TECHNICAL DATA
MODEL A
NOMINAL SIZE 200, 150, 100, 80 & 50NB
MAXIMUM SERVICE 12 Bar (175 PSI)
PRESSURE
THREADED OPENING BSPT
MOUNTING 90° pattern inlet to outlet
vertical mounting
FACTORY 25 Kg./sq.cm. (350 PSI)
HYDROSTATIC
TEST PRESSURE
LISTED
FLANGE ANSI B 16.1 FF # 125 9P76
CONNECTION (Flange drilling matching
to ANSI B 16.5 # 150)
and restriction orifice from the system supply side to
TRIM Galvanized Steel with Brass the top chamber, so that supply pressure in the top
Valves chamber acts across the diaphragm operated clapper
WET PILOT As per graph in the catalogue which holds the seat against the inlet supply pressure
SPRINKLER because of differential pressure design.
HEIGHT LIMITATION On detection of fire the top chamber is vented to
NET WEIGHT 200NB - 214 Kg atmosphere through the outlet port via opened
WITHOUT TRIM 150NB - 131 Kg actuation device(s). The top chamber pressure cannot
100NB - 77 Kg be replenished through the restricted inlet port,
80NB - 50 Kg thus it reaches less than half the supply pressure
50NB - 47 Kg instantaneously and the upward force of the supply
pressure lifts the clapper allowing water to enter the
FINISH Red RAL 3001 system piping network and alarm devices.
APPROVAL UL Listed
TRIM DESCRIPTION
ORDERING Specify :
INFORMATION 1) Size of valve a) BASIC TRIM
2) Trim type - Dry Pilot The basic trim is required on deluge valve
Wet Pilot regardless of the release system. It contain
Electric Release those components which are required in all
Test & Alarm types of installation, such as the main drain valve,
priming connection, drip check valve, emergency
release valve and pressure gauges.
b) DRY PILOT TRIM (PNEUMATIC RELEASE)
DESCRIPTION
Dry pilot operation uses a pilot line of closed
Deluge Valve is known as a system control valve in a
Sprinklers / QB detectors containing air under
deluge system, used for fast application of water in a
pressure, located in the area to be protected.
spray system. Deluge valve protects areas such as
It requires regulated dry air supply with main
power transformer installation, storage tank, conveyor
supply point through restricted orifice.
protection and other industrial application etc. With
the addition of foaming agent deluge valve can be used The pilot line is connected directly to the top
to protect aircraft hanger and inflammable liquid fire. of POSITIVE DRAIN ACTUATOR (PDA). The
bottom of PDA is connected to the top chamber
VALVE OPERATION of the deluge valve.
Deluge valve is a quick release, hydraulically operated When the air pressure drops, due to release of
diaphragm valve. It has three chambers, isolated from any of the release devices on detection of fire,
each other by the diaphragm operated clapper and the diaphragm of PDA is lifted and allows the water
seat seal. While in ‘SET’ position, water pressure is to drain. This reduces the water pressure in
transmitted through an external bypass check valve the top chamber of the deluge valve and when
the pressure in the top chamber reaches 50% of Note: Trim without Test and Alarm trim, without
the supply pressure, the deluge valve opens. Drain & drip valve can be supplied for which please
contact marketing.
The direct drain of PDA start when the top chamber
pressure of deluge valve reaches approximately
0.7 Kg/sq.cm. This positive drain will not permit
RESETTING PROCEDURE FOR
the deluge valve to close unless the PDA is set (i) Close the upstream side stop valve provide
manually. The recommended air supply pressure below the deluge valve.
is as per TABLE-1.
(ii) Open both the drain valves and close them when
the flow of water has ceased.
TABLE 1
LINE WATER AIR PRESSURE IN DETECTION (iii) Inspect and release if required, or close the
PRESSURE LINE Kg./ Sq.cm. section of the detection system subjected to
Kg./ Sq.cm. “Fire condition”.
MAXIMUM MINIMUM MAXIMUM
(iv) In case of dry pilot detection system, open the
2 1.2 3.0 air supply valve to build-up air pressure as shown
in TABLE-1. Open the priming valve fully and
4 1.5 3.0 press hold the knob of PDA till the water
6 2.0 3.5 pressure gauge indicate full service line
8 2.5 3.5 pressure, then release the PDA knob. Open the
upstream side of the stop valve provided below
10 3.0 3.5 the deluge valve. No water should flow into the
12 3.5 4.0 system, this can be checked by depressing the
drip check valve knob.
c) WET PILOT TRIM ( HYDRAULIC RELEASE )
CAUTION
Wet pilot operation uses a pilot line of closed
sprinklers containing pressurised water, a. Do not close the priming valve, down stream and
supplied through the upstream side of the deluge upstream stop valves, while the system is in
valve, through a restricted orifice. All the release service.
lines are connected to a common release line. b. The releasing device must be maintained in the
Due to release of any one of the release devices, open position, when actuated, to prevent
the water pressure in the top chamber of the the deluge valve from closure.
deluge valve reaches 50% of the supply pressure,
the deluge valve opens. c. While using a Deluge valve in the wet pilot
system the height and the length of the wet
CAUTION pilot detection line is to be limited as shown
in the wet pilot sprinkler limitation graph.
While using a deluge valve in the wet pilot system the
height and the length of the wet pilot detection line is d. Do not connect the Sprinkler Alarm outlet
to be limited as given in the wet pilot sprinkler height drainline to close a common drain as it may
limitation graph. create back pressure and Sprinkler Alarm may
not fuction.
d) ELECTRIC RELEASE TRIM
e. Deluge valve must have support to absorb
To actuate a deluge valve electrically, a solenoid sudden opening or closing vibration shock
valve is provided to drain the water from the top to the piping.
chamber of the deluge valve. A pressure switch
is provided to activate an electric alarm, to shut f. The responsibility of maintenance of the
down the desired equipment or to give “Tripped” protection system and devices in proper
indication to the panel. operating condition lies with the owner of
the system.
In addition to this two nos of pressure
switchs can be used to monitor “Low air g. Deluge Valve & its trim shall be maintained at
pressure” and “Fire condition” when used a minimum temperature of 4ºC, Heat tracing
in dry pilot air line. is not permitted.
e) TEST AND ALARM TRIM WITH h. Deluge Valve must be used in pressurised
SPRINKLER ALARM system
This trim is supplied with the sprinkler alarm SYSTEM TESTING PROCEDURE
bell, which bells on actuation of the deluge valve.
(i) Keep the upstream side of the stop valve
A test valve is provided to test the normal
partially open. Open the upstream side of the
operation of the sprinkler alarm bell.
NOTE:
(1) UL Listing is valid only when Deluge Valve is (3) The pneumatic system must have restricted
installed with trim set as per trim drawing. orifice at air or gas supply point. The
restriction nozzle are supplied with HD dry pilot
(2) The trip time of deluge valve on of device through actuation trim.
detection network, will depend on volume
of detection network. If the trip time of (4) UL Listing is valid only when Listed Solenoid Valve
deluge valve is more, then it can be substantially provided for electric operation of the deluge valve
reduced by installing check valve in branch of is retained in the trim. If any other solenoid valve
release line in the detection network. The check is used, the deluge valve trip time may be quite
valve flow shall be towards releasing device. high or deluge valve may not trip.
NOMINAL A B C D
SIZE OF
OUTLET VALVE
200 NB 540 455 330 230
150 NB 464 382 300 200
B
*Ductile Iron is standard supply, Bronze & Stainless Steel is optional supply.
** EPDM is standard supply with Stainless Steel Seat. Neoprene is optional supply with Stainless Steel & Bronze Seat.
NA - Parts replacement not available.
Note: Seat is not replaceable and is Stainless Steel standard supply, Bronze is optional supply.
11
10
A1
# M R
FRO RESSO # ELECTRIC TRIM OPTIONAL
M P
CO
38
TO
DETE #
LIN CTION
E A3
A2
16
HD
FIR
E PRO
TE
PVT
. LTD
.
U
L
AIR/W
ATER
13
17
LISTED PRESSU
40 BN FIRE RE
PROTEC
SERVIC GAUGE
MODEL E TION FOR
- HDP
6
16 12
7 11 14
7
10
6 18
5
15
7 4
8 3 7 TO OPEN
HD
FIR
E PRO
TE
PVT
11
. LTD
.
U
L
AIR/W
ATER
LISTED PRESSU
40 BN FIRE RE
PROTEC
SERVIC
MODEL E
GAUGE
TION FOR
DRAIN
13
- HDP
7 TO OPEN
12
2 11
DRAIN # 28
9 10
S1
S2
1 20
S3 TO OPEN
TO PRIMING DRAIN
CONNECTION
S4
(BELOW UP STREAM
STOP VALVE) EN 19
OP
TO RAIN
D
28
33 HD
FIR
E PRO
TE
P3
PVT
. LTD
.
13
U
L
AIR/W
ATER
LISTED PRESSU
40 BN FIRE RE
PROTEC
SERVIC GAUGE
MODEL E TION FOR
- HDP
34
P2 #
P1 21 12
29 35
22
17
30
23 31 16
7
32 6
22
**
24
26 36
27/2 22
37
25 TO
27/1 SPRI
NK
ALA LER
TO DRAIN RM
TO DRAIN
NOTE: WHEN ELECTRIC TRIM IS SUPPLIED THEN SL.NO.28 PLUG NOT REQUIRED.
** TO SUIT AT SITE BY INSTALLER
* SUPPLIED FITTED TOGETHER
14
6
5 TO DETECTION
15
7 LINE
4
8 3
TO OPEN
HD
FIR
E PRO
TE
PVT
11
. LTD
.
UL AIR/W
LISTED PRESSATER
40 BN FIRE URE
PROTEGAUGE
SERVIC
MODEL E CTION FOR
DRAIN
13
- HDP
7 12
2 11
# 27
9 10
S1
S2
1 19
S3 TO OPEN
TO PRIMING DRAIN
CONNECTION
S4
(BELOW UP STREAM
STOP VALVE) EN 18
OP
TO RAIN
D
27
32 HD
FIR
E PRO
TE
P3
PVT
. LTD
.
13
UL AIR/W
LISTED PRESSATER
40 BN FIRE URE
PROTEGAUGE
SERVIC
MODEL E CTION FOR
- HDP
33
P2 #
P1 20 12
28 34
21
17
29
22 30 16
7
31 6
21
23 **
25 35
26/2 21
36
24
26/1 TO
SPRI
NK
TO DRAIN ALA LER
RM
TO DRAIN
NOTE: WHEN ELECTRIC TRIM IS SUPPLIED THEN SL.NO.28 PLUG NOT REQUIRED.
** TO SUIT AT SITE BY INSTALLER
TO DETECTION FROM
~
LINE PS COMPRESSOR
PG
RN
NO
PDA
~ PG
NO
OD
~
SV
M
NO PG PS
ER
TO
SYSTEM DV
~
~
NO
OD
NC
NC
G
~
DR.V
NRV CD
~ ~ NC F
~
OD CD OD
~
FROM
SUPPLY
TO DETECTION PG
~
LINE
NO
OD
~
SV
M
NO PG PS
ER
TO
SYSTEM DV
~
~
NO
OD
NC
NC
G
~
DR.V
NRV CD
~ ~ NC F
~
CD OD
OD
~
FROM
SUPPLY
E
E
D
D
COMPRESSED
AIR LINE
C
C
TO
TO SPRINKLER
SPRINKLER ALARM TO OPEN
ALARM TO OPEN DRAIN TO PRIMING
DRAIN TO PRIMING CONNECTION
CONNECTION
TO DRAIN
TO DRAIN
A B
A B
SIZE 200NB 150NB 100NB 80NB 50NB SIZE 200NB 150NB 100NB 80NB 50NB
A 390 370 370 350 350 A 390 370 370 350 350
B 525 500 450 450 450 B 525 500 450 450 450
C 1050 1025 950 930 930 C 875 800 750 700 700
D 510 500 450 450 450 D 510 500 450 450 450
E 500 480 420 410 410 E 500 480 420 410 410
KG/SQCM KG/SQCM
2 4 6 8 10 12 2 4 6 8 10 12
140 140
130 40 130 40
MAXIMUM PILOT LINE HIGHT - FEET ------
T ET
120 F EE 120 FE T
25 35 25 E 35
100 T 30 100 30
FEE EE
T
90 300 90 50
0F
80 25 80 25
METERS
METERS
T
FEE
70 500 70
20 20
60 60
50 15 50 15
40 40
10 30 10
30
20 5 20 5
10 10
KG/SQCM KG/SQCM
2 4 6 8 10 12 2 4 6 8 10 12
140 140
130 40 130 40
MAXIMUM PILOT LINE HIGHT - FEET ------
120 E ET 120 ET E ET
5F E
2 35 5F 0F 35
2 30
110 110 ET
E ET 0 FE
100 0F 30 100 50 30
30
90 EET
90
F
80 500 25 80 25
METERS
METERS
70 70
20 20
60 60
50 15 50 15
40 40
10 30 10
30
20 5 20 5
10 10
2 4 6 8 10 12 2 4 6 8 10 12
140 140
130 40 130 40
MAXIMUM PILOT LINE HIGHT - FEET ------
120 T 120
FEE 35 35
110 25 110 ET
FE T
25 F EE
100 30 100 300 30
90 FEE
T 90
F EET
80 300 25 500 25
80
METERS
METERS
70 EE T 70
0F 20 20
60 50 60
50 15 50 15
40 40
30 10 10
30
20 5 20 5
10 10
KG/SQCM KG/SQCM
2 4 6 8 10 12 2 4 6 8 10 12
140 140
40 130 40
120 120
35 35
110 110 T
F EE
100 FEET 30 100 25 30
25 T
90 EE
90 30
0F
25 80 25
METERS
80 FEE
T
FEE
T
70 500
70 300 20
20
60 60
50 15 50 15
T
40 FEE 40
500
10 30 10
30
20 20 5
5
10 10
KG/SQCM KG/SQCM
2 4 6 8 10 12 2 4 6 8 10 12
140 140
130 40 130 40
MAXIMUM PILOT LINE HIGHT - FEET ------
MAXIMUM PILOT LINE HIGHT - FEET ------
120 120
35 35
110 110
ET
FE
100 FEE
T
30 100 25 30
25
90 90 ET
0 FE
25 30 25
80 80
METERS
T T
FEE EE
70 300 70 0F
50
20 20
60 60
50 15 50 15
FEET
40 500 40
10 30 10
30
20 5 20 5
10 10
1
0.8
0.6
Nominal Pressure Loss in kg/sqcm
0.5
0.4
0.3
0.2
)
)
CH
CH
CH
IN
IN
IN
(4
(8
(6
NB
)
0.1
NB
NB
CH
0.08
0
0
IN
10
20
15
)
(3
CH
0.06
NB
IN
0.05
80
(2
0.04
NB
0.03
50
0.02
0.01
100 200 300 400 600 800 1000 2000 3000 5000 7000 10000 13500 20000
LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person
to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of
shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty.
No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained.
HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer’s representatives.
HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is
found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly
or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any
damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s product liability exceed an amount equal to the sale price.
The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited
to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.
NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the
provision of government codes or ordinances wherever applicable.
The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope.
Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or
damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with
the company.
D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA.
HD FIRE PROTECT PVT. LTD. • TEL: + (91) 22 2158 2600 • FAX: +(91) 22 2158 2602
Protecting What Matters Most to You • EMAIL: info@hdfire.com • WEB: www.hdfire.com