Sie sind auf Seite 1von 114

POWER GRID COMPANY OF BANGLADESH

LIMITED

Tender Document
for
Procurement of

Design, Supply, Erection, Testing and


Commissioning of New 132/11kV Air
Insulated Substation at Payra and extension
of 132 kV bays at existing Patuakhali
132/33kV Substation on Turnkey Basis

(Contract No. PGCB/132KV/PP/SS)

Volume 3 of 3

Issued on: May 31, 2017


Invitation for Bids No. 01/PGCB/Sec/(SSD&QC)/2017/3423
Employer: Power Grid Company of Bangladesh Limited (PGCB)
Country: Peoples Republic of Bangladesh
Funded by: Government of Bangladesh and PGCB
INDEX TO VOLUMES

Volume 1 of 3

PART I Bidding Procedures


Section 1 - Instructions to Bidders (ITB)
Section 2 - Bid Data Sheet (BDS)
Section 3 - Evaluation and Qualification Criteria (EQC)
Section 4 - Bidding Forms (BDF)
Section 5 - Eligible Countries (ELC)
PART II Requirements
Section 6 - Employer’s Requirements (ERQ)
PART III Conditions of Contract and Contract Forms
Section 7 - General Conditions of Contract (GCC)
Section 8 - Special Conditions of Contract (SCC)
Section 9 - Contract Forms (COF)

Volume 2 of 3

Scope of Work
Technical Specifications
Drawings forming Part of Specifications

Volume 3 of 3

Bid Forms
Schedule A Introduction & Preamble to the Price & Technical Schedules
Schedule B Bid Prices
Schedule C Bar Chart Programme of Key Activities
Schedule D Manufacturers, Places of Manufacture and Testing
Schedule E Technical Particulars and Guarantees
Schedule F Departure from Specifications
Schedule G Proposed Alternative Standards to which Equipment shall Provided
Schedule H Proposed Contract and Site Organization
Schedule I Drawings and Documents to be Submitted with Bid
Schedule J Proposed Subcontractors
Schedule_A: Requirements

POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation
at Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation
on Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE A

INTRODUCTION & PREAMBLE TO THE PRICE & TECHNICAL SCHEDULES

BRIEF DESCRIPTION OF THE WORKS

The bidder shall be deemed to have visited site, inspected, gathered data and verified
details of the as-built system in order to design, supply and interface their new equipment.
All necessary materials, adjustments, dismantling, remedial and tiding-up work in order to
complete the work specified shall be included in the contract price. The contractor is
responsible for ensuring that all and/or and any item(s) of work required for the
safe, efficient and satisfactory completion and functioning of the works, are
included in the Bid Price whether they be described in the specification or not.

The scope of work comprises the following: -

DESCRIPTION OF WORKS

The scope of work under this turnkey Bid is design, supply, delivery, installation, testing &
commissioning of outdoor type AIS substation. Break-up of detail scope is as follows:

A) Payra 132/11kV Substation:

New 132kV Air Insulated Switchgear (AIS) Switching station at Payra, which will comprise
the following:

Payra 132kV Switchyard, which will be double bus scheme.

Two overhead 132kV line bays to connect 230 kV double circuit lines (Patuakhali-1 & 2,
which will be temporarily charged at 132kV).

One 132kV transformer bay for one set of 132/11kV, 25/41MVA power transformer
(132/11kV power transformer to be supplied & installed by another contractor).

One bus-coupler bay to connect two 132kV buses.

The scope of work also includes associated control, protection, fibre optic multiplexer
equipment for communication & protection, substation automation, station power facilities
and associated civil works.

B) Patuakhali 132/33kV Substation:


Extension of 132 kV bays at existing 132/33kV Patuakhali Substation, which will comprise
the following:

SA-1
Schedule_A: Requirements

Bus extension at Patuakhali 132kV Switchyard, which is ‘main & transfer’ bus scheme.
Two overhead 132kV line bays to connect 230 kV double circuit lines (Payra-1 & 2), which
will be temporarily charged at 132kV.

The scope of work also includes associated control, protection, fibre optic multiplexer
equipment for communication & protection, substation automation, station power facilities
and associated civil works.

DETAIL DESCRIPTION OF WORKS

1) Payra 132/11kV Substation

The configuration of the 132kV busbar shall be ‘double’ busbar scheme.

132kV Air Insulated Switchgears (AIS):

132kV AIS switchyard for two(2) 132kV line bays in order to connect 230kV double
circuit overhead line (Patuakhali-1 & 2, which will be temporarily charged at 132kV),
one(1) bus coupler bay, one 132kV transformer bay for 132/11kV, 25/41MVA power
transformer. 132/11kV, 25/41MVA power transformer is not within this scope, that is
to be supplied & installed by another contractor.

11/0.415kV auxiliary transformer:

Two (2) sets of 11/0.415kV, 200kVA, outdoor type auxiliary transformers to supply
the substation auxiliary loads, including all necessary 11kV connections (with pole,
clamps, fittings, etc. if required) from 11kV source which is either within the
switchyard or nearly 1500m away from 132kV switchyard. These auxiliary
transformers are to be installed in the 132kV switchyard premises

Control, Protection, Substation Automation & Metering:

Associated control, metering, protection equipment, synchronizing scheme and


substation automation system for complete substation.

Fiber Optic Multiplexer Equipment for Communication and Protection:

Indoor type Fiber Optic Multiplexer and communication Equipment for protection &
communication.

DC and LVAC System:

Complete set of 110V DC & 48V DC and LVAC system with all necessary materials
required for the plant being installed with 50% spares for future use. The system
shall be comprises with a backup/standby set.

Civil Works, Building and Foundation:

Complete design, supply and construction of all civil items required for the outdoor
works suitable for switchyard gantry & equipment foundations, transformer
foundations, blast walls, oil pit, entrance & internal roads, outdoor lighting system,

SA-2
Schedule_A: Requirements

cable trenches, septic tank, surfacing, drainage, security fences, guard house,
earthing & lightning protection, switchyard lighting, etc.

Complete design, supply and construction of all civil items including all necessary
architecture & structural requirements; cable trays, fittings and flooring & finishes; air-
conditioning and lighting for a new two storied main control room building.

SCADA system for Telecontrol and Telemetering:

Complete design, supply, delivery, installation, testing & commissioning of hardware


and software to provide the telecontrol & telemetering facilities required at the
existing National Load Despatch Center(NLDC) at Rampura and Backup station at
Bidyut Bhabanfor integration of complete new 230kV switching station. All required
electrical signals shall be transmitted to the NLDC, Rampura and Backup station at
Bidyut Bhaban through the Industrial Gateway of the substation automation system.
All HV breakers, motorized disconnectors, tap changer, etc. shall be controlled form
NLDC through the Gateway of the substation automation system using IEC 60870-5-
104 protocol. All necessary modification works in the software of master station of
NLDC, Rampura and Backup station at Bidyut Bhaban are to be carried out.

2) Extension of existing 132kV Switchyard at Patuakhali 132/33kV Substation

The configuration of the existing 132kV busbar is MAIN & TRANSFER busbar
scheme.

132kV Air Insulated Switchgears (AIS):

Two overhead 132kV line bays to connect 230 kV double circuit lines (Payra-1 & 2),
which will be temporarily charged at 132kV.

Control, Protection, Substation Automation & Metering:

Associated control, metering, protection equipment and synchrocheck scheme for


extension of two 132kV bays.

Fibre Optic Multiplexer Equipment for Communication and Protection:

Extension of existing Fibre Optic Multiplexer and communication equipment for


protection & communication. The existing Fiber optic multiplexer and
communication equipment is GE (AREVA, France) made MSE 5001 type.

DC and LVAC System:

All necessary switchgears and interconnection cables required for extension of


existing system in order to facilitate service of the plant and equipment to be
supplied under this contract.

Civil Works, Building and Foundation:

Complete design, supply and construction of all civil items required for the outdoor
works suitable for switchyard gantry & equipment foundations, cable trenches, earth
filling, surfacing, drainage, outdoor lighting system, security fences, including

SA-3
Schedule_A: Requirements

earthing& lightning protection, switchyard lighting, etc. for extension of two 132kV
line bays.

SCADA system for Telecontrol and Telemetering:

Complete design, supply, delivery, installation, testing & commissioning of hardware


and software to provide the telecontrol & telemetering facilities required at the
existing National Load Despatch Center (NLDC) at Rampura for integration of two
new 132kV line bays. All required electrical signals shall be transmitted to the NLDC,
Rampura and Backup station at Bidyut Bhaban through the Remote terminal units
(RTU). All HV breakers, motorized disconnectors etc. shall be controlled form NLDC
through the Remote terminal units (RTU) using IEC 60870-5-101/104 protocol. All
necessary modification works in the software of master station of NLDC, Rampura
and Backup station at Bidyut Bhaban are to be carried out. The existing Remote
terminal unit is AREVA, France made MiCOM C264 type.

3) Mandatory Spares, Maintenance tools & test Equipment

Mandatory Spares, Maintenance tools &Test Equipment:

Supply of complete mandatory spare and spare parts of switchgear, control


equipment, protection relays, meters, maintenance tools& test equipment. The
materials shall have to be handed over to the designated store as per instruction of
the Engineer.

4) Inspection & Training

The Contract Price shall include all costs of training & inspection of Employers and
the instruction of staff on site for the following:

a) The Employer and the Project Manager or their designated representatives are
entitled to attend the factory acceptance tests, which shall be performed at the
Manufacturer's works/testing laboratories. Factory acceptance tests shall be
organized for each equipment and shall be performed for the following equipment:
circuit breaker 132 kV (one visit), disconnectors 230 & 132 kV (one visit),
instrument transformers 230 & 132 kV (one visit), surge arresters for 132 kV (one
visit), substation automation system and protection relays (one visit), and
communication equipment (one visit).

The Contractor is responsible for bearing the costs for the above mentioned
witnessing of factory acceptance tests for 2 (two) Employer's Engineers in each
visit, considering visa fees and health insurance to cover all medical costs that may
be required during the visits, return economy-class air fare, hotel charges,
travelling expenses from airport to hotel and hotel to place of testing and return,
together with a per diem allowance of USD 100 for actual working days, excluding
travelling time, for each visit and for each of the Employer's Engineers.

b) The Contractor shall provide separate training programs for PGCB Officials as
below:

SA-4
Schedule_A: Requirements

 Operation & Maintenance of HV switchgear equipment (one training


program),
 Basic & Design of substation automation system & protection
equipment (one training program).

The Contractor is responsible for bearing the costs for the above mentioned
trainings for 4 (four) Employer's Engineers in each training, considering visa fees
and health insurance to cover all medical costs that may be required during the
visits, the return air fare (economy class), hotel charges, travelling expenses from
airport to hotel and hotel to place of training and return, together with a per diem
allowance of USD 100 for minimum 10 (ten) working days, excluding travelling
time, (as per the necessary and agreed training schedule), for each training and for
each of the Employer's Engineers.

c) On-site instruction by the manufacturer’s certified trainer on operations and


maintenance of the Substation automation system at Payra for one(1) week and for
ten(10) PGCB engineers at each location.

All costs for above items are deemed to be included in the Contract price.

SA-5
Schedule_A: Requirements

SCHEDULE A

REQUIREMENTS

1) Payra 132/11kV AIS substation

The equipment to be designed, supplied, installed, tested & commissioned


as stipulated in bid specification and shown in bid drawings (volume 2 of 3):

Item Description

1A 230kV Air Insulated Switchgear (AIS)


. .
1A1 Six (06) nos. of single-phase, 2-core ( √ / ) , 40kA/1sec, 50Hz,
√ √
1050kVp BIL, inductive voltage transformers (IVT) for line circuit
(Patuakhali-1 & 2) bays.

1A2 Two (2) sets of 230kV, 2500A, 40kA/1sec, 50Hz, 1050kVp BIL, double side
break, post type, motor operated disconnectors with earthing switch, for line
circuit (Patuakhali-1 & 2) bays.

1A3 Eight (08) nos. of 230kV Post Insulators (whose foundation shall be for
230kV, 2500A, 40kA Disconnector)

1A4 One (1) lot of flexible bus conductors, insulators, fittings including all
necessary clamps and connectors required for completing 245kV busbar
and switchgear connection.

1A5 One (1) lot of steel structures for gantry and equipment supports required
for completing 245kV busbar and switchgear. (Note: Bay width (gantry
length) shall be considered 16.0 meter. Height of lower gantry (beam) shall
be considered 12.0 meter and height of upper gantry (beam) shall be
considered 17.0 meter. Tower (gantry) peak shall be considered where it is
found necessary during execution stage.)

Item Description

1B 132kV Air Insulated Switchgear (AIS)

The 132kV AIS shall comply with the particular requirements as detailed in
the Schedule of Technical Requirements included as Appendix A1 to this
section and shall comprise the following:-

1B1 Two (2) sets of 145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, single pole operated, SF6 gas circuit breakers with spring-stored
energy operating mechanism for Patuakhali-1 & 2 line circuit bays.

1B2 One (1) set of 145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, gang operated SF6 gas circuit breakers with spring-stored energy
operating mechanism for transformer bay.

SA-6
Schedule_A: Requirements

1B3 One (1) set of 145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, gang operated SF6 gas circuit breakers with spring-stored energy
operating mechanism for bus coupler circuit bay.

1B4 Nine (9) sets of 145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, double
side break, post type, motor operated disconnectors without earthing
switch, for line & transformer circuit bays.

1B5 Two (2) sets of 145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL, double side
break, post type, motor operated disconnectors without earthing switch for
bus coupler circuit bays.

1B6 Nine (09) nos. of single-phase, 4-core, single ratio, 145kV, 31.5kA/1sec,
50Hz, 650kVp BIL, post type current transformer for line & transformer
circuit bays.(1250/1-1-1A, 5P20 30VA & 1250/1A, 10VA, 0.2 class)

1B7 Six(6) nos. of single-phase, 2-core, single ratio (3000/1-1A), 145kV,


31.5kA/1sec, 50Hz, 650kVp BIL, post type current transformer for bus
coupler circuit bay.
. .
1B8 Nine (9) nos. of single-phase, 2-core ( √ / ), 31.5kA/1sec, 50Hz,
√ √
650kVp BIL, inductive voltage transformers (IVT) for line & transformer
circuit bays.
. .
1B9 Six (6) nos. of single-phase, 2-core, ( / ), 31.5kA/1sec, 50Hz,
√ √ √
650kVp BIL, inductive voltage transformers (IVT) for bus circuit bays.

1B10 Fifteen (15) nos. of 120kV rated voltage, 102kV(rms) continuous operating
voltage at 500c, 10kA nominal discharge current, 50Hz, Heavy duty station
class, gapless metal oxide type, single phase surge arresters.

1B11 One (1) lot of flexible bus conductors, insulators, fittings including all
necessary clamps and connectors required for completing 145kV busbar
and switchgear connection.

1B12 One (1) lot of steel structures for gantry and equipment supports required
for completing 145kV busbar and switchgear . (Note: Bay width (gantry
length) shall be considered 12.0 meter. Height of lower gantry (beam) shall
be considered 9.0 meter and height of upper gantry (beam) shall be
considered 12.0 meter. Tower (gantry) peak shall be considered where it is
found necessary during execution stage.)

1C Auxiliary Transformers

1C1 One set of 132/11kV, 25/41MVA power transformer, which is not within this
scope, will be supplied & installed by another contractor.

1C2 Two (2) sets 11/0.415 kV, 200kVA three phase outdoor type auxiliary
transformers (to be installed at 145kV switchyard premise) with associated

SA-7
Schedule_A: Requirements

bushing CTs, dropout fuses, and steel support structures including all
necessary connections (with poles, clamps, fittings, etc.) from 11kV source
of 132/11kV transformer which will be installed either within the 132kV
switchyard or nearly 1500m away from 132kV switchyard.

1D Control, Protection & Metering Panel and Substation Automation


System

230kV Circuits

The equipment to be designed, supplied, installed and commissioned is


shown in bid drawings are comprising of:-

1D1 Control, metering (for voltage only) and Substation Automation System for
230kV line (only disconnector and PT for each line).

145kV Circuits

The equipment to be designed, supplied, installed and commissioned is


shown in bid drawings are comprising of:-

1D2 Control, Protection, Metering & Substation Automation System including


event recording function for two (2) sets of overhead line circuits
(Patuakhali-1 & 2). Regarding protection, only over current function is
required which is to be integrated in respective BCU.

1D3 Control, Protection, Metering & Substation Automation System including


event recording function for one (01) set of 132/11 kV power transformer
circuits including transformer tap changer control. Regarding protection,
only over current function is required which is to be integrated in respective
BCU. Transformer main differential protection is to be provided by another
contractor.

1D4 Control, Protection, Metering & Substation Automation System including


event recording function for one (1) set of bus coupler circuit.

1D5 Deleted.

1D6 One (1) lot of Tariff metering panel to accommodate programmable &
recordable digital 3-phase, 4-wire import and export MWh and MVArh
meters (accuracy class 0.2) for each 230 kV line (temporarily to be charged
with 132kV) feeder & transformer feeder. For each feeder minimum two
meters (main & check). All the meters shall be integrated with SAS. The
scope of works also includes supply of software(s) of the above energy
meters for future re-configuration.

1D7 1 lot of tariff metering system for 11kV system at 132/11kV transformer (to
be installed by BCPCL either at their premise or at 132kV switchyard)

1E Deleted
1F Multicore Control & Power Cables

SA-8
Schedule_A: Requirements

One (1) lot complete set of multicore low voltage XLPE insulated power and
control cables (IEC 60502) shall be supplied, installed, glanded, terminated
and have individual cores identified to be used for connection of all
equipment supplied under the Contract. The overall substation cable
routing and core schedules shall also be provided.

1G Earthing and Lightning Protection

1G1 One(1) lot of design, supply and installation of earthing system and
lightning protection screen including connections, connectors and clamps to
suit the substation overall arrangement and provide supporting design
calculations.

1G2 One(1) sets of 3-phase portable (maintenance) earthing equipment devices


with connectors and telescopic glass fibre operating pole suitable for plant
supplied.

1H Batteries, Chargers and DC Distribution

1H1 110V substation alkaline batteries complete with chargers and distribution
switchboard to be supplied installed and commissioned to provide all DC
supplies to equipment being supplied & installed and for powering two sets
of 240V, 50Hz, 1.5kVA UPS for one (01) hour.

The system shall generally be as shown in bid drawing and shall include:

(i) Two (2) sets of 100% batteries complete, each capacity shall not be
less than 330Ah at the 5-hour rate of discharge. This capacity shall
be confirmed during execution stage with calculation submitted by
the contractor considering at least 12 nos. 230kV bays, 12 nos.
132kV bays and 3 nos. 33kV bays. The battery with higher capacity,
if required, after calculation shall be supplied within the same price.

(ii) Two (2) sets of battery chargers complete, each float charge shall
not be less than 90A rating. This capacity shall be confirmed during
execution stage with calculation submitted by the contractor. The
charger with higher capacity, if required, after calculation shall be
supplied within the same price.

(iii) One (1) lot of DC distribution board. The DC distribution board shall
be with 50% overall spare switches for future use.

(iv) Two (02) sets of online UPS 240V, 50Hz, 1.5kVA powered from
110V DC distribution board for Substation Automation System
panels.

1H2 48V DC system and distribution equipment to be supplied, installed and


commissioned in the main control building for the new fibre optic multiplexer
equipment for communication and protection. One set shall be used as
standby supply.

SA-9
Schedule_A: Requirements

The system shall generally be as shown in bid drawing and shall include:

(i) Two (2) sets of 100% batteries complete, each capacity shall not be
less than 150Ah at the 5-hour rate of discharge. This capacity shall
be confirmed during execution stage with calculation submitted by
the contractor. The battery with higher capacity, if required, after
calculation shall be supplied within the same price.

(ii) Two (2) sets of battery chargers of output 48V DC, 50A and input
voltage three phase 50Hz, 415 V AC. This capacity shall be
confirmed during execution stage with calculation submitted by the
contractor. The charger with higher capacity, if required, after
calculation shall be supplied within the same price.

(iii) One (1) lot of DC distribution board. The DC distribution board shall
be suitable to connect the new fibre optic multiplexer equipment for
communication and protection with 50% overall spare switches for
future use.

1I LVAC Distribution

1I1 One(1) lot of LVAC switchboard for substation services to be supplied,


installed and commissioned, to provide the 415/240V supplies to all
equipment being supplied under this turnkey Bid.

1I2 One(1) lot of Tariff metering panel to accommodate programmable &


recordable digital 3-phase, 4-wire import and export MWh and MVArh
meters (accuracy class 0.2) for two 11/0.415 kV station auxiliary
transformer feeder circuits. All the meters shall be integrated with SAS. For
each feeder minimum two meters (main & check).

1I3 Deleted.

1I4 One (1) set of 125A outdoor weather proof 3-phase with neutral and earth
switched socket outlet and plug,(as per IEC 309) drawer type breakers; to
be installed, cabled and connected adjacent to the auxiliary Transformer
415V side .

1J Civil Works, Building and Foundation

1J1 One(1) lot of complete design, supply and construction of all civil items
required for the outdoor works suitable for switchyard gantry & equipment
foundations, entrance & internal roads, cable trenches, septic tank,
surfacing, drainage, security fences, guard house, etc.

1J2 One(1) lot of complete design, supply and construction of all civil items and
facilities required for the single storied (20x17.5 Sq.Meter) main control
building with 1.8 meter height cable basement and single storied (4x15
Sq.Meter) Ansar Barack.

SA-10
Schedule_A: Requirements

1J3 NA

1K Lighting, Small Power, Air Conditioning and Ventilation

1K1 One(1) lot of complete design, supply, installation and commissioning of


equipment to provide lighting, LV power supply, air conditioning system,
ventilation system and emergency DC lighting for the main control building.

1K2 One(1) lot of complete set of design, supply, installation and commissioning
of equipment to provide lighting (flood light; sodium/mercury) for security,
roadway, switchyard and emergency DC lighting at strategic locations for
equipment operation and inspection.

1L Fibre Optic Multiplexer Equipment for Communication and Protection

1L1 The equipment to be supplied, installed and commissioned shall be as


shown on bid drawing. One (1) lot complete set of design, supply,
installation and commissioning of fibre optic multiplexer equipment
including necessary works to interface with existing system is to be
provided for:

- 87 or 21 relay for each transmission line protection (through fibre


cores)
- 21 relay carrier signal (main and back-up)
- SCADA data from switchgear and control system
- Hot-line telephone system

1L2 Underground optical fibre cables (48 cores for 132kV switchyard) from
terminal box gantry structure at each 230kV double circuit transmission line
termination point to MDF (Main distribution Frame) to be installed in control
room. The Contract includes supply and installation of MDF and pigtail
cables with adequate length.

1M SCADA system for Telecontrol and Telemetering

1M1 One(1) lot of complete design, supply, delivery, installation, testing &
commissioning of hardware and software to provide the telecontrol &
telemetering facilities required at the existing National Load Despatch
Center(NLDC) at Rampura and Backup station at Bidyut Bhaban for
integration of complete new Payra 132/11kV substation. All required
electrical signals shall be transmitted to the NLDC at Rampura and Backup
station at Bidyut Bhaban through the Industrial Gateway of the substation
automation system. All HV breakers, motorized disconnectors, tap changer,
etc. shall be controlled form NLDC through the Gateway of the substation
automation system using IEC 60870-5-104 protocol. All necessary
modification works in the software of master station and backup station of
NLDC and Backup station at Bidyut Bhaban are to be carried out.

2) Extension of 132kV AIS bays at Existing Patuakhali 132/33kV Substation

The equipment to be designed, supplied, installed, tested & commissioned


as stipulated in bid specification and shown in bid drawings (volume 2 of 3):

SA-11
Schedule_A: Requirements

Item Description

2A 145kV Air Insulated Switchgear (AIS)

The 145kV AIS shall comply with the particular requirements as detailed in
the Schedule of Technical Requirements included as Appendix A1 to this
section and shall comprise the following:-

2A1 Two (2) sets of 145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, single pole operated, SF6 gas circuit breakers with spring-stored
energy operating mechanism (for line bay).

2A2 Deleted

2A3 Deleted

2A4 Two (2) sets of 145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, double side
break, post type, motor operated disconnectors with manual earthing switch
for line circuit bays.

2A5 Four (4) sets of 145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, double
side break, post type, motor operated disconnectors without earthing switch.

2A6 Deleted

2A7 Deleted

2A8 Six (06) nos. of single-phase, 4-core, single ratio, 145kV, 31.5kA/1sec, 50Hz,
650kVp BIL, post type current transformer (1250/1-1-1-1A) for line circuit
bays.

2A9 Deleted
. .
2A10 Six (6) nos. of single-phase, 2-core ( − kV) , 145kV, 31.5kA/1sec ,
√ √ √
50Hz, 650kVp BIL, Inductive voltage transformers (IVT) for line circuit bays.

2A11 Deleted

2A12 Six (6) nos. of 120kV rated voltage, 102kV(rms) continuous operating
voltage at 500C, 10kA nominal discharge current, 50Hz, Heavy duty station
class, gapless metal oxide type, single phase surge arresters.

2A13 One(1) lot of flexible bus conductors, insulators, fittings including all
necessary clamps and connectors required for extending 145kV busbar and
completing switchgear connection as specified in the technical
specifications and bid drawings.

2A14 One(1) lot of steel structures for gantry and equipment supports required for
extending 145kV busbar and completing switchgear connection as
specified in the technical specifications and bid drawings. (Note: Bay width

SA-12
Schedule_A: Requirements

(gantry length), height of lower gantry (beam) and height of upper gantry
(beam) shall be considered as existing. Tower (gantry) peak shall be
considered where it is found necessary during execution stage.)

2A15 Deleted

2B Deleted

2C Deleted

2D Control, Protection & Metering Panel

132 kV Circuits
The equipment to be designed, supplied, installed and commissioned is
shown in bid drawings are comprising of :-

2D1 Control, Protection, Metering panel for two (2) sets of overhead line circuit
bays (Payra-1 & 2). Regarding protection, main 1, distance and backup
over current protection are to be integrated in respective BCU.

2D2 Deleted

2D3 Deleted

2D4 Deleted

2D5 One (1) lot of Tariff metering panel to accommodate programmable &
recordable digital 3-phase, 4-wire import and export MWh and MVArh
meters (accuracy class 0.2) for each 132 kV line .For each feeder minimum
two meters (main & check). The scope of works also includes supply of
software(s) of the above energy meters for future re-configuration.

2D6 Deleted

2D7 Deleted

2E Deleted

2F Multicore Cables

2F1 One(1) lot complete set of multicore low voltage XLPE insulated power and
control cables (IEC 60502) shall be supplied, installed, glanded, terminated
and have individual cores identified to be used for connection of all
equipment supplied under the Contract. The overall cable routing and core
schedules shall also be provided.

2G Earthing and Lightning Protection

2G1 One(1) lot of design, supply and installation for extension of existing
earthing system and lightning protection screen including connections,

SA-13
Schedule_A: Requirements

connectors and clamps, to suit the substation overall arrangement and


provide supporting design calculations.

2G2 Deleted

2H DC Distribution

2H1 One (1) lot of all necessary switchgears and interconnection cables
required for extension of existing 110V DC system to provide service of the
plant and equipment to be supplied under this contract.

2H2 One (1) lot of all necessary switchgears and interconnection cables
required for extension of existing 48V DC system to provide service of the
plant and equipment to be supplied under this contract.

2I LVAC Distribution

2I1 One(1) lot of all necessary switchgears and interconnection cables required
for extension of existing LVAC switchboard for substation services to be
supplied, installed and commissioned, to provide the 415/240V supplies to
all equipment being supplied under this turnkey Bid.

2J Civil Works, Building and Foundation

2J1 One(1) lot of complete design, supply and construction of all civil items
required for the outdoor works suitable for switchyard gantry & equipment
foundations, internal roads, cable trenches, surfacing, drainage, fences,
etc. to accommodate extension of two 132kV line bays at new location.

2J2 Deleted.

2K Lighting, Small Power, Air Conditioning and Ventilation

2k1 Extension of existing lighting system to provide lighting (flood light;


sodium/mercury) for security, roadway, switchyard for two bays and
emergency DC lighting at strategic locations for equipment operation and
inspection required for all equipment being supplied under this turnkey Bid.

2L Fibre Optic Multiplexer Equipment for Communication and Protection

2L1 The equipment to be supplied, installed and commissioned shall be as


shown on bid drawing. One (1) lot complete set of design, supply,
installation and commissioning for extension of existing fibre optic
multiplexer equipment including necessary works to be provided for:

- 87 or 21 relay for each transmission line protection (through fibre cores)


- 21 relay carrier signal (main and back-up)
- SCADA data from switchgear and control system
- Hot-line telephone system

SA-14
Schedule_A: Requirements

The existing fibre optic multiplexer equipment is GE (AREVA France) make


MSE5001 type.

2L2 Underground optical fibre cables (48 cores for 132kV switchyard) from
terminal box gantry structure at each 132kV double circuit transmission line
termination point to MDF (Main distribution Frame) installed in control room.
The Contract includes supply and installation pigtail cables with adequate
length.

2M SCADA system for Telecontrol and Telemetering

2M1 One(1) lot of complete design, supply, delivery, installation, testing &
commissioning of hardware and software to provide the telecontrol &
telemetering facilities required at the existing National Load Despatch
Center (NLDC) at Rampura and Backup station at Bidyut Bhaban for
integration of new two 132kV overhead line bays (for two 230kV line circuits
to be charged at 132kV) to Patuakhali substation. All HV breakers,
motorized disconnectors, tap changer, etc. shall be controlled form NLDC
and Backup station at Bidyut Bhaban through the Gateway of the
substation automation system using IEC 60870-5-101/104 protocol. All
necessary modification works in the software of master station and backup
station of NLDC and Backup station at Bidyut Bhaban are to be carried out.

3) Mandatory Spares, Erection & Test Equipment

Supply of complete spares and spare parts of switchgear, control


equipment, protection relays, meters, erection & test equipment as per
quantity mentioned in Schedule B. Test equipment are to be supplied from
Europe, USA or Japan origin. Printed catalogue, operation and service
manual are to be provided. The materials shall have to be handed over to
the designated store as per instruction of the Engineer.

SA-15
Schedule_A: Requirements

APPENDIX- A1

SCHEDULE OF TECHNICAL REQUIREMENTS OF


230kV & 132kVAIR INSULATED SWITCHGEAR (AIS)

Sl. No. Description Unit 132kV 230kV


1. Site Condition
Max. Altitude above sea level m not more than 1000
Max. Ambient temperature ℃ +45
outdoor
Min. Ambient temperature ℃ +4
outdoor
Max. Ambient relative humidity % 100
Max. Seismic acceleration at
floor level
- horizontal g 0.2
- vertical g 0.2
2. Electrical Data
Rated Voltage kV 145 245
Rated Frequency Hz 50 50
Insulation Level
- lightning impulse withstand kVp 650 1050
- switching impulse withstand kVp — —
- 50 Hz withstand 1 minute kV 275 460
Rated continuous current at
40℃ambient temperature
- main busbar and bus A 3000 2500
coupler
- transformer bay A 1250 2500
- line bay A 1250 2500
Rated short time withstand
- current kA 31.5 40
- duration Sec 1 1
Rated peak withstand current kA 80 100
3. Secondary Circuit
Auxiliary voltage

SA-16
Schedule_A: Requirements

- for control and signal V dc 110


- for remote control V dc 110
- for heating V ac 415/240
- tolerances % -15/+10

4. Circuit Breakers

4.1 245kV Class Circuit Breakers (NOT APPLICABLE)

4.2 145kV Class Circuit Breakers

1 Type Outdoor,
SF6 insulated, live tank
type
2 Standard IEC 62271-100
3 Rated voltage 145 kV
4 Rated short-duration power frequency withstand voltage (1
min.)
- Between line terminal and ground 275 kV rms
- Between terminals with CB open 275 kV rms
- Between terminals with isolator open 315 kV rms
5 Rated lightning impulse withstand voltage
- Between line terminal and ground 650 kV peak
- Between terminals with CB open 650 kV peak
- Between terminals with isolator open 750 kV peak
6 First pole to clear factor 1.5
7 Rated current
- Bus coupler 3000 A
- Transformer bay 1250 A
- Line bay 1250 A
8 Rated short circuit breaking current 31.5 kA rms
9 Rated short circuit making current 80 kA peak
10 Short time withstand current for 1 sec. 31.5 kA rms
11 Max. radio interference voltage for frequency between 500 micro V
0.5MHz and 2MHz in all positions (at 92 kV rms)
12 Total closing time Not more than 150 ms
13 Total breaking time 65 ms
14 Operating mechanism Spring

15 Rated duty cycle O-0.3s-CO-3min-CO


16 Reclosing Single phase (if
applicable) & Three

SA-17
Schedule_A: Requirements

phase auto-reclosing

17 Creepage distance 25 mm/kV


18 Number of closing coils 1
19 Number of tripping coils 2
20 Number of auxiliary contacts for:
- Making Min. 12
- Breaking Min. 12
- Middle position 0
21 Protection class IP55

SA-18
Schedule_A: Requirements

5. Disconnector Switches/Isolators

5.1 245kV Disconnector Switches/Isolators and Earthing Switch

1 Type Outdoor, double side air break,


motor-operated, post type
2 Standard IEC 62271-102
3 Rated voltage 245 kV
4 Rated short-duration power frequency withstand
voltage (1 min.) 460 kV rms
- To earth 530 kV rms
- Across isolating distance
5 Rated lightning impulse withstand voltage
- To earth 1050 kV peak
- Across isolating distance 1200 kV peak
6 Rated normal current

- Line bay 2500 A


7 Rated short circuit current (Ith), 1s 40 kA rms
8 Rated short circuit current (Idyn) 100 kA peak
9 Creepage distance of insulator 25 mm/kV
10 Operating mechanism of isolator / earthing switch AC motor operated
11 Number of auxiliary contacts for main switch
- Making Min. 16
- Breaking Min. 16
- Middle position Min. 1
12 Number of auxiliary contacts for earthing switch
- Making Min. 10
- Breaking Min. 10
- Middle position Min. 1
13 Radio interference level for 0.5 MHz to 2 MHz 1000 micro V
(at 156 kV rms)

5.2 145kV Class Isolators and Earthing Switch


1 Type Outdoor,
Double side break
2 Standard IEC 62271-102
3 Rated voltage 145 kV
4 Rated short-duration power frequency withstand voltage (1
min.)
- To earth 275 kV rms
- Across isolating distance 315 kV rms
5 Rated lightning impulse withstand voltage
- To earth 650 kV peak

SA-1
Schedule_A: Requirements

- Across isolating distance 750 kV peak

6 Rated normal current


- Bus coupler 3000 A
- Transformer bay 1250 A
- Line bay 1250 A
7 Rated short circuit current (Ith), 1s 31.5 kA rms
8 Rated short circuit current (Idyn) 80 kA peak
9 Creepage distance of insulator 25 mm/kV
10 Operating mechanism of isolator AC motor operated
earthing switch manual operated
11 Number of auxiliary contacts for main switch
- Making Min. 12
- Breaking Min. 12
- Middle position Min. 1
12 Number of auxiliary contacts for earthing switch
- Making Min. 10
- Breaking Min. 10
- Middle position Min. 1
13 Radio interference level for 0.5 MHz to 2 MHz 500 micro V
(at 92 kV rms)

6. Instrument Transformers

6.1 Instrument Transformers


145kV 230kV
1 Rated lightning impulse withstand 650kVp 1050 kVp
voltage

2 Rated switching impulse withstand -


-
voltage
Power frequency withstand voltage 275kVrms 460 kVrms
3
(1 min.)
4 Corona extinction voltage 156 kVrms
-

5 Radio interference level for 0.5 MHz 1000 micro V 1000 micro V
to 2 MHz (at 92 kVrms)
6 Partial discharge level 10 pC (at 156 kVrms)
7 Type of insulation Class A 10 pC

6.2 245kV Class Current Transformers (NOT APPLICABLE)

6.3 245kV Class Voltage Transformer (IVT)


1 Rated voltage levels 245 kV
2 High frequency capacitance for entire Within 80% to 150% of rated capacitance
carrier frequency range

SA-2
Schedule_A: Requirements

3 Rated Voltage Factor 1.2 continuous; 1.5 for 30 seconds


4 Rated total capacitance(pF) NA
5 Phase angle error (minutes) 20
6 Acceptable limit of variation of total NA
capacitance over the entire carrier
frequency range
7 Equivalent series resistance over the NA
entire carrier frequency range or
temperature range (ohms)
8 Stray capacitance and stray NA
conductance of low voltage terminal
over the entire capacitance.
9 Standard reference range of frequencies 97% to 103% for protection
for which the accuracies are valid 99% to 101% for metering
10 Core details Core-I : Core-II : Core-III :

11 Purpose Protection Metering Protection

12 Secondary Voltage 110/√3 110/√3 NA

13 Burden (VA) 10 10 NA

14 Class of accuracy 3P 0.2 NA

15 Rated total thermal burden(VA) 150 150 NA

16 One minute power frequency 4(10 if the low voltage terminal is


withstand voltage between LV terminal exposed)
and earth(kV rms)
17 Withstand voltage for secondary 2
winding (kV rms)

6.4 145kV Class Current Transformers (for bus coupler bay)


1 Core No. I II
2 Ratio 3000/1 3000/1
3 Purpose Protection Measuring
4 Class of accuracy 5P20 0.2
5 Burden(VA) 30 10
6 Min. knee point voltage at 600 and over 600 and over
lowest ratio(Volts)
7 Max. magnetising M.R M.R
current guaranteed at
knee point voltage & the
lowest ratio(mA)
8 Max. resistance of M.R M.R

SA-3
Schedule_A: Requirements

secondary winding at
75 0C and at lowest ratio
(ohms)

6.5 145kV Class Current Transformers (for line & transformer bay)
1 No. of Cores 4
2 Ratio 1250/1-1-1-1A;

3 Class of accuracy - Busbar Protection : 5P20


- Protection : 5P20
- Metering : Class 0.2
4 Burden(VA) 30VA for protection core, 10VA
for metering core
5 Min. knee point voltage at lowest ratio(Volts) 600 and over
6 Max. magnetizingcurrent guaranteed at M.R
knee point voltage & the lowest ratio(mA)
7 Max. resistance of secondary winding at M.R
75 0C and at lowest ratio (ohms)

6.6 145kV Class Voltage Transformer (IVT)


1 Rated voltage levels 145 kV
2 High frequency capacitance for entire NA
carrier frequency range
3 Rated Voltage Factor 1.2 continuous;1.5 for 30 seconds
4 Rated total capacitance(pF) NA
5 Phase angle error (minutes) 20
6 Acceptable limit of variation of total NA
capacitance over the entire carrier
frequency range
7 Equivalent series resistance over the NA
entire carrier frequency range or
temperature range (ohms)
8 Stray capacitance and stray NA
conductance of low voltage terminal
over the entire capacitance.
9 Core details Core-I : Core-II :
10 Purpose Protection Metering
11 Secondary Voltage 110/√3 110/√3
12 Burden (VA) 10 10
13 Class of accuracy 3P 0.2
14 Rated total thermal burden(VA) 200 200
15 One minute power frequency 4(10 if the low voltage terminal is
withstand voltage between LV terminal exposed)
and earth(kV rms)

SA-4
Schedule_A: Requirements

16 Withstand voltage for secondary 2


winding (kV rms)

7 Surge Arresters
1 Max. highest system voltage 145kV 230kV
(NOT
APPLICABLE)
2 Type Outdoor type, ZnO, Gapless
3 Standard IEC 60099-4
4 Rated voltage 120kV 196kV
5 Max. continuous operating 102kVrms 162kV
voltage
6 Nominal discharge current 10kA 10kA
7 Discharge class Heavy Heavy
duty 3 duty 3
8 Surge counter Yes Yes
9 Leakage current detector Yes Yes

APPENDIX- A2.1

NOT APPLICABLE

APPENDIX- A3

SCHEDULE OF TECHNICAL REQUIREMENTS OF


11/0.415 kV AUXILIARY (STATION SERVICE) TRANSFORMER

SL. No. Description

AUXILIARY TRANSFORMER
1. Nominal rating kVA 200
2. Number of phase 3
3. Frequency Hz 50
4. No-load voltage ratio kV 11/0.415
5. Corresponding highest system voltage kV 12/1.1
6. Type of cooling ONAN
7. Coolant Mineral Oil
8. Type Core, Conservator Type
9. Installation Outdoor, Tropical and high rainfall and
humidity
10. Earthing Neutral solidly earthed in interconnected star
winding
Neutral earthed in LT, 3 phase, 4 wire
system
11. Windings Double wound of high conductivity
copper

SA-5
Schedule_A: Requirements

12. Test voltage


Impulse test voltage (1.2/50 ㎲) kV 75/10 (HT/LT)
Power frequency withstand voltage kV 28/2.5 (HT/LT)
for 1 min
13. Vector group Dyn11
14. Neutral to be brought out HT: NA, LT: Yes
15. Neutral insulation Full insulation and 100% loading
capacity
16. LT bushing 4 nos.
17. Impedance voltage % 5
18. Tapping range Off load tap changer
±5% in the step of 2.5
19. Tap changer control Manual

APPENDIX- A4

SCHEDULE OF TECHNICAL REQUIREMENTS OF

NI-CAD BATTERY

SL. No. Description


1. Installation : Indoor
2. Cell type : Ni-cd
3. Voltage (Normal) : 1.2 volts per cell
4. Float voltage : 1.40-1.42 volt/cell
5. Equalizing voltage : 1.55 - 1.65 volt/cell
6. Capacity in AH at 20°C :330AH@ 5Hr (for 110 V DC)
: 150 AH @ 5Hr (for 48V DC)
7. Ambient temperature : 45°C
8. Positive plate : Tubular
9. Negative plate : Pasted
10. Type of container : Plastic polymer
11. Discharge voltage : 1.0 V/Cell
12. Sp. gravity of electrolyte : 1.19 ± 1%
13. Sp. gravity of electrolyte (Charged) : 1.23 ± .010 at 20°C
14. Vent plug : Anti-corrosive & fire proof
15. Cell condition : Pre-charged.
16. Battery stand : Steel frame of step type
17. Standard : IEC or equivalent

SA-6
Schedule_A: Requirements

APPENDIX- A5

SCHEDULE OF TECHNICAL REQUIREMENTS OF


110V BATTERY CHARGER

SL. No. Description

A) GENERAL

1. Installation :Indoor
2. Rectifier type :Thyristor controlled.
3. Rated D.C. voltage :110V ±5%
4. Rated output current :90 Amps
5. Charging mode : Both constant current & constant voltage
6. High Voltage Insulation : 1000 V AC for 1 minute between
input to output and input to ground
7. Insulation resistance :10 M with 500V DC for 1minute
8. Cooling system :Self & natural air cooled.
9. Relative humidity :Upto 98%
10. Ambient temperature :45°C (max.)
11. Noise level :65 dB (max)
12. Altitude : 1000 m
13. Applicable Standard :IEC or equivalent.

B) TECHNICAL DATA

A.C. INPUT

1. Voltage :415 Volts


2. Phase :3 Phase
3. Frequency :50±5% Hz
4. Input AC voltage variation :±5%
5. Power factor (Full range) : 0.8
6. Efficiency (Full load) :85%
7. Charge Characteristics : Constant current /Constant voltage(During
float charge)
8. Current limitation :110%

D.C. OUTPUT

1. Voltage :110±5% volt


2. Ripple Voltage (Full load) :±3%
3. Charge modes (3 level) :Charge, Float charge& Boost charge
4. Float Voltage (adjustable) :1.42volt/cell
5. Boost Voltage (adjustable) :1.53 volt/cell

SA-7
Schedule_A: Requirements

APPENDIX- A6

SCHEDULE OF TECHNICAL REQUIREMENTS OF


48 V BATTERY CHARGERS

SL. No. Description

A) GENERAL

1. Installation :Indoor
2. Rectifier type :Thyristor controlled.
3. Rated D.C. voltage :48V ±5%
4. Rated output current :50 Amps
5. Charging mode :Both constant current & constant voltage
6. High Voltage Insulation : 1000 V AC for 1 minute between
input to output and input to ground
7. Insulation resistance :10 M with 500V DC for 1minute
8. Cooling system :Self & natural air cooled.
9. Relative humidity :Upto 98%
10. Ambient temperature :45°C (max.)
11. Noise level :65 dB (max)
12. Altitude :1000 m
13. Applicable Standard :IEC or equivalent.

B) TECHNICAL DATA

A.C. INPUT

1. Voltage :415 Volts


2. Phase :3 Phase
3. Frequency :50±5% Hz
4. Input AC voltage variation :±5%
5. Power factor (Full range) :0.8
6. Efficiency (Full load) :85%
7. Charge Characteristics : Constant current /Constant voltage (During
float charge)
8. Current limitation :110%

D.C. OUTPUT

1. Voltage :48±5% volt


2. Ripple Voltage (Full load) :±3%
3. Charge modes (3 level) :Charge, Float charge& Boost charge.
4. Float Voltage (adjustable) :1.42 volt/cell
5. Boost Voltage (adjustable) :1.53 volt/cell

SA-8
Schedule_A: Requirements

APPENDIX- A7

SCHEDULE OF TECHNICAL REQUIREMENTS OF


SUBSTATION AUTOMATION SYSTEM

1. General Requirement:
Standards to be complied with Substation Automation system
Test Ca. Damp heat steady state IEC 60068-2-3
Test Db and guidance; Damp heat cyclic IEC 60068-2-30
Digital I/O, Analogue I/O dielectric Tests IEC 60870-3 class
Digital I/O, Surge withstand test 2
Radio interference test IEC 60801-5/Class
2
Transient fast burst test
IEC 60870-3/Calss
Static Discharge
2
Electromagnetic fields
IEC 60801-4/4
IEC 60801-2/4
IEC 60801-3-3
Temperature range (min/max) ℃ 0/50
Relative humidity % 93
Intelligent Electronic Devices (IED’s)
- serial communication interface included? Yes
- Protection & Control IED’s connected same bus? Yes
- self monitoring Yes
- display of measured values Yes
- remote parameterization Yes
- disturbance record upload and analysis Yes
Availability Calculation shall be furnished for each
equipments as well as for the entire system Yes
The main part of the system, HMI, Gateway,IED Yes
shall be furnished with dual communication port
against any failure.

SNTP server shall provide GPS time-sync Yes


information to all communication (HMI, Gateway,
IED) and the system shall be synchronized.
Ethernet switch shall have dual system topology Yes
not to lose entire system with single swithing
system failure.
2. Detailed Requirements:
Number of years of proven field experience of 5 Yrs.
offered system.
(Note: proof of experience should be furnished.
The
components used in the offered system and those

SA-9
Schedule_A: Requirements

with 20 Yrs
field experience should be the same) ISO 9001/9002 or
Design life of substation Automation System equivalent
Manufacturers quality assurance system
Dimensions of cubicle mm
- Width mm
- Depth mm
- Height N/m2 max.600
Floor load
3. Station Level Equipment:
Station Controller Industrial PC
MTBF (Mean time between Failures) Hrs
MTTR (Mean time to repair) Hrs
Station computer shall have dual connection to Yes
Ethernet switch as redundant (hot, standby)
Hot standby take over time Seconds
Dual Wide Monitor each HMI (over 25”) Yes
Single wide screen Yes
Annunciator for Station PC system software 16 Windows
Number of years of proven field experience of 5 Yrs
offered software

Operating System Windows


All standard picture as per spec included in HMI Yes
Process Status Display & Command Procedures Yes
Event processing as per spec Yes
Alarm processing as per spec Yes
Reports as per spec Yes
Trend Display as per spec Yes
Graphical fault information receiving function Yes
Disturbance & Fault recording and analysis with Yes
graphical format
User Authority levels as per spec Yes
System supervision & monitoring as per spec Yes
Automatic sequence control as per spec Yes
4. Gateway to National Load dispatch Center
Number of years of proven filed experience of 5Yrs
offered unit
Insulation tests IEC 60255-5
Fast disturbance tests IEC 61000-4-4,Calss 4
Industrial environment EN 50081-2 Class A
Industrial grade hardware with no moving parts Yes
(PC based gateway is not accepted)
Design life of offered equipment 20 Yrs
Redundant communication channel Yes

SA-10
Schedule_A: Requirements

Redundant CPU Yes


Redundant DC/DC Supply Yes
MTBF (Mean time between Failures) Hrs
MTTR (Mean time to repair) Hrs
Gateway shall have dual connection to ethernet Yes
switch(hot and standby)
5. Station Bus:
Physical Meduim Glass fibre optic
Each communication devices shall have dual Yes
connection, hot and standby.
6. Interbay Bus
Physical Meduim Glass fibre optic
7. Printer server
MTBF Hrs
8. Event Printer
MTBF Hrs
9. Hard Copy colour Printer
MTBF Hrs
10. Master Clock – GPS (Global Positioning System) Receiver:
MTBF Hrs
11. Bay control Unit – HV(230 & 132kV)
Number of years of proven field experience of 5 Yrs
offered unit
Separate Bay controller unit provided for each bay Yes
& feeder
Type of bay controller offered HV/MV
HV
Select Before Operate with Open Execute & Close
Yes
Execute
Single bit dependence
No
Interlocking, bay & Station wide
Yes
Synchrocheck function
- Maximum Voltage difference
Specify range
- Maximum Frequency difference
Specify range
- Maximum Phase difference
Specify range
Double command blocking
Yes
Independent settable parameter groups
4
Local Display Unit
Yes
Sequence of event recorder
- Events
256
- Time resolution
1 ms
Disturbance recording file transfer function
Yes
Comtrade file generation function of Distrubance
Recorder Yes
IED shall have dual connection to Ethernet switch
(hot & standby) Yes

SA-11
Schedule_A: Requirements

Comprehensive self-supervision
Battery free backup of events and disturbance Yes
records Yes
Insulation tests
Fast disturbance tests IEC 60255-5
MTBF IEC 61000-4-4, Class 4
MTTR Hrs
Temperature range: IED’s Hrs
- Operation
- Transport and storage ℃ -10 to +50
Relative humidity: ℃ -10 to +50
- Operating max./min
- Transport and storage
% 93
% 93
12. Back up control mimic – HV(230 & 132kV)
Control functionality:
Control of breaker as well as all isolators/earthing
switch
(Control functionality should not be affected if bay Yes
controller fails)
Key-Locked Yes
Interlock override function Yes
Separate backup control mimic provided for each Yes
bay
& feeder
13. System Performance:
Exchange of display (First reaction) <1s
Presentation of a binary change in the process < 0.5 s
display
Presentation of an analogue change in the process <1s
display
From order to process output < 0.5 s
From order to updated of display < 1.5 s

SA-12
Schedule_A: Requirements

APPENDIX- A8

SCHEDULE OF TECHNICAL REQUIREMENTS OF


FIBRE OPTIC MULTIPLEXER EQUIPMENT

UNIT REQUIRED
SL.No. DESCRIPTION
GENERAL:
1.0
1.1 Type of multiplexer SDH: ADM
1.2 Complying to ITU-T rec. Yes
1.3 Transmission Capacity Mbit/s STM-4: 620
1.4 Access capacity on 64 kbit/s channels Minimum 200
1.5 Access capacity on 2 Mbit/s channels Minimum 40
1.6 Redundant central processor Shall be available
1.7 Digital cross connect function Fully non-blocking
2.0 Available AGGREGATES:
2.1 Optical aggregates (ITU-T G.957) L-1.1, L-1.2
3.0 Available TRUNK INTERFACES:
3.1 HDB3, 2 Mbit/s interfaces per module No. Minimum 8
3.2 Complying to ITU-T rec. G.703, transparent
G.704, selectable
3.3 HDSL, 2Mbit/s interface: no of copper No. 4 or 2
wires ch 30 or 15
Capacity on 2Mbit/s or on 1Mbit/s ch / pair of 30 / 2 pairs
Capacity selectable wire 30 / 1 pair
15 / 1 pair
4.0 Available USER INTERFACES
4.1 Voice interfaces for trunk lines:
4.1.1 1 + 1 com path protection, available for all yes
4.1.2 Analogue, 4wire with E&M: Input level dBr +7.5 .. –16
Output level +7.0 .. –16.5
4.1.3 Analogue, 2wire with E&M: Input level dBr +6.5 .. –12.5
Output level –1.0 .. -20
4.1.4 Digital, 2Mbit/s CAS or PRI yes
4.2 Voice interfaces for remote subscriber:
4.2.1 2wire, subscriber side dBr -5 .. +4 / -7.5 .. -1
4.2.2 2wire, PABX side dBr -5 .. +4 / -7.5 .. -3
4.3 Integrated teleprotection
4.3.1 Interface for Commands:
4.3.1.1 Number of independent commands No. 4
4.3.1.2 Transmission time max. ms 6
4.3.1.3 Signal voltage Vpeak 250
4.3.1.4 1 + 1 com path protection yes
4.3.2 Interface(s) for Differential Protection:
4.3.2.1 Electrical interface: G.703 kbit/s 64
4.3.2.2 Optical Interface kbit/s Minimum 64
4.4 Data: channels per module

4.4.1 1 + 1 com path protection, available for all yes


4.4.2 V.24/V.28 (RS-232): up to 38.4kbit/s No. 4
4.4.3 V.11/X.24 (RS-422): 64kbit/s No. 4

SA-13
Schedule_A: Requirements

4.4.4 V.35: 64kbit/s No. 4


4.4.5 V.36 (RS-449): 64kbit/s No. 2
4.4.6 G.703: 64kbit/s No. 8
4.4.7 Ethernet: 10/100 BaseT No. 1
WAN capacity Mbit/s Min: 2x 2Mbit/s
Protocols Min.: IP
4.5 Integrated alarm gathering module:
4.5.1 Number of external alarms per module No. Min. 20
4.5.2 Auxiliary power supply for ext. contacts Yes
4.6 Network Management System
4.6.1 Type/Name of configuration tool
4.6.2 For fault / configuration management Yes / yes
4.6.3 For local / remote operation Yes / yes
4.6.4 Data communication network (DCN) Ethernet / IP or
Ethernit / OSI
4.7 Ambient Conditions:
4.7.1 Storage: ETS 300 019-1-1, class 1.2 °C / % hum -25 .. + 55 / class 1.2
4.7.2 Transport: ETS 300 019-1-2, class 2.2 °C / % hum -25 .. + 70 / class 2.2
4.7.3 Operation: ETS 300 019-1-3, class 3.1E °C / % hum -5 .. +45 / class 3.1E
4.8 Power Supply
4.8.1 Operation VDC 48 / 60 (-15/+20%)
4.8.2 Fully redundant power supply yes

APPENDIX- A9

SCHEDULE OF TECHNICAL REQUIREMENTS OF


OPERATIONAL TELEPHONE SYSTEM (PABX)

(NOT APPLICABLE)

APPENDIX- A10.1

SCHEDULE OF TECHNICAL REQUIREMENTS OF


INSULATOR
1 Rated Voltage 145kV 245kV
2 Lightning impulse withstand positive and 650 1050
negative (kVp)(Dry and wet)
3 Switching impulse withstand voltage (kVp) - -
4 One min. power freq. withstand voltage(kVrms) (Wet 275 460
and Dry)
5 Total creepage distance (mm) pedestal 3625 6125
6 Total min. cantilever strength (kg) 800 800
7 Corona extinction voltage (kVrms) - 156
8 Total min. height of insulator (mm) 2500 2500

SA-14
Schedule_A: Requirements

APPENDIX- A 10.2

SCHEDULE OF TECHNICAL REQUIREMENTS OF


INSULATOR STRING
1 Rated voltage 145kV 245kV
2 Type Anti FOG Anti FOG
3 Size of insulators units (mm) 255 x 145 255 x 145
4 Creepage distance of individual insulator 430 430
unit
(Minimum or as required to obtain total
creepagedistance, mm)
5 Electromechanical strength (kN) 120 120
6 Power frequency withstand voltage of the 275 460
complete string (kVrms)
7 Lightning impulse withstand voltage of 650 1050
the
complete string with C.C. ring (Dry and
wet, kVp)
8 Switching surge withstand voltage of the - -
complete
string with C.C. rings(Dry & wet, kVp)
9 Power frequency puncture withstand 1.3 times the actual wet 1.3 times the
voltage for a flashover voltage of the actual wet
string insulator unit unit. flashover voltage
of the unit.
10 Minimum corona extinction voltage level - 156
of the complete string with C.C. ring (Dry,
kVrms)
11 R.I.V. Level of the complete string with 500 1000
C.C. ring.
(micro V)
12 Total creepage distance of complete 3625 6125
insulator
string (mm)

APPENDIX- A 10.3

SCHEDULE OF TECHNICAL REQUIREMENTS OF XLPE POWER CABLE

(NOT APPLICABLE)

SA-15
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
Section-1: Payra 132/11kV AIS switching station
1A 230kV Air Insulated Switchgear (AIS)
single-phase, 2-core ((230/(√3))⁄(0.11/√3/0.11/√3
1A1 kV)), 40kA/1sec, 50Hz, 1050kVp BIL, inductive nos. 6
voltage transformers (IVT) for bus circuit bays.
230kV, 2500A, 40kA/1sec, 50Hz, 1050kVp BIL,
double side break, post type, motor operated
1A2 set 2
disconnectors with earthing switch, for line circuit
(Patuakhali-1 & 2) bays
230kV Post Insulators (whose foundation shall be
1A3 nos. 8
for 230kV, 2500A, 40kA Disconnector)
Flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
1A4 lot 1
required for completing 245kV busbar and
switchgear connection
Steel structures for gantry and equipment
1A5 supports required for completing 245kV busbar lot 1
and switchgear
i) Columns for gantry with single beam nos. 8*
ii) Columns for gantry with double beam nos. 16*
iii) Beam nos. 17*
iv) Steel structure for equipment support lot 1
1B 145kV Air Insulated Switchgear (AIS)
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, single pole operated, SF6 gas
1B1 circuit breakers with spring-stored energy set 2
operating mechanism for Patuakhali-1 & 2 line
circuit bays
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, gang operated SF6 gas circuit
1B2 set 1
breakers with spring-stored energy operating
mechanism for transformer bay
145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, gang operated SF6 gas circuit
1B3 set 1
breakers with spring-stored energy operating
mechanism for bus coupler circuit bay

Schedule No.1-1
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
1B4 set 9
disconnectors without earthing switch, for line &
transformer circuit bays
145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
1B5 set 2
disconnectors without earthing switch for bus
coupler circuit bays
single-phase, 4-core, single ratio, 145kV,
31.5kA/1sec, 50Hz, 650kVp BIL, post type
1B6 current transformer for line & transformer circuit nos. 9
bays.(1250/1-1-1A, 5P20 30VA & 1250/1A,
10VA, 0.2 class)
single-phase, 2-core, single ratio (3000/1-1A),
145kV, 31.5kA/1sec, 50Hz, 650kVp BIL, post
1B7 nos. 6
type current transformer for bus coupler circuit
bay.
single-phase, 2-core ((132/(√3))⁄(0.11/√3/0.11/√3
kV)), 31.5kA/1sec, 50Hz, 650kVp BIL, inductive
1B8 nos. 9
voltage transformers (IVT) for line & transformer
circuit bays.

single-phase, 2-core ((132/(√3))⁄(0.11/√3/0.11/√3


1B9 kV)), 31.5kA/1sec, 50Hz, 650kVp BIL, inductive nos. 6
voltage transformers (IVT) for bus circuit bays.
120kV rated voltage, 102kV(rms) continuous
operating voltage at 500c, 10kA nominal
1B10 discharge current, 50Hz, Heavy duty station nos. 15
class, gapless metal oxide type, single phase
surge arresters
flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
1B11 lot 1
required for completing 145kV busbar and
switchgear connection.
steel structures for gantry and equipment
1B12 supports required for completing 145kV busbar lot 1
and switchgear .
i) Columns for gantry with single beam nos. 4*
ii) Columns for gantry with double beam nos. 9*
iii) Beam nos. 12*
iv) Steel structure for equipment support lot 1
1C Auxiliary Transformers
1C1 132/11kV, 25/41MVA power transformer set 0
11/0.415 kV, 200kVA three phase outdoor type
auxiliary transformers (to be installed at 145kV
switchyard premise) with associated bushing
CTs, dropout fuses, and steel support structures
1C2 including all necessary connections (with poles, lot 2
clamps, fittings, etc.) from 11kV source of
132/11kV transformer which will be installed
either within the 132kV switchyard or nearly
1500m away from 132kV switchyard
11/0.415 kV, 200kVA three phase outdoor type
auxiliary transformers (to be installed at 145kV
switchyard premise) with associated bushing
1C2 (i) set 2
CTs, dropout fuses, and steel support structures
excluding pole (with clamps, fittings, etc.) &
conductor
1C2 (ii) Pole (with clamp, fittings, etc.) nos. 50*
1C2 (iii) Conductor (conductor size for at least 100A) m 3600*

Schedule No.1-2
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
Control, Protection & Metering Panel,
1D
Substation Automation System
230kV Circuit
Control, metering (for voltage only) and
1D1 Substation Automation System for 230kV line set 1
(only disconnector and PT for each line).
145kV Circuit
Control, Protection, Metering & Substation
Automation System including event recording
function for two (2) sets of overhead line circuits
1D2 set 2
(Patuakhali-1 & 2). Regarding protection, only
over current function is required which is to be
integrated in respective BCU
Control, Protection, Metering & Substation
Automation System including event recording
function for one (01) set of 132/11 kV power
transformer circuits including transformer tap
1D3 changer control. Regarding protection, only over set 1
current function is required which is to be
integrated in respective BCU. Transformer main
differential protection is to be provided by another
contractor
Control, Protection, Metering & Substation
1D4 Automation System including event recording set 1
function for one (1) set of bus coupler circuit
1D5 NA lot 0
1D6 Tariff metering panel lot 1
11kV Circuit
1D7 Tariff metering panel lot 1

Schedule No.1-3
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
1E NA lot 0
1F Multicore LV Control & Power Cables
i) _LV Control Cable lot 1
ii) _LV Power Cable lot 1
1G Earthing and Lightning Protection
1G1 Earthing and Lightning Protection
i) Earthing system for complete substation lot 1
Lighting Protection System for complete
ii) lot 1
substation
Portable (maintenance) earthing equipment
1G2 devices with connectors and telescopic glass set 1
fibre operating pole suitable for plant supplied.

1H Batteries, Chargers and DC Distribution


1H1 110V System
i) 110V Battery Banks, 330Ah set 2
ii) Charger, 90A set 2
iii) 110V DC Distribution panel, MCC type lot 1
1H2 48V System
i) 48V Battery Banks, 150Ah set 2
ii) Charger , 50A set 2
iii) 48V DC Distribution panel, MCC type lot 1
iv) Inverter for 48V system, 1kVA set 1
1I LVAC Distribution
1I1 LVAC Distribution lot 1
1I2 Tariff metering lot 1
1I3 NA lot 0
125A outdoor weatherproof 3-phase with neutral
1I4 and earth switched socket outlet and plug, (as set 1
per IEC 309) drawer type breakers

Schedule No.1-4
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
1J Civil Works, Building and Foundation
Complete civil items required for outdoor works
1J1
including boundary wall
Complete Land development with carried
i) CuM 0
earthfilling**
ii) _Outdoor gantry foundation 230kV switchyard lot 1
a. Foundation for gantry with single beam nos. 8*
b. Foundation for gantry with double beam nos. 16*
_Outdoor equipment foundation 230kV
iii) lot 1
switchyard
iv) _Indoor equipment foundation 11kV switchyard lot 0
_Transformer foundation including oilpit &
v) lot 0
carrage way
vi) _Blast wall lot 0
vii) _Security Boundary Wall lot 0
a. _Retaining Wall on the property line *** lot 0
b. _Normal Wall with slope protection lot 0
1) _Normal Wall *** m 0
2) _Slope Protection lot 0
viii) _Substation Main gate each 1
ix) _Barbed Wire Fencing lot 1
x) _Approach raod lot 1
xi) _Internal road lot 1
xii) _Surface drain lot 1
xiii) _Cable Trench lot 1
xiv) _Switchyard surface finishing lot 1
xv) _Gravel laying lot 1
xvi) _Septic tank, sowak way lot 1
_Pump house including deep tubewell, motor,
xv) lot 1
pump, water reservaoir, water pipe line etc.
xvi) _Gurd house, sentry post, car port lot 1
xvii) _Outdoor gantry foundation 145kV switchyard lot 1
a. _Foundation for gantry with single beam nos. 4*
b. _Foundation for gantry with double beam nos. 9*
_Outdoor equipment foundation 145kV
xviii) lot 1
switchyard
Complete civil items and facilities for a two
1J2 storied main control building & single storied lot 1
Ansar Barack
Complete fire fighting system for transformers
1J3 including water pond/reservoir, pipe network and lot 0
pump

Schedule No.1-5
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
Lighting, small power, air conditioning and
1K
Ventilation
Lighting, small power, air conditioning and
1k1 Ventilation and emergency DC lighting for control lot 1
building

Lighting for ouside building for security, roadway,


1k2 lot 1
switchyard and emergency DC lighting
Fibre Optic Multiplexer Equipment for
1L
Communication and Protection
1L1 Indoor Fibre Optic Multipexer Equipment lot 1
1L2 Fibre Optic cable , MDF,pigtail cable, termination
lot 1
box etc.
SCADA system for Telecontrol and
1M
Telemetering
1M1 Complete SCADA hardware & software lot 1
Section-2: Extension of 132kV bays at Patuakhali substation
2A 145 kV Air Insulated Switchgear
1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, single pole operated, SF6 gas circuit
2A1 set 2
breakers with spring-stored energy operating
mechanism (for line bay).
2A2 Deleted
2A3 Deleted
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
2A4 set 2
disconnectors with manual earthing switch for
line circuit bays.
1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, double
2A5 side break, post type, motor operated set 4
disconnectors without earthing switch.
2A6 Deleted
2A7 Deleted
single-phase, 4-core, single ratio, 145kV,
31.5kA/1sec, 50Hz, 650kVp BIL, post type
2A8 nos. 6
current transformer (1250/1-1-1-1A) for line
circuit bays.
2A9 Deleted
single-phase, 2-core ((132/(√3))⁄(.11/√3-0.11/√3
2A10 nos. 6
kV)) , 145kV, 31.5kA/1sec , 50Hz, 650kVp BIL,
2A11 Deleted
120kV rated voltage, 102kV(rms) continuous
operating voltage at 500C, 10kA nominal
2A12 discharge current, 50Hz, Heavy duty station nos. 6
class, gapless metal oxide type, single phase
surge arresters.
flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
2A13 lot 1
required for completing 145kV busbar and
switchgear connection
steel structures for gantry and equipment
2A14 supports required for completing 145kV busbar lot 1
and switchgear
i) Columns for gantry with single beam nos. 4*
ii) Columns for gantry with double beam nos. 6*
iii) Beam nos. 4*
iv) Steel structure for equipment support lot 1

Schedule No.1-6
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
2B Deleted
2C Deleted
2D Control, Protection & Metering Panel
132kV Circuit
Control, Protection, Metering panel for two (2)
2D1 set 2
sets of overhead line circuits
2D2 Deleted
2D3 Deleted
2D4 Deleted
2D5 Tariff metering panel lot 1
2D6 Deleted
2D7 Deleted
2E Deleted
2F Multicore LV Control & Power Cables
i) _LV Control Cable lot 1
ii) _LV Power Cable lot 1
2G Earthing and Lightning Protection
2G1 Earthing and Lightning Protection
Modification of Earthing system for complete
i) lot 1
substation
Modification of Lighting Protection System for
ii) lot 1
complete substation
2G2 Deleted
2H Batteries, Chargers and DC Distribution
Modification of 110V DC Distribution panel, MCC
2H1 lot 1
type
Modification of 48V DC Distribution panel, MCC
2H2 lot 1
type
2I LVAC Distribution
2I1 Modification of LVAC Distribution lot 1

Schedule No.1-7
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
2J Civil Works, Building and Foundation
Complete civil items required for outdoor works
2J1
including boundary wall
Complete Land development with carried
i) CuM 0
earthfilling**
_Outdoor gantry foundation for extension of
ii) lot 1
132kV switchyard
a. _Foundation for gantry with single beam nos. 4*

b. _Foundation for gantry with double beam nos. 6*


_Outdoor equipment foundation for extension of
iii) lot 1
132kV switchyard
iv) _Indoor equipment foundation 11kV switchyard NA
_Transformer foundation including oilpit &
v) NA
carrage way
vi) _Blast wall NA

vii) _Security Boundary Wall with slope protection NA

viii) _Substation Main gate NA

ix) _Barbed Wire Fencing

a) _Dismantling of a portion of Barbed Wire Fencing lot 1

b) _Extension of Barbed Wire Fencing lot 1

x) _Approach raod NA

xi) _Extension of Internal road lot 1

xii) _Extension of Surface drain lot 1

xiii) _Extension of Cable Trench lot 1


xiv) _Extension of Switchyard surface finishing lot 1
xv) _Extension of Gravel laying lot 1

xvi) _Septic tank, sowak way NA


_Pump house including deep tubewell, motor,
xv) NA
pump, water reservaoir, water pipe line etc.
xvi) _Gurd house, sentry post, car port NA
Complete civil items for modificaion of existing
2J2 lot 1
control room

Schedule No.1-8
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9
Lighting, small power, air conditioning and
2K
Ventilation
Extension of Lighting, small power for extended
2k1 lot 1
bays
2k2 NA lot 1
Fibre Optic Multiplexer Equipment for
2L
Communication and Protection
Modification of existing Fibre Optic Multipexer
2L1 lot 1
Equipment
Optical Fiber Cable, juctionBox, MDF, pigtail
2L2 lot 1
cable etc.
SCADA system for Telecontrol and
2M
Telemetering
2M1 Modification of existing SCADA System lot 1
Section-3: Mandatory Spare Parts,Tools & Test
equipment
3A 245 kV Air Insulated Switchgear

Complete SF6 gas, live tank type 245kV, 2500A


i) NA 0
Circuit Breaker (single-pole operation type)

ii) Complete 245 kV, 2500A disconnector switch NA 0


Set of interrupting chamber including insulators,
iii) fixed and moving contacts for 245kV offered type NA 0
circuit breaklers
iv) 245 kV post insulators suitable for disconnector NA 0

Set (three phase) contacts for 245 kV


v) NA 0
disconnector
vi) 196 kV surge arrester NA 0
vii) 245 kV Inductive voltage transformer NA 0
viii) Closing coils NA 0
ix) Tripping coils NA 0

Motor for 245 kV circuit breaking operating


x) NA 0
mechanism

xi) Motor for disconnector drive NA 0


xii) Coils for Blocking magnet in disconnector drive NA 0

Schedule No.1-9
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9

3B 145 kV Air Insulated Switchgear


Complete SF6 gas, live tank type 145kV, 1250A
i) set 1
Circuit Breaker (single-pole operation type)

ii) Complete 145 kV,1250A disconnector switch sets 1

Set of interrupting chamber including insulators,


iii) fixed and moving contacts for 145kV offered type sets 1
circuit breaklers

iv) 145 kV post insulators suitable for disconnector nos. 3

Set (three phase) contacts for 145 kV


v) sets 1
disconnector

vi) 120 kV surge arrester nos. 3

vii) 145 kV capacitive voltage transformer nos. 3

viii) Closing coils nos. 3

ix) Tripping coils nos. 3

Motor for 145 kV circuit breaking operating


x) nos. 1
mechanism
xi) Motor for disconnector drive nos. 1

xii) Coils for Blocking magnet in disconnector drive nos. 3

Schedule No.1-10
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.1: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Outside the
Employer's Country
Total
Unit Price1
Price1
Country of Foreign Foreign Taxes and Duties-
Item Description Unit Quantity Currency Currency Local Currency
origin
Portion CIP Portion

[xxxxx] [xxx]
1 2 3 4 5 6 7 8=4x6 9

3C Protection
Line Distance relay with complete protection
i) NA 0
element
Transformer Differential relay with complete REF
ii) NA 0
function
iii) Overcurrent and earth fault relay set 1
iv) Tripping relay (electrical reset) sets 1
v) Trip circuit supervision relay,3 phase sets 1
vi) Bay Control Unit sets 1
vii) Ammeter nos. 3
viii) Voltmeter nos. 3
ix) Annunciator bulbs nos. 60
x) Bulbs for discrepancy switches nos. 30
xi) kWh & kVarh meter nos. 1
3D Test and O & M Equipment
Set of gas filling equipment and 1 bottle of SF6
i) sets 1
gas
ii) SF6 gas sniffer sets 1
Portable vacuum pump suitable for SF6 circuit
iii) set 1
breaker
Contact resistance measurement test set
iv) (suitable for measurement down to 1 µ ohm at set 1
10A d.c.)
5 kV insulation resistance test set (range 0.5 –1.0
v) sets 1
- 2.5 - 5 kV)
Earth resistance test set (range 10-100-1000
vi) sets 1
ohm: min scale division 0.1 ohm)
vii) Clip-on mA meter (for spill current) nos. 1
viii) Portable Earthing Leads sets 2

Total Columns 8 to be carried forward to Schedule No. 5 - Grand Summary


* Payment shall be on actual basis
The quantity mentioned above as"CuM/m^3"may increase or decrease during execution stage, but the payment shall be at actual
** basis.

1 Specify currencies in accordance with ITB 19.1 of the BDS.

Schedule No.1-11
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
Section-1: Payra 132/11kV AIS switching station
1A 230kV Air Insulated Switchgear (AIS)
single-phase, 2-core ((230/(√3))⁄(0.11/√3/0.11/√3
1A1 kV)), 40kA/1sec, 50Hz, 1050kVp BIL, inductive nos. 6
voltage transformers (IVT) for bus circuit bays.
230kV, 2500A, 40kA/1sec, 50Hz, 1050kVp BIL,
double side break, post type, motor operated
1A2 set 2
disconnectors with earthing switch, for line circuit
(Patuakhali-1 & 2) bays
230kV Post Insulators (whose foundation shall be
1A3 nos. 8
for 230kV, 2500A, 40kA Disconnector)
Flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
1A4 lot 1
required for completing 245kV busbar and
switchgear connection
Steel structures for gantry and equipment
1A5 supports required for completing 245kV busbar lot 1
and switchgear
i) Columns for gantry with single beam nos. 8*
ii) Columns for gantry with double beam nos. 16*
iii) Beam nos. 17*
iv) Steel structure for equipment support lot 1
1B 145kV Air Insulated Switchgear (AIS)
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, single pole operated, SF6 gas
1B1 circuit breakers with spring-stored energy set 2
operating mechanism for Patuakhali-1 & 2 line
circuit bays
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, gang operated SF6 gas circuit
1B2 set 1
breakers with spring-stored energy operating
mechanism for transformer bay
145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, gang operated SF6 gas circuit
1B3 set 1
breakers with spring-stored energy operating
mechanism for bus coupler circuit bay

Schedule No.2-1
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
1B4 set 9
disconnectors without earthing switch, for line &
transformer circuit bays
145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
1B5 set 2
disconnectors without earthing switch for bus
coupler circuit bays
single-phase, 4-core, single ratio, 145kV,
31.5kA/1sec, 50Hz, 650kVp BIL, post type
1B6 current transformer for line & transformer circuit nos. 9
bays.(1250/1-1-1A, 5P20 30VA & 1250/1A,
10VA, 0.2 class)
single-phase, 2-core, single ratio (3000/1-1A),
145kV, 31.5kA/1sec, 50Hz, 650kVp BIL, post
1B7 nos. 6
type current transformer for bus coupler circuit
bay.
single-phase, 2-core ((132/(√3))⁄(0.11/√3/0.11/√3
kV)), 31.5kA/1sec, 50Hz, 650kVp BIL, inductive
1B8 nos. 9
voltage transformers (IVT) for line & transformer
circuit bays.

single-phase, 2-core ((132/(√3))⁄(0.11/√3/0.11/√3


1B9 kV)), 31.5kA/1sec, 50Hz, 650kVp BIL, inductive nos. 6
voltage transformers (IVT) for bus circuit bays.
120kV rated voltage, 102kV(rms) continuous
operating voltage at 500c, 10kA nominal
1B10 discharge current, 50Hz, Heavy duty station nos. 15
class, gapless metal oxide type, single phase
surge arresters
flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
1B11 lot 1
required for completing 145kV busbar and
switchgear connection.
steel structures for gantry and equipment
1B12 supports required for completing 145kV busbar lot 1
and switchgear .
i) Columns for gantry with single beam nos. 4*
ii) Columns for gantry with double beam nos. 9*
iii) Beam nos. 12*
iv) Steel structure for equipment support lot 1

Schedule No.2-2
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
1C Auxiliary Transformers
1C1 132/11kV, 25/41MVA power transformer set 0
11/0.415 kV, 200kVA three phase outdoor type
auxiliary transformers (to be installed at 145kV
switchyard premise) with associated bushing
CTs, dropout fuses, and steel support structures
1C2 including all necessary connections (with poles, lot 2
clamps, fittings, etc.) from 11kV source of
132/11kV transformer which will be installed
either within the 132kV switchyard or nearly
1500m away from 132kV switchyard
11/0.415 kV, 200kVA three phase outdoor type
auxiliary transformers (to be installed at 145kV
switchyard premise) with associated bushing
1C2 (i) set 2
CTs, dropout fuses, and steel support structures
excluding pole (with clamps, fittings, etc.) &
conductor
1C2 (ii) Pole (with clamp, fittings, etc.) nos. 50*
1C2 (iii) Conductor (conductor size for at least 100A) m 3600*
Control, Protection & Metering Panel,
1D
Substation Automation System
230kV Circuit
Control, metering (for voltage only) and
1D1 Substation Automation System for 230kV line set 1
(only disconnector and PT for each line).
145kV Circuit
Control, Protection, Metering & Substation
Automation System including event recording
function for two (2) sets of overhead line circuits
1D2 set 2
(Patuakhali-1 & 2). Regarding protection, only
over current function is required which is to be
integrated in respective BCU
Control, Protection, Metering & Substation
Automation System including event recording
function for one (01) set of 132/11 kV power
transformer circuits including transformer tap
1D3 changer control. Regarding protection, only over set 1
current function is required which is to be
integrated in respective BCU. Transformer main
differential protection is to be provided by another
contractor

Schedule No.2-3
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
Control, Protection, Metering & Substation
1D4 Automation System including event recording set 1
function for one (1) set of bus coupler circuit
1D5 NA lot 0
1D6 Tariff metering panel lot 1
11kV Circuit
1D7 Tariff metering panel lot 1
1E NA lot 0
1F Multicore LV Control & Power Cables
i) _LV Control Cable lot 1
ii) _LV Power Cable lot 1
1G Earthing and Lightning Protection
1G1 Earthing and Lightning Protection
i) Earthing system for complete substation lot 1
Lighting Protection System for complete
ii) lot 1
substation
Portable (maintenance) earthing equipment
1G2 devices with connectors and telescopic glass set 1
fibre operating pole suitable for plant supplied.
1H Batteries, Chargers and DC Distribution
1H1 110V System
i) 110V Battery Banks, 330Ah set 2
ii) Charger, 90A set 2
iii) 110V DC Distribution panel, MCC type lot 1
1H2 48V System
i) 48V Battery Banks, 150Ah set 2
ii) Charger , 50A set 2
iii) 48V DC Distribution panel, MCC type lot 1
iv) Inverter for 48V system, 1kVA set 1
1I LVAC Distribution
1I1 LVAC Distribution lot 1
1I2 Tariff metering lot 1
1I3 NA lot 0
125A outdoor weatherproof 3-phase with neutral
1I4 and earth switched socket outlet and plug, (as set 1
per IEC 309) drawer type breakers

Schedule No.2-4
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
1J Civil Works, Building and Foundation
Complete civil items required for outdoor works
1J1
including boundary wall
Complete Land development with carried
i) CuM 0
earthfilling**
ii) _Outdoor gantry foundation 230kV switchyard lot 1
a. Foundation for gantry with single beam nos. 8*
b. Foundation for gantry with double beam nos. 16*
_Outdoor equipment foundation 230kV
iii) lot 1
switchyard
iv) _Indoor equipment foundation 11kV switchyard lot 0
_Transformer foundation including oilpit &
v) lot 0
carrage way
vi) _Blast wall lot 0
vii) _Security Boundary Wall lot 0
a. _Retaining Wall on the property line *** lot 0
b. _Normal Wall with slope protection lot 0
1) _Normal Wall *** m 0
2) _Slope Protection lot 0
viii) _Substation Main gate each 1
ix) _Barbed Wire Fencing lot 1
x) _Approach raod lot 1
xi) _Internal road lot 1
xii) _Surface drain lot 1
xiii) _Cable Trench lot 1
xiv) _Switchyard surface finishing lot 1
xv) _Gravel laying lot 1
xvi) _Septic tank, sowak way lot 1
_Pump house including deep tubewell, motor,
xv) lot 1
pump, water reservaoir, water pipe line etc.
xvi) _Gurd house, sentry post, car port lot 1
xvii) _Outdoor gantry foundation 145kV switchyard lot 1
a. _Foundation for gantry with single beam nos. 4*
b. _Foundation for gantry with double beam nos. 9*
xviii) _Outdoor equipment foundation 145kV switchyard lot 1
Complete civil items and facilities for a two
1J2 storied main control building & single storied lot 1
Ansar Barack
Complete fire fighting system for transformers
1J3 including water pond/reservoir, pipe network and lot 0
pump

Schedule No.2-5
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
Lighting, small power, air conditioning and
1K
Ventilation
Lighting, small power, air conditioning and
1k1 Ventilation and emergency DC lighting for control lot 1
building

Lighting for ouside building for security, roadway,


1k2 lot 1
switchyard and emergency DC lighting
Fibre Optic Multiplexer Equipment for
1L
Communication and Protection
1L1 Indoor Fibre Optic Multipexer Equipment lot 1
1L2 Fibre Optic cable ,MDF,pigtail cable, termination
lot 1
box etc.
SCADA system for Telecontrol and
1M
Telemetering
1M1 Complete SCADA hardware & software lot 1
Section-2: Extension of 132kV bays at Patuakhali substation
2A 145 kV Air Insulated Switchgear
1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, single pole operated, SF6 gas circuit
2A1 set 2
breakers with spring-stored energy operating
mechanism (for line bay).
2A2 Deleted
2A3 Deleted
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
2A4 set 2
disconnectors with manual earthing switch for
line circuit bays.
1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, double
2A5 side break, post type, motor operated set 4
disconnectors without earthing switch.
2A6 Deleted
2A7 Deleted
single-phase, 4-core, single ratio, 145kV,
31.5kA/1sec, 50Hz, 650kVp BIL, post type
2A8 nos. 6
current transformer (1250/1-1-1-1A) for line
circuit bays.

Schedule No.2-6
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
2A9 Deleted
single-phase, 2-core ((132/(√3))⁄(.11/√3-0.11/√3
2A10 nos. 6
kV)) , 145kV, 31.5kA/1sec , 50Hz, 650kVp BIL,
2A11 Deleted
120kV rated voltage, 102kV(rms) continuous
operating voltage at 500C, 10kA nominal
2A12 discharge current, 50Hz, Heavy duty station nos. 6
class, gapless metal oxide type, single phase
surge arresters.
flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
2A13 lot 1
required for completing 145kV busbar and
switchgear connection
steel structures for gantry and equipment
2A14 supports required for completing 145kV busbar lot 1
and switchgear
i) Columns for gantry with single beam nos. 4*
ii) Columns for gantry with double beam nos. 6*
iii) Beam nos. 4*
iv) Steel structure for equipment support lot 1
2B Deleted
2C Deleted
2D Control, Protection & Metering Panel
132kV Circuit
Control, Protection, Metering panel for two (2)
2D1 set 2
sets of overhead line circuits
2D2 Deleted
2D3 Deleted
2D4 Deleted
2D5 Tariff metering panel lot 1
2D6 Deleted
2D7 Deleted
2E Deleted
2F Multicore LV Control & Power Cables
i) _LV Control Cable lot 1
ii) _LV Power Cable lot 1

Schedule No.2-7
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
2G Earthing and Lightning Protection
2G1 Earthing and Lightning Protection
Modification of Earthing system for complete
i) lot 1
substation
Modification of Lighting Protection System for
ii) lot 1
complete substation
2G2 Deleted
2H Batteries, Chargers and DC Distribution
Modification of 110V DC Distribution panel, MCC
2H1 lot 1
type
Modification of 48V DC Distribution panel, MCC
2H2 lot 1
type
2I LVAC Distribution
2I1 Modification of LVAC Distribution lot 1
2J Civil Works, Building and Foundation
Complete civil items required for outdoor works
2J1
including boundary wall
Complete Land development with carried
i) CuM 0
earthfilling**
_Outdoor gantry foundation for extension of
ii) lot 1
132kV switchyard
a. _Foundation for gantry with single beam nos. 4*

b. _Foundation for gantry with double beam nos. 6*


_Outdoor equipment foundation for extension of
iii) lot 1
132kV switchyard
iv) _Indoor equipment foundation 11kV switchyard NA
_Transformer foundation including oilpit &
v) NA
carrage way
vi) _Blast wall NA

vii) _Security Boundary Wall with slope protection NA

viii) _Substation Main gate NA

Schedule No.2-8
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10

ix) _Barbed Wire Fencing

a) _Dismantling of a portion of Barbed Wire Fencing lot 1

b) _Extension of Barbed Wire Fencing lot 1

x) _Approach raod NA

xi) _Extension of Internal road lot 1

xii) _Extension of Surface drain lot 1

xiii) _Extension of Cable Trench lot 1


xiv) _Extension of Switchyard surface finishing lot 1
xv) _Extension of Gravel laying lot 1

xvi) _Septic tank, sowak way NA


_Pump house including deep tubewell, motor,
xv) NA
pump, water reservaoir, water pipe line etc.
xvi) _Gurd house, sentry post, car port NA
Complete civil items for modificaion of existing
2J2 lot 1
control room
Lighting, small power, air conditioning and
2K
Ventilation
Extension of Lighting, small power for extended
2k1 lot 1
bays
2k2 NA lot 1
Fibre Optic Multiplexer Equipment for
2L
Communication and Protection
Modification of existing Fibre Optic Multipexer
2L1 lot 1
Equipment
Optical Fiber Cable, juctionBox, MDF, pigtail
2L2 lot 1
cable etc.
SCADA system for Telecontrol and
2M
Telemetering
2M1 Modification of existing SCADA System lot 1

Schedule No.2-9
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
Section-3: Mandatory Spare Parts,Tools & Test
equipment
3A 245 kV Air Insulated Switchgear

Complete SF6 gas, live tank type 245kV, 2500A


i) NA 0
Circuit Breaker (single-pole operation type)

ii) Complete 245 kV, 2500A disconnector switch NA 0


Set of interrupting chamber including insulators,
iii) fixed and moving contacts for 245kV offered type NA 0
circuit breaklers
iv) 245 kV post insulators suitable for disconnector NA 0

Set (three phase) contacts for 245 kV


v) NA 0
disconnector
vi) 196 kV surge arrester NA 0
vii) 245 kV Inductive voltage transformer NA 0
viii) Closing coils NA 0
ix) Tripping coils NA 0

Motor for 245 kV circuit breaking operating


x) NA 0
mechanism

xi) Motor for disconnector drive NA 0


xii) Coils for Blocking magnet in disconnector drive NA 0

3B 145 kV Air Insulated Switchgear


Complete SF6 gas, live tank type 145kV, 1250A
i) set 1
Circuit Breaker (single-pole operation type)

ii) Complete 145 kV,1250A disconnector switch sets 1


Set of interrupting chamber including insulators,
iii) fixed and moving contacts for 145kV offered type sets 1
circuit breaklers
iv) 145 kV post insulators suitable for disconnector nos. 3

Schedule No.2-10
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
Set (three phase) contacts for 145 kV
v) sets 1
disconnector

vi) 120 kV surge arrester nos. 3

vii) 145 kV capacitive voltage transformer nos. 3

viii) Closing coils nos. 3

ix) Tripping coils nos. 3

Motor for 145 kV circuit breaking operating


x) nos. 1
mechanism
xi) Motor for disconnector drive nos. 1

xii) Coils for Blocking magnet in disconnector drive nos. 3

3C Protection
Line Distance relay with complete protection
i) NA 0
element
Transformer Differential relay with complete REF
ii) NA 0
function
iii) Overcurrent and earth fault relay set 1
iv) Tripping relay (electrical reset) sets 1
v) Trip circuit supervision relay,3 phase sets 1
vi) Bay Control Unit sets 1
vii) Ammeter nos. 3
viii) Voltmeter nos. 3
ix) Annunciator bulbs nos. 60
x) Bulbs for discrepancy switches nos. 30
xi) kWh & kVarh meter nos. 1

Schedule No.2-11
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and
extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract
No. PGCB/230KV/PP/SS)
Schedule No.2: Price for Itemised Works, Goods or Services including Mandatory Spare Parts Supplied from Within the
Employer's Country

Unit Price1 Total Price1


Taxes and
Country of Local Local Duties-
Item Description Unit Quantity Foreign Foreign
origin Currency Currency Local
Currency Currency
Portion Portion Currency
Portion Portion
EXW EXW
[CIP] [CIP]
[BDT] [BDT]
1 2 3 4 5 6 7 8=4x6 9=4x7 10
3D Test and O & M Equipment
Set of gas filling equipment and 1 bottle of SF6
i) sets 1
gas
ii) SF6 gas sniffer sets 1
Portable vacuum pump suitable for SF6 circuit
iii) set 1
breaker
Contact resistance measurement test set
iv) (suitable for measurement down to 1 µ ohm at set 1
10A d.c.)
5 kV insulation resistance test set (range 0.5 –1.0
v) sets 1
- 2.5 - 5 kV)
Earth resistance test set (range 10-100-1000
vi) sets 1
ohm: min scale division 0.1 ohm)
vii) Clip-on mA meter (for spill current) nos. 1
viii) Portable Earthing Leads sets 2

Total Column 8 & 9 to be carried forward to Schedule No. 5 - Grand Summary


* Payment shall be on actual basis
The quantity mentioned above as"CuM/m^3"may increase or decrease during execution stage, but the payment shall be at actual
** basis.

1 Specify currencies in accordance with ITB 19.1 of the BDS.


Column 6, EXW Price shall include all customs duties and sales and other taxes already paid or payable on the components and
raw materials used in the manufacture or assembly of the item or the customs duties and sales and other taxes already paid on
previously imported items

Schedule No.2-12
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and extension of 132 kV bays at
existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract No. PGCB/230KV/PP/SS)

Schedule No.3: Design Services

Unit Price1 Total Price1

Local Foreign
Item Description Unit Quantity Local Currency Portion Currency Currency
Foreign Currency Portion [xxxxx]
[BDT] Portion Portion
[BDT] [xxx]

1 2 3 4 5 6 7=4x5 8=4x6

21 145 kV switchgear, equipment connection and steel structures Lump sum 1

Total Columns 7 and 8 to be carried forward to Schedule No. 5 - Grand Summary

1 Specify currencies in accordance with ITB 19.1 of the BDS. Create additional columns for up to a maximum of three foreign currencies, if so required.

Schedule No.3-1
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
Section-1: Payra 132/11kV AIS switching station
1A 230kV Air Insulated Switchgear (AIS)
single-phase, 2-core ((230/(√3))⁄(0.11/√3/0.11/√3
1A1 kV)), 40kA/1sec, 50Hz, 1050kVp BIL, inductive nos. 6
voltage transformers (IVT) for bus circuit bays.
230kV, 2500A, 40kA/1sec, 50Hz, 1050kVp BIL,
double side break, post type, motor operated
1A2 set 2
disconnectors with earthing switch, for line circuit
(Patuakhali-1 & 2) bays
230kV Post Insulators (whose foundation shall be
1A3 nos. 8
for 230kV, 2500A, 40kA Disconnector)
Flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
1A4 lot 1
required for completing 245kV busbar and
switchgear connection
Steel structures for gantry and equipment
1A5 supports required for completing 245kV busbar lot 1
and switchgear
i) Columns for gantry with single beam nos. 8*
ii) Columns for gantry with double beam nos. 16*
iii) Beam nos. 17*
iv) Steel structure for equipment support lot 1
1B 145kV Air Insulated Switchgear (AIS)
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, single pole operated, SF6 gas
1B1 circuit breakers with spring-stored energy set 2
operating mechanism for Patuakhali-1 & 2 line
circuit bays
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
live tank type, gang operated SF6 gas circuit
1B2 set 1
breakers with spring-stored energy operating
mechanism for transformer bay

Schedule No.4-1
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7

145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL,


live tank type, gang operated SF6 gas circuit
1B3 set 1
breakers with spring-stored energy operating
mechanism for bus coupler circuit bay
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
1B4 set 9
disconnectors without earthing switch, for line &
transformer circuit bays
145kV, 3000A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
1B5 set 2
disconnectors without earthing switch for bus
coupler circuit bays
single-phase, 4-core, single ratio, 145kV,
31.5kA/1sec, 50Hz, 650kVp BIL, post type
1B6 current transformer for line & transformer circuit nos. 9
bays.(1250/1-1-1A, 5P20 30VA & 1250/1A,
10VA, 0.2 class)
single-phase, 2-core, single ratio (3000/1-1A),
145kV, 31.5kA/1sec, 50Hz, 650kVp BIL, post
1B7 nos. 6
type current transformer for bus coupler circuit
bay.
single-phase, 2-core ((132/(√3))⁄(0.11/√3/0.11/√3
kV)), 31.5kA/1sec, 50Hz, 650kVp BIL, inductive
1B8 nos. 9
voltage transformers (IVT) for line & transformer
circuit bays.

single-phase, 2-core ((132/(√3))⁄(0.11/√3/0.11/√3


1B9 kV)), 31.5kA/1sec, 50Hz, 650kVp BIL, inductive nos. 6
voltage transformers (IVT) for bus circuit bays.
120kV rated voltage, 102kV(rms) continuous
operating voltage at 500c, 10kA nominal
1B10 discharge current, 50Hz, Heavy duty station nos. 15
class, gapless metal oxide type, single phase
surge arresters
flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
1B11 lot 1
required for completing 145kV busbar and
switchgear connection.
steel structures for gantry and equipment
1B12 supports required for completing 145kV busbar lot 1
and switchgear .
i) Columns for gantry with single beam nos. 4*
ii) Columns for gantry with double beam nos. 9*
iii) Beam nos. 12*
iv) Steel structure for equipment support lot 1

Schedule No.4-2
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
1C Auxiliary Transformers
1C1 132/11kV, 25/41MVA power transformer set 0
11/0.415 kV, 200kVA three phase outdoor type
auxiliary transformers (to be installed at 145kV
switchyard premise) with associated bushing
CTs, dropout fuses, and steel support structures
1C2 including all necessary connections (with poles, lot 2
clamps, fittings, etc.) from 11kV source of
132/11kV transformer which will be installed
either within the 132kV switchyard or nearly
1500m away from 132kV switchyard
11/0.415 kV, 200kVA three phase outdoor type
auxiliary transformers (to be installed at 145kV
switchyard premise) with associated bushing
1C2 (i) set 2
CTs, dropout fuses, and steel support structures
excluding pole (with clamps, fittings, etc.) &
conductor
1C2 (ii) Pole (with clamp, fittings, etc.) nos. 50*
1C2 (iii) Conductor (conductor size for at least 100A) m 3600*
Control, Protection & Metering Panel,
1D
Substation Automation System
230kV Circuit
Control, metering (for voltage only) and
1D1 Substation Automation System for 230kV line set 1
(only disconnector and PT for each line).
145kV Circuit
Control, Protection, Metering & Substation
Automation System including event recording
function for two (2) sets of overhead line circuits
1D2 set 2
(Patuakhali-1 & 2). Regarding protection, only
over current function is required which is to be
integrated in respective BCU

Schedule No.4-3
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
Control, Protection, Metering & Substation
Automation System including event recording
function for one (01) set of 132/11 kV power
transformer circuits including transformer tap
1D3 changer control. Regarding protection, only over set 1
current function is required which is to be
integrated in respective BCU. Transformer main
differential protection is to be provided by another
contractor
Control, Protection, Metering & Substation
1D4 Automation System including event recording set 1
function for one (1) set of bus coupler circuit
1D5 NA lot 0
1D6 Tariff metering panel lot 1
11kV Circuit
1D6 Tariff metering panel lot 1
1E NA lot 0
1F Multicore LV Control & Power Cables
i) _LV Control Cable lot 1
ii) _LV Power Cable lot 1
1G Earthing and Lightning Protection
1G1 Earthing and Lightning Protection
i) Earthing system for complete substation lot 1
Lighting Protection System for complete
ii) lot 1
substation
Portable (maintenance) earthing equipment
1G2 devices with connectors and telescopic glass set 1
fibre operating pole suitable for plant supplied.

1H Batteries, Chargers and DC Distribution


1H1 110V System
i) 110V Battery Banks, 330Ah set 2
ii) Charger, 90A set 2
iii) 110V DC Distribution panel, MCC type lot 1

Schedule No.4-4
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
1H2 48V System
i) 48V Battery Banks, 150Ah set 2
ii) Charger , 50A set 2
iii) 48V DC Distribution panel, MCC type lot 1
iv) Inverter for 48V system, 1kVA set 1
1I LVAC Distribution
1I1 LVAC Distribution lot 1
1I2 Tariff metering lot 1
1I3 NA lot 0
125A outdoor weatherproof 3-phase with neutral
1I4 and earth switched socket outlet and plug, (as set 1
per IEC 309) drawer type breakers
1J Civil Works, Building and Foundation
Complete civil items required for outdoor works
1J1
including boundary wall
Complete Land development with carried
i) CuM 0
earthfilling**
ii) _Outdoor gantry foundation 230kV switchyard lot 1
a. Foundation for gantry with single beam nos. 8*
b. Foundation for gantry with double beam nos. 16*
_Outdoor equipment foundation 230kV
iii) lot 1
switchyard
iv) _Indoor equipment foundation 11kV switchyard lot 0
_Transformer foundation including oilpit &
v) lot 0
carrage way
vi) _Blast wall lot 0
vii) _Security Boundary Wall lot 0
a. _Retaining Wall on the property line *** lot 0
b. _Normal Wall with slope protection lot 0
1) _Normal Wall *** m 0
2) _Slope Protection lot 0

Schedule No.4-5
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
viii) _Substation Main gate each 1
ix) _Barbed Wire Fencing lot 1
x) _Approach raod lot 1
xi) _Internal road lot 1
xii) _Surface drain lot 1
xiii) _Cable Trench lot 1
xiv) _Switchyard surface finishing lot 1
xv) _Gravel laying lot 1
xvi) _Septic tank, sowak way lot 1
_Pump house including deep tubewell, motor,
xv) lot 1
pump, water reservaoir, water pipe line etc.
xvi) _Gurd house, sentry post, car port lot 1
xvii) _Outdoor gantry foundation 145kV switchyard lot 1
a. _Foundation for gantry with single beam nos. 4*
b. _Foundation for gantry with double beam nos. 9*
_Outdoor equipment foundation 145kV
xviii) lot 1
switchyard
Complete civil items and facilities for a two
1J2 storied main control building & single storied lot 1
Ansar Barack
Complete fire fighting system for transformers
1J3 including water pond/reservoir, pipe network and lot 0
pump
Lighting, small power, air conditioning and
1K
Ventilation
Lighting, small power, air conditioning and
1k1 Ventilation and emergency DC lighting for control lot 1
building

Lighting for ouside building for security, roadway,


1k2 lot 1
switchyard and emergency DC lighting
Fibre Optic Multiplexer Equipment for
1L
Communication and Protection
1L1 Indoor Fibre Optic Multipexer Equipment lot 1
1L2 Fibre Optic cable ,MDF,pigtail cable, termination
lot 1
box etc.

Schedule No.4-6
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
SCADA system for Telecontrol and
1M
Telemetering
1M1 Complete SCADA hardware & software lot 1
Section-2: Extension of 132kV bays at Patuakhali substation
2A 145 kV Air Insulated Switchgear
1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, live tank
type, single pole operated, SF6 gas circuit
2A1 set 2
breakers with spring-stored energy operating
mechanism (for line bay).
2A2 Deleted
2A3 Deleted
145kV, 1250A, 31.5kA/1sec, 50Hz, 650kVp BIL,
double side break, post type, motor operated
2A4 set 2
disconnectors with manual earthing switch for
line circuit bays.
1250A, 31.5kA/1sec, 50Hz, 650kVp BIL, double
2A5 side break, post type, motor operated set 4
disconnectors without earthing switch.
2A6 Deleted
2A7 Deleted
single-phase, 4-core, single ratio, 145kV,
31.5kA/1sec, 50Hz, 650kVp BIL, post type
2A8 nos. 6
current transformer (1250/1-1-1-1A) for line
circuit bays.
2A9 Deleted
single-phase, 2-core ((132/(√3))⁄(.11/√3-0.11/√3
2A10 nos. 6
kV)) , 145kV, 31.5kA/1sec , 50Hz, 650kVp BIL,
2A11 Deleted
120kV rated voltage, 102kV(rms) continuous
operating voltage at 500C, 10kA nominal
2A12 discharge current, 50Hz, Heavy duty station nos. 6
class, gapless metal oxide type, single phase
surge arresters.
flexible bus conductors, insulators, fittings
including all necessary clamps and connectors
2A13 lot 1
required for completing 145kV busbar and
switchgear connection
steel structures for gantry and equipment
2A14 supports required for completing 145kV busbar lot 1
and switchgear
i) Columns for gantry with single beam nos. 4*
ii) Columns for gantry with double beam nos. 6*
iii) Beam nos. 4*
iv) Steel structure for equipment support lot 1

Schedule No.4-7
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
2B Deleted
2C Deleted
2D Control, Protection & Metering Panel
132kV Circuit
Control, Protection, Metering panel for two (2)
2D1 set 2
sets of overhead line circuits
2D2 Deleted
2D3 Deleted
2D4 Deleted
2D5 Tariff metering panel lot 1
2D6 Deleted
2D7 Deleted
2E Deleted
2F Multicore LV Control & Power Cables
i) _LV Control Cable lot 1
ii) _LV Power Cable lot 1
2G Earthing and Lightning Protection
2G1 Earthing and Lightning Protection
Modification of Earthing system for complete
i) lot 1
substation
Modification of Lighting Protection System for
ii) lot 1
complete substation
2G2 Deleted
2H Batteries, Chargers and DC Distribution
Modification of 110V DC Distribution panel, MCC
2H1 lot 1
type
Modification of 48V DC Distribution panel, MCC
2H2 lot 1
type

Schedule No.4-8
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
2I LVAC Distribution
2I1 Modification of LVAC Distribution lot 1
2J Civil Works, Building and Foundation
Complete civil items required for outdoor works
2J1
including boundary wall
Complete Land development with carried
i) CuM 0
earthfilling**
_Outdoor gantry foundation for extension of
ii) lot 1
132kV switchyard
a. _Foundation for gantry with single beam nos. 4*

b. _Foundation for gantry with double beam nos. 6*


_Outdoor equipment foundation for extension of
iii) lot 1
132kV switchyard
iv) _Indoor equipment foundation 11kV switchyard NA
_Transformer foundation including oilpit &
v) NA
carrage way
vi) _Blast wall NA

vii) _Security Boundary Wall with slope protection NA

viii) _Substation Main gate NA

ix) _Barbed Wire Fencing

a) _Dismantling of a portion of Barbed Wire Fencing lot 1

b) _Extension of Barbed Wire Fencing lot 1

x) _Approach raod NA

xi) _Extension of Internal road lot 1

xii) _Extension of Surface drain lot 1

xiii) _Extension of Cable Trench lot 1


xiv) _Extension of Switchyard surface finishing lot 1
xv) _Extension of Gravel laying lot 1

xvi) _Septic tank, sowak way NA

Schedule No.4-9
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7
_Pump house including deep tubewell, motor,
xv) NA
pump, water reservaoir, water pipe line etc.
xvi) _Gurd house, sentry post, car port NA
Complete civil items for modificaion of existing
2J2 lot 1
control room
Lighting, small power, air conditioning and
2K
Ventilation
Extension of Lighting, small power for extended
2k1 lot 1
bays
2k2 NA lot 1
Fibre Optic Multiplexer Equipment for
2L
Communication and Protection
Modification of existing Fibre Optic Multipexer
2L1 lot 1
Equipment
Optical Fiber Cable, juctionBox, MDF, pigtail
2L2 lot 1
cable etc.
SCADA system for Telecontrol and
2M
Telemetering
2M1 Modification of existing SCADA System lot 1
Section-3: Mandatory Spare Parts,Tools & Test
equipment
3A 245 kV Air Insulated Switchgear

Complete SF6 gas, live tank type 245kV, 2500A


i) NA 0
Circuit Breaker (single-pole operation type)

ii) Complete 245 kV, 2500A disconnector switch NA 0


Set of interrupting chamber including insulators,
iii) fixed and moving contacts for 245kV offered type NA 0
circuit breaklers
iv) 245 kV post insulators suitable for disconnector NA 0

Set (three phase) contacts for 245 kV


v) NA 0
disconnector
vi) 196 kV surge arrester NA 0
vii) 245 kV Inductive voltage transformer NA 0
viii) Closing coils NA 0
ix) Tripping coils NA 0

Schedule No.4-10
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7

Motor for 245 kV circuit breaking operating


x) NA 0
mechanism

xi) Motor for disconnector drive NA 0


xii) Coils for Blocking magnet in disconnector drive NA 0

3B 145 kV Air Insulated Switchgear


Complete SF6 gas, live tank type 145kV, 1250A
i) set 1
Circuit Breaker (single-pole operation type)

ii) Complete 145 kV,1250A disconnector switch sets 1


Set of interrupting chamber including insulators,
iii) fixed and moving contacts for 145kV offered type sets 1
circuit breaklers
iv) 145 kV post insulators suitable for disconnector nos. 3

Set (three phase) contacts for 145 kV


v) sets 1
disconnector

vi) 120 kV surge arrester nos. 3

vii) 145 kV capacitive voltage transformer nos. 3

viii) Closing coils nos. 3

ix) Tripping coils nos. 3

Motor for 145 kV circuit breaking operating


x) nos. 1
mechanism
xi) Motor for disconnector drive nos. 1

xii) Coils for Blocking magnet in disconnector drive nos. 3

Schedule No.4-11
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey
Basis (Contract No. PGCB/230KV/PP/SS)
Schedule No. 4. Installation and Other Services

Unit Price1 Total Price1

Country of Local Foreign Local Foreign


Item Description Unit Quantity Currency Currency Currency Currency
origin
Portion Portion Portion Portion
[BDT] [xxxxx] [BDT] [xxx]

1 2 3 4 5 6 7 8=4x6 9=4x7

3C Protection
Line Distance relay with complete protection
i) NA 0
element
Transformer Differential relay with complete REF
ii) NA 0
function
iii) Overcurrent and earth fault relay set 1
iv) Tripping relay (electrical reset) sets 1
v) Trip circuit supervision relay,3 phase sets 1
vi) Bay Control Unit sets 1
vii) Ammeter nos. 3
viii) Voltmeter nos. 3
ix) Annunciator bulbs nos. 60
x) Bulbs for discrepancy switches nos. 30
xi) kWh & kVarh meter nos. 1
3D Test and O & M Equipment
Set of gas filling equipment and 1 bottle of SF6
i) sets 1
gas
ii) SF6 gas sniffer sets 1
Portable vacuum pump suitable for SF6 circuit
iii) set 1
breaker
Contact resistance measurement test set
iv) (suitable for measurement down to 1 µ ohm at set 1
10A d.c.)
5 kV insulation resistance test set (range 0.5 –1.0
v) sets 1
- 2.5 - 5 kV)
Earth resistance test set (range 10-100-1000
vi) sets 1
ohm: min scale division 0.1 ohm)
vii) Clip-on mA meter (for spill current) nos. 1
viii) Portable Earthing Leads sets 2

Total Column 7 to be carried forward to Schedule No. 5 - Grand Summary


* Payment shall be on actual basis
The quantity mentioned above as"CuM/m^3"may increase or decrease during execution stage, but the payment shall
** be at actual basis.

1 Specify currencies in accordance with ITB 19.1 of the BDS.

Schedule No.4-12
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra
and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis
(Contract No. PGCB/230KV/PP/SS)
Schedule No. 5. Grand Summary

Total Price1

Country Local Currency Foreign Currency


Schedule No. Description
of origin Portion Portion
[BDT] [xxx]

1 2 3 8 9

1 Plant and Mandatory Spare Parts Supplied from Abroad2

Plant and Mandatory Spare Parts Supplied from Within the


2
Employer's Country2

3 Design Services
4 Installation and Other Services

Grand Total to be carried forward to Letter of Price Bid

1 Specify currencies in accordance with ITB 19.1 of the BDS.

Taxes and/or duties from Schedules 1 and 2 may be added to the contract price in accordance with GCC 14 (Taxes and Duties)
2
but excluded from bid evaluation in accordance with ITB 36.4.

Schedule No. 5- 1
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at Payra and extension
of 132 kV bays at existing Patuakhali 132/33kV Substation on Turnkey Basis (Contract No.
PGCB/230KV/PP/SS)
Schedule No. 6. Recommended Spare Parts

Unit Price1 Total Price1


Foreign Foreign
Country Local Currency Currenc Local Currency Currency
Item Description Unit Quantity
of origin Portion EXW y Portion EXW Portion
[BDT] Portion [BDT] CIP
CIP [xxx]
1 2 3 4 5 6 7 8=5x6 9=5x7
245 kV switchgear,
equipment

145 kV switchgear,
equipment
connection and
steel structures

1 Specify currencies in accordance with ITB 19.1 of the BDS.

Schedule No.6-1
POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE C

TIMES FOR DELIVERY AND COMPLETION

The individual dates are all contractually binding.

The times given under Column D are the commissioning target dates at present planned to be
achieved and may be the subject of mutual adjustment.

Column A details the earliest dates by which access to site can be given for storage purposes.
The times entered under column B are to be the dates guaranteed for arrival at Site of the first
shipment of parts for the circuits in question being also the dates when the contractor requires
access to the Site for plant erection, to the extent necessary to enable him to proceed with
work to meet the dates under column C guaranteed for complete delivery, erection and
commissioning of the Plant.

The times include all necessary control, relay, metering, auxiliary power ancillary equipment
to enable the respective circuit or item of plant to be completely commissioned and put into
commercial operation, together with such other associated equipment, e.g. busbars, etc as will
ensure that subsequent shutdown are unnecessary or at least only of a temporary or short time
nature.

The dates assume an order is placed by . . . . . . . . . . . . . . . . . . . . .


(to be advised or stated by Bidder)

A* B* C* D*
Lattest Guaranteed Guaranteed Target
Access Arrival of first Completion Completion
Site Permitted shipment
Payra & 7 days from the
Patuakhali date of contact 12
signing

* Time in months, after contract effective date.

Preliminary SLD, overall layout and control building drawings of the Technical Specification
shall be provided within 2.0 months of the contract commencing date with final drawings
following one month later.

Schedule C: Times for Delivery and Completion SC-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE D

MANUFACTURERS, PLACES OF MANUFACTURE AND TESTING

The following Subcontractors and/or manufacturers are proposed for carrying out the item of
the facilities indicated.

Bidders are free to propose more than one for each item.

Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection
1 245 kV AIS SWITCHGEAR

Steel Structure

Disconnector

Instrument Transformer (PT)

2 145 kV AIS SWITCHGEAR

Circuit Breaker

Disconnector

Instrument Transformer (CT)

Instrument Transformer (PT)

Surge Arrester

Steel Structure

3 NA

Schedule D: Manufactures, place of manufacture and testing SD-1


Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection
4 11/0.415 kV AUXILIARY
TRANSFORMERS

DELETED

DELETED

5 PROTECTION
METERING AND
CONTROL

Panels

Instruments

Protective relays

Substation automation
system

Meters

Transducers

Remote Terminal Unit (RTU)

6 FLEXIBLE CONDUCTOR,
RIGID TUBULAR BUS

245kV

Rigid Tubular Bus (N/A)

Flexible Conductor

Insulator

Fittings and Clamps

145kV

Rigid Tubular Bus (N/A)

Flexible Conductor

Schedule D: Manufactures, place of manufacture and testing SD-2


Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection
Insulator

Fittings and Clamps

7 DC EQUIPMENT

Batteries

Chargers

Distribution Boards

8 415 kV SWITCH FUSE


BOARD

9 MULTICORE CABLES

PVC Insulated Cables

Cable trays

8 EARTHING

Copper tape

Insulated copper
Conductor

10 FIBRE OPTIC
MULTIPLEXER
EQUIPMENT

11 TELEPHONE SYSTEM

12 SITE ERECTION AND


COMMISSIONING BY
CIVIL WORKS

Design to be performed
by:-
Constructed by:-

Schedule D: Manufactures, place of manufacture and testing SD-3


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE E

TECHNICAL PARTICULARS AND GUARANTEES

General

245kV and 145kV AIR INSULATED SWITCHGEAR (AIS)

Sl. No. Description Unit 245kV 132kV


1. Site Condition
Max. Altitude above sea level m
Max. Ambient temperature outdoor ℃
Min. Ambient temperature outdoor ℃
Max. Ambient relative humidity %
Max. Seismic acceleration at floor level
- horizontal g
- vertical g
2. Electrical Data
Rated Voltage kV
Rated Frequency Hz
Insulation Level
- lightning impulse withstand kVp
- switching impulse withstand kVp
- 50 Hz withstand 1 minute kV
Rated continuous current at 40℃
ambient temperature
- main busbar and bus coupler A
- transformer bay A
- line bay A
Rated short time withstand
- current kA
- duration Sec
Rated peak withstand current kA
3. Secondary Circuit
Auxiliary voltage
- for control and signal V dc
- for remote control V dc
Technical particulars & Guarantees SE-1
- for heating V ac
- tolerances %

PART 1 - SWITCHGEAR

1.1. HV OUTDOOR CIRCUIT BREAKERS

Bidders Data
Sl.
No. 245kV
Description Unit
(NOT 145kV
APPLICABLE)

1 Manufacturer

2 Type Reference (Manufacturer’s designation)

3 Number of Poles

4 Rated Voltage

5 Rated frequency

6 Rated normal current-feeder/transformer/bus A


coupler

7 Rated breaking currents: kA rms


Line charging
Cable charging
Small inductive

8 Rated short-circuit breaking current kA,rms

9 First pole to clear factor

10 Rated transient recovery voltage for terminal faults kV


if other than standard

11 Rated characteristics for short-line faults

12 Rated short-circuit making current kA

13 Rated operating sequence

14 Rated duration of short-circuit s

15 Rated out of phase breaking current kA

16 Rated opening time ms

17 Rated break time ms

18 Rated closing time ms


Maximum arcing time of any duty cycle to IEC 56
19 ms

20 Is circuit-breaker re-strike free Yes/No


21 Test Authority

22 Test Certificate ref.

23 Rated short time withstand current kA

24 Rated duration of short-circuit s

Technical particulars & Guarantees SE-2


Bidders Data
Sl.
No. 245kV
Description Unit
(NOT 145kV
APPLICABLE)

25 Rated peak withstand current kA

26 Rated insulation levels:-

26.1 Lightning impulse withstand to earth kV pk

(wave shape 1.2/50µs)

26.2 Lightning impulse withstand across open kV pk

contacts (wave shape 1.2/50µs)

26.3 Power frequency voltage withstand to earth kV rms

26.4 Power frequency voltage withstand across open kV rms


contacts

27 Rated supply pressure of gas for interruption MPa (g)

28 Limits for correct operation


max MPa (g)
min MPa (g)

29 Frequency of operation yr-1

30 Operating mechanism Manufacturer

31 Mechanism Type:

32 Trip free/or fixed trip

33 Is lockout facility fitted?

34 Closing supply
Volts max/min V
Amps A

35 Rated supply voltage of shunt opening release V

36 Current required at rated supply voltage to open A


circuit-breaker
37 Spring charging motor
- Current A
- Voltage AC/DC V

38 Number of auxiliary switch contacts


- normally open
- normally closed
- adjustable

39 Other auxiliary loads:


Voltage:
Current:

40 Degree of Protection for


(a) auxiliary circuits
(b) moving parts

Technical particulars & Guarantees SE-3


Bidders Data
Sl.
No. 245kV
Description Unit
(NOT 145kV
APPLICABLE)

41 Minimum clearances in air:


(a) between phases mm
(b) phases to earth mm
(c) across interrupters mm
(d) live parts to ground level mm

42 Minimum creepage
(a) to earth mm
(b) across interrupter terminals mm

43 Radio interference voltage μV

44 Guaranteed maximum gas leakage % per


annum

45 Number of interrupters per pole

46 Material of interrupter chamber

47 Wall thickness of interrupter chamber mm

48 Material of contact surfaces primary arcing

49 Length of each break mm

50 Length of stroke mm

51 Operating rod for moving contact(s) material


dimensions, etc.

52 Weight of circuit-breaker unit complete kg

53 Maximum shock load imposed on floor or


foundations when opening under fault conditions
(state whether tension or compression)
kg

54 Quantity of gas in complete three-phase circuit


breaker

55 Maximum pressure rise in circuit breakers due to


the making or breaking of rated current

56 Routine pressure test on circuit-breaker tanks or


containers

57 Pressure type test on circuit-breaker tanks or


containers

58 Interrupting gas pressure at 20C Normal

59 Limits of gas pressure at 20C Maximum


Minimum

60 Period of time equipment has been in commercial


operation

61 Number of the same type of circuit breakers


supplied to date

62 Pre insertion Resistor(PIR) for 400kV OHM


Technical particulars & Guarantees SE-4
1.2 DISCONNECTORS AND EARTHING SWITCHES

Bidders Data
Sl.
No. 145kV
Description Unit 245kV

1 Manufacturer

2 Type Number

3 Operating type

(a) horizontal/vertical break

(b) Pantograph

(c) Number of support insulation for pole

(d) Number of breaks per pole

(e) Material of contact surfaces

(f) Type of Contacts

4 Rated normal current A

5 Rated short time withstand current kA, rms

6 Rated duration of short time current s

7 Rated peak withstand current kA pk

8 Rated insulation levels:

8.1 Lightning impulse withstand to earth


(waveshape: 1.2/50µs) kV pk

8.2 Lightning impulse withstand across open contacts kV pk


(waveshape: 1.2/50µs)

8.3 Power frequency voltage withstand to earth kV rms

8.4 Power frequency voltage withstand across open kV rms


contacts

9 Method of operation

10 Type of operating mechanism


manual/power

11 Operating power

12 Voltage/pressure rated V/MPa(g)


max V/MPa(g)
min V/MPa(g)

13 Consumption electric A

14 Operating time: open max ms


min ms

15 Operating time: close max ms


min ms

16 Manual operating torque kNm


Technical particulars & Guarantees SE-5
Bidders Data
Sl.
No. 145kV
Description Unit 245kV

17 Load switching capability A

18 Mechanical Terminal Load N

19 Insulator Creepage mm

20 Radio interference voltage mV

21 Number of auxiliary switches


- normally open
- normally closed
- adjustable

22 Other auxiliary loads


- voltage
- current

23 Mechanical endurance:

Number of operations carried out for mechanical


operation test

24 Degree of protection for


1) auxiliary circuits
2) moving parts

25 Total weight of three pole disconnector complete kg

26 Type test certificate date/reference

27 Period of time equipment has been in commercial


operation

28 Number of the same type of disconnectors supplied


to date

1.3 CURRENT TRANSFORMERS

Sl. Bidders Data


No. Description Unit 245kV (NA)
145kV

1 Manufacturer/type

2 Rated primary current A rms

3 Rated secondary current A rms

4 Rated frequency Hz

5 Highest voltage for equipment kV

6 Rated insulation level - primary winding kV

7 Lightning impulse withstand kV pk

8 (a) Power frequency withstand (dry) kV rms


(b) Power frequency withstand (wet) kV rms

9 Insulator creepage (phase to earth) mm

10 Electrical dissipation factor at power frequency test


voltage

Technical particulars & Guarantees SE-6


11 Radio influence voltage measured at U/3 1 MHz µV

12 Rated short term thermal current for 1s A rms


13 Rated short term thermal current for 3s A rms

14 Rated dynamic current kA pk


15 Insulation class

16 Number of secondary windings


Location of core
Core 1 Rated output
Accuracy class *
Accuracy limit factor
Core 2 Rated output
Accuracy class *
Accuracy limit factor
Core 3 Rated output
Accuracy class *
Accuracy limit factor
Core 4 Rated output
Accuracy class *
Accuracy limit factor
Class x winding:
- Rated knee point emf V
- Exciting current
*including instrument security factor where
A
applicable
17 Is earth screen fitted between primary and
secondary windings
18 Type test certificate ref/date

1.4 VOLTAGE TRANSFORMERS


Description Bidder’s Data
Sl. Unit
No. 245kV
145kV

1 Manufacturer -

2 Type No. -

3 Transformer type -

4 Rated primary voltage kV rms

Rated secondary voltage for each secondary


5 kV rms
winding

Accuracy class for each winding


6 Rated output for each winding VA
Rated volt-ampere rating for each winding VA

7 Rated voltage factor

8 Type of Insulation

9 Maximum temperature rise C

10 Short-circuit withstand capability kA rms

11 Primary insulation

Technical particulars & Guarantees SE-7


Description Bidder’s Data
Sl. Unit
No. 245kV
145kV

11.1 Lightning impulse withstand dry kV pk

11.2 (a) Power frequency withstand wet kV rms


(b) Power frequency withstand dry kV rms

12 Partial discharge magnitude pC

13 Total external creepage distance mm

Radio influence voltage measured at


14 µV
11 Um/3 at 1 MHz

15 Total installed weight kg

16 Capacitor

16.1 High voltage capacitor (C1) pF

16.2 Intermediate - voltage capacitor (C2) pF

16.3 Total Capacitor (Cn) pF

17 Open circuit intermediate voltage kV


18 Rated open-circuit intermediate voltage kV
19 Reference range of frequency +/- Hz
o
20 Reference range of temperature C

21 Protective device to limit overvoltage

1.5 SURGE ARRESTERS


Bidder’s Data
Sl. Description Unit
No. 196kV (NA) 120kV

1 Manufacturer

2 Model Number

3 Type:

4 Continuous operating voltage kV rms

5 Rated voltage kV rms

6 Standard nominal discharge current kA

7 Reference current at ambient temperature mA

8 Reference voltage for above kV rms

9 Steep current impulse residual voltage kV pk

Technical particulars & Guarantees SE-8


10 Lightning impulse residual voltage at
5kA kV pk
10kA kV pk
20kA kV pk

11 Duty Class

12 Discharge class

13 Pressure relief class

14 Nominal diameter of resistor blocks mm

15 Number of resistor blocks connected electrically


in parallel

16 Number of separately housed units per phase

17 Overall height of arrester (without supporting m


structure)

18 Overall height of arrester including grading ring mm


if applicable

19 Clearances:
phase to earth (from centre line) mm
phase to phase (centre line to centre line) mm

20 Overall Weight of arrester (without supporting kg


structure)

21 Maximum cantilever strength Nm

22 Maximum force due to wind (at maximum Nm


specified gust speed)

23 Minimum creepage distance over insulator mm


housing

24 Insulator shed profile - Reference Document

25 Terminal palm details - Drawing No.

26 Earthing terminal - Drawing No.

27 Type & Description of surge monitoring device

28 Type test certificate ref/date

29 Number of the same type of surge arresters


supplied to date

Technical particulars & Guarantees SE-9


PART 2 – TRANSFORMERS

2.1 NA

2.2 11/0.415 kV AUXILIARY TRANSFORMERS

Sl. No. Description Unit Bidder's Data

1 Rated short time (10 second) current neutral A

2 Current density in the interconnected star winding at


rated short time current A/mm2

3 Current density in the


interconnected star winding
-at CMR and A/mm2
-5 second fault rating simultaneously A/mm2

4 Maximum flux density in


core iron at normal
voltage and frequency Tesla

5 CMR of lower voltage star winding kVA

6 No load losses kW

7 Load losses at 75C at CMR


of lower voltage winding kW

8 Impedance voltage at CMR


of lower voltage winding
between HV and LV winding %
Total range of variation of off load
9
ratio ....... plus %
ratio ...... plus %
Size of step

SE-10
10 Resistance of higher voltage ohms per
winding at 75C phase

11 Zero phase sequence impedance at 75C with LV ohms per


windings open circuited phase

12 Total oil required litres

13 Weight of complete transformer (including oil) tonnes

14 Height from base to bottom of neutral bushing


insulator mm

PART-3

3.1 XLPE POWER CABLES (NA)


(Schedule to be completed if manufacture not to BS.6346)

SE-11
3.2 AUXILIARY POWER AND MULTICORE CONTROL CABLES

Item 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Number of core
Core section mm2
Core diameter mm
Conductor insulation mm
Type of filler
Type of tape
Sheath thickness mm
Sheath outer diameter mm
Armour wires no.
Armour wires diameter mm
Outer covering type
Outer covering thickness
Completed cable:
diameter mm
weight per metre kg
maximum drum length m
Minimum installed bending
radius mm
Maximum conductor temperature C

SE-12
PART 4 - DC EQUIPMENT

4.1 110 V BATTERIES AND CHARGERS

Sl. N
Description Unit Bidder’s Data
o.
Battery
1 Manufacturer
2 Type
3 Electrolyte
4 Nominal voltage V
5 Capacity at 5 hour rate Ah
6 Number of cells
7 Float voltage per cell V
8 Battery voltage at end of the duty cycle V
9 Normal charging rate A
10 Maximum charging rate A
11 Ampere-hour efficiency at ten hour rate %
12 Ampere-hour efficiency at one hour rate %
13 Dimensions of cells mm
14 Dimensions of battery complete mm
15 Weight of cell complete with electrolyte kg
16 Internal resistance per cell when fully charged ohms
17 Material of battery case
Charger
18 Manufacturer
19 Type
20 AC input voltage and range kVA
21 DC output of charger kW
22 Type of DC voltage control
23 Range of DC voltage V
24 Output current sharing facility
(for parallel operation of chargers)
25 Regulation %
Charger Cubicle Complete
26 Manufacturer
27 Overall dimensions mm
28 Total weight Kg
DC Switchboard
29 Manufacturer
30 Type
31 Busbars:
- maximum current rating A
- dimensions mm
32 Boost charge contactors:
- manufacturer
- maximum current rating

Technical particulars & Guarantees SE-13


Sl. N
Description Unit Bidder’s Data
o.
- coil rating
- method of interlocking
33 Alarm relays:
- manufacturer
- type and reference
- power consumption:
a) quiescent A
b) operated mA
34 Number and rating of distribution circuits
35 Overall dimensions mm
36 Total weight kg

4.2 48 V BATTERIES AND CHARGERS

Sl. N
Description Unit Bidder’s Data
o.
Battery
1 Manufacturer
2 Type
3 Electrolyte
4 Nominal voltage V
5 Capacity at 5 hour rate Ah
6 Number of cells
7 Float voltage per cell V
8 Battery voltage at end of the duty cycle V
9 Normal charging rate A
10 Maximum charging rate A
11 Ampere-hour efficiency at ten hour rate %
12 Ampere-hour efficiency at one hour rate %
13 Dimensions of cells mm
14 Dimensions of battery complete mm
15 Weight of cell complete with electrolyte kg
16 Internal resistance per cell when fully charged ohms
17 Material of battery case
Charger
18 Manufacturer
19 Type
20 AC input voltage and range kVA
21 DC output of charger kW
22 Type of DC voltage control
23 Range of DC voltage V
24 Output current sharing facility
(for parallel operation of chargers)
25 Regulation %
Charger Cubicle Complete

Technical particulars & Guarantees SE-14


Sl. N
Description Unit Bidder’s Data
o.
26 Manufacturer
27 Overall dimensions mm
28 Total weight Kg
DC Switchboard
29 Manufacturer
30 Type
31 Busbars:
- maximum current rating A
- dimensions mm
32 Boost charge contactors:
- manufacturer
- maximum current rating
- coil rating
- method of interlocking
33 Alarm relays:
- manufacturer
- type and reference
- power consumption:
c) quiescent A
d) operated mA
34 Number and rating of distribution circuits
35 Overall dimensions mm
36 Total weight kg

Technical particulars & Guarantees SE-15


PART 5 - LV AC EQUIPMENT

Sl.No. Description Bidder's Data

5.1 Distribution Board

1 Manufacturer

2 Manufacturer’s type designation

3 Rating Amps

4 Fault Rating for 1 sec KA

5 Voltage Volts

5.2 Miniature Circuit Breakers

1 Manufacturer

2 Type

3 Rating Amps

4 Fault Rating for 1 sec kA

PART 6 - SUBSTATION AUTOMATION SYSTEM

Sl. No.
Description Unit Bidder’s Data

1 General Requirement:
Standards to be complied with Substation Automation system
Test Ca. Damp heat steady state
Test Db and guidance; Damp heat cyclic
Digital I/O, Analogue I/O dielectric Tests
Digital I/O, Surge withstand test
Radio interference test
Transient fast burst test
Static Discharge
Electromagnetic fields
Temperature range (min/max) ℃
Relative humidity %
Intelligent Electronic Devices (IED’s)
- serial communication interface included?
- Protection & Control IED’s connected same bus?
- self monitoring
- display of measured values
- remote parameterization
- disturbance record upload and analysis

Technical particulars & Guarantees SE-16


Sl. No.
Description Unit Bidder’s Data

Availability Calculation shall be furnished for each


equipments as well as for the entire system

Main system, HMI, Gateway, IEC have dual communication port


SNTP server provide GPS time synchronization to HMI, Gateway, IE
D
System topology
2 Detailed Requirements:
Manufacturer of Substation Automation System
Name and type of product in supplier’s catalogue
Origin of manufacturer
Number of years of proven field experience of offered system. Yrs
(Note: proof of experience should be furnished. The
components used in the offered system and those with
field experience should be the same)
Design life of substation Automation System Yrs
Manufacturers quality assurance system
Dimensions of cubicle:
- Width mm
- Depth mm
- Height mm
- Floor load N/㎡
3 Station Level Equipment:
Station Controller
MTBF (Mean time between Failures)
MTTR (Mean time to repair)
Station computer dual connection to Ethernet
Dual wide screen monitor inch
Dual Station Computers Provided in redundant hot
Standby
Hot standby take over time
Annunciator for Station PC system software
Number of years of proven field experience of offered
Yrs
software
Operating System
All standard picture as per spec included in HMI
Process Status Display & Command Procedures
Event processing as per spec
Alarm processing as per spec
Reports as per spec
Trend Display as per spec
Graphical Fault l information receiving function
Disturbance & Fault recording and analysis with graphical format
User Authority levels as per spec
System supervision & monitoring as per spec
Automatic sequence control as per spec

Technical particulars & Guarantees SE-17


Sl. No.
Description Unit Bidder’s Data

4 Gateway to National Load dispatch Center


Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
Number of years of proven filed experience of offered unit Yrs
Insulation tests
Fast disturbance tests
Industrial environment
Industrial grade hardware with no moving parts
(PC based gateway is not accepted)
Design life of offered equipment Yrs
Redundant communication channel
Redundant CPU
Redundant DC/DC Supply
MTBF (Mean time between Failures)
MTTR (Mean time to repair)
Dual connection to Ethernet
5 Station Bus:
Type of bus/protocol
Physical Medium
Dual connection
Transfer rate/bus speed
6 Interbay Bus
Type of bus/protocol
Physical Medium
Transfer rate/bus speed
7 Printer server
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
MTBF
8 Event Printer
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
Print speed
Paper feed/width
Character set
MTBF
9 Hard Copy colour Printer
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
Print speed
Colours
Resolution

Technical particulars & Guarantees SE-18


Sl. No.
Description Unit Bidder’s Data

Character set
MTBF
10 Master Clock GPS (Global Positioning System) Receiver:
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
Stability
MTBF
11 Bay control Unit - HV
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
Number of years of proven field experience of offered unit Yrs
Separate Bay controller unit provided for each bay & feeder
Type of bay controller offered HV/MV
Select Before Operate with Open Execute & Close Execute
Single bit dependence
Interlocking, bay & Station wide
Dual connection to Ethernet sw
Synchrocheck function:
- Maximum Voltage difference
- Maximum Frequency difference
- Maximum Phase difference
Double command blocking
Independent settable parameter groups
Local Display Unit
Sequence of event recorder:
- Events
- Time resolution
Disturbance recorder function
Disturbance record transfer function
Comtrde file generation
Comprehensive self-supervision
Battery free backup of events and disturbance records
Insulation tests
Fast disturbance tests
MTBF
MTTR
Temperature range: IED’s
- Operation
- Transport and storage
Relative humidity:
- Operating max./min. %
- Transport and storage %
12 Back up control mimic -HV
Manufacturer

Technical particulars & Guarantees SE-19


Sl. No.
Description Unit Bidder’s Data

Name and type of product in supplier’s catalogue


Origin of manufacturer
Control functionality:
Control of breaker as well as all isolators/earthing switch
(Control functionality should not be affected if bay controller fails)
Key-Locked
Interlock override function
Separate backup control mimic provided for each bay & feeder
13 Bay Control Unit – LV(Only for 11kV Transformer Bay)
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer
Number of years of proven field experience of offered unit Yrs
Separate Bay controller unit provided for each bay & feeder
Control functionality implementation in software:
Select before Operate with Open Execute & Close Execute
Interlocking, Bay & Station Wide
Dual connection to Ethernet sw
Synchrocheck function
- Maximum Voltage difference
- Maximum Frequency difference
- Maximum Phase difference
Local Display Unit
Sequence of event recorder
- Events
- Time resolution ms
Disturbance recorder function
Disturbance record transfer function
Comtrde file generation
Comprehensive self-supervision
Insulation tests
Fast disturbance tests
MTBF
MTTR
Temperature range: IED’s
- Operation
- Transport and storage
Relative humidity:
- Operating max./min. %
- Transport and storage %
14 Back up control mimic - LV(Only for 11kV Transformer Bay)
Manufacturer
Name and type of product in supplier’s catalogue
Origin of manufacturer

Technical particulars & Guarantees SE-20


Sl. No.
Description Unit Bidder’s Data

Control functionality:
Control of breaker as well as all isolators/earthing switches
Separate backup control mimic provided for each bay & feeder
15 System Performance:
Exchange of display (First reaction) s
Presentation of a binary change in the process display s
Presentation of an analogue change in the process display s
From order to process output s
From order to updated of display S
16 Deviations
Please state all deviations from specification

PART 7 - FIBRE OPTIC MULTIPLEXER EQUIPMENT

SL.
Description Unit Bidder’s Data
No.
1 GENERAL:
Manufacturer
Model No.
Type
Type of multiplexer
Complying to ITU-T rec.
Transmission Capacity Mbit/s
Access capacity on 64 kbit/s channels
Access capacity on 2 Mbit/s channels
Redundant central processor
Digital cross connect function
2 Available AGGREGATES:
Optical aggregates (ITU-T G.957)
3 Available TRUNK INTERFACES:
HDB3, 2 Mbit/s interfaces per module No.
Complying to ITU-T rec.
HDSL, 2Mbit/s interface: no of copper wires No.
- Capacity on 2Mbit/s or on 1Mbit/s ch
- Capacity selectable ch / pair of wir
e
4 Available USER INTERFACES
5 Voice interfaces for trunk lines:
1 + 1 com path protection, available for all
Analogue, 4wire with E&M: Input level dBr
Output level dBr
Analogue, 2wire with E&M: Input level dBr
Output level dBr
Digital, 2Mbit/s CAS or PRI
6 Voice interfaces for remote Subscriber:
2wire, subscriber side dBr
2wire, PABX side dBr
7 Integrated teleprotection

8 Interface for Commands:


Number of independent commands No.

Technical particulars & Guarantees SE-21


SL.
Description Unit Bidder’s Data
No.
Transmission time max. ms
Signal voltage Vpeak
1 + 1 com path protection
9 Interface(s) for Differential Protection:
Electrical interface: G.703 kbit/s
Optical Interface kbit/s
10 Data: channels per module
1 + 1 com path protection, available for all
V.24/V.28 (RS-232): up to 38.4kbit/s No.
V.11/X.24 (RS-422): 64kbit/s No.
V.35: 64kbit/s No.
V.36 (RS-449): 64kbit/s No.
G.703: 64kbit/s No.
Ethernet: 10/100 BaseT No.
WAN capacity Mbit/s
Protocols Mbit/s
11 Integrated alarm gathering module:
Number of external alarms per module No.
Auxiliary power supply for ext. contacts
12 Network Management System
Type/Name of configuration tool
For fault / configuration management
For local / remote operation
Data communication network (DCN)
13 Ambient Conditions:
Storage: ETS 300 019-1-1, class 1.2 °C / % hum
Transport: ETS 300 019-1-2, class 2.2 °C / % hum
Operation: ETS 300 019-1-3, class 3.1E °C / % hum
14 Power Supply
Operation VDC
Fully redundant power supply

Bidder shall provide all necessary information which deem to be necessary to complete the
project in all respects.

PART 8 – DIGITAL PABX EQUIPMENT


(NOT APPLICABLE)

PART 9 – PROTECTION

9.1 230 kV Line Distance Relay for Patuakhali #1, 2


SL.
Description Unit Bidder’s Data
No.
1 Manufacturer
2 Type designations
3 Phase switched
4 Zone switched
5 Number of zones
Shape of impedance characteristic:
6
Zone 1/Zone 2/Zone 3
Reverse looking element
7
(blocking signal initiation)

Technical particulars & Guarantees SE-22


8 Sensitivity:
Minimum operation current:
8.1 A
Earth faults/Phase faults
Minimum necessary voltage for fault at Zone 1 r
8.2 each point (if applicable): V
Earth faults/Phase faults
Minimum Zone 1 ohmic impedance to which
8.3 ohms
relay can be set
Maximum Zone 1 ohmic impedance to which
8.4 ohms
relay can be set and maintain accuracy
Minimum Zone 2 ohmic impedance to which
8.5 ohms
relay can be set
Maximum Zone 2 ohmic impedance to which
8.6 ohms
relay can be set and maintain accuracy
Maximum Xone 3 ohmic reach:
8.7 ohms
Forward reach/Reverse reach
Arc forward and reverse reach setting
9 Yes/No
independent of each other?
Can resistance and reactance reaches be set
10 Yes/No
independent of each other
11 Directional sensitivity V
12 Current transformer requirements
13 Voltage transformer requirements
14 Back up Zone time ranges: Zone 2/ Zone 3 sec.
15 Method used to clear close-in faults:
which occur when line is already energized in
service
which exist upon line energisation
Has distance protection previously been used in
the type of blocking scheme offered for this
16 contract? Yes/No
If yes:
number of scheme in service/year first in service
Approximate number of years distance relay in s
ervice (A complete reference list should be
17
submitted stating client, system voltage and
year of going into service).
18 Zone 1 operating times on fault position:
Earth faults: 0, 50, 90% of relay setting ms (min./max.)
Phase to phase faults: 0, 50, 90% of relay setting ms (min./max.)
Three phase faults: 0, 50, 90% of relay setting ms (min./max.)

9.2 230 kV Busbar Protection (Payra)


SL.
Description Unit Bidder’s Data
No.
1 Manufacturer
2 Type designations
3 Operating principle, e.g. high impedance
4 Minimum relay setting A
Sensitivity of scheme (allowing for CT
5
magnetizing current, etc.)
Maximum through fault current at which
6 A
protection is stable
Technical particulars & Guarantees SE-23
7 Current transformer requirements
8 Estimated magnetizing current at relay setting A
9 Operating time at twice relay minimum setting ms
Operating time at ten times relay minimum
10 ms
setting

9.3 Breaker Failure Protection


SL.
Description Unit Bidder’s Data
No.
1 Manufacturer
2 Type designations
Setting of current elements:
3 A
Phase faults/Earth faults
4 Timer setting range sec.
Burden of relay at minimum current setting at
5 ten times CT secondary rated current during: VA
Phase faults/Earth faults
6 Operating time/Reset time ms

9.4 Tripping Relays


SL.
Description Unit Bidder’s Data
No.
1 Manufacturer
2 Type designations
3 Nominal operating voltage V
4 Minimum operating voltage V
5 Operation indicator
6 Operating time at nominal voltage ms
Contact rating:
Make and carry continuously VA
7 Make and carry for 3 sec. VA
Break: resistive W
inductive VA

9.5 Overall Fault Clearance Times


SL.
Description Unit Bidder’s Data
No.
1 132 kV Busbar Faults:
Main protection relay operating time ms
Auxiliary and tripping relay time (where used) ms
Circuit breaker time ms
Total ms
2 132/11 kV Transformer Faults:
Main protection relay operating time ms
Auxiliary and tripping relay time ms
Circuit breaker time ms
Total ms
3 Ishurdi-Ruppur 132 kV Line Faults:
3.1 Fault Clearance at Ishurdi:
Distance protection maximum operating time ms
Permissive scheme time delay ms
Technical particulars & Guarantees SE-24
Auxiliary relay time (where used) ms
Circuit breaker time ms
Total ms
3.2 Fault Clearance at Ruppur
Distance protection maximum operating time ms
Permissive scheme time delay ms
Auxiliary relay time (where used) ms
Circuit breaker time ms
Total ms

PART 10– OTHERS

Sl. No.
Description Unit 145kV 12kV

1 Structural Steel
Type and standard specification
Manufacturer and country
Kg/ m
Minimum yield strength
m2
Kg/ m
Ultimate tensile strength
m2
2 Copper Conductors for Earthing system
Type and standard specification
Manufacturer and country
Conductor material
Size of conductors
mm2
(Solid copper rods)
Size of conductors (Flat copper bars)
mm
(Width×Thickness×Bundles)
Rated current A
Short time withstand current kA rms
Peak withstand current kA pk
3 High Voltage Bus Work
3.1 Switchyard Conductor
3.1.1 Tubular Conductors for Busbar
Type and standard specification
Manufacturer and country
Inner diameter mm
Outer diameter mm
Rated continuous current (site rating) A rms
Temperature rise at rated current ℃
Rated short time current kA rms
Peak withstand current kA pk
Weight kg/m
Moment of inertia kg-m2
3.1.2 Busbar conductor for Baybus
connetion
Type and standard specification

Technical particulars & Guarantees SE-25


Sl. No.
Description Unit 145kV 12kV

Manufacturer and country


Conductor type
Conductor size
Standing
- No. of Al wires
- Dia. Of each wire mm
Overall conductor dia. mm
Cross-sectional area mm2
Rated continuous current (site rating) A rms
Temperature rise at rated current ℃
Rated short time current kA rms
Peak withstand current kA pk
Rated ultimate tensile strength kN
Mass, nominal kg/m
No. of conductors per bundle
Bundle configuration
Bundle spacing
3.1.3 Flexible Bus Conductor
Type and standard specification
Manufacturer and country
Conductor type
Conductor size
Standing
- No. of Al wires
- Dia. Of each wire mm
Overall conductor dia. mm
Cross-sectional area mm2
Rated continuous current (site rating) A rms
Temperature rise at rated current ℃
Rated short time current kA rms
Peak withstand current kA pk
Rated ultimate tensile strength kN
Mass, nominal kg/m
No. of conductors per bundle
Bundle configuration
Bundle spacing
3.1.3 Shield Wire
Type and standard specification
Manufacturer and country
Dia. of galvanized steel wire mm
Stranding
- No. of Al wires
- Dia. Of each wire mm
Grade of wire
Weight of wire kg/km
Minimum breaking strength of wire kN

Technical particulars & Guarantees SE-26


Sl. No.
Description Unit 145kV 12kV

3.2 Insulators
3.2.1 Station Post Type (for rigid Busbar)
Type and standard specification
Manufacturer and country
Insulator unit, length/height mm
No. of units in each insulator
Power frequency flashover voltage
- Dry kV
- Wet kV
Impulse flashover voltage
- Positive kV
- Negative kV
Power frequency withstand voltage
- 1 min. dry kV
- 10 sec. wet kV
Power frequency puncture voltage kV
Switching impulse withstand voltage, wet kV pk
Lightning impulse withstand voltage kV pk
Radio interference voltage
- Test voltage to ground
kV rms
- Max. RIV at 1.1xUr//3 line to ground
micro
voltage, when tested as per IEC 6069
V
4
Leakage distance mm
Mechanical values, failing load (min.)
- Cantilever strength N
- Tensile strength N
- Torsional strength N-m
- Compressional strength N
- Combined electrical and mechnc N
al strength
- Impact strength N-m
3.2.2 String Type
Type and standard specification
Manufacturer and country
Insulator unit, length mm
No. of units in each insulator
No. of insulator strings per conductor
(at each end)
Dia. of disc mm
Disc spacing mm
Power frequency flashover voltage
- Dry kV
- Wet kV
Impulse flashover voltage
- Positive kV
- Negative kV

Technical particulars & Guarantees SE-27


Sl. No.
Description Unit 145kV 12kV

Power frequency withstand voltage


- 1 min. dry kV
- 10 sec. wet kV
Power frequency puncture voltage kV
Switching impulse withstand voltage, wet kV pk
Lightning impulse withstand voltage kV pk
Dry arcing distance mm
Radio interference voltage
- Test voltage to ground
kV rms
- Max. RIV at 1.1xUr//3 line to ground
micro
voltage, when tested as per IEC 6069
V
4
Leakage distance mm
Mechanical values, failing load (min.)
- Tensile strength N
- Torsional strength N-m
- Compressional strength N
- Combined electrical and mechanical N
strength
- Impact strength N-m
3.3 Clamps and Fittings
Type and standard specification
Manufacturer and country
Maximum working stresses
All accessories for installation
(bolts, nuts, etc.)

Technical particulars & Guarantees SE-28


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE F

DEPARTURES FROM THE SPECIFICATION

Bidders are to list all departures from the requirements of the specification in this schedule.

All departures whether they be commercial, financial, technical or of a contractual nature are
to be included and shall be submitted with the Technical proposal

Any item that does not have a departure listed in this schedule will be deemed to be in full
accordance with the requirements of the specification.

No other document or detail accompanying the tender will be considered in evaluating


departures.
Bidders are not permitted to offer any alternative to this schedule.

Item Volume Clause Detail of Departure from Specification

Schedule F: Departure from Specification SF-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE G

PROPOSED ALTERNATIVE STANDARDS TO WHICH


EQUIPMENT SHALL BE PROVIDED

The bidder shall list below all the alternative engineering and design Standards, which he
proposes to use in his design, manufacture and testing of equipment to be supplied. Should
these standards differ from the specified standard in any respect, the bidder shall detail the
differences between the proposed and specified standard.

Compliance with any standard equal or superior to those specified will be considered
acceptable.

In the absence of any listed alternative standard, it is deemed that the standards specified in
the Tender documents are fully complied with.

Specified Standard Alternative Standard


Number Title

Schedule G: Proposed Alternative standards SG-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE H

PROPOSED CONTRACT & SITE ORGANISATION

Personnel

Bidders should provide the names of suitably qualified personnel to meet the requirements
specified in Section 3 (Evaluation and Qualification Criteria) of Volume 1 of 3 of the Bidding
Document. The data on their experience should be supplied using the Form below for each
candidate.

Form PER – 1: Proposed Personnel

1. Title of position*

Name

2. Title of position*

Name

3. Title of position*

Name

4. Title of position*

Name

*As listed in Section 3 (Evaluation and Qualification Criteria).

Schedule H: Proposed contract & site organization and site resources SH-1
Form PER – 2: Resume of Proposed Personnel

Position

Personnel Name Date of birth


information

Professional qualifications

Present Name of employer


employment

Address of employer

Telephone Contact (manager / personnel officer)

Fax E-mail

Job title Years with present employer

Summarize professional experience in reverse chronological order. Indicate particular technical and
managerial experience relevant to the project.

From To Company / Project / Position / Relevant technical and management experience

Schedule H: Proposed contract & site organization and site resources SH-2
POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE I

DRAWINGS AND DOCUMENTS TO BE SUBMITTED WITH TENDER

The following drawings/documents shall be submitted with the Tender:

1.1 Typical plan and section drawings of 145kV switch bay for feeders for each
substation.

1.2 Typical arrangement drawings of control and relay cubicles, fibre optic multiplexer
equipment, digital fault & disturbance recorder (DFDR), LVAC and DC distribution boards.

1.3 Typical block, schematic and logic diagrams of all protection, control and substation
automation schemes.

1.4 Plan and section of new substation building architecture and scheme drawing.

1.5 Outline drawings of all switchgear equipment:


• Showing installed dimensions and weights;
• Showing transport dimensions and weights;

1.6 Following type test reports/certificates of the equipment of similar or higher


specifications (higher voltage & higher capacity) required by the bid shall be submitted as per
relevant IEC/BS.

(i) Circuit Breaker

– Lightning impulse voltage withstand dry test.


– Temperature rise test.
– Power frequency withstand test
– Short time withstand & Peak withstand current test.
– Mechanical operation tests.
– Short circuit Current making & breaking test.
– Out of phase making & breaking test.

Schedule I: Drawings and Documents SI-1


(ii) Disconnector

– Lightning Impulse voltage withstand dry test.


– Power frequency voltage withstand dry test.
– Short time withstand current test.

(iii) Current Transformer

– Short time current test.


– Impulse voltages withstand tests for current transformers for service in exposed
installation.
– Power frequency voltage withstand test.
– Temperature rise test.

(iv) Voltage Transformer

– Temperature rise test.


– Impulse voltages withstand tests for voltage transformers for service in exposed
installation.
– Short circuit test
– Short time over voltage test

(v) Lightning arrester

– Power frequency voltage withstands (wet & dry) and lightning impulse voltage
withstand tests on complete arrester housing.
– Operating duty test.
– Long duration current impulse withstand test.
– Residual voltage test.
– Pressure relief test.
– Artificial pollution test.
– Partial discharge test

(vi) (a) For insulator units (Disc & Post):

Type test report for insulator units shall include the following tests performed on all the
offered types of insulators as per IEC:

– Dry lightning impulse voltage withstand test;


– Wet power frequency voltage withstand test;
– Electro-mechanical failing load test;
– Thermal mechanical performance test;
– Impulse voltage puncture test;
– Power arc test.

(b) For insulator string sets:


Type test reports for insulator string sets which shall include the following tests
performed on the offered or similar types of insulator string sets as per IEC.

Schedule I: Drawings and Documents SI-2


– Dry lightning impulse voltage withstand test;
– Wet power frequency voltage withstand test;
– Radio interference voltage test;
– Power arc test.

All the offered above equipment must be type tested. The above mentioned type tests shall be
conducted in an independent accredited laboratory (accredited based on ISO / IEC Guide 25 /
17025 by the national accreditation body of the country where laboratory is located). Such
type test reports are required to be submitted with bid.

2.6 Quality Assurance Certificate ISO9001 Certification (or equivalent) and Quality
Assurance Programme & Typical Quality Plan for the work from the manufacturers of
the following equipment:

(i) Circuit breaker.


(iii) Disconnector switch.
(iv) Current transformer.
(v) Voltage transformer.
(vi) Lightning arrester.
(vii) Insulator.
(viii) Relays
(ix) Digital fault & disturbance recorder (DFDR)
(x) Fibre Optic Multiplexer Equipment for protection & communication

Schedule I: Drawings and Documents SI-3


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at


Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE J

PROPOSED SUBCONTRACTORS

The bidder shall propose a list of the Sub-contractors in the following table as per sub-clause
2.7, Item 2, Civil Subcontractors, Section-3, Evaluation and Qualification Criteria, Volume 1
of 3 of the Bidding Document.

Sl. No. Name and Address of the Subcontractor

Signature ----------------------------------
Date ----------------------------------

Schedule J: Proposed Subcontractor SJ-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
For
Design, Supply, Erection, Testing and Commissioning of New 132/11kV substation at
Payra and extension of 132 kV bays at existing Patuakhali 132/33kV Substation on
Turnkey Basis (Contract No. PGCB/132KV/PP/SS)

SCHEDULE K

COEFFICIENT AND INDICES FOR PRICE ADJUSTMENT

Not Applicable

SK-1
Schedule K: Coefficient and Indices for Price Adjustment