based variable nature of fault current levels and the demand for
sources is discussed in the present work. The proposed interface cheaper protection system make the new designs challeng-
protection relay algorithm uses instantaneous symmetrical volt- ing. In various research works, attempts have been made to
age components for fault detection. The effectiveness of proposed modify traditional relays to meet the protection requirements
relay algorithm is evaluated by conducting simulation studies
using PSCAD/EMTDC software. of the active distribution networks. A the method that uses
Index Terms—Fault protection, Distributed generation, In- zero sequence and negative sequence currents to distinguish
verter interfaced sources, Interface protection various fault types is discussed [4]. Another suggested method
is adaptive protection, in which over-current relay settings are
I. I NTRODUCTION changed online with the aid of communication networks when
network conditions changes or when new DG sources are
The increased integration of renewable power generating added. A centralized or distributed computing facility is used
sources to existing distribution networks are extensively en- for conducting fault analysis to estimate the relay settings. But
couraged all around the world for reducing greenhouse gases the knowledge of DG status alone won’t be sufficient to
and harvesting cheaper energy[1]. These distributed generating accurately predict the fault levels. The use of communication
(DG) sources raises challenges to the power network operators systems and intelligent computing increases the cost of the
in terms of controllability and protection. The protection issues protection systems. The use of directional relays for addressing
remains as one of the prime concerns for increased integration bi-directional fault currents does not ensure flawless operation
of DG sources to distribution networks. Conventionally, in in networks with IIDG sources, as the fault behavior of IIDG
radial distribution networks, the main feeder substation is the sources are different from conventional generating sources
only source of fault current contribution. The time graded [1]. Distance relays can be an alternative, but have the similar
settings for protective devices are done on this basic idea of a operational issues. Differential relays are reliable, but its costly
radial distribution system. The introduction of DG sources on solution and possess various technical challenges when used
the load side poses sensitivity and selectivity issues to existing for network protection [3]. Despite the progress in research
protection devices. Out of the various DG technologies In- towards new protection systems, an industry proven solution is
verter Interfaced DG (IIDG) technologies have gained greater still lacking [1]. A protection technique using microprocessor-
acceptance due to their flexibility in control options [1]. based relays is proposed in reference [5]. This methodology
In conventional power distribution networks, fault protection can address protection issues in the grid connected mode
is based on detection of fault current magnitudes. The primary and islanded mode of operation without using communication
purpose of network protection is to limit the fault currents network.
without crossing thermal limits of conductors by opening A promising way to address these issues is to group the
the circuit breaker [2]. The challenge in designing protection distributed loads and sources to a single controllable unit
schemes for networks with IIDG sources is that the fault called microgrid. These microgrids are capable of operating
currents are internally regulated by the source controller to as grid connected and stand alone modes. The distribution
protect its power semiconductor switches. This causes the networks can host a number of microgrids to form a networked
network protection devices incapable of detecting the faults microgrid [6]. A new protection methodology for distribution
based on fault current magnitudes. More over the maximum networks with inverter based sources are discussed in the
fault current capacity of an IIDG is variable depending on present work. The idea is to identify areas that can operate
maximum power generation. This limits the off-line studies as microgrids and design an Interface Protection Relay [IPR]
to accurately predict the settings for network protection re- at its boundary. The controllers of inverter based sources are
978-1-5386-1379-5/17/$31.00 2017
c IEEE envisaged to get modified for fault-ride through and allow
the network protection device to isolate faults. A protection to protect the power semiconductor switches. Following a
strategy for microgrids using microprocessor based relays is fault inception, when the current through the VSC reaches a
proposed in [7] need further modifications. A fault detection maximum threshold limit, the control loop switches to constant
strategy based on voltage sag estimation is proposed in present current reference and behaves as a constant current source[9].
work. Voltage is a regulated network parameter and change According to IEEE 1547 integration standard DG sources
from the defined values indicates ill conditioning of the have to be disconnected from the network following a fault
network. Hence threshold settings can be done irrespective of in the distribution feeder [10]. This is to restrict fault current
operating mode; islanded or grid connected. In the present contribution from DG sources so that conventional network
method instantaneous voltage symmetrical components are protection is not affected and to avoid formation of uninten-
used for sag detection. The positive sequence component from tional islands. The DG sources will be having anti-islanding
the instantaneous voltages of the fundamental frequency is protection for detecting the islanding condition. A study of
estimated. The polar plot of positive sequence component has commercially available VSCs by different vendors shows that
the signature of type and intensity of faults. This is used as the IIDG sources trip in ten cycles after fault inception [1]. But
the basis for fault detection. For a network fault protection with increased integration, IIDG sources have to be equipped
device, two thresholds to be decided are relay pickup setting with fault ride-through capacity thereby allowing the network
and trip time delay [2]. The threshold setting is made facile protection device to isolate the fault. This can increase prof-
by using voltage as fault detection parameter. The threshold itability by maximizing the renewable energy utilization. Also
values are independent of the mode of operation and variable it will increase reliability by ensuring isolation of minimum
power capacities of renewable sources. But the limitation with faulty area and continued operation of remaining healthy
the voltage based scheme is selectivity issue. As the voltage part. The controlled fault current should be supplied by IIDG
being a universal parameter in distribution networks with short sources for a definite time decided by the standards.
spans, the voltage sags due to faults will be sensed in the
entire network. Hence discrimination of protection zones is III. I NTERFACE P ROTECTION R ELAY
difficult. In the proposed method the fault discrimination is A simplified block diagram for proposed interface protec-
done by estimating the changes in current magnitude after the tion relay logic is given in Fig 1. The relay algorithm is
inception of voltage sag. classified into three functional modules - voltage module,
current module and direction module.
II. P ROTECTION ISSUES IN ACTIVE DISTRIBUTION
NETWORKS WITH IIDG SOURCES V oltage
Module
In conventional distribution systems reclosers and fuses Re(v) Th1 td1
are used as protection devices due to economic considera- v3Φ
F ilter Mag
tions. The protective devices installed serially are time coor-
Im(v) Th2
dinated to ensure selectivity. To avoid expensive rewiring fuse
saving scheme is commonly used in radial distribution feeders td2
[2]. The contribution of DG sources to faults creates issues Direction
Module Th3
with this scheme of protection. Nuisance tripping is caused Trip T rip
Dir Logic
when DG sources contributes fault currents to an upstream Select
fault. When a fault is being fed in parallel by two sources, Th4
the fault current seen by a protective relay will be different Current td3
from the actual fault current. This is referred to as blinding of Module
Re(i) Th5
protection in relay philosophy[1]. The fault currents depends i3Φ
on the type of DG technologies. The IIDG sources behave dif- F ilter Mag

ferently than conventional synchronous sources. Detail studies Im(i) Th6 td4
Delay
of fault behavior of distributed sources are necessary to decide
correct protection schemes.
The DG sources integrated to distribution network through Fig. 1: Proposed Interface Protection Relay logic
voltage source converters (VSC) are considered for present
studies. The fault response of an IIDG source depends on the The voltage module estimates voltage sags at the time of
inverter controller design [8]. In grid tied operation the primary fault inception. Generally low voltage (LV) distribution net-
objective of the inverter controller is to deliver constant works have short span and hence line impedances are of lower
power and in standalone mode the controller regulates output magnitudes. Hence voltage sags induced by faults in network
voltage. The multi-loop control implemented in dq0 reference will be sensed in the entire network. This creates difficulty in
frame is considered for present studies [9]. The output power discrimination of faults based on local voltage measurements
is regulated by outer power control loop and inner current alone. The current module determines the faulty condition by
control loop follows the reference set by this power control comparing change in current magnitude with threshold The
loop. The maximum current output of IIDG is regulated change in current magnitude followed by a fault is estimated
based on fault induced current components which ensures frequency components. The vector magnitude of instantaneous
a definite way to discriminate faults. Direction is estimated positive sequence components and compared with thresholds
based on phase angle difference between positive sequence to detect voltage sags.
voltage and currents. The direction module identifies the fault 1) Instantaneous symmetrical components: The decompo-
location as forward or reverse with respect to IPR. The fault sition of unbalanced steady state phasors to a set of balanced
discrimination is done to select different time delays based phasors was introduced by Fortescue in 1918 and is tradi-
on zones of protection thereby increasing selectivity. Definite tionally used for analyzing unbalanced power systems. These
time delays are selected based on the fault direction, severity of phasors are estimated when a steady state condition is reached
fault and sensitivity of loads to under voltage. The delay block after transient states. The same is used in protection relay
ensures delay for ensuring coordination with other relays. In algorithms, for estimating fault currents and voltages, by
present work delays are calculated based on off-line studies. It transforming measured instantaneous components to phasor
can be made on-line with the help of a central computer to domain. Instantaneous symmetrical components transforma-
change the delay settings in accordance with topology changes. tion of time dependent variables was introduced by Lyon in
In the proposed method small areas with adequate gener- 1954 on the basis of same transformation matrix [13]. The in-
ation for islanded operation is selected to operate as micro- stantaneous symmetrical components can be used for dynamic
grids. The fuses which are used traditionally for feeder pro- analysis of asymmetrical faults in power systems [14]. The
tection are assumed to be replaced by digital relays. The IPR instantaneous symmetrical components transformation for an
is envisaged to be placed at the boundary of a microgrid. The arbitrary time signal can be expressed as in equation 1
IPR classify fault cases as forward or reverse faults based
fa0 (t)
    
on relative location of fault with respect to the relay. For a 1 1 1 fa (t)
1
fa+ (t) = √ . 1 B
fault in upstream feeder IPR operate in reverse mode isolating B 2   fb (t)  (1)
the sustainable microgrid for ensuring islanded operation. It fa− (t) 3 1 B2 B fc (t)
is assumed that the source generation is adequate to meet the
load demand, or load management is done otherwise. This will where the constant B=ej2π/3 , and the variables
help to improve reliability of supply and better utilization of fa (t), fb (t), fc (t) are the instantaneous voltages or currents
resources. For a fault is inside microgrid the IPR operates of a three phases system. Even though this transformation
in forward mode as a conventional over-current relay, to can be applied to arbitrary time varying signals [15] analysis
isolate the microgrid leaving the healthy upstream feeder. It on a single-frequency sinusoidal signals is considered in the
is assumed that the source protection will trip the individual present work. Lyon vector in complex domain written as
IIDG sources inside the microgrid. Fault in the neighboring
microgrid area which is considered as a reverse fault and 1
IPR ensures backup protection. Further after clearing fault fa+ (t) = √ [fa (t) + Bfb (t) + B 2 fc (t)] (2)
3
synchronization with main grid is done by IPR.
In the vector form, fa+ (t) can be written as sum of real and
A. Voltage module imaginary components
Various techniques are commonly used for detecting voltage
sags. Estimating peak amplitude and comparing with threshold fa+ (t) = Real[fa+ (t)] + jImag[fa+ (t)] (3)
is an simple way of detecting voltage sag inception. This
where
method has an estimation time of nearly half a cycle. Another
common method is by estimating RMS value using a moving 1 1
Real[fa+ (t)] = √ [fa (t) − [fb (t) + fc (t)]] (4)
window of fixed size. The estimation time depends on the 3 2
window size. Fourier methods are best suited if the measured
and
signals have harmonics and transient signals as it can estimate
magnitude and phase angle information of fundamental signal 1
Imag[fa+ (t)] = [fb (t) − fc (t)] (5)
accurately. Various signal processing methods like wavelet 2
transformation is also used in power system analysis. These The vector magnitude can be calculated as,
algorithms are single phase techniques and has to be applied q
to each phase separately [11]. In present work instantaneous mag[fa+ (t)] = (Real[fa+ (t)])2 + (Imag[fa+ (t)])2 (6)
positive sequence components are used for detecting volt-
age sags. Instantaneous measurements advantages that no
frequency estimation is required. Instantaneous line currents The polar plot or Lyon graph is a circle under balanced condi-
are used for current differential protection of transmission tions and an ellipse in the presence of unbalance. The vector
lines. It is asserted that phasor computation will be distorted magnitude will be constant under balanced states and during
in presence of decaying DC component as well as character- unbalanced conditions it sinusoidally oscillates at double the
istic frequencies [12]. The three phase instantaneous voltages power frequency between maximum and minimum value. This
measured at relay terminals are filtered to get fundamental fundamental concept is used for estimating fault conditions.
2) Threshold setting and time delays: The inception of fault when the microgrid is in grid connected mode (2) Low
sag is detected when RMS value of any one phase voltage fault currents for reverse faults and for forward faults in
falls below a threshold of 0.88 p.u. Considering a three phase islanded mode. Based on these two different cases delay time
system having a voltage sag in one phase, the relation with is selected.
positive sequence magnitude is derived as follows [11].
√ C. Direction module
va (t) = 2 × k × Sin(wt)
√ The fault direction is determined by estimating the phase
vb (t) = 2 Sin(wt − 120)
√ relationship between positive sequence voltage and current
vc (t) = 2 Sin(wt + 120) (7) components as it is commonly used in conventional re-
where, k is the fractional dip in voltage 0<k<1.The instanta- lays. This can discriminate forward or reverse faults. The
neous positive sequence components are as in equation 8 algorithm discussed in reference [5] is used along with the
proposed method. The definite time delays are selected based
1
va+ (t) = √ [va (t) + Bvb (t) + B 2 vc (t)] (8) on fault direction.
3
Utility Grid
Equation 8 can be simplified as 11 kV
√ 11/0.400 kV
Feeder
2 1 3
va+ (t) = √ {(K + )sinwt − j coswt} (9) Distribution
Transformer
3 2 2
F eeder1 CB F eeder2 CB F eeder3 CB
The vector manitude can be estimated as.
√ L1.1 L2.1 L3.1

2 1 1 − cos2wt 9 1 + cos2wt 1
|va1 | = √ {(K + )2 + } 2 (10)
3 2 2 4 2
F1
L1.2 L1.3 L3.2 L3.3
Equation 10 represents an ellipse whose maximum and mini- Load2.1
mum magnitudes will be
√ IPR CB
M icrogrid 1
IPR CB
M icrogrid 2
3
|va1 |max = √ (11) L1.4 Load1.2 L3.4 Load3.2
2 F2
√ IIDG IIDG
2 1 Load1.1 Load3.1
|va1 |min = √ (k + ) (12) L1.5 Load1.3
3 2 Load3.3

Load1.4
In the present work the under voltage trip settings for
grid connected distributed sources as mentioned by interfacing Fig. 2: Single line diagram of test system for simulation studies
standard IEEE 1547 is considered. The sources are given fault
ride through and will supply fault currents until fault is cleared
by IPR. Two cases are considered (1) Fault impedance is very
IV. R ESULTS OF SIMULATION STUDIES
low and V<0.5 p.u. delay time of 6 cycles is considered (2) for
medium impedance faults 0.5pu ≤ V < 0.88pu and the time The effectiveness of proposed IPR algorithm has been evalu-
delay selected is 120Cycles. ated by conducting simulation studies in the PSCAD/EMTDC
software environment. A European Low voltage radial dis-
B. Current module
tribution network discussed in reference [5] and [17] with
Fault generated current components are extracted by cal- modifications is considered for simulation studies. The single
culating difference in the instantaneous currents during fault line schematic diagram of the distribution test feeder under
and the pre-fault conditions [16]. This gives the estimate of consideration is shown in Fig 2. The distribution system
the the fault-generated current components. The advantage consists of three load feeders connected to the main utility grid
of using fault components, is that it is independent of load with system frequency 50Hz, through a 2 MVA, 11/0.4 kV ,
conditions. Mathematically it is expressed in equation. Dyn11 step-down transformer. The short-circuit capacity of the
xf k = xk − xk−4N (13) 11 kV bus is accounted as 80 MVA. The distribution system is
envisaged to have connected with IIDG sources in load feeder
where xf k is the fault component sample,xk represents the 1 and in load feeder 3,which is regarded as equivalent sources
present sample and N is the number of samples in one power- in microgrid areas as shown in Fig 2. The proposed IPR is
frequency cycle. This algorithm is able to provide four cycles in the boundary of microgrid and distribution feeder. Feeder
of fault component data after inception of fault [16]. Two cases protection relays which are overcurrent relays are considered
are considered (1) High fault current magnitude,for a forward at the beginning of the each load feeder.
Va Vb Vc Va Vb Vc
Voltage(kV)

Voltage(kV)
0.2 0.2

0 0

−0.2 −0.2

2.98 3 3.02 3.04 3.06 3.08 2.98 3 3.02 3.04 3.06 3.08
(a) Time(Seconds) (a) Time(Seconds)

0.4 Vreal Vimag Vmag 0.4 Vreal Vimag


Voltage(kV)

Voltage(kV)
V
Vmag−minthreshold Vmag
Vthreshold
0.2 0.2
0 0
−0.2 −0.2

2.98 3 3.02 3.04 3.06 3.08 2.98 3 3.02 3.04 3.06 3.08
(b) Time(Seconds) (b) Time(Seconds)
1 1 Ia Ib Ic
Ia
0.5 Ib Ic
Current(kA)

Current(kA)
0 0
−0.5
−1
−1
−1.5
2.98 3 3.02 3.04 3.06 3.08 2.98 3 3.02 3.04 3.06 3.08
(c) Time(Seconds) (c) Time(Seconds)
1 Imag Imagmax 1 Ireal Iimag Imag Imagmax
0.5 Ithreshold 0.5 I
threshold
Current(kA)

Current(kA)

0
0
Iimag −0.5
−0.5
−1
−1 Ireal
−1.5
2.98 3 3.02 3.04 3.06 3.08 2.98 3 3.02 3.04 3.06 3.08
(d) Time(Seconds) (d) Time(Seconds)

Fig. 3: Interface Protection Relay mesurements for a single Fig. 4: Interface Protection Relay mesurements for a three
phase to ground fault at F1 phase to Ground fault at F1

A. A Single phase to ground fault in Feeder 1 B. A three phase to Ground fault in Feeder 1
A single line to ground fault is simulated at time t=3 seconds Fig 4(a) shows the voltage and Fig 4(b) shows the in-
at fault position F1 in feeder 1 with a fault resistance of stantaneous symmetrical components of voltages, estimated
0.01 Ohm. Fig 3(a) shows three phase voltages and Fig 3(b) after three phase to ground fault inception at simulation time
shows the instantaneous symmetrical components of voltages t=3 seconds, at fault position F1, indicated in Fig 2 with a
as estimated by equations (4) - (6). During normal operations, fault resistance of 0.01 Ohm. The Fault is triggered when
the instantaneous magnitude will be constant, and during line the minimum peak of instantaneous magnitude falls below
to ground faults, it oscillates between maximum and minimum the set threshold. Fig 4(c) shows the fault induced current
peak values. The Fault is triggered when the minimum peak components estimated and Fig 4(d) shows the maximum peak
of instantaneous magnitude falls below the set threshold. The of instantaneous symmetrical component magnitude compared
fault induced currents estimated as in IPR algorithm using with threshold. The change in current magnitudes confirms the
equation 13 is given in Fig 3(c). The IPR senses the change upstream feeder fault. The relay trip command is triggered
in current magnitude due to the fault current contribution after the predefined delay time.
from source at the microgrid interface. The IPR trip command
triggers after a predefined delay time. Islanded operation of C. A Three line to Ground fault in Microgrid 1
the isolated microgrid is not considered in present work. It is A three phase line to ground fault is simulated inside
assumed that source is equipped with self-protection and stops microgrid 1 at fault position F2 as in Fig 2. Fig 5(a) shows
firing if conditions for islanded operations are not met. voltage and current response. The fault impedance is con-
Va Vb Vc crogrids with inverter based sources to distribution networks
Voltage(kV) 0.2 is proposed. The effectiveness of proposed IPR algorithm
has been evaluated by conducting simulation studies in the
0 PSCAD/EMTDC software environment. Islanded operation of
−0.2 microgrids after fault isolation is not considered in present
work. Further studies have to be conducted for ensuring time
2.98 3 3.02 3.04 3.06 3.08 coordination with other protection relays in the distribution
(a) Time(Seconds) network.
0.4 VI. ACKNOWLEDGEMENT
Vreal Vimag
Voltage(kV)

0.2 Vmag Vthreshold The authors acknowledge gratefully, the support provided
by Maschinenfabrik Reinhausen (MR) through the IGCS Re-
0 search Programme on Sustainable Power Engineering.
−0.2 R EFERENCES
2.98 3 3.02 3.04 3.06 3.08 [1] A. Hooshyar and R. Iravani, “Microgrid protection,” Proceedings of the
IEEE, vol. 105, no. 7, pp. 1332–1353, July 2017.
(b) Time(Seconds) [2] ALSTOM(Firm), Network protection & automation guide. ALSTOM,
20 2002.
Ia Ib Ic [3] S. Mirsaeidi, D. M. Said, M. W. Mustafa, M. H. Habibuddin, and
10 K. Ghaffari, “Progress and problems in micro-grid protection schemes,”
Renewable and Sustainable Energy Reviews, vol. 37, pp. 834–839, 2014.
Current(kA)

0 [4] H. Nikkhajoei and R. H. Lasseter, “Microgrid fault protection based


on symmetrical and differential current components,” Power System
−10 Engineering Research Center, pp. 71–74, 2006.
[5] M. A. Zamani, T. S. Sidhu, and A. Yazdani, “A protection strategy and
−20 microprocessor-based relay for low-voltage microgrids,” Power delivery,
2.98 3 3.02 3.04 3.06 3.08 IEEE transactions on, vol. 26, no. 3, pp. 1873–1883, 2011.
(c) Time(Seconds) [6] Z. Li, M. Shahidehpour, F. Aminifar, A. Alabdulwahab, and Y. Al-Turki,
“Networked microgrids for enhancing the power system resilience,”
20 Proceedings of the IEEE, vol. 105, no. 7, pp. 1289–1310, July 2017.
Ireal Iimag Imag Imagmax [7] S. F. Zarei and M. Parniani, “A comprehensive digital protection
10 Ithreshold scheme for low-voltage microgrids with inverter-based and conventional
Current(kA)

distributed generations,” IEEE Transactions on Power Delivery, vol. 32,


no. 1, pp. 441–452, 2017.
0 [8] M. E. Baran and I. El-Markaby, “Fault analysis on distribution feeders
with distributed generators,” IEEE Transactions on Power Systems,
−10 vol. 20, no. 4, pp. 1757–1764, Nov 2005.
[9] z. shuai, C. Shen, X. Yin, x. liu, and J. Shen, “Fault analysis of inverter-
2.98 3 3.02 3.04 3.06 3.08 interfaced distributed generators with different control schemes,” IEEE
(d) Time(Seconds) Transactions on Power Delivery, vol. PP, no. 99, pp. 1–1, 2017.
[10] “Ieee standard for interconnecting distributed resources with electric
Fig. 5: Interface Protection Relay mesurements for a three power systems,” IEEE Std 1547-2003, pp. 1–28, July 2003.
[11] S. Jothibasu and M. K. Mishra, “An improved direct ac converter for
phase to Ground fault fault at F2 voltage sag mitigation,” IEEE Transactions on Industrial Electronics,
vol. 62, no. 1, pp. 21–29, Jan 2015.
[12] S. Dambhare, S. Soman, and M. Chandorkar, “Current differential
protection of transmission line using the moving window averaging
sidered high. It can be seen that due to the parallel feeding technique,” in IEEE PES General Meeting, July 2010, pp. 1–1.
from distributed source fault current magnitudes are less than [13] G. C. Paap, “Symmetrical components in the time domain and their
without IIDG source. The proposed protection scheme will application to power network calculations,” IEEE Transactions on power
systems, vol. 15, no. 2, pp. 522–528, 2000.
operate without fail. [14] S. Leva, “Power network asymmetrical faults analysis using instanta-
The robustness of the algorithm for faults in feeders with neous symmetrical components,” Journal of Electromagnetic Analysis
higher fault resistance is tested. High impedance faults have and Applications, vol. 1, no. 04, p. 205, 2009.
[15] M. Iravani and M. Karimi-Ghartemani, “Online estimation of steady
voltage and current parameters equivalent to loads hence are state and instantaneous symmetrical components,” IEE Proceedings-
difficult to be detected by the present method. Use of dedicated Generation, Transmission and Distribution, vol. 150, no. 5, pp. 616–622,
high impedance detection methods is suggested, which is 2003.
[16] H. Gao and P. A. Crossley, “Design and evaluation of a directional
not considered now. In present studies, the maximum fault algorithm for transmission-line protection based on positivesequence
impedance is restricted to half of load impedance. fault components,” IEE Proceedings - Generation, Transmission and
Distribution, vol. 153, no. 6, pp. 711–718, November 2006.
V. C ONCLUSION [17] S. Papathanassiou, N. Hatziargyriou, K. Strunz et al., “A benchmark low
voltage microgrid network,” in Proceedings of the CIGRE symposium:
The traditional protection systems in distribution networks power systems with dispersed generation, 2005, pp. 1–8.
fails to operate satisfactorily for network faults when IIDG
sources are present. A new interface protection relay, based
on instantaneous symmetrical components, for integrating mi-

Das könnte Ihnen auch gefallen