Sie sind auf Seite 1von 51

Instrument Air

A BeaconMedæs Continuing Education Publication

A company within the Atlas Copco Group


Notes
Notes on Using this Pamphlet:
This pamphlet is presented to assist an engineer or medical facility contemplating the installation of an Instrument Air
system as countenanced under the NFPA 99 Healthcare Facilities standard, 2005 version.

Users are cautioned that this pamphlet is intended to be used in conjuction with the standard, which should be
obtained from:

National Fire Protection Association


1 Batterymarch Park
Quincy, MA 02269-9101
Phone 1-800-344-3555
Internet www.NFPA.org

Users are cautioned to read the pamphlet and the standard carefully, and are encouraged to use the information
herein as suited to the conditions of their project, where such modification does not conflict with applicable local
standards.

This pamphlet only encompasses the requirements of the NFPA 99 through the 2005 version. Please contact
BeaconMedaes to ensure you are using the most recent version of this pamphlet.

Any opinions expressed and/or interpretations given or implied are the sole responsibility of BeaconMedaes, and
should not be relied upon without reference to the NFPA 99 standard and Local Authorities Having Jurisdiction.

This edition August 2006


No Previous Editions

Comments on this booklet or on any aspect of medical gases are welcome and encouraged. Please send to mallen@
beaconmedaes.com

This Pamphlet in both print and electronic versions is Copyright 2006 BeaconMedæs. All Rights are Reserved, and
no reproduction may be made of the whole or any part without permission in writing. Distribution of the Electronic
version is permitted only where the whole is transmitted without alteration, including this notice.

Instrument Air Page 


Table of Contents Abstract

Pneumatic power and medicine ………………….… 2 The paper reviews the background of the most recent
The purpose and the history of Medical Support gases. addition to NFPA’s piped gas systems and discusses
when the use of Instrument Air might be appropriate.
Why Change ……………………………………….… 3 Also reviewed are the rules for the application. Design
Why consider instrument air in lieu of Nitrogen? guidance is provided to allow a system to be sized and
implemented.
Dollars and Cents …………………………….…… 4
How to estimate the economics of an instrument air
system.
Pneumatic power and Medicine
NFPA Rules for Instrument Air …………………….… 4
What is an instrument air system and what are the Medical facilities are very familiar with compressed air. A
requirements as found in the standard. typical facility uses any number of individual air systems
for power and control. These are as diverse as the laundry
Design and installation …………………………….… 8 compressor for running the washers and dryers, a sterilizer
Design issues with instrument air pipelines. compressor for the autoclaves and decontamination systems
in central sterile supply and the HVAC compressor for the
Change of Use …………………………………….… 11 pneumatic controls in the air conditioning system.
Converting nitrogen pipelines to run instrument air.
Given how familiar hospitals are with compressed air, it
seems odd that most North American hospitals of any size
supply nitrogen into the operating rooms to run surgical
tools - a task easily within the capabilities of an appropriate
compressed air system.

Compressed air systems require only occasional


maintenance, the air is of course free, and there is no
management required. By comparison, the nitrogen
system is an unending hassle. The nitrogen is in cylinders
or containers which must be purchased, inventoried, and
changed. Since hustling the cylinders or containers is labor
intensive, there is always an overhead in costs and labor
associated with its use.

Although the nitrogen system could be used for many


purposes per the NFPA standard, the nitrogen gas is
relatively expensive so it is not wise to use it for all the
applications for which it might otherwise be appropriate.
This leaves a quandary when the facility wants pneumatic
power in places like the morgue or central sterile supply.
Often the unsatisfactory solution is to install separate local
systems, which is expensive and increases the maintenance
burden.

Compressed air was in fact the original choice when gas


- powered tools first came into the operating room, and
only in North America was compressed air supplanted by
Nitrogen. The reason for this decision is obscured by time,
but most likely derives from difficulties with the quality of
the air available at the time. Piped air was typically wet,
often oily and sometimes dirty, none of which is good
for high speed turbine tools. Nitrogen was the driest,
cleanest gas they could easily substitute, so it became
the gas of choice. Over time, primarily through received
knowledge, it acquired the patina of a de facto standard.
In fact, Nitrogen for tools has never been required by any
Page  Instrument Air
published standard. Nevertheless, Engineers continue even So the most compelling reason to consider an Instrument
today to design, and facilities continue to install, nitrogen Air system over a Nitrogen system is dollars and cents.
systems for the driving of surgical tools. The cost of operating a nitrogen system can be surprisingly
high, depending on the amount of nitrogen used. Nitrogen
In most of the world, compressed air never left the O.R. In sources imply three particular costs:
the United Kingdom for instance, it is common to install
a “7 bar” or “13 bar” surgical air system specifically for 1. The cost of the gas itself.
driving tools alongside the “4 bar” medical air for treating
patients. 2. The cost of the demurrage (rental of the cylinders).

There is a vestigial holdover from the use of compressed 3. The management cost, including the labor involved in
air for surgical tools in use in North America even today. hustling the cylinders from the dock to the manifold,
Surgical tool hoses are still often fitted with a quick attaching and detaching them, and moving the
connect fitting on the end called a “Schræder” connector empties back to the dock, plus the management
- originally manufactured by the Schræder Automotive involved in keeping track of cylinder inventories and
Division, and used in garages to run their air-powered reordering).
tools (the historic origin of our elegant surgical tools is not
medical, but industrial). While it is possible to reduce these costs in many cases by
using cryogenic liquid in place of gas cylinders, the costs
Oddly, although the pipelines changed from air to nitrogen, are never completely eliminated, and the installation of
Schraeder never did make the change. Even today the a large cryogenic source system may be problematic in
version of that connector in most common use is stamped other ways.
“Air” - Schræder itself never made a nitrogen-specific
connector, and only very recently have their successor Generally speaking, an Instrument Air system is going to
companies created one. be more expensive to purchase than a similar capacity
manifold or bulk liquid system. However, the Instrument
Although Nitrogen systems have become the general Air itself is less costly on a volume to volume basis, so
standard, there have always been a small number of North the Instrument Air system will pay for itself over time.
American facilities willing to question this. These facilities Exactly when the crossover will occur will vary. In some
have installed air systems to drive tools, following their own cases, the crossover may be so far out that an Instrument
instincts in light of an absence of guidance in the NFPA Air system would be a questionable investment. In other
or CSA standards. The trend has accelerated somewhat cases the payback is so quick that Instrument Air would be
in the last decade, and in the 2002 edition NFPA for the worth retrofitting even where a nitrogen system is already
first time included guidance on these systems. Although in place. In the next chapter entitled “Dollars and Cents”,
that might make it seem to be something new, in truth it is we give some guidance on how to calculate the crossover
actually a return to something very old. point for your facility.

When the Instrument Air system first appeared in the 2002 The other reason for considering Instrument Air is the
NFPA 99, there was no Instrument Air terminal unit, and variety of applications for which it can be used. NFPA has
thus no outlets, controls or hoses were available. This continuously sought to keep medical gas systems separate
was a problem which prevented many facilities from from all other systems and to ensure that the medical gases
seriously looking at the Instrument Air option. In 2005, are not compromised by use for other purposes. NFPA 99
the Compressed Gas Association resolved this with the 2005 5.1.3.4.2 states “Central supply systems for oxygen,
assignment of the CGA 2080 connection to Instrument Air. medical air, nitrous oxide, carbon dioxide and all other
The only remaining hurdle therefore is the lack of design patient medical gases shall not be piped to, or used
guidance, which this publication should help address. for, any purpose except patient care application”. The
practical effect of this prohibition is found in the Annex
Why Change? A.5.1.3.4.2 “Prohibited uses of medical gases include
fueling torches, blowing down or drying any equipment
There are two reasons to consider an Instrument Air system, such as lab equipment endoscopy or scopes, or any other
and it is important to note that neither is specifically purposes. Also prohibited is using the oxygen or medical
medical. In fact, from the medical standpoint, there is very air to raise, lower or otherwise operate booms or other
little to choose between Instrument Air and nitrogen. Both devices…”.
will drive the tools, both (as contemplated by NFPA 99)
have similar dryness, cleanliness, and operating pressures. Certain of these prohibitions are controversial, but
Except for the costs involved, there is no reason a facility the difficulty they cause can be illustrated. Consider
could not simply continue to use nitrogen. endosurgical areas or central sterile supply. Here, a gas
source is desirable to blow out or dry instruments during
Instrument Air Page 
cleaning and sterilization. Medical Air cannot be used Dollars and Cents
for this purpose, so the only acceptable alternative has
been to install nitrogen. Aside from the cost of nitrogen, A decision to use an Instrument Air system will hinge on
this use implies releasing quantities of Nitrogen into the the payback for most facilities. This can be calculated with
room. Although Nitrogen is itself non-toxic, the release reasonable accuracy if a few questions can be answered.
of too much nitrogen will dilute or displace the oxygen in Clearly, a facility which has some history with an existing
the air and can cause asphyxiation. Nitrogen is therefore nitrogen system will be at an advantage when collecting
not ideal for use in workspace applications such as this, many of these answers, but even while a project is only in
whereas Instrument Air is very suitable. planning one can make a satisfactory estimate. Detail 4
is a listing of the data required. Once you have obtained
Applications for Instrument Air are discussed in NFPA this data, your BeaconMedaes Sales Consultant has a pre
99 5.1.3.8.2.1: “Instrument Air shall be permitted to be configured spreadsheet which they can use to help you
used for any medical support purpose (e.g. to operate calculate the relative costs and system payback.
tools, air driven booms, pendants or similar applications)
and (if appropriate to the procedures) to be used in NFPA Rules for Instrument Air
laboratories.”
The requirements for Instrument Air sources are found in
Whereas Medical Air is and Nitrogen may be prohibited the NFPA 99 under 5.1.3.8, and a few other requirements
from or undesirable in certain applications, Instrument Air are found throughout the document.
may be used for any of them.
Instrument Air and nitrogen under the standard are meant
The simple conclusion is that Instrument Air offers a very to be opposite sides of the same coin. Indeed, a simple
worthwhile design option. It is not for every facility, guiding principle for working with these systems is that if
because in some it will not offer benefits sufficient to justify in doubt, do what you would have done for Nitrogen, and
the additional up-front costs. But in our studies to date, we you will probably have done the right thing.
are surprised how often and at how low a nitrogen usage we
can justify these systems purely on the money saved. Our The one place where an Instrument Air system is unique
experience suggests it is an option every facility (including is in the design of the source. Instrument Air source
facilities already using nitrogen) should at least examine. equipment is unique in it’s form, permitted options and
operating requirements. An overall view of the components
of an Instrument Air source under NFPA 99 are shown in
Detail 5 & 6.

Detail 4
Calculating Comparitive Costs for Nitrogen vs. Instrument Air
Number of cylinders or containers used per Month
A
(if you are evaluating a facility which is not yet in operation, see Detail 12) #
B Cost of each cylinder $
C Cost of each Container (if used) $
D Cost of cylinder rental (demurrage) per month $
E Cost of container rental (demurrage) per month $
Labor rate / Hour for the person changing the cylinders or containers
F
(include benefits and overhead costs if appropriate) $
Estimated time required to complete a standard cylinder or container
G change to ONE side of the manifold, including time to travel to and from the
manifold location. (If your estimate is in minutes, ÷60 for hours) Hours
H Labor cost per change $
Number of cylinders or containers on ONE side of the manifold.
I
(if you are evaluating a facility which is not yet in operation, see Detail X) #
Other known costs (delivery charges, supplier labor charges, manifold
J maintenance or repair, etc.) Ensure these charges are per month.
(if you only know overall charges per year, ÷12 for monthly average) $
K Cost of Power per kWh ¢
L Years for amortization of capital yrs.

Page  Instrument Air


Primary Supply Secondary Supply Quality Control Monitoring

Cylinder Cylinder
Header Header
(manifold)
• Medical Air in Cylinders,
purchased per USP.

• Medical Air in Cylinders,


purchased per USP.
• Reserve Supply in Use
• Reserve Low

• Pressure Low
• Pressure High

• Oil indicators on Filter.


• Dew point Monitoring,
alarm at -30°C (-22°F)

200 psi+ 200 psi+ • Lag Alarm


Compressor(s) Compressor(s) • Oil Separation
• Dryer for -40°
• Filtration to 0.01µ
• Charcoal Odor/Taste Removal

Detail 5 : Instrument Air Source System configurations (Per NFPA 99 )

The particular aspects unique to Instrument Air can be transition to nitrogen was wet air. In applications like
summarized: tool drive, the dryness of the air is particularly significant,
as the rapid expansion of air in the tools can produce
1. Compressor Type: A compressor used for Instrument Air adiabatic cooling which can condense moisture where it
may be of any type which can produce a pressure greater would otherwise never appear. Therefore, unlike medical
than 200 psig. Instrument Air compressors do not have air, Instrument Air must be dried to a nominal -40° dew
to be oilless or oilfree (unlike compressors for Medical point. This will necessitate desiccant dryers in virtually
Air) but may include lubricated types. This is because all cases.
the high pressure required makes lubrication inescapable,
and since Instrument Air is not breathed by the patient or This combination of filters and dryers is intended to produce
mixed with oxygen, any oil (should it enter the system) is air which will comply with or exceed the specifications
less hazardous. of the Instrument Society of America standard S-7.0.01
Quality Standard for Instrument Air.
The extraordinary pressure requirement comes from the
need to ensure that the system can emulate the traditional 4. A secondary or backup system. Unlike other medical gas
nitrogen system, which may operate as high as 185 psig. systems, failure of an Instrument Air system is unlikely to be
185 psig is the pressure at which the Instrument Air pipeline fatal. Nevertheless, the system is critical to any number of
system is designed to operate. Clearly, a compressor with procedures, and if the procedure was suddenly terminated
a top pressure of 175 psig will not be able to achieve this the patient(s) could be at risk. Thus a backup, just like any
requirement. other medical gas system, is required.

2. Specific Filtration and Purification: Although a Unlike other systems however, the requirement for that
lubricated compressor is permitted, oil is not permitted in backup is much less stringent. Uniquely, an Instrument Air
the system. Instrument Air sources must have coalescing compressor may include a redundant compressor(s) (similar
filters to remove liquid oil and activated carbon absorbers to that required for Medical air) or it may be seconded by
to eliminate vapor and gaseous oil. A particulate filter is a bank of cylinders sufficient for one hour’s operation (a
also required with a nominal pore size of 0.01µ. hybrid configuration).

3. Dry to -40°: Recall that a major reason for the historic The allowance for a cylinder secondary offers a much less

Instrument Air Page 


Instrument Air
Pressure
Relief Valve
Guage
Change
ASME Cylinder Reserve Indicators
Header
5.1.3.4.8 Charcoal
Sight Adsorbers
Glass Regulator
Automatic
Drain
Inlet
Isolation
Manual Valves
Drain
Intake(s) Reserve
Relief Source Filter Outlet
Valve Compressor(s) Isolation
Valve or Check
Receiver
Check Air
Valve Treatment
Aftercooler/ & Control Pressure System
air dryer Monitoring Indicator Pressure
Relief Switch/Sensor
Inlet Isolation Source Valve Demand
Isolation Valve Valve Check
means Compressor
(valve shown)
Source
Valve
Inlet
Isolation Outlet
Valve(s) Isolation
Aftercoolers Valve(s) Legend
Automatic
Ball Valve Trap & Drain
Inlet D.P.
Outlet Isolation Dryer(s)
Valve(s) Check Valve
Isolation Dew Point Demand Pressure
Valve(s) Monitor Check Relief
Pressure Valve
Indicator
Automatic Demand Check
Trap & Drain
Pressure Regulator
Elements of an Instrument Air Source Filter with Change Indicator

Page 
After NFPA 99 2002 Figure A-5.1.3.8
Detail 6 : Instrument Air Source Systems (Per NFPA 99 A.5.1.3.8 )
expensive option for installing smaller systems, and yet
does not greatly reduce the operational safety of the system

Note (3)
Note (3)
System
overall if properly alarmed.

Fault
Where this cylinder secondary is applied, there is a
special allowance in the standard for placing the cylinder

Note (3) Single signal alternate to having each signal on the master. Must activate when any signal within the double lines in that row activates.
header with the Instrument Air compressor itself. This

Header
Low
2ndry
is an exception to the general rule that cylinders are not
permitted to be in the same room with compressors or
pumps. It applies only to the active header used to back
up an Instrument Air compressor. There is no exception for

Header
In Use
2ndry
loose cylinders, even if those are intended for the Instrument
Air system, so these must be stored in an appropriate room
just like all other medical gas cylinders.

Water in
Receiver
Note (1)
Note (1)
High
Although Instrument Air systems are clearly intended to be
compressor driven (otherwise the operating economies will
be lost) it is possible to use a standard medical gas style
manifold to source an Instrument Air system as well.

down Separator
Water in

Note (1)
Note (1)
High
5. The distribution system for Instrument Air will typically

Reserve
be similar to that for Nitrogen, but given it’s many potential

Low

Note (1) Recommended when the compressor is water cooled or a water cooled aftercooler is used.

Detail 7.2 : Instrument Air Source Alarms


uses, it may also be significantly more complex. The actual

Thermal

Note (2)
Note (2)
Shut-
design will of course depend on the facility’s convenience
and preferences. Some options are illustrated in Details

Reserve
in Use
8-10.

Lag in
Use
6. Outlets for Instrument Air must be non interchangeable
with other medical gases. It is not appropriate to use
Header
Low
2ndry

medical air outlets or nitrogen outlets in an Instrument


Air system, even if they are relabelled. NFPA has three

point
High
Dew
requirements for any outlet:

Note (2) Recommended when appropriate for the compressor or pump.


Change-
over

a. Each outlet for a specific gas must be provided with an


outlet not interchangeable with any outlet for another Press or
Low

gas. Vac
Press
Low

b. That when a single gas is operated at multiple pressures,


Press or

the outlet for each pressure be non interchangeable


High

Vac
Press
High

with the outlet for another pressure.

c. That when an outlet is operated at pressures greater


Instrument Air, duplex/multiplex compressor

than 80 psig, that the outlet be of the DISS (threaded)


type, or include a pressure interlock to prevent the
Cylinder x Cylinder x Cylinder Manifold

hose from flying out of the outlet when disengaged.

These requirements taken together mean that the ideal


Instrument Air outlet is the CGA DISS outlet, and this is
Cylinder x Cylinder manifold

the outlet BeaconMedæs recommends for all Instrument


Air terminals, hoses and accessories.
Instrument Air, Hybrid
Source Type
Source

Detail 7.1 : A pipeline label for Instrument Air

Instrument Air Page 


7. Instrument Air has it’s own color coding and labelling some specific alarm signals (see Detail 7.2).
(see Detail 7.1). The color for Instrument Air is a red ground
with white lettering, and the abbreviation is “Instrument Design and Installation
Air”. Standard pressure is 160-185 psig through the
pipeline, and the nonstandard pressure rules will apply for Instrument Air systems are designed in the same manner as
Instrument Air systems operated at different pressures (see any medical gas system (please refer to the BeaconMedæs
NFPA 99 5.1.5.15, 5.1.11.1, 5.1.11.2.2, 5.1.11.3.2). Medical Gas Design Guide, Chapter 9 for Medical Support
Gases for detailed instructions).
8. Alarm requirements for Instrument Air are similar in
most respects to those for any medical gas system (local, The design of an Instrument Air system and the selection
master and area alarms are all required). However, the of the source requires knowing all the many applications
unique configurations permitted for the source do imply which it is intended to serve. The first step in the design

Line Pressure
Indicator
Dew Point
Monitor Source Valve D.C. To High
°C Pressure
D.C. Terminals
D.C.

Isolating Valve Line Pressure


Pressure Alarm Switch/Sensor
Indicator Pressure
Relief
Line Pressure Valves,
Regulators

Isolation Valve
Instrument Air
Source
High Pressure

Line Pressure
Indicator

Dew Point
Monitor Source Valve D.C. To Low
°C Pressure
D.C. Terminals
D.C.

Isolating Valve Line Pressure


Pressure Alarm Switch/Sensor
Indicator Pressure
Relief
Line Pressure Valves,
Regulators

Isolation Valve

Low Pressure
Detail 8
A Dual Pressure Arrangement per NFPA 99 5.1.3.4.6
Page  Instrument Air
Area Alarm
Switch/Sensor
Service Valve
Future Valve D.C.
D.C.

Zone Valve
Remote,
pressure controlled IAir Control Panel
Outlet(s) Pressure controlled
outlet on the
Control Panel

Line Pressure
Indicator
Dew Point
Monitor Source Valve D.C.
°C
D.C.

D.C.

Isolating Valve Line Pressure


Pressure Alarm Switch/Sensor
Indicator Pressure
Relief
Line Pressure Valves,
Regulators
Instrument
Air Isolation Valve
Source

High Pressure
Detail 9
Local Pressure Control

must be to determine what all the applications demand in low pressure applications from the same source of supply,
terms of pressure and flow, and then to determine the size there are some considerations which will affect the design.
of compressor required. NFPA 99 5.1.3.4.6 discourages the construction of what is
termed a distributed pressure system in favor of two distinct
An Instrument Air system will fall into either (and in some pipeline systems divided at the source and separately
cases both) of two types. Systems for use at high pressures provided with all the necessary controls (see Detail 8).
(e.g. to substitute for Nitrogen) will be designed as would Nevertheless, the language is sufficiently open, and the
Nitrogen systems. Systems for exclusively lower pressure application sufficiently unique that some degree of local
applications (e.g. for labs, central sterile supply, etc.) can pressure control may be permissible.
be laid out like any other pressure gas system.
If local pressure control is desired, the design of the
If it is the desire of the facility to supply both high and system would roughly follow the current practice in the
Instrument Air Page 
Area Alarm
Switch/Sensor
Service Valve
Future Valve D.C.
D.C.

Secondary Regulator
(Provide one for Device Regulator
each device) (Fixed or
adjustable output)
Zone Valve
Uncontrolled
Outlet(s)

Adapter
To Device(s)
fitting
Outlet
Line Pressure
Indicator
Dew Point
Monitor Source Valve D.C.
°C
D.C.

D.C.

Isolating Valve Line Pressure


Pressure Alarm Switch/Sensor
Indicator Pressure
Relief
Line Pressure Valves,
Regulators
Instrument
Air Isolation Valve
Source

High Pressure
Detail 10
Secondary Pressure Control

O.R. There, the pipeline delivers the maximum pressure It is also possible to blend the elements of the systems
to ensure the best possible flow rate, and Instrument Air shown in these three figures to create a hybrid system
control panels are placed where necessary for control of appropriate to the facility’s needs.
the pressure to the tools. Similar local pressure control can If a multiple pressure system is contemplated, be sure
be provided for other devices (see Detail 9). to size each of the branches at the appropriate pressure.
Only for the purpose of sizing the source should they be
A third option does exist but is rarely the preferred considered as one system.
implementation. This is illustrated in Detail 10, and simply
involves the piping of the Instrument Air to uniform outlets In the layout process, outlets are placed first. In O.R.
operated at the standard 185 psig, and then regulating each settings where tool drive is required, a pressure control
device with it’s own portable regulator fitted to the device box is placed on a convenient wall, and includes one
or the permanent outlet. outlet. A second and occasionally a third outlet are placed
in the closest possible proximity to the O.R. table. These
Page 10 Instrument Air
are often found on the ceiling columns or booms. These The first consideration in sizing is to ensure that the tools
outlets may be “slaved” from the wall mounted control or which are likely to be in simultaneous use are covered.
they may employ a scaled down version of the control itself These tools can be very demanding, with typical usages
in the ceiling column or boom. Mounting the controller ranging from 225-425 lpm (8-15 scfm). At least this
on the column or boom is generally superior when flow is quantity of air must be available, so this is the minimum
considered, but less desirable from the viewpoint of staff size for a system.
access and ease of use.
More than one location will involve some degree of
After outlets are placed, the actual piping can be run and simultaneous use, and the calculation we recommend is
pipe sizing determined. This aspect of design is covered that used by the HTM 2022 standard from the U.K., which
in detail in Chapter 9 of the BeaconMedæs Design Guide allows for one tool at 100% and all remaining tools at 25%.
for Medical Gases. The formula used is :
350 + ((n-1) x 87.5)
Change of Use Where n is the number of locations using the system.

The economic benefits of Instrument Air can be surprising, Where 350 lpm is taken as the base load for a tool, and
and of course it is the facility which is already struggling “n” is the number of locations piped with Instrument Air
with the costs of a nitrogen system who is likely to see or the number of tools.
them most clearly. NFPA does provide for a system to be
converted from one gas to another in a process termed If other applications are intended to use Instrument
“Change of Use”. Air, they must be added to the tool demand based on a
knowledge of the actual demand from that application.
Change of Use requires that a system originally intended for Some examples might include: operating pneumatic brakes
one gas and therefore made non-interchangeable for that for booms, which use negligible amounts of air and can
gas be converted so that it is equally non-interchangeable be ignored as a capacity requirement; operating tools in
for the new gas. This means changing the source, changing the morgue, which might be treated like another tool-using
the outlets, changing the demand checks on alarm location; operating a pneumatic O.R. table, which would
components, relabelling and retesting as if the system have to be assessed based on a knowledge of the table
was new. A conversion from nitrogen to Instrument Air itself; general lab uses, which might easily be greater than
is very feasible under these rules. Since the pipeline itself the use of air for tools when totalled.
need not be disturbed, the cost of such a conversion is
not excessive. The sizing of the reserve is identical if a duplex compressor
is used as the source configuration. If the source
Sizing and Selecting an Instrument Air Source configuration is a compressor with a cylinder header as
reserve (a hybrid configuration), then the secondary must
Any Instrument Air source will consist of a primary source contain one hour’s supply. This is most easily assessed
(usually a compressor) and a reserve source (a second by taking the total demand calculated for the primary
compressor or a manifold header). Each element is sized source and multiplying it by 60 (minutes to hours), then
separately and by it’s own rules. dividing by 6,200 l (220 scfm) to determine the number of
cylinders required in the secondary (Detail 12 allows you
To size the primary compressor, there are two considerations: to determine this with minimal calculations).
first, the compressor must be large enough to drive all the
tools, and second we don’t want to make the compressor In the rare event that a manifold source will be used, this
any larger than is absolutely necessary. This is particularly will be sized using a simple calculation of one cylinder
true since there is a very large diversity in Instrument Air for each ordinary O.R., and two for each O.R. intended
usage and in fact the average Instrument Air compressor for orthopedic or neurological surgery. Both sides of the
will not run very much. To express this another way, when manifold will be identically sized. If other applications
the Instrument Air is needed, there must be enough of it, are also going to be served form the manifold, they must
but it is only typically needed in short bursts, so the system be assessed individually.
may sit idle for long periods.
The selection of the Instrument Air source may be made
The picture can be further complicated if the Instrument Air from Detail 13, which also will link you to the necessary
is being used for purposes in addition to driving surgical information for system dimensions.
tools. Naturally, some of the other applications may
place more steady demand on the system and change the Conclusions and Cautions
diversity required.
We believe that ultimately Instrument Air, especially when

Instrument Air Page 11


Source Ranges Instrument Air
(Locations scale reflects Tool use only, HTM 2022 Sizing Method)

(3) 7.5 Hp. (3) 10 Hp.


Quadruplex

Triplex Note: Larger I. Air


systems are possible.
Duplex Please contact
10 Hp. (2) 10 Hp.* BeaconMedæs for
information.
7.5 Hp. (2) 7.5 Hp.*

}
Compressor(s)
5 7 11 16 Secondary Cylinder Hybrid Systems
Counts
14x14 7-14
13x13 6-13 Source Type Legend
12x12 6-12
11x11 5-11
10x10 5-10
9x9 4-9
8x8 4-8
Cylinder
7x7 3-7 Manifolds
6x6 3-6
5x5 2-5
4x4 2-4
3x3 1-3
2x2 1-2

1 10 20
Number of Locations piped with Instrument Air
Notes: The ranges given for manifolds reflect a low (dark blue) and a high (white)
estimate. The low estimate applies only if all locations are of the general O.R. type,
the high estimate applies if all are of the specialty O.R. type. Factor your selection
based on the proportion of each in the project.
* Hybrid configurations marked with a “*” are systems with two compressors of this
size as the primary source. They are not duplex systems in the usual meaning of one
compressor in service, one on standby, but have two compressors available in the
primary role with cylinders as the secondary.

Detail 12 : Instrument Air Source Selector

compared to Nitrogen, is a superior choice for any facility frame for that payback. Naturally, the general rule will be
which needs high pressure gas for any reason. In the long the more gas used, the faster the payback. Small facilities
run, the benefits are so compelling that we can anticipate using very little gas may find the payback too far in the
nitrogen systems disappearing from the scene, entirely future to justify the initial outlay, large facilities with heavy
replaced by Instrument Air. usage may find the savings grand enough to justify even
However, that is some time in the future, and any facility a complicated change of use program. The only way to
built since at least the 1970’s probably has a nitrogen know is to do the math.
system already in place. Although the economics of
Instrument Air are compelling, they are far more complex We highly recommend that every medical gas design
when a legacy system must also be considered. engineer add Instrument Air to their repertoire, and in
future evaluate every facility as a potential candidate. They
Instrument Air systems are more costly initially, but the will find in most cases Instrument Air is a money saver for
gas is far less expensive per liter. This means that there their client.
is a payback for virtually any Instrument Air installation,
whether new or a change of use. The question is the time Facilities who have to work to keep their nitrogen
Page 12 Instrument Air
systems from going empty should also look closely at the well enough alone in the interim.
possibilities of performing a change of use conversion.
They are likely to find the economics more favorable than There are other possibilities for reducing the cost and labor
they expected. involved with nitrogen which may be a half-way solution
for such facilities. These involve conversion from cylinder
That middle range of facilities whose nitrogen usage is (gaseous) sources to container (liquid) sources. While
a nuisance but not high enough to justify the costs of nitrogen will always be more expensive than compressed
conversion will be the ones who will have to refuse change air, the reduction in cost can be significant, and the
of use. Should they ever be fortunate enough to renovate reduction in labor can be greater yet. More details on these
their O.R. or build new, they will certainly find Instrument systems can be obtained in the BeaconMedaes Applications
Air very attractive, but they may be best advised to leave Guide to Cryogenic Liquid Manifolds available through
your BeaconMedaes representative.

Detail 13
System Selection Table, Instrument Air Compressors
Capacity NFPA Complete System
@ 200 psig Envelope Dimensions (inches)
Cyl. Information
SCFM LPM Format HP Count Width Height Depth Sheet Page
16.5 467 Duplex1 7.5 NA 103.5 84.5 67 SSB-120-10 15
24 679 Duplex1 10 NA 103.5 84.5 67 SSB-120-10 15
33 934 Triplex1 7.5 NA 138 84.5 67 SSB-120-11 17
48 1,359 Triplex1 10 NA 138 84.5 67 SSB-120-11 17
49.5 1,401 Quadruplex1 7.5 NA 172.5 84.5 67 SSB-120-12 19
72 2,038 Quadruplex1 10 NA 172.5 84.5 67 SSB-120-12 19
Hybrid Systems
16.5 467 Simplex2 7.5 5 89.5 85 67 SSB-120-10 21
24 679 Simplex2 10 7 89.5 85 67 SSB-120-10 21
33 934 Duplex2 7.5
Call for information
48 1,359 Duplex2 10

Notes
1. Capacites are shown as NFPA capacities with one compressor running and one in standby. Capacity shown is net
system capacity, not simple compressor capacity (systems losses are already deducted).
2. Capacites are shown as NFPA capacities with compressor(s) running and cylinder header in standby. Capacity
shown is net system capacity, not simple compressor(s) capacity (systems losses are already deducted).

Instrument Air Page 13


DUPLEX 7.5-10
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-10
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air Duplex Single Point Connection (SPC) Base Mount Systems
(7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) System Design Isolation System
The instrument air system shall be of a single point connection Each compressor and motor assembly shall be fully isolated
base mounted design consisting of two compressor modules from the main compressor module base by means of a four
with dryers, and a single control module with control panel, point, heavy duty, spring isolation system for a minimum of
air receiver, filtration system and oil/water condensate 95% isolation efficiency. Where required by local or state
separator. Each module has a maximum base width of 34.50" regulation, optional seismically restrained isolators can be
(88 cm), and be fully compliant with the latest edition of provided at an additional cost. Each main compressor module
NFPA 99. The modules shall be assembled as one unit with base frame shall not exceed 34.50" in width.
single point connections for air discharge, electrical and
condensate drain. Control Module with Air Receiver/Filter/Regulator
Compressor/Dryer Module (Compressor, Drive, Motor, System
Piping, Dryer) The control module shall include a NEMA 12, U.L. labeled
The compressor shall be a high pressure "oil-lubricated" control system, duplexed final line filters, regulators, oil
continuous duty rated type. The design shall be two staged, indicators, and a condensate oil/water separator and dew point
air-cooled, reciprocating type with corrosion resistant reed monitor. All of the above shall be factory piped and wired in
type valves with stainless steel reeds. Both oil scrapper ring accordance with NFPA 99 and include valving to allow
and piston rings shall be made from long lasting special cast complete air receiver bypass and an air sampling port. The
iron and designed for continuous duty operation. The vertical air receiver shall be ASME Coded, National Board
crankshaft shall be constructed of forged steel and fully Certified, galvanized, rated for a minimum 250 PSIG design
supported on both ends by heavy duty ball bearings and seals. pressure and includes a liquid level gauge glass, safety relief
The crankcase shall be constructed of gray cast iron. valve, manual drain valve, and automatic solenoid drain valve.
Maximum heat dissipation shall be achieved through cast iron Control System
cylinders with external cooling vanes. Cylinder sleeves are not The control system shall have an HMI touch screen control,
required. Both low and high pressure pistons are made from automatic lead/lag sequencing with circuit breaker disconnects
cast aluminum with chrome-moly piston pins. Second stage for each motor with external operators, full voltage motor
cylinder head shall be equipped with a wired shutdown switch starters, overload protection, 24V control circuit and hand-off-
for high discharge air temperature. The connecting rod shall auto selector switch for each compressor. Automatic
be of a one-piece design. The compressor shall be v-belt alternation of both compressors based on first-on/first-off
driven through a combination flywheel/sheave and steel motor principle with provisions for simultaneous operation if
sheave with tapered bushing and protected by an OSHA required. Automatic activation of reserve unit, if required, will
approved totally enclosed belt guard. A sliding motor activate an audible alarm as well as a visual alarm on the
mounting base that is fully adjustable through twin adjusting HMI. The HMI displays service due, run hours for each
screws shall achieve belt tensioning. The motor shall be a compressor, system status, operating pressure, dew point and
NEMA rated, open drip proof, 1800 RPM, with 1.15 service high discharge air temperature shutdown. A complete alarm
factor suitable for 208 or 230/460V electrical service. Each and service history is available on the HMI.
compressor shall have its own inlet air filter mounted on the
first stage compressor heads. Discharge air from the first Dew Point Transmitter
stage compressor cylinder passes through an air-cooled The control module shall incorporate a dew point transmitter
intercooler prior to entering the second stage. The second that is mounted, pre-piped, wired to the control panel and
stage discharge air then passes through an air-cooled displayed on the HMI touch screen. The transmitter probe
aftercooler designed for a maximum approach temperature of shall be 316L SS with sintered stainless steel filter and thin
12° F complete with moisture separator and zero loss film polymer sensor. The system accuracy shall be ± 2° C.
automatic drain valve prior to entering the dryer. The Dew point alarm shall be factory set at -22° F (-30° C) per
compressor discharge line shall include a flex connector, NFPA 99 with remote alarm contacts in the control panel.
safety relief valve, isolation valve, and check valve. The Statement of Warranty
discharge air piping shall be of ASTM B-819 copper tubing, BeaconMedæs warrants all Instrument Air Systems, to be free
brass, and/or stainless steel. The discharge flex connector shall of defects in material and workmanship under normal use for
be braided 304 stainless steel, brass, or bronze. Each a period not to exceed thirty (30) months from date of
compressor has its own dedicated dryer. Each dryer is shipment, or twenty four (24) months from date of start-up.
individually sized for peak calculated demand and capable of
producing a -40° F (-40° C) pressure dew point. Dryer purge
only occurs when it’s respective compressor is running.
Upstream of the dryer will be a separator with a zero loss
drain valve followed by a 0.01 micron coalescing filter. Both
filters shall have element change indicators.

BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949 Page 15
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-10
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air System Specifications1

Complete System Capacity2 System FLA


System3 Receiver4 Noise5
System HP
BTU/HR (Gallons) Level
Model No. 200 psig 208V 230V 460V
HPA-7D-D200 7½ 16.5 17,062 200* 76 46 41 20
HPA-10D-D200 10 24 23,014 200* 79 60 52 26

Notes: 1 Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities (reserve compressor on standby) and are shown in Inlet Cubic
Feet per Minute (ICFM). System losses subtracted from pump capacity.
3 All system BTU/HR is shown with reserve compressor on standby.
4 * Indicates standard receiver
5 All noise levels are shown in dB(A) and reflect one pump running.

Page 16
BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
TRIPLEX 7.5-10
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-11
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air Triplex Single Point Connection (SPC) Base Mount Systems
(7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) System Design Isolation System
The instrument air system shall be of a single point connection Each compressor and motor assembly shall be fully isolated
base mounted design consisting of three compressor modules from the main compressor module base by means of a four
with dryers, and a single control module with control panel, point, heavy duty, spring isolation system for a minimum of
air receiver, filtration system and oil/water condensate 95% isolation efficiency. Where required by local or state
separator. Each module has a maximum base width of 34.50" regulation, optional seismically restrained isolators can be
(88 cm), and be fully compliant with the latest edition of provided at an additional cost. Each main compressor module
NFPA 99. The modules shall be assembled as one unit with base frame shall not exceed 34.50" in width.
single point connections for air discharge, electrical and
condensate drain. Control Module with Air Receiver/Filter/Regulator
Compressor/Dryer Module (Compressor, Drive, Motor, System
Piping, Dryer) The control module shall include a NEMA 12, U.L. labeled
The compressor shall be a high pressure "oil-lubricated" control system, duplexed final line filters, regulators, oil
continuous duty rated type. The design shall be two staged, indicators, and a condensate oil/water separator and dew point
air-cooled, reciprocating type with corrosion resistant reed monitor. All of the above shall be factory piped and wired in
type valves with stainless steel reeds. Both oil scrapper ring accordance with NFPA 99 and include valving to allow
and piston rings shall be made from long lasting special cast complete air receiver bypass and an air sampling port. The
iron and designed for continuous duty operation. The vertical air receiver shall be ASME Coded, National Board
crankshaft shall be constructed of forged steel and fully Certified, galvanized, rated for a minimum 250 PSIG design
supported on both ends by heavy duty ball bearings and seals. pressure and includes a liquid level gauge glass, safety relief
The crankcase shall be constructed of gray cast iron. valve, manual drain valve, and automatic solenoid drain valve.
Maximum heat dissipation shall be achieved through cast iron Control System
cylinders with external cooling vanes. Cylinder sleeves are not The control system shall have an HMI touch screen control,
required. Both low and high pressure pistons are made from automatic lead/lag sequencing with circuit breaker disconnects
cast aluminum with chrome-moly piston pins. Second stage for each motor with external operators, full voltage motor
cylinder head shall be equipped with a wired shutdown switch starters, overload protection, 24V control circuit and hand-off-
for high discharge air temperature. The connecting rod shall auto selector switch for each compressor. Automatic
be of a one-piece design. The compressor shall be v-belt alternation of all compressors based on first-on/first-off
driven through a combination flywheel/sheave and steel motor principle with provisions for simultaneous operation if
sheave with tapered bushing and protected by an OSHA required. Automatic activation of reserve unit, if required, will
approved totally enclosed belt guard. A sliding motor activate an audible alarm as well as a visual alarm on the
mounting base that is fully adjustable through twin adjusting HMI. The HMI displays service due, run hours for each
screws shall achieve belt tensioning. The motor shall be a compressor, system status, operating pressure, dew point and
NEMA rated, open drip proof, 1800 RPM, with 1.15 service high discharge air temperature shutdown. A complete alarm
factor suitable for 208 or 230/460V electrical service. Each and service history is available on the HMI.
compressor shall have its own inlet air filter mounted on the
first stage compressor heads. Discharge air from the first Dew Point Transmitter
stage compressor cylinder passes through an air-cooled The control module shall incorporate a dew point transmitter
intercooler prior to entering the second stage. The second that is mounted, pre-piped, wired to the control panel and
stage discharge air then passes through an air-cooled displayed on the HMI touch screen. The transmitter probe
aftercooler designed for a maximum approach temperature of shall be 316L SS with sintered stainless steel filter and thin
12° F complete with moisture separator and zero loss film polymer sensor. The system accuracy shall be ± 2° C.
automatic drain valve prior to entering the dryer. The Dew point alarm shall be factory set at -22° F (-30° C) per
compressor discharge line shall include a flex connector, NFPA 99 with remote alarm contacts in the control panel.
safety relief valve, isolation valve, and check valve. The Statement of Warranty
discharge air piping shall be of ASTM B-819 copper tubing, BeaconMedæs warrants all Instrument Air Systems, to be free
brass, and/or stainless steel. The discharge flex connector shall of defects in material and workmanship under normal use for
be braided 304 stainless steel, brass, or bronze. Each a period not to exceed thirty (30) months from date of
compressor has its own dedicated dryer. Each dryer is shipment, or twenty four (24) months from date of start-up.
individually sized for peak calculated demand and capable of
producing a -40° F (-40° C) pressure dew point. Dryer purge
only occurs when it’s respective compressor is running.
Upstream of the dryer will be a separator with a zero loss
drain valve followed by a 0.01 micron coalescing filter. Both
filters shall have element change indicators.

BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
Page 17
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-11
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air System Specifications1

Complete System Capacity2 System FLA


System3 Receiver4 Noise5
System HP
BTU/HR (Gallons) Level
Model No. 200 psig 208V 230V 460V
HPA-7T-D200 7½ 33 34,124 200* 76 69 60 30
HPA-10T-D200 10 48 46,028 200* 79 90 78 39

Notes: 1 Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities (reserve compressor on standby) and are shown in Inlet Cubic
Feet per Minute (ICFM). System losses subtracted from pump capacity.
3 All system BTU/HR is shown with reserve compressor on standby.
4 * Indicates standard receiver
5 All noise levels are shown in dB(A) and reflect one pump running.

Page 18
BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
BASE MOUNT
SSB-120-12

QUAD 7.5-10
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air Quadruplex Single Point Connection (SPC) Base Mount Systems
(7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) System Design Isolation System
The instrument air system shall be of a single point connection Each compressor and motor assembly shall be fully isolated
base mounted design consisting of four compressor modules from the main compressor module base by means of a four
with dryers, and a single control module with control panel, point, heavy duty, spring isolation system for a minimum of
air receiver, filtration system and oil/water condensate 95% isolation efficiency. Where required by local or state
separator. Each module has a maximum base width of 34.50" regulation, optional seismically restrained isolators can be
(88 cm), and be fully compliant with the latest edition of provided at an additional cost. Each main compressor module
NFPA 99. The modules shall be assembled as one unit with base frame shall not exceed 34.50" in width.
single point connections for air discharge, electrical and
condensate drain. Control Module with Air Receiver/Filter/Regulator
Compressor/Dryer Module (Compressor, Drive, Motor, System
Piping, Dryer) The control module shall include a NEMA 12, U.L. labeled
The compressor shall be a high pressure "oil-lubricated" control system, duplexed final line filters, regulators, oil
continuous duty rated type. The design shall be two staged, indicators, and a condensate oil/water separator and dew point
air-cooled, reciprocating type with corrosion resistant reed monitor. All of the above shall be factory piped and wired in
type valves with stainless steel reeds. Both oil scrapper ring accordance with NFPA 99 and include valving to allow
and piston rings shall be made from long lasting special cast complete air receiver bypass and an air sampling port. The
iron and designed for continuous duty operation. The vertical air receiver shall be ASME Coded, National Board
crankshaft shall be constructed of forged steel and fully Certified, galvanized, rated for a minimum 250 PSIG design
supported on both ends by heavy duty ball bearings and seals. pressure and includes a liquid level gauge glass, safety relief
The crankcase shall be constructed of gray cast iron. valve, manual drain valve, and automatic solenoid drain valve.
Maximum heat dissipation shall be achieved through cast iron Control System
cylinders with external cooling vanes. Cylinder sleeves are not The control system shall have an HMI touch screen control,
required. Both low and high pressure pistons are made from automatic lead/lag sequencing with circuit breaker disconnects
cast aluminum with chrome-moly piston pins. Second stage for each motor with external operators, full voltage motor
cylinder head shall be equipped with a wired shutdown switch starters, overload protection, 24V control circuit and hand-off-
for high discharge air temperature. The connecting rod shall auto selector switch for each compressor. Automatic
be of a one-piece design. The compressor shall be v-belt alternation of all compressors based on first-on/first-off
driven through a combination flywheel/sheave and steel motor principle with provisions for simultaneous operation if
sheave with tapered bushing and protected by an OSHA required. Automatic activation of reserve unit, if required, will
approved totally enclosed belt guard. A sliding motor activate an audible alarms as well as a visual alarm on the
mounting base that is fully adjustable through twin adjusting HMI. The HMI displays service due, run hours for each
screws shall achieve belt tensioning. The motor shall be a compressor, system status, operating pressure, dew point and
NEMA rated, open drip proof, 1800 RPM, with 1.15 service high discharge air temperature shutdown. A complete alarm
factor suitable for 208 or 230/460V electrical service. Each and service history is available on the HMI.
compressor shall have its own inlet air filter mounted on the
first stage compressor heads. Discharge air from the first
stage compressor cylinder passes through an air-cooled Dew Point Transmitter
intercooler prior to entering the second stage. The second The control module shall incorporate a dew point transmitter
stage discharge air then passes through an air-cooled that is mounted, pre-piped, wired to the control panel and
aftercooler designed for a maximum approach temperature of displayed on the HMI touch screen. The transmitter probe
12° F complete with moisture separator and zero loss shall be 316L SS with sintered stainless steel filter and thin
automatic drain valve prior to entering the dryer. The film polymer sensor. The system accuracy shall be ± 2° C.
compressor discharge line shall include a flex connector, Dew point alarm shall be factory set at -22° F (-30° C) per
safety relief valve, isolation valve, and check valve. The NFPA 99 with remote alarm contacts in the control panel.
discharge air piping shall be of ASTM B-819 copper tubing, Statement of Warranty
brass, and/or stainless steel. The discharge flex connector shall BeaconMedæs warrants all Instrument Air Systems, to be free
be braided 304 stainless steel, brass, or bronze. Each of defects in material and workmanship under normal use for
compressor has its own dedicated dryer. Each dryer is a period not to exceed thirty (30) months from date of
individually sized for peak calculated demand and capable of shipment, or twenty four (24) months from date of start-up.
producing a -40° F (-40° C) pressure dew point. Dryer purge
only occurs when it’s respective compressor is running.
Upstream of the dryer will be a separator with a zero loss
drain valve followed by a 0.01 micron coalescing filter. Both
filters shall have element change indicators.

BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
Page 19
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-12
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air System Specifications1

Complete System Capacity2 System FLA


System3 Receiver4 Noise5
System HP
BTU/HR (Gallons) Level
Model No. 200 psig 208V 230V 460V
HPA-7Q-D200 7½ 49.5 51,186 200* 76 92 80 40
HPA-10Q-D200 10 72 69,042 200* 79 119 104 52

Notes: 1 Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities (reserve compressor on standby) and are shown in Inlet Cubic
Feet per Minute (ICFM). System losses subtracted from pump capacity.
3 All system BTU/HR is shown with reserve compressor on standby.
4 * Indicates standard receiver
5 All noise levels are shown in dB(A) and reflect one pump running.

Page 20
BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
SIMLEX 7.5-10
BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-13
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air Simplex Single Point Connection (SPC) Base Mount Systems
with Cylinder Air Back-up Header (7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) System Design Control Module with Air Receiver/Filter/Regulator
The instrument air system shall be of a single point connection System
base mounted design consisting of one compressor module The control module shall include a NEMA 12, U.L. labeled
with dryer, and a single control module with control panel, air control system, duplexed final line filters, regulators, oil
receiver, filtration system, oil/water condensate separator and indicators, condensate oil/water separator, dew point monitor
backup cylinder header for cylinder air. Each module has a and an air sample port, backup cylinder header and cylinder
maximum base width of 34.50" (88 cm), and be fully restraint system. All of the above shall be factory piped and
compliant with the latest edition of NFPA 99. The modules wired in accordance with NFPA 99. The vertical air receiver
shall be assembled as one unit with single point connections shall be ASME Coded, National Board Certified, galvanized,
for air discharge, electrical and condensate drain. rated for a minimum 250 PSIG design pressure and includes a
Compressor/Dryer Module (Compressor, Drive, Motor, liquid level gauge glass, safety relief valve, manual drain
Piping, Dryer) valve, and automatic solenoid drain valve.
The compressor shall be a high pressure "oil-lubricated" Backup Air Cylinder Header
continuous duty rated type. The design shall be two staged, A high-pressure header shall be provided to accommodate
air-cooled, reciprocating type with corrosion resistant reed multiple air cylinders with staggered cylinder connections on
type valves with stainless steel reeds. Both oil scraper ring and 5" centers. The header shall be designed for inlet pressures up
piston rings shall be made from long lasting special cast iron to 3000 psig and shall be provided with a flexible pigtail with
and designed for continuous duty operation. The crankshaft
shall be constructed of forged steel and fully supported on check valve for each cylinder connection. Pigtail connections
both ends by heavy duty ball bearings and seals. The shall be CGAV-1 #346 cylinder connections. A pressure
crankcase shall be constructed of gray cast iron. Maximum regulator (field adjustable; 40 to 300 psig) shall be provided
heat dissipation shall be achieved through cast iron cylinders on the backup header to regulate the cylinder pressure. The
with external cooling vanes. Cylinder sleeves are not required. regulator shall utilize high-pressure brass unions at the inlet
Both low and high pressure pistons are made from cast and outlet connections for attachment to the header assembly
aluminum with chrome-moly piston pins. Second stage and supply line. The simplex header shall be provided with a
cylinder head shall be equipped with a wired shutdown switch backup low pressure switch and a low flow adapter. The
for high discharge air temperature. The connecting rod shall header shall be provided with a high-pressure master shut-off
be of a one-piece design. The compressor shall be v-belt
driven through a combination flywheel/sheave and steel motor valve to isolate the header from the system, during service and
sheave with tapered bushing and protected by an OSHA repairs, without affecting the remainder of the system. The
approved totally enclosed belt guard. A sliding motor header shall be factory piped to the inlet side of the duplexed
mounting base that is fully adjustable through twin adjusting final line filters.
screws shall achieve belt tensioning. The motor shall be a Control System
NEMA rated, open drip proof, 1800 RPM, with 1.15 service The duplex mounted and wired control system shall be NEMA
factor suitable for 208 or 230/460V electrical service. Each 12 and U.L. labeled. The control system shall have an HMI
compressor shall have its own inlet air filter mounted on the touch screen control, automatic lead/lag sequencing with
first stage compressor heads. Discharge air from the first circuit breaker disconnects for each motor with external
stage compressor cylinder passes through an air-cooled operators, full voltage motor starters, overload protection, 24V
intercooler prior to entering the second stage. The second control circuit and hand-off-auto selector switch for each
stage discharge air then passes through an air-cooled compressor. Automatic alternation of both compressors based
aftercooler designed for a maximum approach temperature of on first-on/first-off principle with provisions for simultaneous
12° F complete with moisture separator and zero loss operation if required. Automatic activation of reserve unit, if
automatic drain valve prior to entering the dryer. The required, will activate an audible alarm as well as a visual
compressor discharge line shall include a flex connector, alarm on the HMI. The HMI displays service due, run hours,
safety relief valve, isolation valve, and check valve. The system status, operating pressure, dew point and high
discharge air piping shall be of ASTM B-819 copper tubing, discharge air temperature shutdown. A complete alarm and
brass, and/or stainless steel. The discharge flex connector shall service history is available on the HMI.
be braided 304 stainless steel, brass, or bronze. The dryer is
individually sized for peak calculated demand and capable of Dew Point Transmitter
producing a -40° F (-40° C) pressure dew point. Dryer purge The control module shall incorporate a dew point transmitter
only occurs when the compressor is running. Upstream of the that is mounted, pre-piped, wired to the control panel and
dryer will be a separator with a zero loss drain valve followed displayed on the HMI touch screen. The transmitter probe
by a 0.01 micron coalescing filter. Both filters shall have shall be 316L SS with sintered stainless steel filter and thin
element change indicators. film polymer sensor. The system accuracy shall be ± 2° C.
Dew point alarm shall be factory set at -22° F (-30° C) per
Isolation System NFPA 99 with remote alarm contacts in the control panel.
The compressor and motor assembly shall be fully isolated
from the main compressor module base by means of a four Statement of Warranty
point, heavy duty, spring isolation system for a minimum of BeaconMedæs warrants all Instrument Air Systems, to be free
95% isolation efficiency. Where required by local or state of defects in material and workmanship under normal use for
regulation, optional seismically restrained isolators can be a period not to exceed thirty (30) months from date of
provided at an additional cost. shipment, or twenty four (24) months from date of start-up.

BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-120-13
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 10/01/06
(704) 588-0854 or (704) 588-4949 (fax) for further information.

Instrument Air System Specifications1


System
Complete System FLA
Capacity2 System3 Receiver4 Noise No. of
System HP
BTU/HR (Gallons) Level5 Cylinders6
Model No. 200 psig 208V 230V 460V
HPA-7S-D200 7½ 16.5 17,062 200* 76 5 23 20 10
HPA-10S-D200 10 24 23,014 200* 79 7 30 26 13
Notes: 1 Normal operating conditions at a maximum ambient of 105° F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities (reserve compressor on standby) and are shown in Inlet Cubic
Feet per Minute (ICFM). System losses subtracted from pump capacity.
3 All system BTU/HR is shown with reserve compressor on standby.
4 * Indicates standard receiver
5 All noise levels are shown in dB(A) and reflect one pump running.
6 Number of air cylinders for 1-hour of backup. All cylinders are supplied by others.

Page 22
BeaconMedæs Š P. O. Box 7064 Charlotte, N. C. 28241 Š Phone: (704) 588-0854 Fax: (704) 588-4949
SERIES B DISS
WALL OUTLET
SSB-840-03
Page 1 of 2
2/01/2006

Series B Recessed Medical Gas Wall Outlet


DISS Key Style
SPECIFICATION
DISS Medical Gas Wall Outlet identification shall be affixed to the inlet tube and the face of
The DISS Medical Gas wall outlets shall be gas specific for the mounting plate. A secondary valve shall be installed in
the services indicated and accept only corresponding DISS the outlet block of the rough-in assembly for both pressure
nuts and nipples. The outlets shall be UL listed, CSA certified, testing and preventing gas flow (except vacuum and WAGD)
and be fully compliant with the latest edition of NFPA 99. All when the latch-valve assembly is removed for service. A 3/8"
outlets shall be 100% tested for flow, leaks and connector high metal flange around the outlet opening shall provide a
attachment. The outlets shall be cleaned for oxygen service plaster barrier. A temporary cover shall be provided to keep
prior to shipping. The outlets shall be made in the U.S.A. A debris out of the outlet during installation. The rough-in
die cast, light gray, epoxy powder coated trim plate can be assembly shall contain a double seal to prevent gas leakage
provided to trim each wall outlet and to fill the space between between the rough-in and latch-valve assemblies after the wall
adjacent outlets. The trim plate shall allow latch valves to be is finished. A single o-ring seal shall not be acceptable.
individually removed for servicing. Latch Valve Assembly
Outlet Design The latch-valve assembly shall include an o-ring seal primary
A complete medical gas outlet shall consist of a gas-specific valve, be gas specific for the labeled service, and accept only
rough-in assembly for installation before the wall is finished corresponding hose and apparatus with DISS nut and nipple
and a matching gas-specific latch-valve assembly and cover adapters. The latch-valve assembly shall be indexed to the
plate for installation after the wall is finished. corresponding rough-in assembly to avoid accidental
Rough-in Assembly cross-connection and shall telescope up to 3/4" to allow for
The rough-in assembly shall be of modular design and include variation in finished wall thickness from 1/2" up to 1-1/4". A
a gas-specific 16-gauge steel mounting plate designed to metal cover plate insert with permanent, color-coded marking
permit on-site ganging of multiple outlets, in any order, on 5" of service identification shall be included as part of the
centerline spacing. A machined brass outlet block shall be latch-valve assembly.
permanently attached to the mounting bracket to permit the
1/2" OD (3/8" nominal),type-K copper inlet tube to swivel
360° for attachment to the piping system. Gas service
Item Concealed Wall Outlet
Gas Service Color Code Complete Assembly Rough-in Assembly Latch-Valve Assembly
Series B O2 White F 6-121100-00 F 6-233110-00 F 6-230910-00
DISS N2O Blue F 6-121101-00 F 6-233111-00 F 6-230911-00
(U.S.) AIR Yellow F 6-121102-00 F 6-233112-00 F 6-230912-00
VAC White F 6-121103-00 F 6-233113-00 F 6-230913-00
N2 Black F 6-121104-00 F 6-233114-00 F 6-230914-00
Instrument Air Red F 6-121108-00 F 6-233118-00 F 6-230916-00
WAGD Purple F 6-121109-00 F 6-233119-00 F 6-230919-00
CO2 Gray F 6-121110-00 F 6-233120-00 F 6-230920-00
CO2-O2 (CO2 >7%) Gray/Green F 6-121111-00 F 6-233121-00 F 6-230921-00
O2 -CO2 (CO2<7%) Green/Gray F 6-121112-00 F 6-233122-00 F 6-230922-00
He-O2 (He > 80%) Brown/Green F 6-121113-00 F 6-233123-00 F 6-230923-00
O2 -He (He < 80%) Green/Brown F 6-121114-00 F 6-233124-00 F 6-230924-00
Series B O2 White F 6-121100-00 F 6-233110-00 F 6-230910-00
DISS N2O Blue F 6-121101-00 F 6-233111-00 F 6-230911-00
(International) AIR Black/White F 6-151012-00 F 6-233116-00 F 6-230917-00
VAC Yellow F 6-151013-00 F 6-233117-00 F 6-230918-00
N2 Black F 6-121104-00 F 6-233114-00 F 6-230914-00
Instrument Air Red F 6-121108-00 F 6-233118-00 F 6-230916-00
WAGD Purple F 6-121109-00 F 6-233119-00 F 6-230919-00
CO2 Gray F 6-121110-00 F 6-233120-00 F 6-230920-00
Miscellaneous Slide* F 6-120978-00
Blank, Gas F 6-120979-00
Duplex Electrical Receptacle (Gray) F 6-120972-00
Trim Plate (5") F 6-325161-00
*Good design practice should include a slide for each vacuum outlet.

BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088
SSB-840-03
Page 2 of 2
2/01/2006

Series B DISS Wall Assembly

DISS Outlet Optional Assemblies

Page 24 BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088
SERIES B DISS
SSB-840-04

CONSOLES
Page 1 of 2
2/01/06

Series B Console and Modular Headwall Medical Gas Outlet


DISS Key Style
SPECIFICATION

DISS Medical Gas Outlet


The DISS Medical Gas outlets for consoles and modular walls Gas service identification shall be affixed to the inlet tube and
shall be gas specific for the services indicated and accept only the face of the mounting plate. A secondary valve shall be
corresponding DISS nuts and nipples. The outlets shall be UL installed in the outlet block of the rough-in assembly for both
listed, CSA certified, and be fully compliant with the latest pressure testing and preventing gas flow (except vacuum and
edition of NFPA 99. All outlets shall be 100% tested for flow, WAGD) when the latch-valve assembly is removed for
leaks and connector attachment. The outlets shall be cleaned service. The rough-in assembly shall contain a double seal to
for oxygen service prior to shipping. The outlets shall be made prevent gas leakage between the rough-in and latch-valve
in the U.S.A. A die cast, light gray, epoxy powder coated or assemblies after the wall is finished. A single o-ring seal shall
plastic trim plate (optional) can be provided to trim each outlet not be acceptable.
assembly.
Latch Valve Assembly
Outlet Design The latch-valve assembly shall include an o-ring seal primary
A complete medical gas outlet shall consist of a gas-specific valve and shall be indexed to the corresponding gas service
rough-in assembly and a matching gas-specific latch-valve rough-in assembly to avoid accidental cross-connection. Latch
assembly. valves shall telescope up to 3/4" to allow for variation in wall
thickness. A metal cover plate insert with permanent
Rough-in Assembly color-coded gas service identification shall be included as part
The rough-in assembly shall be of modular design and include of the latch valve assembly.
a gas-specific 16-gauge steel mounting plate designed to
permit on-site installation. A machined brass outlet block shall
be permanently attached to the mounting bracket to permit the
1/2" OD (3/8" nominal), type-K copper inlet tube to swivel
360° for attachment to the piping system.

Item Standard Console


Gas Service Color Code Complete Assembly* Latch-Valve Assembly Rough-in Assembly
O2 White F 6-121050-00 F 6-230910-00 F 6-233010-00
N2O Blue N/A F 6-230911-00 F 6-233011-00
AIR Yellow F 6-121052-00 F 6-230912-00 F 6-233012-00
Series B
VAC White F 6-121053-00 F 6-230913-00 F 6-233013-00
DISS
(U.S.) Inst Air Red N/A F 6-230916-00 F 6-233018-00
WAGD Purple N/A F 6-230919-00 F 6-233019-00
N2 Black N/A F 6-230914-00 F 6-233014-00
CO2 Gray N/A F 6-230920-00 F 6-233020-00
Series B O2 White N/A F 6-230910-00 F 6-233010-00
DISS AIR Black/White N/A F 6-230917-00 F 6-233016-00
(International)
VAC Yellow N/A F 6-230918-00 F 6-233017-00
Slide F 6-135012-00
Miscellaneous Blank, Gas F 6-415169-00

*Complete assembly consists of a rough-in assembly and latch-valve assembly. Optional trim plate must be ordered separately.

BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088 Page 25
SSB-840-04
Page 2 of 2
2/01/06

Series B DISS Console Assembly

Optional assemblies shown with optional 5” trim plate

Page 26 BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088
SSB-850-01
Page 2 of 2
2/01/06

Gas Control Panels

HORIZONTAL
CONTROL
PANEL

VERTICAL
CONTROL
PANEL

BeaconMedæs Š 14408 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088 Page 27
Page 28
SSB-890-01

ASSEMBLIES
Page 1 of 7

HOSE
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION

Fittings and Components Gas Specific DISS Nipples


All BeaconMedaes DISS valves, bodies, nuts and nipples are The gas specific DISS nipple mates with the gas specific DISS
manufactured to comply with the latest edition of CGA V-5, valve or valve body. They are supplied with O-rings where
Diameter Index Safety System (Non-interchangeable low required and are available with 1/4 -18 NPT male threads,
pressure connections for medical gas applications) 1/8 -27 NPT male threads or barbed ends for installation in
hose assemblies
Gas Specific DISS Valve or DISS Body
DISS BODY: When the DISS nut and nipple are disconnected DISS Nut
gas will continue to flow. The DISS nut is used to secure the DISS nipple to the valve or
DISS VALVE: Contains a valve mechanism and begins to flow valve body. Often times the DISS nut may be used on several
gas when the DISS nut and nipple are connected and stops flow different gases. The valve or body and the nipple are the
when the DISS nut and nipple are disconnected. components to make the system gas specific.

DISS valves and valve bodies are available with 1/4 -18 NPT
male threads, 1/8 -27 NPT male threads or barbed ends for For assistance in determining the components you may require,
installation in hose assemblies please call 1-888-4MEDGAS to speak with one of our
specialists.

HOSE ASSEMBLIES
To order hose assemblies:
1. Select the fitting for each end of the hose assembly-one from (A) and one from (C) using the matrix shown.
2. Choose the appropriate part number according to the gas service required (B).
3. Replace the XX with a two-digit number from the chart (D). This two-digit number corresponds with the length of the hose required.
Example: A hose assembly for oxygen that is five feet long and uses a Geometric valve on one end and a Diameter-Index Safety System
(DISS) nut and nipple on the other end would carry a part number of 6-139103-05
NOTE:
Maximum length is thirty feet. Unless otherwise specified, all assemblies utilize 1/4” ID hose.

BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088 Page 29
SSB-890-01

ASSEMBLIES
Page 2 of 7

HOSE
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION (continued)

C
HOSE ASSEMBLIES

DISS nut and nipple Geometric adapter


Latch Key adapter Pin Index adapter
A B
Schrader quick-connect
N2 6-132184-XX

O2 6-132106-XX 6-132026-XX 6-132500-XX


N2O 6-132107-XX 6-132027-XX 6-132501-XX
DISS nut and nipple
AIR 6-132110-XX 6-132028-XX 6-132502-XX
VAC 6-132111-XX 6-132029-XX 6-123503-XX
N2 6-132112-XX
CO2 6-132118-XX
WAGD 6-132364-XX 6-132401-XX 6-132504-XX
O2 6-139103-XX 6-139012-XX
Geometric valve N2O 6-139105-XX 6-139013-XX
AIR 6-139109-XX 6-139014-XX
VAC 6-139108-XX 6-139015-XX
VAC 5/16” ID 6-139500-XX 6-139501-XX
WAGD 6-139366-XX 6-139340-XX
O2 6-139380-XX 6-139391-XX
Pin Index valve N2O 6-139381-XX 6-139392-XX
AIR 6-139382-XX 6-139393-XX
VAC 6-139383-XX 6-139394-XX
VAC 5/16” ID 6-139502-XX 6-139503-XX
WAGD 6-139384-XX 6-139395-XX
O2 6-139370-XX 6-139396-XX
Latch Key valve N2O 6-139371-XX 6-139397-XX
AIR 6-139372-XX 6-139398-XX
VAC 6-139373-XX 6-139399-XX
VAC 5/16” ID 6-139504-XX 6-139505-XX
WAGD 6-139374-XX 6-139400-XX
O2 6-139140-XX 6-139016-XX
N2O 6-139141-XX 6-139017-XX
DISS male valve
AIR 6-139142-XX 6-139018-XX
VAC 6-139143-XX 6-139019-XX
VAC 5/16” ID 6-139506-XX 6-139507-XX
N2 6-139144-XX
WAGD 6-139149-XX 6-139390-XX
CO2 6-139385-XX

Refer to the table below for overall length of hose assembly. Use the numbers in the XX column to denote hose length.
D
XX HOSE LENGTH1 (ft) XX HOSE LENGTH1 (ft) XX HOSE LENGTH2 (in) NOTE
1
01 1 09 9 31 32” XX numbers 01 through 30 represent hose length
02 2 10 10 32 38” in feet.
03 3 11 11 33 44” DOES NOT INCLUDE END FITTINGS.
2
04 4 12 12 34 50” XX numbers 31 through 36 represent special
05 5 15 15 35 56” application sizes (ceiling drop hoses) in inches.
06 6 22 22 36 68” INCLUDES END FITTINGS.
08 8 30 30

Page 30 BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088
SSB-890-01

ASSEMBLIES
Page 3 of 7

HOSE
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION (continued)
VALVES
The check valves below operate smoothly and are available with U.S. or international color coding. Gas-specific components are
permanently indexed to prevent accidental incorrect assembly.
NOTE: Unless otherwise specified, hose barb check valves are for 1/4” ID hose

Geometric DISS Valve Pin Index Latch Key

HOSE BARB CONNECTION


Gas Geometric DISS Pin Index Latch Key
Oxygen 6-121200-10 6-121201-10 6-121202-10 6-121203-10
Nitrous Oxide 6-121200-11 6-121201-11 6-121202-11 6-121203-11
Air 6-121200-12 6-121201-12 6-121202-12 6-121203-12
Vacuum 6-121200-13 6-121201-13 6-121202-13 6-121203-13
Vacuum 5/16” ID hose 6-121200-53 6-121201-53 6-121202-53 6-121203-53
Nitrogen 6-121201-14
Instrument Air 6-121201-18
WAGD 6-121200-19 6-121201-19 6-121202-19 6-121203-19
Carbon Dioxide 6-121201-20

INTERNATIONAL COLOR CODING


Oxygen 6-121200-15 6-121201-15 6-121202-15 6-121203-15
Air 6-121200-16 6-121201-16 6-121202-16 6-121203-16
Vacuum 6-121200-17 6-121201-17 6-121202-17 6-121203-17
Vacuum 5/16” ID hose 6-121200-57 6-121201-57 6-121202-57 6-121203-57

Geometric DISS Valve Pin Index Latch Key

1/4 - 18 NPT CONNECTION


Gas Geometric DISS Pin Index Latch Key
Oxygen 6-121210-10 6-121211-10 6-121212-10 6-121213-10
Nitrous Oxide 6-121210-11 6-121211-11 6-121212-11 6-121213-11
Air 6-121210-12 6-121211-12 6-121212-12 6-121213-12
Vacuum 6-121210-13 6-121211-13 6-121212-13 6-121213-13
Nitrogen 6-121211-14
Instrument Air 6-121211-18
WAGD 6-121210-19 6-121211-19 6-121212-19 6-121213-19
Carbon Dioxide, CO2-O2 6-121211-20
O2-CO2 6-121211-22
Helium, He-O2 6-121211-23
O2-He 6-121211-24

INTERNATIONAL COLOR CODING


Oxygen 6-121210-10 6-121211-10 6-121212-15 6-121213-15
Air 6-121210-16 6-121211-12 6-121212-16 6-121213-16
Vacuum 6-121210-17 6-121211-13 6-121212-17 6-121213-17

BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088 Page 31
SSB-890-01

ASSEMBLIES
Page 4 of 7

HOSE
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION (continued)
VALVES (continued)

Geometric DISS Valve Pin Index Latch Key


1/8 - 27 NPT CONNECTION
Gas Geometric DISS Pin Index Latch Key
Oxygen 6-121208-10
Nitrous Oxide 6-121208-11
Air 6-121208-12
Nitrogen 6-121208-14

DISS FITTINGS

DISS NIPPLES WITH O-RINGS TO MALE PIPE THREAD


PART NUMBER DESCRIPTION
NUT NIPPLE
6-825000-00 6-510016-00 Nipple, oxygen with o-ring to 1/8 -27 NPT male
6-511511-00 6-511605-00 Nipple, nitrous oxide with o-ring to 1/4 -18 NPT male
6-511511-00 6-511604-00 Nipple, air nipple with o-ring to 1/4 -18 NPT male
6-511511-00 6-512070-01 Nipple, vacuum with o-ring to 1/4 -18 NPT male
6-511511-00 6-511603-00 Nipple, nitrogen with o-ring to 1/4 -18 NPT male
6-511518-00 6-511620-00 Nipple, instrument air with o-ring to 1/4 -18 NPT male
6-511510-00 6-510079-00 Nipple, WAGD with o-ring to 1/8 -27 NPT male
6-511511-00 6-511612-00 Nipple, carbon dioxide, CO2-O2 mixture with o-ring to 1/4 -18 NPT male
6-511511-00 6-511614-00 Nipple, O2-CO2 mixture with o-ring to 1/4 -18 NPT male
6-511511-00 6-511616-00 Nipple, helium, He-O2 mixture with o-ring to 1/4 -18 NPT male
6-511511-00 6-511617-00 Nipple, O2-He with o-ring to 1/4 -18 NPT male

DISS NUT AND NIPPLE ASSEMBLIES WITH O-RINGS TO 1/8 -27 NPT MALE THREADS
PART NUMBER DESCRIPTION

6-121209-10 Assembly, oxygen nut and nipple with o-ring to 1/8 -27 NPT
6-121209-11 Assembly, nitrous oxide nut and nipple with o-ring to 1/8 -27 NPT
6-121209-12 Assembly, air nut and nipple with o-ring to 1/8 -27 NPT
6-121209-13 Assembly, vacuum nut and nipple with o-ring to 1/8 -27 NPT
6-121209-14 Assembly, nitrogen nut and nipple with o-ring to 1/8 -27 NPT
6-121209-19 Assembly, WAGD nut and nipple with o-ring to 1/8 -27 NPT
6-121209-20 Assembly, carbon dioxide nut and nipple with o-ring to 1/8 -27 NPT

Page 32 BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088
SSB-890-01
Page 5 of 7
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION (continued)
QUICK-CONNECT FITTINGS
GEOMETRIC QUICK-CONNECT ADAPTERS WITH PIPE THREADS
PART NUMBER DESCRIPTION
6-512013-00 Adapter, oxygen, 1-3/4” long, with 1/4 –18 NPT male thread
6-512001-00 Adapter, nitrous oxide, with 1/4 –18 NPT male thread
6-210636-00 Adapter, air, 1-3/4” long, non-swivel, with 1/4 –18 NPT male thread
6-512003-00 Adapter, vacuum, with 1/4 –18 NPT male thread

6-512092-00 Adapter, oxygen, with 1/8 –27 NPT male thread


6-512094-00 Adapter, vacuum, with 1/8 –27 NPT male thread

6-512542-00 Adapter, oxygen, 2-15/16” long, with 1/4 –18 NPT male thread
6-230338-00 Adapter, air, 2-15/16” long, with 1/4 –18 NPT male thread
6-230348-00 Adapter, WAGD, 2-15/16” long, with 1/4 –18 NPT male thread

GEOMETRIC QUICK-CONNECT ADAPTER WITH DISS THREAD

6-512019-00 Adapter, oxygen, with 9/16 –18 DISS male thread

PIN INDEX QUICK-CONNECT ADAPTERS


6-230625-00 Adapter, oxygen, with 1/4 –18 NPT male thread
6-230624-00 Adapter, oxygen, International, with 1/4 –18 NPT male thread
6-230627-00 Adapter, air, with 1/4 –18 NPT male thread
6-230628-00 Adapter, vacuum, with 1/4 –18 NPT male thread

6-231025-00 Adapter, oxygen, with 1/8 –27 NPT male thread


6-231027-00 Adapter, air, with 1/8 –27 NPT male thread
6-231029-00 Adapter, vacuum, with 1/8 –27 NPT male thread

LATCH KEY QUICK-CONNECT ADAPTERS


6-231030-00 Adapter, oxygen, round striker, with 1/4 –18 NPT male thread
6-231032-00 Adapter, air, rectangular striker, with 1/4 –18 NPT male thread
6-231034-00 Adapter, vacuum, rectangular striker, with 1/4 –18 NPT male thread

DISS BODY ADAPTERS


PART NUMBER DESCRIPTION

6-513001-00 Adapter, oxygen, with 1/4 –18 NPT male thread

6-511554-00 Adapter, nitrogen, with 1/4 –18 NPT male thread


6-520287-00 Adapter, vacuum, with 1/4 –18 NPT male thread
6-520395-00 Adapter, nitrous oxide, with 1/4 –18 NPT male thread
6-520396-00 Adapter, air, with 1/4 –18 NPT male thread
6-515606-00 Adapter, WAGD, with 1/4 –18 NPT male thread
6-511558-00 Adapter, instrument air with 1/4-18 NPT male thread
6-520288-00 Adapter, CO2 and CO2-O2 mixtures with 1/4 -18 NPT male threads

BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088 Page 33
SSB-890-01
Page 6 of 7
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION (continued)
HOSE BARB ADAPTERS, HOSE RETRACTORS, BULK HOSES, AND FERRULES

Geometric DISS Pin Index Latch Key

HOSE BARB ADAPTERS FOR 1/4” ID HOSE


Geometric DISS
Gas Geometric Pin Index Latch Key
With Ferrule Nipple w/O-ring Nut
Oxygen 6-210221-00 6-512007-00 6-512076-00 6-825000-00 6-231016-00 6-232114-00
Nitrous Oxide 6-210220-00 6-512018-00 6-511611-00 6-511511-00 6-232129-00 6-232115-00
Air 6-210222-00 6-230339-00 6-511609-00 6-511511-00 6-231018-00 6-232116-00
Vacuum 6-210223-00 6-512009-00 6-512077-00 6-511511-00 6-231017-00 6-232117-00
Nitrogen 6-511610-00 6-511511-00
Instrument Air 6-511621-00 6-511518-00
WAGD 6-230350-00 6-511515-00 6-511510-00 6-232139-00 6-232118-00
Carbon Dioxide 6-511607-00 6-511511-00

HOSE BARB ADAPTERS FOR 5/16” ID HOSE


Fittings and Components
DISS
Gas Geometric
Nipple w/O-ring Nut Unless otherwise indicated, the fittings and
Vacuum 6-512115-00 6-134157-00 6-511511-00 components listed in this catalog are designed for low
WAGD 6-230349-00 6-511606-00 6-511510-00 pressure medical gas systems where pressure does not
exceed 200 psig. In addition to fittings and
HOSE RETRACTOR components that utilize geometric shape indexing and
DISS connections, a complete offering of general
purpose fittings is also available.
Heavy Duty, Double Retractor for
all Pressure and Vacuum Service 6-132002-00 Caution:
Common threads, crimp or slip-fit connections
permit the assembly of components which may
permit the cross-indexing of services, unanticipated
BULK HOSE 1/4” ID (Length sold per foot) performance, poor flow, and excessive pressure
drops. The user is cautioned to consider such
Gas Service Color Code Part Number
factors when using these components.
Oxygen Green 6-611044-02
Nitrous Oxide Blue 6-611044-01 BeaconMedæs fittings and components are medical-
Air Yellow 6-611044-03 grade fittings, carefully machined to precise
Vacuum White 6-611044-04 dimensions, and offer outstanding durability.
WAGD Purple 6-611044-05
Nitrogen Black 6-611044-00
All Others Black 6-611044-00
5/16” ID
Vacuum White 6-656010-06

FERRULES
For 1/4” ID Hose (pressure) 6-355021-00
For 5/16” ID Hose (vacuum) 6-405000-00
Ferrule Hand Crimping Tool 6-995508-00

Page 34 BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088
SSB-890-01

ASSEMBLIES
Page 7 of 7

HOSE
8/1/06

Hose Assemblies, Valves, Fittings, and Components


SPECIFICATIONS AND ORDERING INFORMATION (continued)
FITTINGS AND COUPLINGS

HOSE/TUBING FITTINGS

6-512012-00 Connector, hose barb for 1/4” ID hose, to 1/4 –18 NPT female thread
6-512506-00 Connector, hose barb for 5/16” ID hose, to 1/4 –18 NPT female thread

6-512508-00 Connector, hose barb for 5/16” ID hose, to 1/4 –18 NPT male thread
6-515002-00 Connector, hose barb for 1/4” ID hose, to 1/4 –18 NPT male thread

DISS BODY WITH HOSE BARB

6-520174-00 Adapter, oxygen, for 1/4” ID hose

6-525300-53 Adapter, vacuum, large bore, for 5/16” ID hose

6-525298-00 Adapter, nitrous oxide, for 1/4” ID hose


6-525299-00 Adapter, air, for 1/4” ID hose
6-525300-00 Adapter, vacuum, for 1/4” ID hose
6-525302-00 Adapter, nitrogen, for 1/4” ID hose
6-525303-00 Adapter, WAGD, for 1/4” ID hose
6-525301-00 Adapter, carbon dioxide, for 1/4” ID hose

COUPLINGS AND BUSHINGS

6-835020-00 Coupling, 1/4 –18 NPT female each end


6-513011-00 Coupling, 1/4 –18 NPT female to 1/8 –27 NPT female

6-513003-00 Coupling, 1/4 –18 NPT male thread x 1/8 -27 NPT male thread

6-835000-00 Bushing, 1/4 –18 NPT male to 1/8 –27 NPT female

6-835001-00 Coupling, 1/4 –18 NPT female thread x 1/8 -27 NPT male

BeaconMedæs Š 14408 W. 105th Street Lenexa, KS 66215 Š Phone: (913) 894-6058 Fax: (913) 894-6088 Page 35
Page 36
®

A company within the Atlas Copco Group

13325 Carowinds Blvd • Charlotte, NC 28273 • Phone 1 888 4 MED GAS • Fax 704 588 4949
www.beaconmedaes.com Page 37
Lessons Learned
from Natural Gas STAR Partners

Convert Gas Pneumatic Controls To


Instrument Air

Executive Summary Technology Background

Pneumatic instrument systems powered by high-pressure The natural gas industry uses a variety of process control
natural gas are often used across the natural gas and devices to operate valves that regulate pressure, flow,
petroleum industries for process control. Typical process temperature, and liquid levels. Most instrumentation and
control applications include pressure, temperature, liquid control equipment falls into one of three categories: (1)
level, and flow rate regulation. The constant bleed of pneumatic; (2) electrical; or (3) mechanical. In the vast
natural gas from these controllers is collectively one of the majority of applications, the natural gas industry uses
largest sources of methane emissions in the natural gas pneumatic devices, which make use of readily available
industry, estimated at approximately 51 billion cubic feet high-pressure natural gas to provide the required energy
(Bcf) per year in the production sector, 14 Bcf per year in and control signals. Pneumatic instrument systems
the transmission sector, and <1 Bcf from processing. powered by high-pressure natural gas are used throughout
the natural gas industry. In the production sector, an
Companies can achieve significant cost savings and estimated 400,000 pneumatic devices control and monitor
methane emission reductions by converting natural gas- gas and liquid flows and levels in dehydrators and
powered pneumatic control systems to compressed separators, temperature in dehydrator regenerators, and
instrument air systems. Instrument air systems pressure in flash tanks. Most processing plants already
substitute compressed air for the pressurized natural gas, use instrument air, but some use gas pneumatics, and
eliminating methane emissions and providing additional including the gathering/booster stations that feed these
safety benefits. Cost effective applications, however, are processing plants, there are about 13,000 gas pneumatic
limited to those field sites with available electrical power, devices in this sector. In the transmission sector, an
either from a utility or self-generated. estimated 85,000 pneumatic devices actuate isolation
valves and regulate gas flow and pressure at compressor
Natural Gas STAR Partners have reported savings of up to stations, pipelines, and storage facilities. Non-bleed
70,000 thousand cubic feet (Mcf) per year per facility by pneumatic devices are also found on meter runs at
replacing natural gas-powered pneumatic systems with distribution company gate stations and distribution grids
instrument air systems, representing annual savings of up where they regulate flow and pressure.
to $490,000 per facility. Partners have found that most
investments to convert pneumatic systems pay for Exhibit 1 depicts a pneumatic control system powered by
themselves in just over one year. Individual savings will natural gas. The pneumatic control system consists of the
vary depending on the design, condition and specific process control instruments and valves that are operated
operating conditions of the controllers. by natural gas regulated at approximately 20-30 pounds

Economic and Environmental Benefits

Volume of Value of Natural Gas Savings ($/


Payback (Months)
Method for Reducing Natural Gas year) Implemen-
Natural Gas Losses Savings (Mcf/ tation Cost ($)a $3 per $5 per $7 per
year) $3 per Mcf $5 per Mcf $7 per Mcf
Mcf Mcf Mcf
Replace Gas with Air in
Pneumatic Systems 20,000 $60,000 $100,000 $140,000 $60,000 12 8 6
(per facility)
General Assumptions:
a Cost of installing compressor, dryer and other accessories, and annual electricity requirements.

1
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

Exhibit 1: Natural Gas Pneumatic


Exhibit 2: Signal and Actuation Schematics
Control System

per square inch (psi), and a network of distribution tubing also vary with the pneumatic gas supply pressure,
to supply all of the control instruments. Natural gas is actuation frequency, and age or condition of the
also used for a few “utility services,” such as small equipment.
pneumatic pumps, compressor motor starters, and
isolation shutoff valves. Exhibit 2 shows a simplified Many Partners have found that it is economic to substitute
diagram of a pneumatic control loop. A process condition, compressed air for natural gas in pneumatic systems. The
such as liquid level in a separator vessel, is monitored by a use of instrument air eliminates methane emissions and
float that is mechanically linked to the liquid level leads to increased gas sales. In addition, by eliminating
controller outside the vessel. A rise or fall in liquid level the use of a flammable substance, operational safety is
moves the float upward or downward, which is translated significantly increased. The primary costs associated with
to small needle valves inside the controller. Pneumatic conversion to instrument air systems are initial capital
supply gas is either directed to the valve actuator by the expenditures for installing compressors and related
needle valve pinching off an orifice, or gas pressure is bled equipment and operating costs for electrical energy to
off the valve actuator. Increasing gas pressure on the power the compressor motor. Existing pneumatic gas
valve actuator pushes down a diaphragm connected by a supply piping, control instruments, and valve actuators of
rod to the valve plug, causing the plug to open and the gas pneumatic system can be reused in an instrument
increasing the flow of liquid draining out of the separator air system.
vessel. Gas pressure relieved from the valve actuator
allows a spring to push the valve plug closed. A compressed instrument air system is shown in Exhibit 3.
In these systems, atmospheric air is compressed, stored in
As part of normal operation, natural gas powered a volume tank, filtered and dried for instrument use. Air
pneumatic devices release or bleed gas to the atmosphere used for utility services (e.g. small pneumatic pumps, gas
and, consequently, are a major source of methane compressor motor starters, pneumatic tools, sand blasting)
emissions from the natural gas industry. Pneumatic does not need to be dried. All other parts of a gas
control systems emit methane from tube joints, controls, pneumatic system will work the same way with air as they
and any number of points within the distribution tubing do with gas.
network. The actual bleed rate or emissions level largely
depends on the design of the device. In general, controllers The major components of an instrument air conversion
of similar design have similar steady-state bleed rates project include the compressor, power source, dehydrator,
regardless of brand name. The methane emission rate will and volume tank. The following are descriptions of each of

2
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

compressors can be cost effective for remote locations,


Exhibit 3: Compressed Instrument Air System which reduces both methane emissions and energy
consumption. Small natural gas powered fuel cells
are also being developed.

Dehydrators. Dehydrators, or air dryers, are an


integral part of the instrument air compressor
system. Water vapor present in atmospheric air
condenses when the air is pressurized and cooled,
and can cause a number of problems to these
systems, including corrosion of the instrument parts
and blockage of instrument air piping and controller
orifices. For smaller systems, membrane dryers have
become economic. These are molecular filters that
allow oxygen and nitrogen molecules to pass through
the membrane, and hold back water molecules. They
are very reliable, with no moving parts, and the filter
element can be easily replaced. For larger
applications, desiccant (alumina) dryers are more
cost effective.

Volume Tank. The volume tank holds enough air to


allow the pneumatic control system to have an
these components along with important installation uninterrupted supply of high pressure air without
considerations. having to run the air compressor continuously. The
volume tank allows a large withdrawal of compressed
Compressor. Compressors used for instrument air air for a short time, such as for a motor starter,
delivery are available in various types and sizes, from pneumatic pump, or pneumatic tools, without
rotary screw (centrifugal) compressors to positive affecting the process control functions.
displacement (reciprocating piston) types. The size of
the compressor depends on the size of the facility, the Economic and Environmental Benefits
number of control devices operated by the system,
and the typical bleed rates of these devices. The
compressor is usually driven by an electric motor Reducing methane emissions from pneumatic devices by
that turns on and off, depending on the pressure in converting to instrument air control and instrumentation
the volume tank. For reliability, a full spare systems can yield significant economic and environmental
compressor is normally installed. benefits for natural gas companies including:

Power Source. A critical component of the Financial Return From Reducing Gas Emission
instrument air control system is the power source Losses. Assuming a natural gas price of $7.00 per
required to operate the compressor. Because high- Mcf, savings from reduced emissions can be
pressure natural gas is abundant and readily estimated at $840 per year per device or $490,000 or
available, gas pneumatic systems can run more per year per facility. In many cases, the cost of
uninterrupted on a 24-hour, 7-day per week schedule. converting to instrument air can be recovered in less
The reliability of an instrument air system, however, than a year.
depends on the reliability of the compressor and
electric power supply. Most large natural gas plants Increased Life of Control Devices and
have either an existing electric power supply or have Improved Operational Efficiency. Natural gas
their own power generation system. For smaller used in pneumatic control devices and instruments
facilities and remote locations, however, a reliable often contains corrosive gases (such as carbon dioxide
source of electric power can be difficult to assure. In and hydrogen sulfide) that can reduce the effective
some instances, solar-powered battery-operated air operating life of these devices. In addition, natural

3
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

gas often produces by-products of iron oxidation, Methane Content of Natural Gas
which can plug small orifices in the equipment
resulting in operational inefficiencies or hazards. The average methane content of natural gas varies by natural gas
When instrument air is used, and properly filtered industry sector. The Natural Gas STAR Program assumes the
and dried, system degradation is reduced and following methane content of natural gas when estimating
methane savings for Partner Reported Opportunities.
operating life is extended.
Production 79 %
Avoided Use Of Flammable Natural Gas. Using Processing 87 %
compressed air as an alternative to natural gas
Transmission and Distribution 94 %
eliminates the use of a flammable substance,
significantly increasing the safety of natural gas
processing plants and transmission and distribution Facility Layout. The layout of a natural gas facility
systems. This can be particularly important at can significantly affect equipment and installation
offshore installations, where risks associated with costs for an instrument air system. For example,
hazardous and flammable materials are greater. conversion to instrument air might not be cost
effective at decentralized facilities where tank
Lower Methane Emissions. Reductions in batteries are remote or widely scattered. Instrument
methane emissions have been reported as high as air is most appropriate when used at offshore
70,000 Mcf per facility annually, depending on the platforms and onshore facilities where pneumatics
device(s) and the type of control application. are consolidated within a relatively small area.

Decision Process Number Of Pneumatics. The more pneumatic


controllers converted to instrument air, the greater
The conversion of natural gas pneumatics to instrument the potential for reduced emissions and increased
air system is applicable to all natural gas facilities and company savings. Conversion to instrument air is
plants. To determine the most cost-effective applications, most profitable when a company is planning a facility
however, requires a technical and economic feasibility -wide change.
study. The six steps outlined below, and the practical
example with cost tables, equations, and factors, can help Available Power Supply. Since most instrument
companies to evaluate their opportunities. air systems rely on electric power for operating the
compressor, a cost-effective, uninterrupted electrical
Step 1: Identify Possible Locations For Instrument Air energy source is essential. While major facilities
System Installations. often have an existing power supply or their own
Most natural gas-operated pneumatic control systems can power generation system, many smaller and remote
be replaced with instrument air. Instrument air systems facilities do not. For these facilities, the cost of power
will require new investments for the compressor, generation generally makes the use of instrument air
dehydrator, and other related equipment, as well as a unprofitable. In addition, facilities with dedicated
supply of electricity. As a result, a first step in a generators need to assess whether the generators
successful instrument air conversion project is screening have enough available capacity to support an air
existing facilities to identify locations that are most compression system, as the cost of a generator
suitable for cost effective projects. In general, three main upgrade can be prohibitive. Remote facilities should
factors should be considered during this process. examine alternatives for power generation, which
range from microturbines to solar power.

Step 2: Determine Optimal System Capacity.


Decision Process for Converting Gas Pneumatic Devices to
Instrument Air: Once project sites have been identified, it is important to
1. Identify possible locations for system installations.
2. Determine optimal system capacity.
determine the appropriate capacity of the new instrument
3. Estimate the project costs. air system. The capacity needed is a direct function of the
4. Estimate gas savings. amount of compressed air needed to both operate the
5. Evaluate the economics. pneumatic instrumentation and meet any utility air
6. Develop an implementation plan.
requirements.

4
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

I n s t r u m e n t A i r Exhibit 4: Calculate Compressor Size for


Requirements. T h e Rule-of-Thumb
Converting Gas Pneumatics to Instrument Air
compressed air needs for the
pneumatic system are equivalent 1 cfm air/control loop Given: For an average size production site with pneumatics, glycol
dehydration, compression, 35 control loops, and an average of
to the volume of gas being used 10 cfm utility gas usage for pneumatic pumps and compressor
to run the existing instrumentation—adjusted for air engine starting.
losses during the drying process. The current volume
A = Total Compressed Air
of gas usage can be determined by a direct meter IAu = Instrument air use
reading (if a meter has been installed). In IAs = Instrument air supply
nonmetered systems, a conservative rule-of-thumb UAs = Utility air supply
for sizing air systems is one cubic foot per minute L = Control loops
(cfm) of instrument air for each control loop Rule-of-thumb: 1 cfm per control loop for estimating
(consisting of a pneumatic controller and a control instrument air systems.
Rule-of-thumb: 17% of air is bypassed in membrane dryers.
valve). Rule-of-thumb: 1/3 of total air used for instruments, 2/3 of
total air used for utility services.
The initial estimate of
instrument air needs should Rule-of-Thumb
Calculate: A = Air compressor capacity required.
A = IAs + UAs
then be adjusted to account for 17 percent of air input IAu = L * (1 cfm/loop)
air losses during the drying is consumed by the
membrane dryer IAs = IAu/(100% - % air bypassed in dryer)
process. Typically, the UAs = IAu * (fraction of utility air use) / (fraction of instrument air
membrane filters in the air dryer consume about 17 use)
A = (35*1) / (100% - 17%) + (35*1) * (2/3) / (1/3) = 112 cfm
percent of the air input. As a result, the estimated
volume of instrument air usage is 83 percent of the
total compressed air supply: i.e., divide estimated air Step 3: Estimate the Project Costs.
usage by 83 percent. Desiccant dryers do not
The major costs associated with installing and operating
consume air and therefore require no adjustment.
an instrument air system are the installation costs for
compressors, dryers, and volume tanks, and energy costs.
Utility Air Requirements. It
Rule-of-Thumb The actual installation costs will be a function of the size,
is common to use compressed air
location, and other location specific factors. A typical
for utility purposes, such as Pneumatic air uses: 1/3
for instrument air; 2/3 conversion of a natural gas pneumatic control system to
engine starters, pneumatic for utility air
compressed instrument air costs approximately $45,000 to
driven pumps, pneumatic tools
$75,000.
(e.g., impact wrenches), and sand blasting. Unlike
instrument air, utility air does not have to be dried.
To estimate the cost for a given project, all expenses
The frequency and volumes of such utility air uses
associated with the compressor, dryer, volume tank, and
are additive. Companies will need to evaluate these
power supply must be calculated. Most vendors are willing
other compressed air services on a site-specific basis,
to provide estimates of the equipment costs and
allowing for the possibility of expansion at the site. A
installation requirements (including compressor size,
general rule-of-thumb is to assume that the
motor horsepower, electrical power requirements, and
maximum rate of compressed air needed periodically
storage capacity). Alternatively, operators can use the
for utility purposes will be double the steady rate
following information on the major system components to
used for instrument air.
estimate the total installed cost of the instrument air
system.
Exhibit 4 illustrates how the instrument air compressor
size can be estimated. Using the rule-of-thumb of 1 cfm/
Compressor Costs. It is common to install two
control loop, the current gas usage would translate to
compressors at a facility (one operating and one
approximately 35 cfm of dry instrument air. Adjusting for
stand-by spare) to ensure reliability and allow for
the dryer's air consumption (17 percent of air input), the
maintenance and overhauls without service
total instrument air supply requirement will be 42 cfm.
interruptions. The capacity for each of the
Factoring in utility air needs of about 70 cfm, the project
compressors must be sufficient to handle the total
would require a total of 112 cfm of compressed air.
expected compressed air volume for the project (i.e.,
both instrument and utility air). Exhibit 5 presents

5
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

cost estimates for purchasing and servicing small, applications is a permeable membrane dryer. Larger
medium, and large compressors. For screw-type air systems can use multiple membrane dryers, or,
compressors, operators should expect to overhaul the more cost effectively, alumina bed desiccant dryers.
unit every 5 to 6 years. This normally involves Membrane dryers filter out oil mist and particulate
exchanging the compressor core for a rebuilt solids and have no moving parts. As a result, annual
compressor at a cost of approximately $3,929, with an operating costs are kept low. Exhibit 7 presents
additional $720 in labor expense and a $650 core equipment and service cost data for different size
exchange credit. dryers. The appropriate sized dryer would need to
accommodate the expected volume of gas needed for
the instrument air system.
Exhibit 5: Air Compressor Costs

Air Comp-
Equip-
Annual Service
Exhibit 7: Air Dryer Costs
Service Horse- ment
Volume ressor Service Life
Size power Costs
(cfm) Type ($/yr) (yrs)
($) Air Annual
Service Dryer Equipment
Volume Service
Recipro Size Type Cost ($)
Small 30 10 3,275a 434 1 (cfm) ($/yr)
-cating

Medium 125 Screw 30 16,371 868 5-6b


Small 30 membrane 1,964 724

Large 350 Screw 75 28,812 868 5-6b


Medium 60a membrane 5,893 2,894
a Cost included package compressor with a volume tank.
b Rebuilt compressor costs $3,929 plus $500 labor minus $500 core exchange credit.

Large 350 alumina 13,096 4,341

Volume Tank. Compressed air supply systems a Largest membrane size; use multiple units, larger volumes.
include a volume tank, which maintains a steady
pressure with the on-off operation of the air Using the equipment information described above, the
compressor. The rule-of-thumb in determining the total installed cost for a project can be calculated. Exhibit
size of the volume tank is 1-gallon capacity for each 8 illustrates this using the earlier example of a medium-
cfm of compressed air. Exhibit sized production facility with an instrument air
6 presents equipment costs for Rule-of-Thumb requirement of 42 cfm and a maximum utility air
small, medium, and large requirement of 70 cfm (for a total of 112 cfm of compressed
volume tanks. Volume tanks 1 gallon tank capacity/1 air). To estimate the installed cost of equipment, it is a
have essentially no operating cfm air common practice in industry to assume that installation
and maintenance costs. labor is equivalent to equipment purchase cost (i.e. double
equipment purchase cost to estimate the installed cost).
Air Dryer Costs. Because instrument air must be This would be suitable for large, desiccant dried
very dry to avoid plugging and corrosion, the instrument air systems, but for small, skid-mounted
compressed air is commonly put through a dryer. instrument air systems a factor of 1.5 is used to estimate
The most common dryer used in small to medium the total installed cost (installation labor is half the cost of
equipment).

Exhibit 6: Volume Tank Costs In addition to the facility costs, it is also necessary to
estimate the energy costs associated with operating the
Equipment Cost system. The most significant operating cost of an air
Service Size Air Volume (gallons)
($) compressor is electricity, unless the site has excess self-
generation capacity. To continue the example from above,
Smalla 80 655
assuming that electricity is purchased at 7.5 cents per
Medium 400 1,964 kilowatt-hour (kWh) and that one compressor is in standby
Large 1,000 3,929 while the other compressor runs at full capacity half the
time (a 50 percent operating factor), the electrical power
a Small reciprocating air compressors, 10 horsepower and less, are commonly supplied with a surge tank.

6
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

years to account for increased leakage associated with


Exhibit 8: Calculate Total Installation Costs wear and tear. Alternatively, installing a meter can be
more accurate, provided monitoring occurs over a long
Given:
enough period of time to take account of all the utility uses
Compressors (2) = $32,742 (Exhibit 5) of gas (i.e., pumps, motor starters, activation of isolation
Volume Tanks (2- = $1,310 (Exhibit 6)
small)
valves).
Membrane Dryer = $5,893 (Exhibit 7)
Installed Cost Factor = 1.5 EPA’s Lessons Learned: Options for Reducing Methane
Emissions from Pneumatic Devices in the Natural Gas
Calculate Total Installed Cost: Industry, provides brand name, model, and gas
Equipment Cost = Compressor Cost + Tank Cost + Dryer consumption information for a wide variety of currently
Cost used pneumatic devices. Manufacturer information and
= $32,742 + $1,310 + $5,893 actual field measurement data, wherever available, are
= $39,945 provided as well (see Appendix of that report). To simplify
Total Cost = Equipment Cost * Installation Cost the calculation of gas savings for the purpose of this lesson
Factor learned analysis, we can use the earlier rules-of-thumb to
= $39,945 * 1.5 estimate the gas savings. The gas savings for the medium-
= $59,917
sized production facility example in Exhibit 4 include the
conservatively estimated 35 cfm used in the 35 gas
cost amounts to $13,140 per year. This calculation is pneumatic controllers plus the gas used occasionally for
shown in Exhibit 9. compressor motor starters and small pneumatic chemical
and transfer pumps. (Note that replacing these gas usages
Step 4: Estimate Gas Savings. will result in direct savings of gas emissions.) Natural gas
is not used for pneumatic tools or sand blasting, so
To estimate the gas savings that result from the
additional compressed air provided for these services does
installation of an instrument air system, it is important to
not reduce methane emissions. Assuming an annual
determine the normal bleed rates (continuous leak from
average of 10 cfm gas use for natural gas powered non-
piping networks, control devices, etc.), as well as the peak
instrument services, the gas savings would be 45 cfm. As
bleed rates (associated with movements in the control
shown in Exhibit 10, this is equivalent to 23,652 Mcf per
devices). One approach is to list all the control devices,
year and annual savings of $165,600.

Exhibit 9: Calculate Electricity Cost Step 5: Evaluate the Economics.

Given: The cost effectiveness of replacing the natural gas


= 30 HP
pneumatic control systems with instrument air systems
Engine Power
Operating Factor (OF) = 50 percent

Electricity Cost = $0.075/kwh Exhibit 10: Calculate Gas Savings


Calculate Required Power:
Given:
Electrical Power = Engine Power * OF * Electricity Cost
Pneumatic instrument gas = 35 cfm
= [30 HP * 8,760 hrs/yr * 0.5 * $0.075/
usage
kwh] / 0.75 HP/kw
Other non-instrument gas = 10 cfm
= $13,140/yr
usage

assess their normal and peak bleed rates, frequency of Calculate Value of Gas Saved:
actuation, and estimates of leakage from the piping Volume of Natural Gas Saved = Instrument Usage + Other Usage
networks. Manufacturers of the control devices usually = 35 cfm + 10 cfm
publish the emission rates for each type of device, and for = 45 cfm
each type of operation. Rates should be increased by 25 Annual Volume of Gas Saved = 45 cfm * 525,600 min/yr / 1000
percent for devices that have been in service without = 23,652 Mcf/yr
overhaul for five to 10 years, and by about 50 percent for Annual Value of Gas Saved = volume * $7.00/Mcf
devices that have not been overhauled for more than 10 = 23,652 Mcf/yr * $7.00/Mcf
= $165,600/year

7
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

can be evaluated using straightforward cost-benefit


economic analyses. Nelson Price Indexes
In order to account for inflation in equipment and
Exhibit 11 illustrates a cost-benefit analysis for the operating & maintenance costs, Nelson-Farrar
medium-sized production facility example. The cash flow Quarterly Cost Indexes (available in the first issue of
over a five-year period is analyzed by showing the each quarter in the Oil and Gas Journal) are used to
magnitude and timing of costs from Exhibits 8 and 9 update costs in the Lessons Learned documents.
(shown in parentheses) and benefits from Exhibit 10. The
annual maintenance costs associated with the compressors The “Refinery Operation Index” is used to revise
and air dryer, from Exhibits 5 and 7, are accounted for, as operating costs while the “Machinery: Oilfield Itemized
well as a five-year major overhaul of a compressor per Refining Cost Index” is used to update equipment
Exhibit 5. The net present value (NPV) is equal to the costs.
benefits minus the costs accrued over five years and To use these indexes in the future, simply look up the
discounted by 10 percent each year. The Internal Rate of most current Nelson-Farrar index number, divide by
Return (IRR) reflects the discount rate at which the NPV the February 2006 Nelson-Farrar index number, and,
generated by the investment equals zero. finally multiply by the appropriate costs in the Lessons
Learned.
Step 6: Develop an Implementation Plan.
After determining the feasibility and economics of
minimize labor costs and disruption of operations. This
converting to an instrument air system, develop a
might include a parallel strategy to install low-bleed
systematic plan for implementing the required changes.
devices in conjunction with the switch to instrument air
This can include installing a gas measuring meter in the
systems. There are similar economic savings for
gas supply line, making an estimate of the number of
conserving instrument air use as for conserving methane
control loops, ensuring an uninterrupted supply of electric
emissions with low bleed pneumatic devices. Whenever
energy for operating the compressors, and replacing old,
specific pneumatic devices are being replaced, such as in
obsolete and high-bleed controllers. It is recommended
the case of alternative mechanical and/or electronic
that all necessary changes be made at one time to

Exhibit 11: Economic Analysis of Instrument Air System Conversion

Year 0 Year 1 Year 2 Year 3 Year 4 Year 5

Implementation Cost ($) (59,917)


(13,140)a (13,140) (13,140) (13,140) (13,140)
O&M Cost ($)
(4,630)b (4,630) (4,630) (4,630) (4,630)
Overhaul Cost ($) 0 0 0 0 0 (6,286)c

Total Cost ($) (59,917) (17,770) (17,770) (17,770) (17,770) (24,057)


d
Gas Savings ($) 0 165,600 165,600 165,600 165,600 165,600

Annual Cash Flow ($) (59,917) 147,830 147,830 147,830 147,830 141,543

Cumulative Cash Flow ($) (59,917) 87,912 235,742 383,571 531,401 672,944

Payback Period (months) 5

IRR 246%
e
NPV $496,570
a Electrical power at 7.5 cents per kilowatt-hour.
b Maintenance costs include $1,736 compressor service and $2,894 air dryer membrane replacement.
c Compressor overhaul cost of $3,929, inflated at 10% per year.
d Value of gas = $7.00/Mcf.
e Net Present Value (NPV) based on 10% discount rate for 5 years.

8
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

systems, the existing pneumatic devices should be replaced Exhibit 12: Gas Price Impact
on a similar economic basis as discussed in the companion on Economic Analysis
document Lessons Learned: Options for Reducing Methane
Emissions from Pneumatic Devices in the Natural Gas
$3/Mcf $5/Mcf $7/Mcf $8/Mcf $10/Mcf
Industry.
Value of
When assessing options for converting gas pneumatic Gas Saved
$70,971 $118,286 $165,600 $189,257 $236,571
controls to instrument air, natural gas price may influence
Payback
the decision making process. Exhibit 12 shows an Period 14 8 5 5 4
economic analysis installing two 30 hp compressors, two (months)
medium sized volume tanks, and a medium sized Internal
membrane dryer at different natural gas prices. Rate of
84% 166% 246% 286% 365%
Return
(IRR)
Partner Experiences Net
Present
$137,853 $317,211 $496,570 $586,249 $765,607
Value
Several EPA Natural Gas Star Partners have reported the (i=10%)
conversion of natural gas pneumatic control systems to
compressed instrument air systems as the single most
Other Technologies
significant source of methane emission reduction and a
source of substantial cost savings. Exhibit 13 below
highlights the accomplishments that several Natural Gas The majority of Partners' experiences in substituting
STAR Partners have reported. natural gas-powered pneumatic devices and control
instrumentation with alternative controllers have involved

Exhibit 13: Partner Reported Experience

Gas STAR Project Cost Annual Emissions


Description of Project Annual Savings ($/yr)a Payback (months)b
Partner ($) Reductions (Mcf/yr)

Installed an air compression


Unocalc (now system in its Fresh Water
$79,000 69,350 $485,450 2
Chevron) Bayou facility in southern
Vermillion Parish, Louisiana
Installed compressed air
Texacoc (now system to drive pneumatic
$52,000 23,000 $161,000 4
Chevron) devices in 10 South Louisiana
facilities
Converted pneumatic
$227,000 over 2
Chevronc controllers to compressed air, 31,700 $221,900 7
years
including new installations
Installed instrument air
d systems at 3 production
ExxonMobil $72,000 19,163 $134,141 7
satellites and 1 central tank
battery at Postle CO2 unit
Used instrument air operated
Shell devices on over 4,300 valves Not available 532,800 $3,729,600 Not available
at off-shore platforms
Installed 15 instrument air
Marathon systems in New Mexico Not available 120 - 38,000 per facility $840 - 226,000 Not available
facilities
a Value of gas = $7.00/Mcf.
b Calculated based on Partner-reported costs and gas savings updated to 2006 costs.
c Data for this report were collected prior to the Chevron-Texaco and Chevron-Unocal mergers.
d Data for this report were collected prior to the Exxon/Mobil merger in 1999.

9
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

the installation of compressed instrument air systems. for Reducing Methane Emissions from Pneumatic Devices
Some additional alternatives to gas pneumatics in the Natural Gas Industry), and to design a maintenance
implemented by Partners are described below: schedule to keep the instruments and control devices in
tune, is often economic. Such actions can significantly
Liquid Nitrogen. In a system using liquid nitrogen, reduce the consumption of instrument air in the overall
the volume tank, air compressor, and dryer are system and, therefore, minimize both the size of the
replaced with a cylinder containing cryogenic liquid compression system and the electricity consumption over
nitrogen. A pressure regulator allows expansion of the life of the plant.
the nitrogen gas into the instrument and control-
piping network at the desired pressure. Liquid Lessons Learned
nitrogen bottles are replaced periodically. Liquid
nitrogen-operated devices require handling of The lessons learned from Natural Gas STAR Partners are:
cryogenic liquids, which can be expensive as well as a
potential safety hazard. Large volume demands on a Installing instrument air systems has the potential to
liquid nitrogen system require a vaporizer. increase revenues and substantially reduce methane
emissions.
Mechanical Controls and Instrumentation
System. Mechanical instrument and control devices Instrument air systems can extend the life cycle of
have a long history of use in the natural gas and system equipment, which can accumulate trace
petroleum industry. They are usually distinguished amounts of sulfur and various acid gases when
by the absence of pneumatic and electric components, controlled by natural gas, thus adding to the
are simple in design, and require no power source. potential savings and increasing operational
Such equipment operates using springs, levers, efficiencies.
baffles, flow channels, and hand wheels. They have
several disadvantages, such as limited application, Remote locations and facilities without a reliable
the need for continuous calibration, lack of source of electric supply often need to evaluate
sensitivity, inability to handle large variations, and alternate power generation sources. When feasible,
potential for sticking parts. solar-powered air compressors provide an economical
and ecologically beneficial alternative to expensive
Electric and Electro-Pneumatic Devices. As a electricity in remote production areas. On site
result of advanced technology and increasing generation using microturbines running on natural
sophistication, the use of electronic instrument and gas is another alternative.
control devices is increasing. The advantage of these
devices is that they require no compression devices to A parallel strategy of installing low-bleed devices in
supply energy to operate the equipment; a simple 120 conjunction with the switch to instrument air
-volt electric supply is used for power. Another systems is often economic.
advantage is that the use of electronic instrument
and control devices is far less dangerous than using Existing infrastructure can be used; therefore, no
combustible natural gas or cryogenic liquid nitrogen pipe replacement is needed. However, existing
cylinders. The disadvantage of these devices is their piping and tubing should be flushed clear of
reliance on an uninterrupted source of electric accumulated debris.
supply, and significantly higher costs.
Rotary air compressors are normally lubricated with
Although these options have advantages, systems using air oil, which must be filtered to maintain the life and
instead of natural gas are the most widely employed proper performance of membrane dryers.
alternative in replacing natural gas-operated pneumatic
control devices. It is important to note that maintaining a Use of instrument air will eliminate safety hazards
constant, reliable supply of dry, compressed air in a plant associated with flammable natural gas usage in
environment is a significant cost, albeit more economic pneumatic devices.
than natural gas. Therefore, a parallel strategy to install
low-bleed devices in conjunction with the switch to Nitrogen-drive systems may be an alternative to
instrument air systems (refer to Lessons Learned: Options instrument air in special cases, but tends to be

10
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

expensive and handling of cryogenic gas is a safety


concern.

Report reductions in methane emissions from


converting gas pneumatic controls to instrument air
in your Natural Gas STAR Annual Report.

References

Adams, Mark. Pneumatic Instrument Bleed Reduction Strategy and


Practical Application, Fisher Controls International, Inc.1995.

Beitler, C.M., Reif, D.L., Reuter, C.O. and James M. Evans. Control
Devices Monitoring for Glycol Dehydrator Condensers: Testing and
Modeling Approaches, Radian International LLC, Gas Research
Institute, SPE 37879, 1997.

Cober, Bill. C&B Sales and Services, Inc. Personal contact.

Fisher, Kevin S., Reuter, Curtis, Lyon, Mel and Jorge Gamez. Glycol
Dehydrator Emission Control Improved, Radian Corp., Public Service
Co. of Colorado Denver, Gas Research Institute.

Frederick, James. Spirit Energy 76. Personal contact.

Games, J.P., Reuter, C.O. and C.M. Beitler, Field Testing Results for the R
-BTEX Process for Controlling Glycol Dehydrator Emissions, Gas
Research Institute, Radian Corporation, SPE 29742, 1995.

Gunning, Paul M. U.S. EPA Natural Gas STAR Program. Personal contact.

Gupta, Arun, Ansari, R. Rai and A.K. Sah. Reduction of Glycol Loss From
Gas Dehydration Unit At Offshore Platform in Bombay Offshore—A
Case Study, N.A.K.R. IOGPT, ONGC, India, SPPE 36225, 1996.

Reid, Laurance, S. Predicting the Capabilities of Glycol Dehydrators, SPE-


AIME, Laurance Reid Associates.

Scalfana, David B., Case History Reducing Methane Emissions From High
Bleed Pneumatic Controllers Offshore, Chevron U.S.A. Production Co.
SPE 37927, 1997.

Schievelbein, V.H., Hydrocarbon Recovery from Glycol Reboiler Vapor


With Glycol-Cooled Condenser, Texaco, Inc. SPE 25949. 1993.

Schievelbein, Vernon H. Reducing Methane Emissions from Glycol


Dehydrators, Texaco EPTD, SPE 37929, 1997.

Soules, J.R. and P.V. Tran. Solar-Powered Air Compressor: An


Economical and Ecological Power Source for Remote Locations, Otis
Engineering Corp. SPE 25550, 1993.

11
Convert Gas Pneumatic Controls To Instrument Air
(Cont’d)

United States
Environmental Protection Agency
Air and Radiation (6202J)
1200 Pennsylvania Ave., NW
Washington, DC 20460

October 2006

EPA provides the suggested methane emissions estimating methods contained in this document as a tool to develop basic methane emissions estimates only. As
regulatory reporting demands a higher-level of accuracy, the methane emission estimating methods and terminology contained in this document may not conform to
the Greenhouse Gas Reporting Rule, 40 CFR Part 98, Subpart W methods or those in other EPA regulations.

12

Das könnte Ihnen auch gefallen