CHECK LIST FOR MAINTENANCE OF4.16 KV VACUUM


Date: 01.10.2015 Page 1 of 6
-CIRCUIT BREAKERS/SWITCH CONTACTOR

CHECK LIST FOR MAINTENANCE OF 4.16


TITLE OF DOCUMENT KV VACUUM -CIRCUIT BREAKERS/SWITCH
CONTACTOR

Revision No Date Revision Details Section Revised


Rev 0 01-10-2015 Document Revalidated NA

PREPARED BY
Signature

Name
Date 01 October 2015
REVIEWED BY

Signature

Name
Date
APPROVED BY
Signature

Name
Date
ISSUED BY
Signature
Name
Date
DISTRIBUTION LIST
General Manager (O&M) Manager (O&M) DC- Yanbu
Manager (W.P)
Doc No: MFQ-Y2-PG-
ELECTRICAL POWER
-MYOW-4- CHECK LIST GENERATION Y-2
PG-316

CHECK LIST FOR MAINTENANCE OF4.16 KV VACUUM


Date: 01.10.2015 Page 2 of 6
-CIRCUIT BREAKERS/SWITCH CONTACTOR

STANDARD MAINTENANCE PROCEDURE

TITLE: CHECK LIST FOR MAINTENANCE OF


VACUUM CIRCUIT BREAKERS/SWITCH CONTACTOR

SMP NO. MYOW-4-PG-316

Equipment Name
Equipment Tag No
Equipment Model / S.No
Equipment Make / Manufacturer
Equipment Type
Equipment Function location
Equipment PM Frequency

PM completed Date
Doc No: MFQ-Y2-PG-
ELECTRICAL POWER
-MYOW-4- CHECK LIST GENERATION Y-2
PG-316

CHECK LIST FOR MAINTENANCE OF4.16 KV VACUUM


Date: 01.10.2015 Page 3 of 6
-CIRCUIT BREAKERS/SWITCH CONTACTOR

TITLE: CHECK LIST FOR MAINTENANCE OF 4.16 KV VACUUM -CIRCUIT


BREAKERS/SWITCH CONTACTOR

1.0 PURPOSE`

To keep Vacuum circuit breaker and Vacuum switch contactor in satisfactory


operational state by providing effective maintenance.
.

2.0 SCOPE

This procedure is applicable to Vacuum circuit breaker and vacuum switch contactor
in 4.16KV switchgears at Marafiq Yanbu II Power generation.

3.0 SAFETY PRECAUTIONS

3.1 MIRA
3.2 Lifting plan (if required)
3.3 PTW compliance
3.4 LOTO
3.5 MARAFIQ Safety Manual guidelines.
3.6 MSDS of surrounding Chemicals
3.7 Emergency safety preparedness.
3.8 Use Proper and approved PPE
3.9 Barricade the maintenance area with warning tape.

4.0 TOOLS & TESTING EQUIPMENTS

4.1 Ring spanner set


4.2 Double end spanner set
4.3 Screw driver set
4.4 Cotton cloth
4.5 Dry lint cloth
4.6 Recommended grease
4.7 Insulation resistance tester(megger)
4.8 Multimeter
Doc No: MFQ-Y2-PG-
ELECTRICAL POWER
-MYOW-4- CHECK LIST GENERATION Y-2
PG-316

CHECK LIST FOR MAINTENANCE OF4.16 KV VACUUM


Date: 01.10.2015 Page 4 of 6
-CIRCUIT BREAKERS/SWITCH CONTACTOR

5.0 PROCEDURE

Refer to Maintenance procedure MYOW-4-PG-316 before executing following activities


CHECK LIST
VACUUM - CIRCUIT BREAKER/SWITCH CONTACTOR
Panel Name : PTW No. :
Panel Tag No : Rated voltage:
SWG No : Rated current :
VCB Sl No : Date :
S.N JOB DESCRIPTION OBSERVATION REMARKS
o.
A PRIMARY CHECKS
1 Check that electrical PTW is available.
2 Ensure the breaker is isolated.
3 Note down the operating counter reading.
4 Disconnect the auxiliary supply.
5 Ensure that spring is discharge.
B CLEANING
1 Dust out the breaker from outside using clean cloth.
2 Clean the jaw contacts and breaker arm.
3 Clean the shrouds and insulators using dry clean cloth.
C OTHER CHECKS
1 Check the free movement of Manually operated Push
button.
2 Check all Post Insulators for any crack or damage.
3 Check the earthing connection of the breaker.
4 Check and apply recommended lubrication on VCB
terminal contact & Bearing articulated joints and other
moving parts.
D JAW CONTACTS
1 Check the contacts for any pitting / physical damage.
2 Check the flexibility of the contacts.
E OPERATING MECHANISM
1 Check visually complete operating mechanism.
2 Check closing and tripping mechanism sequence operate
it a few times.
3 Operate the breaker 2 times by charging the closing
spring manually. Also check for proper operation of
indicators.
Doc No: MFQ-Y2-PG-
ELECTRICAL POWER
-MYOW-4- CHECK LIST GENERATION Y-2
PG-316

CHECK LIST FOR MAINTENANCE OF4.16 KV VACUUM


Date: 01.10.2015 Page 5 of 6
-CIRCUIT BREAKERS/SWITCH CONTACTOR

4 Emergency open mechanism if provided


5 Key lock if provided
6 Locking electromagnet operation RL1
7 Auxiliary contacts operation
F ELECTRICAL TESTS
1 Measure the IR value for below conditions with 2.5KV
megger. Min value should be100 Mega Ohm
1. Each pole to body with contacts and between pole
to pole in closed conditions
2. Between Open and close poles in contact open
condition
2 Check the contact resistance.
3 Check the operation of circuit breaker by stimulation of
trip relay.
G CABLE COMPARTMENT
1 Check the cable termination and clean the compartment.
2 Check for the loose bolts and gap between panel
sections. Extra holes if any to be sealed.
3 Measure the IR values of the cables by 5KV Megger.
4 Check the CT connections for looseness.
H RELAY AND METERING COMPARTMENT
1 Check for the loose connection at connectors, relays and
meter terminals.
2 Check that all fuses are in healthy conditions & of correct
rating as per scheme drawing. If not replace.
3 Check the healthiness of indication lamps. Replace fused
lamp.
4 Dress all the cables neatly and put cable bay covers.
5 Check the all earthing connection of breaker and panel..
6 Check the condition of door gaskets.
7 Check for damage or dent on the trolley traveling path.
8 Check breaker auxiliary switch connections and 72 pin
top for any damage (pitting, bend).
9 Ensure that no tools, tackles, materials kept inside
breaker, cable, relay compartment.
10 Check the relay settings with relay setting schedule
11 After completion of the job ensure that all doors are firmly
closed with all bolts in position.
12 After completion of the job, ensure that all waste material
Doc No: MFQ-Y2-PG-
ELECTRICAL POWER
-MYOW-4- CHECK LIST GENERATION Y-2
PG-316

CHECK LIST FOR MAINTENANCE OF4.16 KV VACUUM


Date: 01.10.2015 Page 6 of 6
-CIRCUIT BREAKERS/SWITCH CONTACTOR

has been completely removed.


13 Close the permit.
PM |Done by :
Name : Date:
Signature :

6.0 RECORDS

7.1 JOB Report in SAP and History File

7.0 REFERENCES

O&M manual 52A Substation document -YT-PF-O-07-00058 Chapter


9.3.2- MV equipment