XLe / XLt models: HE-XE102 / HE-XT102

12 Digital Input DC / 4 Analog Inputs (medium resolution) / 6 Relay Outputs SPST-NO


Man 5000601

1 Specifications Notes: The tolerance to meet NEMA standards is  0.005” (0.1 mm).
Max. panel thickness: 5 mm.
Digital Inputs DC
Inputs per Module 12 (including 4 HSC inputs)
Faixa de tensão de entrada 12 VDC / 24 VDC
Absolute Max. Voltage 35 VDC Max.
Input Impedance 10 k
Input Current Positive Logic Negative Logic
Upper Threshold 0.8 mA -1.6 mA
Lower Threshold 0.3 mA -2.1 mA
Max Upper Threshold 8 VDC
Min Lower Threshold 3 VDC 3 Ports / Connectors / Cables
OFF to ON Response 1 ms To Remove Back Cover unscrew 4 screws located on the back of the unit.
ON to OFF Response 1 ms I/O Jumpers: (Not Shown): I/O Jumpers (JP) are located internally. To access,
10 kHz Totalizer/Pulse, Edges remove back cover of unit.
HSC Max. Switching Rate 5 kHz Frequency/Pulse, Width Wiring Connectors (J1 / J2): I/O Jumpers (JP1 / JP2), and External Jumpers
2.5 kHz Quadrature (RS-485) are described in the Wiring and Jumpers section of this document.
Relay Outputs Memory Slot: Uses Removable Memory for data logging, screen captures,
program loading and recipes. Novus Part No.: HE-MC1
Outputs per Module 6 relay SPST-NO
Serial Communications: MJ1: (RS-232 / RS-485) Use for Cscape programming
Max. Output Current per Relay 3 A at 250 VAC, resistive and Application-Defined Communications. MJ2: (RS-232 / RS-485) Use for
Max. Total Output Current 5 A continuous Application-Defined Communications.
Max. Output Voltage 275 VAC , 30 VDC
Max. Switched Power 1250 VA, 150 W
Contact Isolation to XLe/XLt
1000 VAC
ground
Max. Voltage Drop at Rated
0.5 V
Current
Expected Life No load: 5,000,000
(See Derating section for chart.) Rated load: 100,000
300 CPM at no load
Max. Switching Rate
20 CPM at rated load
Type Mechanical Contact
Response Time One update per ladder scan plus 10 ms
Analog Inputs, Medium Resolution Power Connector and Can Connector
Number of Channels 4
Input Ranges 0 - 10 VDC / 0 – 20 mA / 4 – 20 mA
Safe input voltage range -0.5 V to +12 V
Input Impedance Current Mode: Voltage Mode:
(Clamped @ -0.5 V to 12 VDC) 100  500 k 
Nominal Resolution 10 Bits
% AI full scale 32,000 counts
Max. Over-Current 35 mA

Conversion Speed
All channels converted once per ladder 4 Serial Communications:
scan
MJ1: (RS-232 / RS-485) Use for Cscape programming and Application-Defined
Max. Error at 25C
Communications.
(excluding zero) 4-20 mA 1.00%
0-20 mA 1.00% MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.
*can be made tighter (~0.25%)
by adjusting the digital filter 0-10 VDC 1.50%*
MJ1 Pins MJ2 Pins
setting to 3. PIN
Additional error for temperatures
Signal Direction Signal Direction
TBD
other than 25C 8 TxD OUT TxD OUT
160 Hz hash (noise) filter 7 RxD IN RxD IN
Filtering
1-128 scan digital running average filter 6 0V GROUND 0V GROUND
General Specifications 5 +5 V OUT +5 V OUT
Required Power (Steady State) 130 mA @ 24 VDC 4 RTS OUT Tx- OUT
Required Power (Inrush) 30 A for 1 ms @ 24 VDC 3 CTS IN Tx+ OUT
Primary Power Range 10 ~ 30 VDC 2 Rx- / Tx- IN / OUT Rx- IN
Relative Humidity 5 to 95% Non-condensing
1 Rx+ / Tx+ IN / OUT Rx+ IN
Clock Accuracy +/- Seven Minutes/Month at 20 C
Operating Temperature 0 C to +50 C
5 Wiring and Jumpers
Terminal Type Screw Type, 5 mm Removable
Weight 12 oz. (340.19 g) Wire according to the type of inputs / outputs used, and select the appropriate
jumper option.
Note: Highest usable frequency for PWM output is 65 kHz
Wiring Specifications
For I/O wiring (discrete): 0.8 mm2 (18 AWG) or larger.
2 Panel Cut-Out and Dimensions For shielded Analog I/O wiring: 0.8 mm2 (18 AWG) or larger.
For CAN wiring: 0.2 mm2 (24 AWG) or larger.
Refer to the XLe/XLt user Manual for panel box information and a handy checklist
of requirements. Use copper conductors in field wiring only, 60/75° C

NOVUS AUTOMATION 1/2


Orange Connector (J1) To terminate, select one of the jumpers shipped with the product and insert it
based upon the option that is desired or, select the switch and configure based
J1 Orange I1 upon the option that is desired.
Terminal Name
I2 As seen when looking at the top of the XLe/XLe unit: Refer to Section 3 for the
Connector
location of the DIP Switches (or External Jumpers).
I1 IN1 I3
I2 IN2 I4
DIPSW3: FACTORY USE ONLY (tiny
I3 IN3 12-24VDC I5 bootloader firmware downloading). NOT
I4 IN4
I6 TO BE USED FOR NORMAL OCS
I5 IN5 OPERATIN.
I7
I6 IN6
I8 DIPSW2: MJ2 Termination (Default –
I7 IN7 none)
I8 IN8 H1
H1 HSC1 /IN9 0V DIPSW1: MJ1 Termination (Default –
20mA none)
0V Ground A1
001XLE037-R1

A1 Analog IN1
A2
A2 Analog IN2 MJ2 Pinouts in Full and Half Duplex Modes
LOOP PWR A3
A3 Analog IN3
A4 MJ2 Full Duplex MJ2 Half Duplex
A4 Analog IN4
0-10VDC
0V PIN Mode Mode
0V Ground
001XLE017
Signal Direction Signal Direction
8 TxD OUT TxD OUT
Black Connector (J2) 7 RxD IN RxD IN
J2 Black 6 0V GROUND 0V GROUND
Terminal Name 230VAC N C6 5 +5 V OUT +5 V OUT
Connector OR
L

C6 COM
25VDC LOAD R6 4 Tx- OUT Tx- OUT
Relay 6 230VAC N C5
3 Tx+ OUT Tx+ OUT
R6 NO OR
L
25VDC R5
2 Rx- IN Tx- / Rx- IN/OUT
LOAD

C5 COM
Relay 5 230VAC C4
R5 NO OR
N
L
1 Rx+ IN Tx+ / Rx+ IN/OUT
25VDC LOAD R4
C4 COM
Relay 4 230VAC C3
R4 NO OR
N
6 Safety
L
C3 COM
25VDC LOAD R3
Relay 3 When found on the product, the following symbols specify:
R3 NO 230VAC N C2
OR
L
C2 COM 25VDC LOAD R2 Warning: Electrical
Relay 2 Warning: Consult
R2 NO 230VAC C1 Shock Hazard.
OR
N user documentation.
L
C1 COM 25VDC LOAD R1
Relay 1
R1 NO H4 This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-
H4 HSC4 / IN12 12-24VDC H3 hazardous locations only

H3 HSC3 / IN11 WARNING – EXPLOSION HAZARD – Substitution of components may impair suitability for
0V ON J1 H2
Class I, Division 2
H2 HSC2 / IN10 001XLE015
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power has been
switched off or the area is known to be non-hazardous.
I/O Jumpers Settings (JP1 - JP2) WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
The jumpers JP1 and JP2 are located in the connectors PCB internal to the
controller. JP1 defines the logic of the digital inputs. JP2 defines the input type WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to
signal of each analog channel. the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of
fire and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated
failure indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation
of this equipment and the hazards involved should install, adjust, operate, or service this
equipment. Read and understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in severe bodily injury or
loss of life.

All applicable codes and standards need to be followed in the installation of this product.
Adhere to the following safety precautions whenever any type of connection is made to the
module:
Connect the safety (earth) ground on the power connector first before making any other
connections.
When connecting to electric circuits or pulse-initiating equipment, open their related
Location of I/O jumpers breakers.
Do not make connections to live power lines.
Make connections to the module first; then connect to the circuit to be monitored.
Route power wires in a safe manner in accordance with good practice and local codes.
Wear proper personal protective equipment including safety glasses and insulated gloves
when making connections to power circuits.
Ensure hands, shoes, and floors are dry before making any connection to a power line.
Current (*) Voltage Positive Logic (*) Negative Logic
Make sure the unit is turned OFF before making connection to terminals.

JP2 Analog In (A1-A4) JP1 Digital DC IN1-12 / HSC1-4 Make sure all circuits are de-energized before making connections.
Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
Note: Use Copper Conductors in Field Wiring Only, 60/75° C
When using JP2 (A1-A4), each channel can be independently configured.
(*) Default 7 Technical Support
External DIP Switch Settings (or Jumpers Settings) For assistance and manual updates, contact Technical Support at the following
locations:
Some XLe/XLt have jumpers to set RS-485 port termination, though most use DIP
Switches. e-mail: suporte@novus.com.br
The External Jumpers or DIP Switches are used for termination of the RS-485 You can find the complete documentation at www.novus.com.br.
ports. The XLe/XLt is shipped un-terminated.

NOVUS AUTOMATION 2/2