Sie sind auf Seite 1von 7

Correlation among ESDD, NSDD and leakage current

in distribution insulators
G. Montoya, I. Ramirez and J.I. Montoya

Abstract: The maintenance of distribution networks is more effective if the insulation


contamination levels are known. The selection of measuring methods of pollution levels is then
crucial. The relationship between several evaluation methods of pollution levels and the operating
behaviour of several insulator profiles in a polluted zone is described. Laboratory tests were carried
out to reproduce pollution levels found in the field. The quantity of non-soluble materials deposited
over the insulators’ surface affect the magnitude of the leakage current generated over a
contaminated insulator. The relationship that defines leakage current with respect to the equivalent
salt deposit density (ESDD) level for a specific non-soluble material level is almost linear, from
which it is possible to develop a relationship between them for each insulator.

1 Introduction the coast of the Gulf of Mexico Veracruz City. To measure


direct effects from storms, the bank was located 500 meters
Since 1980, investigations on improving the design of from the beach on the North coast of the port. The
overhead lines in polluted zones have been carried out in contamination level registered in this bank agrees with the
Mexico. As a result of these investigations, there are standard IEC 60815 [5] ‘very heavy’ contamination
available maps of the areas with high contamination levels, classification.
and guides for line design and insulator selection [1]. At A wind speed faster than 40 km/h registered in the Gulf
present, insulators with new profiles and materials are under of Mexico, with a duration of more than 24 hours is
evaluation in polluted areas to avoid or diminish the designated as a storm called a ‘North’. A ‘North’ generates
insulator maintenance programmes. However, a selective an abrupt change in the pollution level of the external
maintenance program is required for installed electric lines insulation in distribution networks. The ‘North’ can be
to achieve the optimum use of resources. This is why it is accompanied by rain (humid North) or it can be dry (dry
crucial to know the pollution levels in the electric network. North). Due to this, the level of pollution associated with a
There are several measuring methods to evaluate the ‘North’ is very variable.
contamination levels on external insulation. In this work, Based on reported rainfall, the months of the year with
three methods were used to evaluate the installed insulation; the heaviest pollution problems are from January to April.
superficial resistance SR [2], ESDD and leakage current During this period ‘dry North’ storms were detected
peaks measuring (LC) [3]. Simultaneously, measurement regularly accompanied by stronger wind speeds (80 km/h)
methods on non-soluble materials (non-soluble deposit and ghost winds; the breeze coming from the sea encrusted
density-NSDD) were also developed. ESDD is a globally the insulators.
used, offline method, which is used for comparison criteria Due to the capacity of the measuring systems, not all the
with other methodologies. insulation was monitored. Nevertheless, all the insulators
The preliminary comparison between the diverse range of were installed at the same time and energised to a nominal
insulators monitored was established based on field data. voltage (13 kV).
Laboratory tests have also been developed to reproduce
pollution levels found in the field, as well as to verify the 3 Comparison of the insulators used
relationship between ESDD and LC. During the observa-
tion period, meteorological factors were also measured. The insulators used in the project are the typical profiles
installed by CFE in its electric distribution network in
2 Test bank polluted areas and are shown in Fig. 1. Their can be
classified into three types: ceramic insulators with great
Field data has been obtained from the ‘Playa Norte’ test creepage distance and cover surface, semiconductor in-
bank; the bank was constructed by the Mexican utility CFE sulators and hybrid insulators.
! Federal de Electricidad) [4]. It is located in on
(Comision
3.1 Ceramic insulators with great creepage
r IEE, 2004
distance and cover surface
IEE Proceedings online no. 20040225 There are two types of ceramic insulators: 13PC and 13AC
doi:10.1049/ip-gtd:20040225 (see Fig. 1). Their main feature is that the internal surface
Paper received 23rd December 2002 and in revised form 8th October 2003 (covered surface) has a great creepage distance. These
G. Montoya and I. Ramirez are with the Instituto de Investigaciones El!ectricas, particular types of profiles are less contaminated than other
Reforma 113, Col. Palmira CP 62490, Cuernavaca, Morelos, Mexico
insulators without the covered surface. Also, it is not easy to
J.I. Montoya is with the Escuela de Ingenier!ıa y arquitectura, Tecnol!ogico de
Monterrey campus, Toluca, Eduardo Monroy C!ardenas #2000, San Antonio wet its covered surface, causing its SR to be greater than
Buenavista, CP 50110 Toluca, Edomex, Mexico other profiles, especially in the the 13AC insulator.
334 IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004
Fig. 1 Insulators used. From left to right 13PH, 13AAF, 13AAC,
13PC, 13AC, 13RG

The disadvantage of the 13PC insulator is that it has a


high LC activity, as shown in Fig. 2, which does not occur
with the 13AC insulator. On the other hand, the
disadvantage of the 13AC insulator is its poor performance
under lightning storms. This problem can be eliminated
if isolated pins are used, as in polymeric concrete
pins (PCP).

Fig. 3 13RG Insulator

similar profile of insulator will be quicker. In Veracruz City,


there is an urban circuit fitted with this type of insulator,
which has not been washed for 3 years. Other profiles must
be washed several times each year.

3.3 Hybrid insulators


The third insulator type is represented by the 13PH, shown
in (Fig. 4). It is conformed by a core of porcelain and shed

Fig. 2 PC type insulator

There are similar profiles for the 13PC insulator at 22 kv


and 33 kV, which belong to 22PC and 33PC. They have the
same problem as the 13PC insulators.

3.2 Semiconductor insulators


The 13RG insulator shown in Fig. 3 represents the second
type of insulator. The main characteristic is a graduate
resistance layer, which permits the generation of a
continuous LC over the insulator surface. The LC heats
up the surface, drying the contaminated layer, which avoids
the flashover on the insulator. This characteristic makes it
competitive with other profiles for pollution.
The 13RG insulator develops high LC levels, especially in
the period of greater contamination. It shows that the
profile of this insulator is not well adapted to the
contamination, which permits the accumulation of con-
taminants over its surface; however a natural washing of a Fig. 4 13PH insulator

IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004 335
of silicon rubber. The LC field measurements from 13PH 10,000
are lower than the measurements in the 13PC insulator. In 13PC
Veracruz City, there are two circuits with this type of 13RG
insulation, which have not been washed since for years. 13AC

resistance, Ω ( × 10 )
22PC

3
Porcelain insulators with isolated pins (polymeric con- 1,000
33PC
crete pins-PCP) can be considered in the group of hybrid
insulators. Diverse applications of PCP together with pin-
type insulators are used, such as metallic-oxide surge
arrester with polymeric concrete housing, creepage distance 100
increment and puncture distance increment (see Fig. 5). The
insulators with PCP tested in the laboratory had a smaller
LC than the 13PC insulators.
10

oc 8

ju 9
no 8
au 8

ja 8
99

99
98

99
m 9

m 9
se 98

de 8

ap 9

au 9
9

9
t9
l9

r9
9

l9
p

ay
c
n

n
n

g
b
g

ar
ju

ju
ju

fe
Fig. 6 SR minimum level

insulator humidification and its pollution level (see Fig. 6).


If the average values of the month are considered, SR
will better reflect the behaviour of the contamination
level (see Fig. 7).

10,000
resistance, Ω ( × 10 )
3

1,000

13PC
100 13RG
13AC
22PC
33PC

10
oc 8

ju 9

99
ja 8
no 8

ap 9
99

99
98

de 98
se 8
au 8

m 9

m 9

au 9
9

9
9
t9

9
9
l9

r9

l9
p

ay

g
c

ar
n

n
n

v
g

b
ju

ju
ju

fe

Fig. 5 13AAF Insulator Fig. 7 SR minimum level average

4 Measuring methods 4.2 Equivalent salt deposit density


The ESDD was another method used for measuring the
4.1 Superficial resistance contamination level. Samples were obtained for one-,
SR measuring is an online, indirect method. It is influenced three-, six- and twelve-month periods. The highest value
by the insulator’s moisture and pollution levels. In [6] and of ESDD measured matches the January 1999 sample
[7] the relationship between SR and diverse meteorological (see Fig. 8).
factors is established. The association between SR and
pollution levels is recognised by the probability of an
insulator flashover when the SR is below a specific level.
This specific level was set to 100 kO which agrees with 1.0
13PC
experimental results [8]. 13RG
The SR is measured in a dummy insulator energised 0.8 22PC
at low voltage. SR measurements are affected by insulator 33PC
surface temperature. As a result, the relationship between 13AC
SR and pollution level is modified when the insulator 0.6
2
mg/cm

surface is ‘heated’. The SR in a dummy insulator is


similar to an insulator energised with high voltage until 0.4
‘dry band’ activity begins over the insulator surface. The
dry band causes heating on the insulator surface, which
0.2
does not happen in the insulator used as ‘dummy’. Owing
to this, a low value of SR reflects only a probability
of flashover that has to be analysed with other SR records 0
nov 98 dec 98 jan 99 feb 99 mar 99 apr 99 may 99
and especially with monthly minimum average values.
Nevertheless, measurements carried out verify the Fig. 8 Month ESDD measurements

336 IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004
ESDD measuring permits the detection of the seasonal and measures the leakage peak currents in an insulator
variation model existing in the test bank. According to the energised with high voltage.
IEC 60815 standard, ESDD classifies the pollution level in All LC events were associated with the presence of storms
the zone as a ‘very heavy’ contamination. By means of this and high humidity in the environment. Table 1 shows the
method, it is possible to detect the growth of the pollution activity registered during one year.
level (Fig. 9). This is an offline method, which has a The base current is the current that circulates
disadvantage; the measurements made after rain will be continuously over the insulator surface. The base
lower because the rain has washed the insulation. current reported is the average of 100 readings carried

0.50

13 PC
0.45 13 RG
22 PC
0.40 33 PC
13 AC
0.35

0.30
2
mg /cm

0.25

0.20

0.15

0.10

0.05

0
Oct 98 Nov 98 Feb 99 Feb 99 NORTH May 99 Aug 99 Aug 99 Aug 99
2 months 2 months 3 months 6 months feb 99 3 months 3 months 6 months 12 months

Fig. 9 ESDD levels. Long sample periods

4.3 Non-soluble deposit density out during a sample period of two hours. It means
As a complement to ESDD measurements, the quantity of that during almost two hours the current average had a
non-solubles contained in the contaminated samples was similar value.
determinated. This quantity was normalised between the The LC method joins the characteristics of the previous
areas of the insulator (NSDD in mg/cm2). methods, since it takes measurements in real time and also it
is a direct method. In Mexico, the LC method has been
4.4 Leakage current used successfully for insulation diagnosis in transmission
LC measurements are carried out using the leakage current lines [3, 9].
peaks measuring system ‘SIPICO’ [3]. This system detects
Scale:

Num. of peaks o100 o3,000 o10,000 o50,000 50,000o

Table 1: Leakage current levels at the field

LC levels (mA) 900o 2,744 2,776 41

700 a 900 3,861 4,121 13


500 a 700 1,305 15,856 49
300 a 500 42,773 66,006 368
100 a 300 126,408 340,111 2,861 4,140 10
Max. Ibase (mA) 4.83 4.14 8.98 1.38 0.69
13PC 22PC 13RG 13AC 13PH
Insulation monitored

Note: 22PC insulator was removed and a 13PH insulator was installed in February 1999

IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004 337
5 Discussion of field results 6.1 Test method
Several problems were found when moistening some
During the time period of insulation exposure (from August insulator profiles, at is the case of 13AC, In the field, the
1998 to August 1999), the months with the higher insulator is humidified by condensation when the wind
contamination were January to April, 1999. During these impacts the rain drops over the insulator. It was decided to
months, all the insulators reached the minimum SR value of start under the premise that the insulator is completely wet
the scale (Fig. 6). The insulator with the lowest SR is the and for that reason, the Japanese method was followed [10].
13RG, while the insulator with highest SR was the 33PC. The purpose of this test is to find the levels of LC; the
The ‘seasonal variation’ accumulation model of the voltage was only increased until it reached the nominal
pollution level predominates over its ‘growth in time’ voltage of the insulator and not until a flashover was
accumulation model. Owing to this, by January the reached as indicated by the method. The activity of LC was
maximum contamination level registered was reached. This extinguished quickly on drying -of the insulator. For this,
result corresponds to a 13RG insulator with a sample clean fog was generated to saturate the chamber before
period of one month (1.008 of ESDD, Fig. 8). introducing the insulator. As a consequence of this
The 13PC, 22PC and 33PC insulators have high LC modification, the LC activity remains almost a minute,
(Table 1). Even when they are energised to 13 kV and are leading in some cases to insulator flashover.
far away from a flashover by contamination, LC could
cause burns on wood, crossover and poles. The 33PC 6.2 Contaminant reproduction and test
insulator flashed-over during the tests carried out in a clean development
fog chamber to nominal voltage (34.5 kV). This means that Since the 13PC insulator registered high LC activity in the
the 33PC insulator does not support higher values of LC. field, this profile was used primarily to determine the
The 13RG insulator also had a high LC level. Likewise, it mixtures of contamination to use. The first tests were
had a higher pollution accumulation reflected by a very high developed with mixtures prepared according to the IEC
level of ESDD. However, due to its easy natural washing, in 60507[11] with high ESDD levels (over 0.6 mg/cm2).
a single year it returned to minimum levels of contamina- However, it was not possible to reproduce the LC levels
tion. In fact, this insulator had the maximum registered level registered in the field. It was decided to analyse the quantity
of ESDD, as well as the minimum level of accumulation of non-solubles in the samples from the field in order to
after the annual rainy season (see Fig. 9). It is recommended determine its relationship NSDD/ESDD.
for zones with periods of high, prolonged rainfall. Based on the relationship NSDD/ESDD, the mixture
The 13AC and 13PH insulators had the best behaviour generated was 600/200. It is composed of 600 grams of
with a low LC. If a PCP is placed to the 13AC insulator its Kaolin and 200 grams of salt dissolved in one litre of water
performance improves. The arrangement of the 13A (a normalised mixture according to IEC 60507 contains
insulator and PCP with shed (13AAF) in the laboratory only 40 grams of Kaolin). This mixture complies with the
had an LC smaller than 13PH and 13AC. relationship of NSDD/ESDD with an ESDD average of
During the year of observation, there were no flashovers 0.70 mg/cm2 and a NSDD of 4.4 mg/cm2. The new tests
on installed insulators. However, they reached very high LC produced expected LC levels; the obtained LC peaks were
and ESDD values. The losses in high LC should be used as higher than 1.5 A (Table 2).
a criteria for the selection of the insulation or for The initial current level of 800 mA was considered as the
maintenance purpose decisions. maximum permitted before generating a contamination
alarm. This value will be adjusted according to field results
6 Tests in clean fog chamber and new laboratory tests.
New tests were developed to obtain two extra points for
The type of pollution and pollution level found in the field the ESDD vs. LC curve. The first mixture (600/200) was
were reproduced in the laboratory in order to verify the diluted 50% each time, but respecting the proportion of
relationship between ESDD and LC. The highest ESDD NSDD/ESDD. New mixtures were made, 300/100 and
level was selected, which was in January, with a sample 150/50. The last mixture generated an LC under 500 mA.
period of one month. All tested insulators, maintained the same relationship

Scale:

Num. of peaks r10 r50 r100 r150 150r

Table 2: Moisture 600/200

average ESDD ¼ 0.70 mg/cm2 average NSDD ¼ 4.4 mg/cm2

LC levels (mA) 41950


1650 – 1950 42
1350 – 1650 106 54 20
1050 – 1350 147 101 69 42 29
750 – 1050 153 194 162 111 133
maximum PEAK (ma) 1,674 1,440 1,362 1,183 1,110
13RG 13PC 13AC 13AAF 13AAC
Insulation evaluated

338 IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004
1800 loses its hydrophobicity. Likewise, the ESDD against LC
1600 curve of the 13PH insulator does not have the same
behaviour as the remaining insulators (see Fig. 11). While
1400
the other insulators maintain the same tendency of growth
leakage current, mA

1200 and relationship among them, the LC growth tendency of


1000 the 13PH insulators changes at higher ESDD levels,
800
diminishing its LC level.
13 PC
600 13 RG
13 AC
400 13 AAF 6.4 Correlation between ESDD, NSDD and
200 13 AAC LC
The ESDD against LC curves from the 13PC insulator is
0
M3 (150/50) M2 (300/100) M1 (600/200)
shown in Fig. 12. The mixtures with the same NSDD (150/
moisture
50, 150/100 and 150/200) form a continuous line. These
points form a linear curve. Extrapolating the other two
Fig. 10 LC levels measured in laboratory points obtained (300/100 and 600/200), it will be observed
that a curve family exists for each insulator as a function of
among of them (Fig. 10). The tested insulators were the NSDD level (150, 300 and 600).
13PC, 13RG, 13AC, 13AAF, and 13AAC (see Fig. 1). The
13PC and 13RG insulators registered the major LC level, 1600
while the 13AAF and 13AAC insulators had the smaller 1400
LC level.
1200

leakage current, mA
6.3 Tests to NSDD constant 1000
Based on previous results, it was decided to set the NSDD
level obtained in the third mixture (150/50) while the ESDD 800
level was also increased. More tests were generated with the 600
mixtures 150/100 and 150/200. With these points a graph of
ESDD vs. LC was obtained (see Fig. 11). A linear 400

relationship between these two variables can be observed. 200


The insulators used in the previous tests maintained the
0
same tendency and relationship among them. The 13PH 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
and 33PC insulators were added to the developed tests. The ESDD, mg/cm
2

33PC insulator registered an LC of great magnitude,


enough to flash-over the insulator during the test with the Fig. 12 ESDD against LC. Curves for 13PC insulator
mixtures 300/100 and 150/100. Likewise, it registered higher
peaks of up to 1.4 A, with the mixture 150/200. From the
previous data, it was deduced that this profile was less 7 Conclusions
effective than its similar 13PC. It must be remembered that
the tests were carried out to nominal voltage, for which the The SR method is an indirect form to evaluate the pollution
voltage applied to a 33PC is 34.5 kV (20.9 kV phase-to- level of an insulator. This method responds to changes in
ground), while in a 13PC it is 15 kV (8.7 kV phase-to- the humidification level and contamination over the
ground). This implies that the effectiveness of an insulator insulator surface. It is necessary to increase the applied
profile is a function of the applied voltage. voltage to the insulator, to avoid the influence of the
humidification in this method.
1400 13 PC The quantity of non-soluble material affects the LC level
13 RG generated in a contaminated insulator. The relationship that
1200 13 AC links LC to ESDD for a specific NSDD is almost linear and
13Abcf
13 ACcb consequently, it is possible to develop a relationship
leakage current, mA

1000
13 PH between them.
33 PC
800 This confirms that the leakage current method is the most
appropriate for insulation diagnosis in distribution net-
600 works.
The Japanese method was modified for the evaluation of
400
several insulator types in a fog chamber. The tests were
200
carried out with a higher level of non-soluble material than
those indicated in the IEC 60507 standard, since the
0 contaminant type found in the test bank was reproduced.
0.1 1
2
ESDD, mg/cm

Fig. 11 Comparison of several profiles monitored 8 Acknowledgments

The authors acknowledge the help of CFE staff for their


The insulator 13PH maintains a constant LC activity at contribution in the development of this project. Special
low magnitude (smaller than 100 mA) for a few minutes thanks are given to Jose del Razo-Contreras, Hector-
after reaching the maximum peak, whereas the remaining Hernandez C. and Raul Usla-Lopez. Special thanks are also
insulators did it for some seconds. This different behaviour given to Dr Carlos Romualdo-Torres for his useful
can occur if the 13PH insulator is completely wet and it comments and advice.
IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004 339
9 References 6 Montoya, G., and Tang, Y.: ‘Parameter identification of pollution
process in external insulation’. Presented at IIE 2nd Int. Electrical
1 Ramos, G., Campillo, T., Geres V. D!ıaz, R., and Vel!azquez, P.: Workshop., Cocoyoc Mor, M!exico 1993, (In Spanish)
‘Results from field experiments on ac polluted insulators in Mexico’. 7 Montoya, G.: ‘Prediction of dynamic systems. application at pollution
Proc. IEEE/KTH; Stockholm Power Tech Int. Symp. on Electric process in external insulators’. Master Thesis, DEPFI Universidad
Power Engineering, Stockholm, Sweden, 18–22 June 1995, Paper Nacional Aut!onoma de M!exico 1993, (In Spanish)
SPT HV 09-01-0003., pp. 276–281 8 Fierro, J.L., and Fierro, D.: ‘Distribution insulator performance in the
2 Astm D257-90: ‘Standard test methods for D-C resistance or laboratory with several pollution and moistening levels’. IEEE secci!on
conductance of insulating materials’ ASTM standard 1990 M!exico.,RVP-96, Tomo III. Acapulco, M!exico, 1996, (In Spanish)
3 Fierro, J.L., Ramirez, I., and Montoya, G.: ‘On-line leakage current 9 Ram!ırez, I., and Fierro, J.L.: ‘Criteria for the diagnostic of polluted
monitoring of 400 kv insulator strings in polluted areas’, IEE Proc., ceramic insulators based on the leakage current monitoring technique’.
Gener. Transm. Distrib., 1996, 143, (6), pp. 560–564 Proc. IEEE Conf. on Electrical Insulation and Dielectric Phenomena
4 Del Razo, J., Fierro, J.L., and Montoya, G.: ‘Insulators test banks (CEIDP) TX, Austin 1999, Vol. 2, p. 175
and prediction of insulators flashover risk using surface resistance 10 Fujitaka, S., Kawamura, T., Tsurumi, S., Kondo, H., Seta, T., and
measuring’. IEEE secci!on M!exico., RVP-94. Tomo III. Acapulco, Yamamoto, M. ‘Japanese method of artificial pollution test on
M!exico 1994, (In Spanish) insulators’. IEEE Trans. Power. Appar. Syst. 1968, 87, pp. 729–735
5 IEC 60815. ‘Guide for the selection of insulators in respect of polluted 11 IEC 60507. 1991-04. ‘Artificial pollution tests on high-voltage
conditions’ 1986 insulators to be used on a.c. systems’

340 IEE Proc.-Gener. Transm. Distrib., Vol. 151, No. 3, May 2004

Das könnte Ihnen auch gefallen