EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-01
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)

Supply Air Duct

1 VCD 1000 350 0.35 0.37 2155


2 Flexible connection 1000 350 0.35 2155
1000 350 0.35 2155
3 Reducer 4 deg 1 0.01133
1000 350 0.35 2155
electric heater 1000 350 0.35 2155
Sound attenuator
4 1000 350 0.35 2155
(ATT-01)
5 Straight duct 1000 350 0.35 2155 1.50
6 Y -Pcs 2155
650 300 0.195 955
7 Reducer 7 deg 0.85714 0.013
650 350 0.2275 2155
8 vcd 650 300 955
9 Straight duct 650 300 0.195 955 7.00
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-01
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
10 Elbow 90 deg 650 300 0.195 0.33 0.65 0.461538462 955
11 Straight duct 650 300 0.195 955 4.90
300 300 0.09 355
12 Reducer 7 deg 0.46154 0.013
650 300 0.195 955
13 Straight duct 300 300 0.09 355 3.10
14 Elbow 90 deg 300 300 0.09 0.33 0.83 1 355
15 Straight duct 300 300 0.09 355 4.60
16 Elbow 90 deg 300 300 0.09 0.33 0.83 1 355
17 Straight duct 300 300 0.09 355 4.70
18 Flexible connection
19 plenum 250 250 355 2.60
20 SLBR
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-01
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
Return Air Duct

Bell mouth with 1200 350 0.42 2155


1 1.2
Wiremesh 1000 350 0.35 2155
2 Straight duct 1000 350 0.35 2155 10.50
Sound attenuator
3 1000 350 0.35 2155
(ATT-01)
4 vcd 1000 350 2155
5 Elbow 90 deg 1000 350 0.35 0.33 0.60 0.35 2155
6 Straight duct 1000 350 0.35 2155 4.60
7 return plenum 2155

FRESH Air Duct


Straight duct 500 150 0.075 385 2.50
vcd 500 150 385
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-01
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
Y pcs 765

Straight duct 650 250 0.1625 765 0.50


Elbow 90 deg 650 250 0.1625 0.33 0.65 0.384615385 765
Straight duct 650 250 0.1625 765 11.00
Elbow 90 deg 650 250 0.1625 0.33 0.65 0.384615385 765
Straight duct 650 250 0.1625 765 0.30
Elbow 90 deg 650 250 0.1625 0.33 0.65 0.384615385 765
Straight duct 650 250 0.1625 765 0.60
vcd 650 250 765
850 250 0.2125 1060
3 Reducer 4 deg 1.30769 0.01133
650 250 0.1625 765
Straight duct 650 250 0.1625 765 0.60
Y -Pcs 1060
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-01
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
Straight duct 850 250 0.2125 1060 9.00
vcd 850 250 1090
Straight duct 850 250 0.2125 1090 14.00
Elbow 90 deg 850 250 0.2125 0.33 0.62 0.294117647 1090
Straight duct 850 250 0.2125 1090 1.90
FD 850 250 0.2125 1090
Straight duct 850 250 0.2125 1090 0.30
REFER TO
FAHU-RF-01

Note-
1) Pressure across sound attenuator has been taken from Manufacturer's data catologue
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-01
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
2) Pressure across Flex connection has been assumed 2 Pa.
3) Pressure drop across Louvers has been taken as per Material submittal

4) Pressure drop across volume control damper has been taken from approved Material submittal
5) Pressure drop across Fire damper is negligible as per manufacturer's comments, hence the same has been calculated by ASHRAE standards

6) Pressure drop across all air terminal devices has been taken as approved material submittal
7) Pressure drop across duct fittings has been calculated with the help ASHRAE standard.
8) Pressure across Bell mouth has been assumed 2 Pa.

9) We have considered Smooth Radius Elbow (Without Vane) for Duct Sizes less than 600 mm and Mitered Elbows Single-Thickness Vane (80 mm Vane Spacing) for
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

6.16 22.00
6.16 2.00
6.16
22.82 0.26
6.16
6.16

6.16 22.82 80.00

6.16 0.41 0.61

4.90
14.44 0.19
9.47
0.00 0.00 25.00
4.90 0.41 2.86
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

4.90 14.44 4.76


4.90 0.41 2.00
3.94
9.37 0.12
4.90
3.94 0.41 1.26
3.94 9.37 3.09
3.94 0.41 1.88
3.94 9.37 3.09
3.94 0.41 1.92
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

5.13
15.85 2.00
6.16
6.16 0.41 4.28

6.16 22.82 80.00

0.00 0.00 25.00


6.16 22.82 7.53
6.16 0.41 1.88

5.13 0.41 1.02


0.00 0.00 25.00
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

4.71 0.41 0.20


4.71 13.34 4.40
4.71 0.41 4.49
4.71 13.34 4.40
4.71 0.41 0.12
4.71 13.34 4.40
4.71 0.41 0.24
0.00 0.00 25.00
4.99
14.98 0.17
4.71
4.71 0.41 0.24
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

4.99 0.41 3.67


0.00 0.00 25.00
5.13 0.41 5.71
5.13 15.84 5.23
5.13 0.41 0.78
5.13
5.13 0.41 0.12

381.94

Safety Factor (15%) 57


Grand total 439
ESP as per Schedule 0
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

hickness Vane (80 mm Vane Spacing) for Duct Sizes greater than 600 mm.
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)

Supply Air Duct

1 VCD 1250 600 0.75 0.37 4830


2 Flexible connection 1250 600 0.75 4830
1250 600 0.75 4830
3 Reducer 4 deg 1 0.01133
1250 600 0.75 4830
electric heater 1250 600 0.75 4830
Sound attenuator
4 1250 600 0.75 4830
(ATT-01)
5 Straight duct 1250 600 0.75 4830 2.10
6 Y -Pcs 4830
1300 400 0.52 3050
7 Reducer 7 deg 1.33333 0.013
650 600 0.39 3050
8 Straight duct 1300 400 0.52 3050 7.00
9 Elbow 90 deg 1300 400 0.52 0.33 0.58 0.307692308 3050
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
10 Straight duct 1300 400 0.52 3050 4.90
11 Y -Pcs 3050
800 300 0.24 1300
12 Reducer 7 deg 0.75 0.013
800 400 0.32 1300
13 Straight duct 800 300 0.24 1300 9.30
14 Elbow 90 deg 800 300 0.24 0.33 0.63 0.375 1300
15 Straight duct 800 300 0.24 1300 3.50
450 300 0.135 600
16 Reducer 7 deg 0.5625 0.013
800 300 0.24 1300
17 Straight duct 450 300 0.135 600 3.30
18 Elbow 90 deg 450 300 0.135 0.33 0.72 0.666666667 600
19 Straight duct 450 300 0.135 600 2.90
300 300 0.09 300
20 Reducer 7 deg 0.66667 0.013
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
20 Reducer 7 deg 0.66667 0.013
450 300 0.135 600
21 Straight duct 300 300 0.09 300 3.10
22 Flexible connection 355
23 plenum 250 250 355 2.10
24 SLBR

Return Air Duct

Bell mouth with 1450 600 0.87 4830


1 1.16
Wiremesh 1250 600 0.75 4830
2 Straight duct 1250 600 0.75 4830 0.50
3 Elbow 90 deg 1250 600 0.75 0.33 0.58 0.48 4830
4 Straight duct 1250 600 0.75 4830 0.50
Sound attenuator
5 1250 600 0.75 4830
(ATT-01)
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
6 vcd 1250 600 4830
7 Straight duct 1250 600 0.75 4830 4.60
8 return plenum 4830

FRESH Air Duct


Straight duct 500 150 0.075 385 0.50
vcd 500 150 385
Y pcs 765

Straight duct 650 250 0.1625 765 0.50


Elbow 90 deg 650 250 0.1625 0.33 0.65 0.384615385 765
Straight duct 650 250 0.1625 765 11.00
Elbow 90 deg 650 250 0.1625 0.33 0.65 0.384615385 765
Straight duct 650 250 0.1625 765 0.30
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
Elbow 90 deg 650 250 0.1625 0.33 0.65 0.384615385 765
Straight duct 650 250 0.1625 765 0.60
vcd 650 250 765
850 250 0.2125 1060
3 Reducer 4 deg 1.30769 0.01133
650 250 0.1625 765
Straight duct 650 250 0.1625 765 0.60
Y -Pcs 1060
Straight duct 850 250 0.2125 1060 9.00
vcd 850 250 1090
Straight duct 850 250 0.2125 1090 14.00
Elbow 90 deg 850 250 0.2125 0.33 0.62 0.294117647 1090
Straight duct 850 250 0.2125 1090 1.90
FD 850 250 0.2125 1090
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
Straight duct 850 250 0.2125 1090 0.30
REFER TO
FAHU-RF-01

Note-

1) Pressure across sound attenuator has been taken from Manufacturer's data catologue
2) Pressure across Flex connection has been assumed 2 Pa.

3) Pressure drop across Louvers has been taken as per Material submittal
4) Pressure drop across volume control damper has been taken from approved Material submittal
5) Pressure drop across Fire damper is negligible as per manufacturer's comments, hence the same has been calculated by ASHRAE standards
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-02
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
6) Pressure drop across all air terminal devices has been taken as approved material submittal
7) Pressure drop across duct fittings has been calculated with the help ASHRAE standard.

8) Pressure across Bell mouth has been assumed 2 Pa.


9) We have considered Smooth Radius Elbow (Without Vane) for Duct Sizes less than 600 mm and Mitered Elbows Single-Thickness Vane (80 mm Vane Spacing) for
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

6.44 22.00
6.44 2.00
6.44
24.97 0.28
6.44
6.44

6.44 24.97 80.00

6.44 0.41 0.86

5.87
20.71 0.27
7.82
5.87 0.41 2.86
5.87 20.71 6.83
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

5.87 0.41 2.00

5.42
17.66 0.23
4.06
5.42 0.41 3.79
5.42 17.66 5.83
5.42 0.41 1.43
4.44
11.89 0.15
5.42
4.44 0.41 1.35
4.44 11.89 3.92
4.44 0.41 1.18
3.33
6.69 0.09
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C
6.69 0.09
4.44
3.33 0.41 1.26

5.55
18.55 2.00
6.44
6.44 0.41 0.20
6.44 24.97 8.24
6.44 0.41 0.20

6.44 24.97 80.00


RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

0.00 0.00 25.00


6.44 0.41 1.88

5.13 0.41 0.20


0.00 0.00 25.00

4.71 0.41 0.20


4.71 13.34 4.40
4.71 0.41 4.49
4.71 13.34 4.40
4.71 0.41 0.12
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

4.71 13.34 4.40


4.71 0.41 0.24
0.00 0.00 25.00
4.99
14.98 0.17
4.71
4.71 0.41 0.24

4.99 0.41 3.67


0.00 0.00 25.00
5.13 0.41 5.71
5.13 15.84 5.23
5.13 0.41 0.78
5.13
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

5.13 0.41 0.12

Sub Total 363


Safety Factor (15%) 54
Grand total 418
ESP as per Schedule 0
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

hickness Vane (80 mm Vane Spacing) for Duct Sizes greater than 600 mm.
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-03
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)

Supply Air Duct

1 VCD 1700 500 0.85 0.37 6820


2 Flexible connection 1700 500 0.85 6820
1700 500 0.85 6820
3 Reducer 4 deg 1 0.01133
1700 500 0.85 6820
4 Straight duct 1700 500 0.85 6820 0.70
5 Elbow 90 deg 1700 500 0.85 0.33 0.56 0.294117647 6820
6 electric heater 1700 500 0.85 6820
Sound attenuator
7 1700 500 0.85 6820
(ATT-01)
8 Straight duct 1700 500 0.85 6820 3.30
9 Y -Pcs 6820
1550 450 0.6975 5320
10 Reducer 7 deg 1.395 0.013
1000 500 0.5 6820
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-03
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
11 Straight duct 1550 450 0.6975 5320 1.20
12 Elbow 90 deg 1550 450 0.6975 0.33 0.56 0.290322581 5320
13 Straight duct 1550 450 0.6975 5320 7.55
14 Y -Pcs 5320
15 vcd 900 400 2250
16 Straight duct 900 400 0.36 2250 4.05
17 Y -Pcs 2250
800 400 0.32 1350
18 Reducer 7 deg 1.33333 0.013
800 300 0.24 1350
19 vcd 800 300 1350
20 Straight duct 800 300 0.24 1350 10.05
21 Elbow 90 deg 800 300 0.24 0.33 0.63 0.375 1350
22 Straight duct 800 300 0.24 1350 6.10
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-03
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
23 Elbow 90 deg 800 300 0.24 0.33 0.63 0.375 1350
24 Straight duct 800 300 0.24 1350 4.80
600 250 0.15 675
25 Reducer 7 deg 0.625 0.013
800 300 0.24 1350
26 Straight duct 600 250 0.15 675 11.50
27 Flexible connection 675
28 plenum 250 250 675 4.60
29 SLBR 675

Return Air Duct

Bell mouth with 1900 500 0.95 6820


1 1.11765
Wiremesh 1700 500 0.85 6820
2 Straight duct 1700 500 0.85 6820 2.80
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-03
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
Sound attenuator
3 1700 500 0.85 6820
(ATT-01)
4 vcd 1700 500 6820
5 Straight duct 1700 500 0.85 6820 4.60
6 return plenum 6820

Fresh Air Duct


1 Straight duct 750 200 0.15 680 5.00
2 vcd 750 200 680
3 Straight duct 750 200 0.15 680 1.30
800 200 0.16 715
4 Reducer 4 deg 1.06667 0.01133
750 200 0.15 680
5 Straight duct 800 200 0.16 715 0.50
fire damper 800 200 715
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-03
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
6 Straight duct 800 200 0.16 715 0.50
refer to FAHU-
RF-01

Note-

1) Pressure across sound attenuator has been taken from Manufacturer's data catologue
2) Pressure across Flex connection has been assumed 2 Pa.
3) Pressure drop across Louvers has been taken as per Material submittal

4) Pressure drop across volume control damper has been taken from approved Material submittal
EXTERNAL STATIC PRESSURE CALCULATION

AHU-FF-03
Area
C0 KCp Air Flow Equivalent
a=H×W A0/A1
S.No. Remark Description W H r/W H/W Q (l/s) Length(m)
(m²) (B) (C)
(D) (E)
(A)
5) Pressure drop across Fire damper is negligible as per manufacturer's comments, hence the same has been calculated by ASHRAE standards
6) Pressure drop across all air terminal devices has been taken as approved material submittal

7) Pressure drop across duct fittings has been calculated with the help ASHRAE standard.
8) Pressure across Bell mouth has been assumed 2 Pa.

9) We have considered Smooth Radius Elbow (Without Vane) for Duct Sizes less than 600 mm and Mitered Elbows Single-Thickness Vane (80 mm Vane Spacing) for
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

8.02 22.00
8.02 2.00
8.02
38.75 0.44
8.02
8.02 0.41 0.29
8.02 38.75 12.79
8.02

8.02 38.75 80.00

8.02 0.41 1.35

7.63
35.02 0.46
13.64
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

7.63 0.41 0.49


7.63 35.02 11.56
7.63 0.41 3.08

0.00 0.00 25.00


6.25 0.41 1.65

4.22
10.71 0.14
5.63
0.00 0.00 25.00
5.63 0.41 4.10
5.63 19.05 6.29
5.63 0.41 2.49
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

5.63 19.05 6.29


5.63 0.41 1.96
4.50
12.19 0.16
5.63
4.50 0.41 4.69

7.18
31.03 2.00
8.02
8.02 0.41 1.14
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

8.02 38.75 80.00

0.00 0.00 25.00


8.02 0.41 1.88

4.53 0.41 2.04


0.00 0.00 25.00
4.53 0.41 0.53
4.47
12.02 0.14
4.53
4.47 0.41 0.20
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

4.47 0.41 0.20

Sub Total 350


Safety Factor (15%) 53
Grand total 403
ESP as per Schedule 0
RE CALCULATION

Velocity Pressure Total Pressure Drop(Pa)


Velocity head= For Duct= E x H
=Q/a (m/s) Drop(Pa/m) For Reducer,FD, VCD = B x G
0.602 V2 (G)
(F) (H) For Elbow = G x C

hickness Vane (80 mm Vane Spacing) for Duct Sizes greater than 600 mm.

Das könnte Ihnen auch gefallen