Beruflich Dokumente
Kultur Dokumente
PLUMBING CALCULATIONS
Q = 5.5 l/s
H = 40 m
HP = Q xH xSP.GR / 3960η
HP = Horse Power
SP.GR = Specific Gravity of Liquid with respect to Water
SP.GR.(Water) = 1.0
Q = 11 l/s
= 0.011 m3 / s
Take D = 100 mm
V = 1.4 m/s
(Referenced to 2007 ASHRAE Handbook- HVAC Applications Chapter 49 Service Water Heating)
No. of fixtures:
Heat losses through pipes = Total pipe length x 40 W/m (Insulated pipes)
(q) = 68000 Watt
Q circulation pump = q/ ρ c p Δt
To get pump head the only loss we have is the line friction loss in all pipes and fitting
System Chosen:
- Choose the combined system to protect the building from fire (hose connections
with automatic sprinkler system)
- Choose the FM 200 system to protect the electric rooms from fire
- Choose the CO2 system to protect the generator & transformer rooms from fire
Classification of Occupancies:
- Assume occupancy classification is Light hazard class III for stand pipe system. NFPA
14 (3-3)
- Assume occupancy classification is Light hazard for sprinkler system. NFPA 13 (2-1)
Pump operation time = 45 min. NFPA 13 (Table 7-2.2.1)
Sprinkler coverage area = 168 ft²
= 15.6 m²
Max. Spacing between two Sprinklers = 15 ft
= 4.75 m
NFPA 13 (Table 5-6.2.2 (a)) for Light Hazard
Design Approaches:
Remoter area (Design area) = 1500 ft²
= 139 m²
Max. area Protected = 4831 m² NFPA 13 (5-2)
Floor area = 12550 m²
No. of zones = 2.6
Take no. of zones =3 Zones
Assume performing calculations on (2) Zones
Fire Fighting Water Demand:
a. Water required for hose stream :
No. of FHC for each zone =2
No. of FHR for each zone =3
Water Demand required for one FHC = 100 gpm NFPA 13 (Table 7-2.3.1.1)
Water Demand required for one FHR = 50 gpm
Q hose streams /zone =350 gpm/zone
If the required head is not available in the header running through the spine, the following
pumps shall be provided:
c. Firefighting Pumps:
1. Electrical Fire Pumps:
Q = 1000 gpm
H = 105 m
Pressure reducing valves should be provided to reduce pressure to 50 m
2. Jockey Pump:
Q = (5-10) % of Q pump
= 100 gpm
H = 115 m
Choose:
2 pumps (One Electrical on duty and one Diesel standby) each of:
Q =1000 gpm & H = 105 m