Beruflich Dokumente
Kultur Dokumente
Jignesh.Parmar ,www.electricalnotes.wordpress.com
Referance: IS 802 PART-1
Pole Detail
1st Part Height: 2.7 Meter
1st Part Diameter: 140 mm
2nd Part Height: 2.7 Meter
2nd Part Diameter: 163 mm
3rd Part Height: 5.6 Meter
3rd Part Diameter: 194 mm
Total Height of Pole: 11 Meter
Self Wieght of Pole: 241 Kg
Other Weights on Pole: 0 Kg
Safety Factor 2
Foundation Detail
Length: 0.7 Meter
Width: 0.7 Meter
Depth: 1.95 Meter
Foundation Concreate Weight: 2500 Kg/M3
Total Weight (Pole +Foundation) 2629.75 Kg
Stabilizing Moment: 920.41 Kg/Meter
Wind Load Calculation
Wind Zone: 3
Basic Wind Speed (Vb): 44 Mile/Second
Co-efficient Factor (K0) 1.375
Risk Co-efficient (K1) 1
Terrain category (K2) 1
Reference Wind Speed (Vr): 32 Mile/Second
Design wind Speed (vd): 32 Mile/Second
Design Wind Pressure (Pd): 614.4 N/m2
Design Wind Pressure (Pd): 61.44 Kg/m2
Wind Pressure on Pole
Overturning Moment due to the wind on 1st Part of the pole : 134.47 Kg/Meter
Overturning Moment due to the wind on 2nd Part of the pole : 112.76 Kg/Meter
Overturning Moment due to the wind on 3rd Part of the pole : 112.14 Kg/Meter
Total Overturning Moment on Pole due to Wind 359.36 Kg/Meter
Table 2 Risk Coefficient K1 for Different Reliability Levels and Wind Zones
Reliability Level Wind Zone-1 Wind Zone-2
1 (Up to 400KV) 1 1
2 (Above 400KV) 1.08 1.1
3 (River Crossing) 1.17 1.22
802-Part1)
Category 3
0.85