OBJECTIVE
To explore various types of three-phase connections by using three single-phase
transformers and to obtain voltage and current relationships between them.
DISCUSSION
Three phase generation and transmission is economical over single phase. It requires
the introduction of three phase transformers. A three phase system can be connected
either in Star or Delta.
The primary and secondary windings of three single-phase transformers can be
connected in different configurations to meet specific 3-phase system requirements. For
single-phase transformers with equal transformation ratio of the phase windings, the
ratio of the line voltages/currents and their phase values depends on the winding
connection. A three-phase transformer may consist of three phase windings on the
same core inside a single tank or three single-phase transformers wired externally in
WYE or DELTA. There are four ways to configure a standard three-phase transformer
bank:
DELTA-DELTA, WYE-WYE, DELTA-WYE and WYE-DELTA. The most commonly
used configuration is DELTA-WYE.
When creating a DELTA/STAR winding using single-phase transformers, great care
must be taken to ensure proper phasing and proper polarity. If a DELTA is completed
with the wrong polarity, it is possible to create a dead short between phases, resulting in
great damage to the transformer. Never close a delta transformer connection without
measuring the voltage across the open corner.
Star VP = VL ÷ √3 VL = √3 × VP IP = IL IL = IP
Delta VP = VL VL = VP IP = IL ÷ √3 IL = √3 × IP
Transformer Delta and Delta Connections
Other possible connections for three phase transformers are star-delta Yd, where the
primary winding is star-connected and the secondary is delta-connected or delta-star Dy
with a delta-connected primary and a star-connected secondary.
Delta-star connected transformers are widely used in low power distribution with the
primary windings providing a three-wire balanced load to the utility company while the
secondary windings provide the required 4th-wire neutral or earth connection.
Star-Delta Turns Ratio
Delta – Delta
Delta – Star
Star – Delta
Star – Star
Three Phase Transformer Example
The primary winding of a delta-star ( Dy ) connected 50VA transformer is supplied with
a 100 volt, 50Hz three-phase supply. If the transformer has 500 turns on the primary
and 100 turns on the secondary winding, calculate the secondary side voltages and
currents.
Given Data: transformer rating, 50VA, supply voltage, 100 V, primary turns 500,
secondary turns, 100.
Then the secondary side of the transformer supplies a line voltage, VL of about 35v
giving a phase voltage, VP of 20v at 0.834 amperes.