Beruflich Dokumente
Kultur Dokumente
COLLEGE OF ENGINEERING
MECHANICAL ENGINEERING DEPARTMENT
ME LABORATORY 3
NME 513-1MET
EXPERIMENT NO.1
PULL DOWN TEST
SUBMITTED BY:
YAP, DANILO JR. R.
20121107753
SUBMITTED TO:
ENGR. DIOSDADO DOCTOR
With the purpose of satisfying the growing demand of ice for food manufacturing
and other processes, ice is produced on very large quantities every year. Commercial
production of ice is made possible by large icemakers found in ice plants that can
produce up to 75 tons of ice per day. And in order to be familiar with the ice makers and
their corresponding operations, experiment in ice plant test rig test was conducted.
I. OBJECTIVES
For the pull down test, there are several objectives which are aimed to fulfill after
conducting the experiment. These objectives are:
1. To study the different parts and controls of ice plant test rig.
2. To carry out pull down test.
3. To determine the theoretical COP of the system.
4. To determine the actual COP of the system.
II. THEORY
Over the years, mechanical refrigeration was widely used in industry especially in
ice manufacturing. In order to produce artificial ice, proper equipment for refrigeration
must be used. And for experimentation, an Ice Plant Test rig may be used. The Mini-Ice
Plant Test Rig works on a simple vapour compression refrigeration cycle that uses
R134a as a primary refrigerant. The system is designed such that students can observe
and study ice formation process without any confusion. It is also useful to understand
working of vapour compression system, due to its sophisticated yet simple performance
and controls.
Based from the description of Ice Plant Test Rig, refrigeration starts as the
Compressor compresses the vapor from the evaporator. Along with the compression is
the increase of refrigerant’s temperature and pressure. The high-temperature and high-
pressure gas will then enter the condenser, where it loses its latent heat. Then the
condensed liquid will pass through the expansion valve. Within the expansion valve,
throttling process occurs and refrigerant’s temperature and pressure will be reduced.
The cooled refrigerant will enter the evaporator where it will absorb heat from the brine
solution. The brine solution acts as a secondary refrigerant that will absorb the heat that
is coming from the water in the ice cans. As the water loses its latent heat, the water will
transform into ice and refrigeration process will repeat its processes.
In ice making, a considerable amount of time and energy are required to attain
equilibrium conditions. So in order to lessen the actual time of ice formation, pull down
test is conducted. Pull down test is considered to be the initial procedure in ice making.
The process involves cooling of the secondary refrigerant which is brine. The brine’s
temperature is lowered until it reaches -4 to -5 oC. After attaining these temperatures,
ice cans will be loaded into brine tank for the ice formation.
III. APPARATUS
In performing the pull down test experiment, there are several devices or
apparatuses needed. Each apparatus is enumerated below along with its function and
specification.
It is working scale model of an ice plant that can be used to observe and study
ice formation processes. The equipment has a capacity of 25 kg ice per 24 hours. The
test rig has 4 ice cans with a capacity of 0.6 kg ice per can. Using the ice cans, ice will
be produced in batches. For every batch, 2.4 kg of ice will be formed and each batch
will be produced for every 2 hours. The electrical supply is 230 Volts, 50 Hz and
considered as 1 phase. The input power of the system is 400 Watts and the rated
current is 3 amps. The Ice Plant Test Rig is composed of different parts and each
specification is shown in Table 1 below.
Table 1. Parts and Specifications of Ice Plant Test Rig
COMPONENT SPECIFICATION
Insulation: 65 mm thick, Polyurethane foam (PUF)
Outer Body: SS304
Outer Dimensions Inner Dimensions
Brine Tank
Length=558.8 mm Length=357 mm
Width= 431.8 mm Width= 226 mm
Height=355.6 mm Height=290 mm
Brand: Stephie Gear Motors
Voltage Rating: 230 V
Stirrer Motor Ampere Rating: 4 Amps
Power Rating: 118 HP
Speed Rating: 1400 RPM
Ice Cans Number of Cans: 4
Outer Dimensions
Can Holder Length=340 mm
Width= 190 mm
Description: Hermetically Sealed
Compressor Brand: Danfoss
Voltage Rating: 220-240 V
Frequency Rating: 60 Hz
Refrigerant : R134A
Capacitor Rating
Capacitor 3 min/ 1.7 % = 220V
1 min/ 0.1% = 300V
Description: Axial Flow Type
Brand: Rexnord
Fan Motor Ampere Rating: 0.4 Amps
Frequency Rating: 220/240 Hz (50/60 Hz)
Diameter of Fan: 195 mm
Description: Forced convection air cooled
Number of Coil Turn: 15 turns
Condenser
Length per turn: 580 mm/turn
Diameter of coil: 11.05 mm
Description: Immersed (Refrigeration grade copper tube);
Direct expansion type
Evaporator Number of Coil Turn: 15 turns
Length per turn: 530 mm/turn
Diameter of coil: 10.7 mm
Liquid Line Diameter: 6.54 mm
Discharge Line Diameter:6.5 mm
Description: Capillary Tube
Number of Coil Turn: 16 turns
Expansion Device
Major Diameter: 21.35 mm
Diameter: 3.34 mm
Description: Molecular sieve type
Drier
Diameter: 6.5 mm
Switches
Main Switch
Stirrer On
Compressor On
Controls Meter
Energy Meter
Discharge Pressure Gauge
Suction Pressure Gauge
Refrigeration Temperature Meter
Primary Refrigerant R134a
Secondary Refrigerant Ethylene Glycol Solution
Energy Meter—a digital meter used for measuring power that is being supplied to
compressor in kilowatt per hour (kWh).
Suction Pressure Gauge—a device used to measure the pressure of the liquid
refrigerant before compression.
Discharge Side Pressure Gauge—a device used to measure the pressure of the liquid
refrigerant after compression.
3. Graduated Cylinder
4. Watch/ Timer
1. Place the test rig in a well ventilated area and with the level to the horizontal. There
should be at least two-meter distance on each side.
2. Supply the machine with a single phase, 230 volts and 60 Hz source. Some of the
accessories will also turn on.
3. List all the readings made by the device after switching on.
6. Check the kWh-meter reading, suction and discharge pressure gauge and record the
given readings.
8. Allow the test rig to run until it reaches the desired temperature of -4° C
9. Continue to record all the readings for every rise of the kWh-meter.
10. Using the available table for R134a, take the corresponding enthalpy for every
increase in pressure. Interpolate as possible.
A. DATA
For the pull down test experiment, time is considered important especially in the
computation that will be done later on. The start and end time are recorded as well as
the time elapsed for every change in power (as shown in Table 2).
Time of Experiment
Time Started: 5: 13 pm
Time End: 6:17 pm
Data Gathered
Table 2 shows the data gathered during the experiment that includes the time
elapsed, refrigerant temperature at different points in the cycle, compressor power,
ambient temperature, initial liquid temperature, air space temperature, suction pressure
and discharge pressure.
Table 2. Data
R-134 A
AMBIENT TEMPERATURE, °C
BRINE TEMPERATURE, °C
TEMPERATURE,
PRESSURE, psi
AIR SPACE, °C
POWER, KWh
SUCTION
DISCHARGE OF
DISCHARGE OF
COMPRESSOR
EVAPORATOR
NO.
CONDENSER
SUCTION OF
1 0 30 0 31 70 40 11 31 40 155
2 13.8 27 12 27 76 41 11 31 40 160
3 13.9 23 12 24 85 41 10 31 40 160
4 14 18 20 20 87 40 9 31 35 155
5 14.1 11 10 19 79 40 4 31 25 140
6 14.2 0 7 17 75 41 0 31 25 130
7 14.2 -4 3 12 67 35 -4 30 25 130
B. ENTHALPY VALUES
Figure 1. PH Diagram
Given the temperature and pressure in suction and discharge, enthalpy values
can be obtained using the tables and charts. In determining the values, enthalpy at
suction (h1) can be obtained from the intersection point of the saturated vapor line and
suction pressure line. On the other hand, enthalpy at discharge (h2) can be obtained
from the intersection point of the constant entropy line and discharge pressure line.
Enthalpy after condensation (h3) and expansion (h4) have the same value and this value
can be taken at the intersection of saturated liquid line and discharge pressure line.
Table 3 shows the enthalpy values at all points.
The refrigerating effect or the theoretical cooling load is the difference between
the enthalpy at suction (h1) and enthalpy after expansion (h4). The equation for
theoretical cooling load can be expressed as:
𝐐𝑨𝒕 = 𝐡𝟏 − 𝐡𝟒 , 𝐤𝐉/𝐤𝐠
The work done by the compressor is the difference between the enthalpy at
suction (h1) and the enthalpy at discharge (h2). Given enthalpy values at Table 3, work
of compression can be solved. The equation for theoretical work of compression can be
expressed as:
𝐓𝐏 = 𝐡𝟐 − 𝐡𝟏 , 𝐤𝐉/𝐤𝐠
Figure 3. Work of Compression
Table 5 shows the work of compression for every brine temperature and the
average work of compression recorded for the whole experiment.
𝐡𝟏 − 𝐡𝟒
𝐂𝐎𝐏𝐓 =
𝐡𝟐 − 𝐡𝟏
Table 6 shows the values of COPT at different brine temperature. The values
were computed using the Microsoft Excel.
Table 6. Theoretical Coefficient of Performance
REFRIGERANT
SUCTION DISCHARGE ENTHALPHY VALUES,
TEMPERATURE, THEORETICAL
PRESSURE, PRESSURE, kJ/kg
°C C.O.P.
Mpa Mpa
te tc t2 h1 h2 h3 / h4
11 40 70 0.27579 1.06869 414.46 450.82 256.39 4.35
11 41 76 0.27579 1.10316 414.46 456.6 257.85 3.72
10 41 85 0.27579 1.10316 407.07 466.13 257.85 2.53
9 40 87 0.24132 1.06869 367.15 468.73 256.39 1.09
4 40 79 0.17237 0.96527 376.15 461.82 256.41 1.40
0 41 75 0.17237 0.89632 401.79 458.62 259.41 2.51
-4 35 67 0.17237 0.89632 368.89 450.4 248.86 1.47
The Actual Refrigerating Effect of the system is the summation of all heat
available while the process is in operation. This is comprised of the Brine Product
Loads, Air Space Product Load, Transmission Load at the brine level and air Level and
Air Infiltration.
One of the sources of heat in the refrigeration system is the Brine Solution
Product Load. Product Load is defined as a primary refrigeration loads from products
brought into the system. and kept in the refrigerated space are heat that must be
removed to bring products to storage temperature (ASHRAE, 2006). Given the mass of
salt (5.5 kg), density of water (1 kg/L) and volume of the water (13 L), the total mass of
brine can be computed using the formula:
𝐌 = 𝐌𝐰𝐚𝐭𝐞𝐫 + 𝐌𝐬𝐚𝐥𝐭
𝐤𝐠
𝐌𝐰𝐚𝐭𝐞𝐫 = 𝟏 (𝟏𝟑 𝐋)
𝐋
𝐌𝐰𝐚𝐭𝐞𝐫 = 𝟏𝟑 𝐤𝐠
Solving for mass of brine:
𝐌 = 𝟏𝟑 𝐤𝐠 + 𝟓. 𝟓𝐤𝐠
𝐌 = 𝟏𝟖. 𝟓 𝐤𝐠
The salt composition is the ratio of mass of salt used to the total mass of brine.
The value of salt composition will be used in computation Specific Heat of brine solution
It is expressed as:
𝐌𝐬𝐚𝐥𝐭
% 𝐒𝐚𝐥𝐭 𝐂𝐨𝐦𝐩𝐨𝐬𝐢𝐭𝐢𝐨𝐧 = × 𝟏𝟎𝟎% (Calister & Rethswich, 2014)
𝐌
kJ kJ
𝐂𝐩𝐁𝐑𝐈𝐍𝐄 = (70.27 % × 4.185 ) + (29.73% × 0.88 )
kg°C kg°C
𝐤𝐉
𝐂𝐩𝐁𝐑𝐈𝐍𝐄 = 𝟑. 𝟐
𝐤𝐠°𝐂
Converting to W:
𝟐𝟎𝟏𝟐. 𝟖 𝐤𝐉
𝐐𝑨 𝑩𝑹𝑰𝑵𝑬 =
𝑻𝑶𝑻𝑨𝑳 𝑻𝑰𝑴𝑬 𝑬𝑳𝑨𝑷𝑺𝑬𝑫
𝟐𝟎𝟏𝟐. 𝟖 𝐤𝐉
𝐐𝑨 𝑩𝑹𝑰𝑵𝑬 =
𝟔𝟎 𝐬
𝟔𝟒𝐦𝐢𝐧 (𝟏 𝐦𝐢𝐧)
𝐐𝑨 𝑩𝑹𝑰𝑵𝑬 = 𝟎. 𝟓𝟐𝟒𝟐 𝒌𝑾
𝐐𝑨 𝑩𝑹𝑰𝑵𝑬 = 𝟓𝟐𝟒. 𝟏𝟕 𝑾
Air Space Product Load
Aside from brine solution, air space also contains product load. For computation
of cooling load for air space, same formula with the product load of brine solution was
used.
Given the inner dimensions of brine tank (shown in Table 7), the inner volume of
brine tank can be computed.
VBRINE TANK = L × W × H
To determine the volume of air space, volume of ice cans (4 L) and volume of
evaporator coils were subtracted from the volume of brine tank. Since the evaporator is
composed of 15 coil turns with a coil diameter of 1 cm and a length of 116 cm per turn;
thus the evaporator coils have a volume of:
𝜋 (1 𝑐𝑚)2
VEVAPORATOR COILS = × 116 𝑐𝑚 𝑝𝑒𝑟 𝑡𝑢𝑟𝑛 𝑥15 𝑡𝑢𝑟𝑛
4
kg
MAIR SPACE = 0.001184 (2.504L)
L
𝐌𝐀𝐈𝐑 𝐒𝐏𝐀𝐂𝐄 = 𝟎. 𝟎𝟎𝟐𝟗𝟔𝟒𝟕𝟑𝟔 𝐤𝐠
0.1044 kJ
QA AIR SPACE =
60 s
64min ( )
1 min
QA AIR SPACE = 2.72 × 10−5 kW
𝐐𝐀 𝐀𝐈𝐑 𝐒𝐏𝐀𝐂𝐄 = 𝟎. 𝟎𝟐𝟕𝟐 𝐖
Transmission Load
Transmission load is defined as the heat loss or heat gain due to a temperature
difference across a building element (Stoecker & Jones, 1982). For the brine tank,
materials used in walls are considered. Table 6 shows the materials used in brine tank
and its corresponding thickness, thermal conductivity and thermal resistance.
THERMAL THERMAL
MATERIALS THICKNESS, m CONDUCTIVITY, RESISTANCE,
W/ ( m∙℃ ) m2∙K /W
Galvanized Iron Sheet 0.0005 18 --
CRCA Stainless Steel 0.0005 16 --
Brine -- 600 --
Polyurethane Foam
Front and Back 0.098
Left and Right Side 0.0875 0.022 --
Bottom 0.036
Source: Refrigeration and Air Conditioning by Stoecker, W.F. & Jones, J.W.
For the computation of transmission load, the general procedure for calculating
heat loss or heat gain was used. The general equation that is going to apply is
expressed as:
Solving for the front and back wall of the brine tank (U1):
Figure 4. Front and Back Wall of Brine Tank
1
𝑈1 =
ΣR
1
𝑈1 =
0.0005 0.0980 0.0005 1
0.12 + 18 + 0.022 + 16 + 600
𝑾
𝑼𝟏 = 𝟎. 𝟐𝟏𝟖𝟔
𝒎𝟐 ∙ 𝑲
Solving for left and right wall of the brine tank (U2):
1
𝑈2 =
ΣR
1
𝑈2 =
0.0005 0.0875 0.0005 1
0.12 + 18 + 0.022 + 16 + 600
𝑾
𝑼𝟐 = 𝟎. 𝟐𝟒𝟒𝟏
𝒎𝟐 ∙ 𝑲
1
𝑈3 =
ΣR
1
𝑈3 =
0.0005 0.0360 0.0005 1
0.11 + 18 + 0.022 + 16 + 600
𝑾
𝑼𝟑 = 𝟎. 𝟓𝟕𝟐𝟏
𝒎𝟐 ∙ 𝑲
1
𝑈4 =
0.0005
0.044 + 16 + 0.16
𝑾
𝑼𝟒 = 𝟒. 𝟗𝟎𝟏𝟐
𝒎𝟐 ∙ 𝑲
Area
𝑨𝟑 = 𝟎. 𝟐𝟑𝟐𝟖 𝒎𝟐
𝑨𝟑 ′ = 𝟎. 𝟐𝟑𝟐𝟖 𝒎𝟐
FRONT (AIR
SOLUTION)
SPACE)
0.2186 0.183596 31 23 8 0.3211 0.2186 0.01659 31 24 7 0.0254 0.3465
0.2186 0.183596 31 18 13 0.5217 0.2186 0.01659 31 20 11 0.0399 0.5616
0.2186 0.183596 31 11 20 0.8027 0.2186 0.01659 31 19 12 0.0435 0.8462
0.2186 0.183596 31 0 31 1.2442 0.2186 0.01659 31 17 14 0.0508 1.2949
0.2186 0.183596 30 -4 34 1.3646 0.2186 0.01659 30 12 18 0.0653 1.4298
0.2186 0.183596 31 30 1 0.0401 0.2186 0.01659 31 31 0 0 0.0401
BACK (BRINE
BACK (AIR
SPACE)
0.2186 0.183596 31 23 8 0.3211 0.2186 0.01659 31 24 7 0.0254 0.3465
0.2186 0.183596 31 18 13 0.5217 0.2186 0.01659 31 20 11 0.0399 0.5616
0.2186 0.183596 31 11 20 0.8027 0.2186 0.01659 31 19 12 0.0435 0.8462
0.2186 0.183596 31 0 31 1.2442 0.2186 0.01659 31 17 14 0.0508 1.2949
0.2186 0.183596 30 -4 34 1.3646 0.2186 0.01659 30 12 18 0.0653 1.4298
0.2441 0.139772 31 30 1 0.0341 0.2441 0.01263 31 31 0 0 0.0341
RIGHT (BRINE
RIGHT(AIR
SPACE)
0.2441 0.139772 31 23 8 0.2729 0.2441 0.01263 31 24 7 0.0216 0.2945
0.2441 0.139772 31 18 13 0.4435 0.2441 0.01263 31 20 11 0.0339 0.4775
0.2441 0.139772 31 11 20 0.6824 0.2441 0.01263 31 19 12 0.037 0.7194
0.2441 0.139772 31 0 31 1.0577 0.2441 0.01263 31 17 14 0.0432 1.1008
0.2441 0.139772 30 -4 34 1.16 0.2441 0.01263 30 12 18 0.0555 1.2155
0.2441 0.139772 31 30 1 0.0341 0.2441 0.01263 31 31 0 0 0.0341
LEFT (BRINE
LEFT (AIR
SPACE)
Air Infiltration
Air infiltration is defined as the heat loss or heat gain due to the infiltration of
outside air into a conditioned space (Stoecker & Jones, 1982). The air infiltration can be
expressed as:
𝐐 𝒊 = 𝐂𝐬 𝐐𝒔 ∆𝐓 (ASHRAE 2009)
For 𝐂𝐬 :
𝑊
Cs = 1.23 𝐿 (Source: ASHRAE 2009; Chapter 18; page 18.14)
∙℃
𝑠
For 𝐐𝒔 :
(22.5)(37.8)(29.0) 1 𝑚2 1000 𝐿
𝐐𝒔 = × 2
×
3600 1 000 000 𝑐𝑚 1 𝑚2
𝐿
𝐐𝒔 = 0.00686
𝑠
Table 12 shows the computation of air infiltration for every temperature difference
using the Microsoft Excel.
Ambient Brine
CS,
Temperature, Temperature, ∆T, °C Q s, L/s Q I, W
W/(L/s∙°C)
°C °C
31 30 1 1.23 0.00686 0.0084378
31 27 4 1.23 0.00686 0.0337512
31 23 8 1.23 0.00686 0.0675024
31 18 13 1.23 0.00686 0.1096914
31 11 20 1.23 0.00686 0.168756
31 0 31 1.23 0.00686 0.2615718
30 -4 34 1.23 0.00686 0.2868852
AVERAGE SENSIBLE HEAT DUE TO INFILTRATION 0.1337994
After getting the product loads of brine solution and air space, transmission load
and air infiltration, the total heat load for the whole experiment can be determined as
shown in Table 13.
Table 13. Total Cooling Load
0.5 kWh
W=
𝑇𝑂𝑇𝐴𝐿 𝐸𝐿𝐴𝑃𝑆𝐸𝐷 𝑇𝐼𝑀𝐸
0.5 kWh
W=
1h
64 MIN. (60 MIN)
0.5 kWh
W=
1h
64 MIN. (60 MIN)
W = 0.46875 𝑘𝑊
𝐖 = 𝟒𝟔𝟖. 𝟕𝟓 𝑾
H. Actual COP
Having the total cooling load and actual work of compressor, then, the actual
Coefficient of Performance can be obtained. It can be expressed as:
632.59 𝑊
𝐶𝑂𝑃 =
468.75 𝑊
𝑪𝑶𝑷 = 𝟏. 𝟑𝟓
VI. GRAPHS
Based from the preliminary data, compressor’s power and brine temperature is
plotted (as shown in Figure 8). The graph has shown that as the power of the
compressor increases, the brine temperature decreases. Thus, the relationship between
the compressor’s power and brine temperature is inversely proportional.
14.05
14
13.95
13.9
13.85
13.8
13.75
13.7
13.65
-4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
BRINE TEMPERATURE, O C
Refrigerant Temperature
Brine Temperature, °C
After Expansion, °C
11 30
11 27
10 26
9 25
4 11
0 0
-4 -4
BRINE TEMPERATURE,
TIME, MIN
°C
0 30
12 27
24 26
44 25
54 11
61 0
64 -4
40
35
30
25
20
15
10
5
0
-4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
BRINE TEMPERATURE, OC
27
25
23
21
19
17
15
13
11
9
7
5
3
1
-1
-4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
BRINE TEMPERATURE, °C
ACTUAL REFRIGERATING
TIME ELAPSED , MINS
EFFECT, QA (W)
0.2901378 0
5.7781512 12
10.4019024 12
16.4702914 20
19.655556 10
25.1557718 7
30.6438852 3
14
12
10
8
6
4
2
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
ACTUAL REFRIGERATING EFFECT, W
Prior to the actual experiment on the ice plant test rig, familiarization of its parts
was conducted. Familiarization involves the study of function as well as the
specification of each parts. The ice plant test rig is composed primarily of the brine tank
where evaporating coils, ice cans and stirrer motor were contained; an accumulator, a
compressor, a condenser together with its fan motor, a refrigerant drier and an
expansion device. The ice plant test rig is also equipped with low pressure and high
pressure gauges, temperature indicator, and switches such as compressor switch and
stirrer motor switch.
After the familiarization of parts, pull down test was conducted. In preparation to
the experiment, brine solution was made. To create the brine solution, 5.5 kilograms of
salt was dissolved in 13 liters of water. The measurement of brine solution later
shows that the mixing ratio of the solution have reached 30% weight salt
composition—weight composition of salt needed for a saturated brine solution.
In ice making, the brine solution serves as the secondary refrigerant of the
refrigeration system. The primary refrigerant cools the brine solution. Then the cooled
brine solution will lower the water’s temperature and will eventually turn it into ice.
Right after mixing the solution, it was added to the brine tank. Then we start the
experiment by collecting the initial data such as ambient temperature, brine tank air
space temperature and the initial temperature of brine solution. The initial readings of
pressure gauges, temperature indicators and energy meter are also recorded. For every
increase of power consumption, these data are recorded accordingly.
Also, the maximum values of refrigerating effect, both actual and theoretical are
easily cooled within the lowest brine temperature. Even though the maximum values of
loads occur, still, it takes the lowest elapsed time to cool throughout the experiment.
Thus, it only shows that lowering the brine temperature greatly helps in speeding
up the ice making process.
VIII. CONCLUSION
Based from the conducted experiment, the following conclusions can be drawn:
5. Lowering the brine temperature as low as -4 oC, will help to speed up the
cooling process within the brine tank.
IX. DOCUMENTATION
Figure 20. Four Ice Cans of the Ice Plant Test Rig
Figure 21. Expansion Device of the Ice Plant Test Rig
Figure 22. Drier and Filter of the Ice Plant Test Rig
Figure 23. Pressure Control Device of the Ice Plant Test Rig
Figure 24. Schematic Diagram of the Ice Plant Test Rig
Figure 28. Discharge Pressure Gauge of the Ice Plant Test Rig
Figure 29. Suction Pressure Gauge of the Ice Plant Test Rig
(C)
Figure 31. Switches and Controls of the Ice Plant Test Rig (A) Main Switch (B)
Compressor Switch and (C) Stirrer Switch
X. REFERENCES
[1] E.G. Pita. Air Conditioning Systems and Principles 4th ed. Columbus, Ohio. Wiley
Plus. 2002.
[2] W.F. Stoecker & J.W. Jones. Refrigeration and Air Conditioning 2nd ed. Mcgraw Hill.
1983.
[3] R.F. Del Rosario. Mechanical Engineering Tables and Charts 5th ed. Manila Review
Institute Inc. 2004.