Beruflich Dokumente
Kultur Dokumente
National Load Despatch Centre (NLDC) has been constituted as per Ministry
of Power (MOP) notification, New Delhi dated 2nd March 2005 and is the apex
body to ensure integrated operation of the national power system.
Role of SLDC:
Metering
Annunciation/Alarms
Mimic diagram/indications
Protection relays
Over current relay, Earth fault relay, Distance protection relay, Differential
relay, REF protection relay are equipped for fault protection of system
operation. They are designed and applied to provide maximum discrimination
between faulty and healthy circuits. System equipment will remain inoperative
during transient phenomena which may arise during switching or other
disturbance to the system.
Optocoupler
It is basically an interface between two circuits i.e. RTU and instruments in C &
R Panel which operate at different voltage levels. This is necessary for the
coupling between high voltage information gathering C & R Panel and low-
voltage digital logic RTU.
Figure :Optocoupler
All the metering, annunciation, status indication data from 110V DC analog
Control and Relay Panel is converted, voltage isolated and transmitted to 48V
digital RTU. All the required circuits are connected to the 8 inputs of the
Optocoupler and one output from Optocoupler is connected to RTU560A DI
card. It only allows signal flow in one direction, responds to dc levels, and offer
an extremely large resistance between the input and output circuits.
SCADA EQUIPMENT:
At 110/11kV city substation, consists of the following SCADA equipments.
They are :
1. RTU 560A along with IF panel.
2. VSAT
Antenna,
IDU,
8 port switch,
telephone
3. 2 kVA UPS (Power One make) along with
8 No of 100Ah, 12V cells
Battery stand
ACDB
RTU 560A
It consists of Basic rack (top rack) with CPU and communication ports,
Extension rack 1 (2nd rack) with Digital Input card (DI) Analog Input card (AI)
and Analog Output card (AO). Digital Output card (DO) at Extension rack 2
(3rd rack) and each rack is supported by separate power supply cards. For load
alarm annunciation, there is rack called SCADA annunciation panel.
Basic rack:
Basic Rack or the Communication Sub Rack houses the brain of the RTU. It
consists of a number of slots into which a set of “Cards” are mounted as shown
in the figure. The Cards are the CPUs of the RTU. They help in coordinating the
flow of data from and into the RTU.
These CPUs are of two types: 3 no. of CMU (Communication unit) Card -
560SLI 01 or 560CMU 04 and 2 no. of ETH (Ethernet) Cards - 560ETH 01.
Communication unit (CMU) Card acts as an interface between the RTU and the
IEDs (Intelligent Electronic Devices) like protection relays, multifunction
meters and battery charger. It consecutively reads data in and out of the IEDs
such as Numerical Relays present on the C&R Panel or MFTs placed on the
MFT panel of the RTU. It communicates with the IEDs through four ports i.e.
A, B, 1 and 2 which are RS485 type and RS232. Each CPU communication
board has an additional serial interface for MMI to a PC which are RS232 type.
The MMI is used for diagnostics, up and download of configuration files, etc
The Ethernet card controls the process events and communications with the
Control Centers. It continually reads the data from the Extension Racks, the
CMU cards and sends it to the control center. The ETH card has a port marked
by “E” used by the RTU to communicate to the Master control center. The ETH
is connected to the Extension Rack through port A or B, called COM A and
COM B. It also has an MMI port similar to the one present in the CMU card.
The ETH and the CMU cards communicate with each other through a dedicated
communication channel present on the back plane of the Basic Rack. It has the
ability to manage and control the input/output boards through RS232/485
interfaces, reads process events from input boards, send commands to output
boards and communicates with control centers via integrated serial line interface
and Ethernet LAN interface.
Extension rack 1 and 2:
Status indication from control & relay panel are given to 8 binary input Digital
card (DI) card - 23BE23 located in extension rack 1. Scanning and processing
of the inputs are executed with the high time resolution of 1 ms. One DI card
have 16 channels, which can be used for connecting the status of field devices
as an indication to MCC. The board has sixteen light emitting diodes to indicate
the signal-state, Each LED indicates ON/OFF status of an input connected to
particular channel of the DI card. It has a buffer which allows the temporary
storage of 50 time-stamped event messages in chronological order designated
for transmission to the communication unit.
The DI card shall accept two types of status inputs i.e. Single point status inputs
and Double point status inputs. Single point status input will be from a
normally-open (NO) or normally-closed (NC) contact which is represented by
1bit in the protocol message. The Double point status input will be from two
complementary contacts (one NO and oneNC) which is represented by 2-bits in
the protocol message. A switching device status is valid only when one contact
is closed and the other contact is open.
Figure : AI Card
Figure : DO Card
AC-DC Converter:
All racks of RTU560A consists of power supply unit 560PSU01 which require
DC supply of 48V, thus AC-DC converter is used. This unit supplies required
DC power to all racks of RTU panel.
It is an IED that can calculate real time analog values such as line voltage, phase
current, frequency, active power, apparent power (MVA), reactive power
(MVAr) and power factor when inputs from secondary of the CTs and PTs are
given. It can measure 96 electrical parameters from single transducer. This
output is transmitted in MODBUS or IEC104 protocol to RTU unit, which in
turn processes and sends across to MCC. There is a communication port
available for each MFT with RS 485 connection scheme. The communication
ports of 8 MFTs are looped through RS485 interface and assigned to the ports
of CMU card through a cable. Baud rate of data transfer between MFTs and
RTU is 19.2 Kbps.
30
Multifunction 30 no. of bays data can be collected.
1 Transducer (MFT)
8
Digital Input Card (DI Each card supports 16 digital inputs.
2 card)
5
Digital output Card Each card supports 16 digital outputs.
3 (DO card)
3
Analog Input Card (AI Each card supports 8 inputs.
4 card) (DC Voltage, Tap position…)
1 2 linear control
Analog Output Card
5 (AO card)
Communication Card 2
Each having 4 ports for
8 communication.
AC-DC Converter 2
For providing DC power supply to
9 rack (48 V).
Optocoupler 3
To isolate voltages (110V dc & 48V).
10
COMMUNICATION BACK BONE
5 W RF 3.8 m COMSAT
Transceiver
Antenna
FX
E
E&
IDU S
Data M P
D
D1
Type A site : D 1 channels RTU 2 A
alone RMMI
Type B site: D1 & D2
channels
Figure :VSAT Configuration
Fig shows the block diagram of basic VSAT satellite communication system.
Satellite communication system consists of many earth stations on the ground
and these are linked with a satellite in space. The user is connected to the Earth
station through a terrestrial network and this terrestrial network may be a
telephone switch or dedicated link to earth station. The user generates a
baseband signal that is processed through a terrestrial network and transmitted
to a satellite at the earth station. The satellite transponder consists of a large
number of repeaters in space which receives the modulated RF carrier in its
uplink frequency spectrum from all the earth station in the network, amplifies
these carriers and retransmits them back to the earth stations in the downlink
frequency spectrum. To avoid the interference, downlink spectrum should be
different from uplink frequency spectrum. The signal at the receiving earth
station is processed to get back the baseband signal, It is sent to the end user
through a terrestrial network.
Commercial communication satellite uses a frequency band of 500 M Hz
bandwidth near 6 G Hz for uplink transmission and another 500 M Hz
bandwidth near 4 G Hz for downlink transmission .An uplink of 5.725 to 7.075
G Hz and downlink of 3.4 to 4.8 G Hz is used. Here the extended C-band is
used with uplink frequency of 6.9350-6.9465 GHz and downlink frequency of
4.710-4.7215 GHz downlink frequency. Modulation used here is QAM to save
the bandwidth. Extended C band is most popular because of less propagation
problem. Rain attenuation and sky noise is low at 4 GHz downlink frequency of
C band. So it is possible to build a receiving system.
The basic block diagram of a VSAT earth-station Transmitter .Thebaseband
signal from the terrestrial network is processed through modulator and then it is
converted to uplink frequency. Finally it is amplified by high power amplifier
and directed towards the appropriate part of antenna.
The acronym VSAT is the earth station antenna used at the earth stations. In
VSAT the earth station antenna size is typically less than 2.4 m in diameter and
the trend is towards even smaller dishes measuring not more than 1.8 m in
diameter. According to European Telecommunication standard Institute, VSAT
is referred as satellite transmit –receive system that has an aperture size
smaller than 2.8m2. VSAT‟s provide cost effective solutions for the growing
telecommunication needs through- out the world. Today‟s satellites are more
powerful, enabling the use of smaller and less-expensive antennas on the
ground. Also, the developments include most of the necessary VSAT functions,
which makes VSATs more effective.
The architecture of the networks is of two types. One is star topology and the
other is mesh topology. The star topology is the traditional VSAT network
topology. Here the communication link is between the hub and the remote
terminal. This topology is well suited for data broadcasting or data collection.
This is not applicable for speech services because the time delay is too severe
(500ms). The access techniques used in a star network can be both FDMA and
TDMA. In mesh topology there is a direct communication between the remote
VSAT terminals. This minimizes the time delay which is concerned with speech
services. The access method used in mesh network is FDMA. Very Small
Aperture Terminals (VSATs) are designed for data transmission and
distribution over a wide geographical area amongst a large number of locations.
The small size and low transmit power of a VSAT station are the factors that
keep the price of the earth station at a level that makes a VSAT network an
economic alternative to a terrestrial data network using telephone lines and
modems. The hub usually houses a central host computer, which can act as a
data switching center. The architecture of the network naturally becomes star
shaped, [Maral, 1995]. The links from the hub to the VSAT are called outbound
links. The links from the VSAT to the hub are called inbound links. Both
inbound and outbound links consist of two parts, uplink and downlink. It is not
unusual that inbound and outbound links operate at different transmission
speeds, i.e. in asymmetrical mode.
Interoperability of 61850
VIDYUTNET
PLCC Terminal:
Translate voice and data into a high frequency carrier. Output power=10 to
80W.
Figure :Components of PLCC
Do not allow the transmitted HF carrier to enter inside the sub-station. (L=0.5 to
2mH) without line trap HF carrier get by-passed to some other line on the same
bus bar and may leak to ground ( a earth switch inside the yard provided for
each bay is kept closed during maintenance. Wave Trap is provided in the line
after the CVT. The impedance offered by inductor Z = wL will be high which
will not allow the high frequency carrier signal to enter into the substation.
The carrier transmitter and receiver are mounted in a cabin in the control house,
and the line tuner are placed in the switchyard. The equipment and the tuner
connected using coaxial cable as there is a large distance between them. The
coaxial cable shields the signal from noise interference. A connection is made
between the coaxial cable and the line tuner mounted in the coupling capacitor’s
base. In case of more than one terminal, before connection to the line tuner, the
signal should pass through an isolation circuit.
LINE TUNER
The line tuner along with the coupling capacitor provides high impedance path
to the power frequency energy and a path of lower impedance for the carrier
energy to the transmission line. The line tuners and coupling capacitors line by
forms a carrier frequency tuned series resonant circuit providing a path of low
impedance to the power line. The capacitor in the coupling capacitor provides a
path of higher impedance to power frequency energy. Though the coupling
capacitors provide high impedance path to power frequencies, they must be
grounded. Grounding is provided by the drain coil placed at coupling
capacitor’s base. As a result of drain coil’s inductance it provides high
impedance to carrier frequency and low impedance to power frequency. The
coupling capacitor, line tuner and drain coil will block the power frequency and
couples the carrier energy to the transmission line. The line tuner also provides
impedance matching between the power line having an impedance of 150 to 500
ohms and coaxial cable, usually with 50 to 70ohms.
A fault in an electric power system can be defined as, any abnormal condition
of the system that
involvestheelectricalfailureoftheequipment,suchas,transformers,generators,busb
ars,etc.
Faults–Types and their Effects
1. Active faults
2. Passive faults
3. Transient faults
4. Permanent faults
5. Symmetrical Faults
6. Unsymmetrical Faults
7. Open circuit faults
8. Short circuit faults
Active Faults:
The “Active” fault is when actual current flows from one phase conductor to
another (phase-to-phase) or alternatively from one phase conductor to earth
(phase-to-earth).This type of fault can also be further classified into two areas,
namely the “solid” fault and the “incipient” fault. The solid fault occurs as a
result of an immediate complete breakdown of insulation as would happen if,
say, a pick struck an underground cable, bridging conductors etc. or the cable
was dug up by a bulldozer. In mining, a rock fall could crush a cable as would a
shuttle car. In these circumstances the fault current would be very high,
resulting in an electrical explosion. This type off fault must be cleared as
quickly as possible otherwise there will be:
Greatly increased damage at the fault location. (Fault energy = 1² Rf t
where ‘t’ is time).
Danger to operating personnel(Flashproducts).
Danger of igniting combustible gas such as methane in hazardous areas
giving rise to a disaster of horrendous proportions.
Increased probability of earth faults spreading to other phases.
Higher mechanical and thermal stressing of all items of plant carrying the
current fault. (Particularly transformers whose windings suffer
progressive and cumulative deterioration because of the enormous
electromechanical forces caused by multi-phase faults proportional to the
current squared).
Sustained voltage dips resulting in motor (and generator) instability
leading to extensiveshut-down at the plant concerned and possibly other
near by plants.
The “incipient” fault, on the other hand, is a fault that starts from very small
beginnings, from say some partial discharge (excessive electronic activity often
referred to as Corona) in a void in the insulation, increasing and developing
over an extended period, until such time as it burns away adjacent insulation ,
eventually running away and developing into a “solid” fault.
Passive Faults:
Passive faults are not real faults in the true sense of the word but are rather
conditions that are stressing the system beyond its design capacity, so that
ultimately active faults will occur. Typical examples are: Overloading –
leading to overheating of insulation (deteriorating quality, reduced life and
ultimate failure).
Overvoltage – stressing the insulation beyond its limits.
Under frequency – causing plant to behave incorrectly.
Power swings – generators going out-of-step or synchronism with each
other.
It is therefore very necessary to also protect against these condition.
Transient & Permanent Faults
Transient faults are faults which do not damage the insulation permanently and
allow the circuit to be safely re-energized after a short period of time. A typical
example would be an insulator flashover following a lightning strike, which
would be successfully cleared on opening of the circuit breaker, which could
then be automatically reclosed. Transient faults occur mainly on outdoor
equipment where air is the main insulating medium. Permanent faults, as the
name implies, are the result of permanent damage to the insulation. In this case,
the equipment has to be repaired and reclosing must not be entertained.
Symmetrical & Unsymmetrical Faults:
Symmetrical Faults:
A symmetrical fault is a balanced fault with the sinusoidal waves being
equal about their axes, and represents a steady state condition.A
symmetrical fault gives rise to symmetrical fault 10 currents that are
displaced with 120˚ each other. Symmetrical fault is also called as balanced
fault. This fault occurs when all the three phases are simultaneously short
circuited. These faults rarely occur in practice as compared with
unsymmetrical faults. Two kinds of symmetrical faults include line to line to
line (L-L-L) and line to line to line to ground (L-L-L-G).
Unsymmetrical Faults:
The most common faults that occur in the power system network are
unsymmetrical faults. This kind of fault gives rise to unsymmetrical fault
currents (having different magnitudes with unequal phase displacement).
These faults are also called as unbalanced faults as it causes unbalanced
currents in the system. An asymmetrical fault displays a dc offset, transient
in nature and decaying to the steady state of the symmetrical fault after a
period of time. The amount of offset depends on the X/R (power factor) of
the power system and the first peak can be as high as 2.55 times the steady
state level. The figure below shows the three types of symmetrical faults
occurred due to the short circuit conditions, namely phase or line to ground
(L-G) fault, phase to phase (L-L) fault and double line to ground (L-L-G)
fault.
Open circuit faults:
These faults occur due to the failure of one or more conductors. The figure
below illustrates the open circuit faults for single, two and three phases (or
conductors) open condition. The most common causes of these faults
include joint failures of cables and overhead lines, and failure of one or
more phase of circuit breaker and also due to melting of a fuse or conductor
in one or more phases. Open circuit faults are also called as series faults.
These are unsymmetrical or unbalanced type of faults except three phase
open fault.
Effects
Abnormal operation of the system
Danger to the personnel as well as animals
Exceeding the voltages beyond normal values in certain parts of the
network, which further leads to insulation failures and developing of
short circuit faults. 11.
Under normal or safe operating conditions, the electric equipments in a
power system network operate at normal voltage and current ratings
Once the fault takes place in a circuit or device, voltage and current
values deviates from their nominal ranges.
The faults in power system causes over current, under voltage, unbalance
of the phases, reversed power and high voltage surges.
This results in the interruption of the normal operation of the network,
failure of equipments, electrical fires, etc.
Usually power system networks are protected with switchgear protection
equipments such as circuit breakers and relays in order to limit the loss of
service due to the electrical failures. Electrical networks, machines and
equipments are often subjected to various types of faults while they are in
operation. When a fault occurs, the characteristic values (such as
impedance) of the machines may change from existing values to different
values till the fault is cleared. Although open circuit faults can be tolerated
for longer periods than short circuit faults, these must be removed as early
as possible to reduce the greater damage.
Effects
Arcing faults can lead to fire and explosion in equipments such as
transformers and circuit breakers.
Abnormal currents cause the equipments to get overheated, which
further leads to reduction of life span of their insulation.
The operating voltages of the system can go below or above their
acceptance values that creates harmful effect to the service rendered
by the power system.
The power flow is severely restricted or even completely blocked as
long as the short circuit fault persists
Lightning Arrester
The device which is used for the protection of the equipment at the
substations against travelling waves, such type of device is called lightning
arrester or surge diverter. In other words, lightning arrester diverts the
abnormals high voltage to the ground without affecting the continuity of
supply. It is connected between the line and earth, i.e., in parallel with the
equipment to be protected at the substation
The following are the damages that are caused by the travelling wave on the
substation equipment.
1. The high peak or crest voltage of the surge may cause flash-over in the
internal winding thereby spoil the winding insulation.
2. The steep wave fronts of the surges may cause external flashover between the
terminal of the transformer.
3. The highest peak voltage of the surge may cause external flashover, between
the terminal of the electrical equipment which may result in damage to the
insulator.
Working of Lightning Arrester
When a travelling wave reaches the arrestor, its sparks over at a certain prefixed
voltage as shown in the figure below. The arrestor provides a conducting path to
the waves of relatively low impedance between the line and the ground. The
surge impedance of the line restricts the amplitude of current flowing to ground.
The lightning arrester provides a path of low impedance only when the
travelling surge reaches the surge diverter, neither before it nor after it. The
insulation of the equipment can be protected.
Wave trap
Line trap (high-frequency stopper) is a maintenance-free parallel resonant
circuit, mounted inline on high-voltage (HV) AC transmission power lines to
prevent the transmission of high frequency (40 kHz to 1000 kHz) carrier signals
of power line communication to unwanted destinations. Line traps are cylinder-
like structures connected in series with HV transmission lines. A line trap is also
called a wave trap.
The line trap acts as a barrier or filter to prevent signal losses. The inductive
reactance of the line trap presents a high reactance to high-frequency signals but
a low reactance to mains frequency. This prevents carrier signals from being
dissipated in the substation or in a tap line or branch of the main transmission
path and grounds in the case of anything happening outside of the carrier
transmission path. The line trap is also used to attenuate the shunting effects of
high-voltage lines.
Wave trap is a parallel tuned inductor - capacitor tank circuit made to be
resonant at desired communication frequency . It reduces corona losses in
transmission lines in power system.
Wave trap is installed in the substation for trapping the high frequency
communication signal sent on the line from remote substation and diverting
them to the telecom panel in substation control room. These high frequency
signal should not be coming on the buses as these may damage the equipments .
A wave trap is a device that allow only a particular frequency to pass through
it that it filters the signals coming on to it . So a wave trap is connected between
buses and the transmission line which allow only 50 Hz signal to pass through
it.
Line trap also is known as Wave trap. What it does is trapping the high
frequency communication signals sent on the line from the remote substation
and diverting them to the telecom/teleportation panel in the substation control
room (through coupling capacitor and LMU). 17
This is relevant in power carrier communication (PLCC) system for
communication among various substation without dependence on telecom
company network. The signals are primarily teleportation signal and in addition
to voice and data communication signal.
ISOLATOR:
Isolator is a manually operated mechanical switch that isolates the faulty
section or the section of a conductor or a part of a circuit of substation meant for
repair from a healthy section in order to avoid occurrence of more severe faults.
Hence, it is also called as a dis connector or disconnecting switch. There are
different types of isolators used for different applications such as single-break
isolator, double-break isolator, bus isolator, line isolator, etc.
Isolator, on the contrary to the circuit breaker, is an off-load device and
performs the task as the name implies. It disconnects or Isolates the circuit from
the main power supply. Isolators are most commonly found in industry level
electric systems.Even though, Isolator is a switch, it is not used as a normal on
off switch. It is used only when the electrical system has to be disconnected
from the main supply, to perform maintenance or related activities, which
involve direct contact with the current carrying components of machinery.
Isolators may provide additional safety features like, when switched off the
trapped charge will be ground through a ground terminal in the isolator.
Isolators are normally placed after the circuit breaker allowing the internal
circuit to be disconnected from the main supply without affecting the
realy.Isolators may be used in high voltage devices like transformers. Isolators
are secured using a locking mechanism on the outside or by a padlock to
prevent inadverten usage.In electronics, the term isolator is used to denote a
device which separates the internal circuits from the main supply, but it is
different from the Isolator switch discussed above. Using opto-couplers an
electronics circuit can be isolated such that overloads do not pass through the
circuit.
Circuit Breaker
Electrical circuit breaker is a switching device which can be operated manually
and automatically for controlling and protection of electrical power system
respectively. As the 18 modern power system deals with huge currents, the
special attention should be given during designing of circuit breaker for safe
interruption of arc produced during the operation of circuit breaker. This was
the basic definition of circuit breaker.
Working Principle of Circuit Breaker
The circuit breaker mainly consists of fixed contacts and moving contacts. In
normal "ON" condition of the circuit breaker, these two contacts are physically
connected to each other due to applied mechanical pressure on the moving
contacts. There is an arrangement stored potential energy in the operating
mechanism of circuit breaker which is released if the switching signal is given
to the breaker. The potential energy can be stored in the circuit breaker by
different ways like by deforming metal spring, by compressed air, or by
hydraulic pressure. But whatever the source of potential energy, it must be
released during operation. The release of potential energy makes the sliding of
the moving contact in a speedy manner.
Types of Circuit Breaker
According different criteria there are different types of circuit breaker.
According to their arc quenching media the circuit breaker can be divided as-
1. Oil circuit breaker.
2. Air circuit breaker.
3. SF6 circuit breaker.
4. Vacuum circuit breaker
Air Circuit Breaker
This circuit breaker will operate in the air; the quenching medium is an Arc at
atmospheric pressure. In many of the countries air circuit breaker is replaced by
oil circuit breaker. About oil circuit breaker we will discuss later in the article.
Thus the importance of ACB is still preferable choice to use an Air circuit
breaker up to 15KV. This is because; oil circuit breaker may catch fire when
used at 15V.
Air Blast Circuit Breaker
Air blast circuit breakers are used for system voltage of 245 KV, 420 KV and
also even more. Air blast circuit breakers are of two types:
Axial blast breaker
Axial blast with sliding moving contact.
SF6 Circuit Breaker
In the SF6 circuit breaker the current carrying contacts operate in sulphur
hexafluoride gas is known as an SF6 circuit breaker. It is an excellent insulating
property and high electro- negativity. It can be understood that, high affinity of
absorbing free electron. The negative ion is formed when a free electron
collides with the SF6 gas molecule; it is absorbed by that gas molecule. The two
different ways of attachment of electron with SF6 gas molecules are
SF6+e=SF6
SF 6 + e = SF5- + F
The negative ions which are formed will be much heavier than a free electron.
Therefore, when compared with other common gases overall mobility of the
charged particle in the SF6 gas is much less. The mobility of charged particles
is majorly responsible for conducting current through a gas. Hence, for heavier
and less mobile charged particles in SF6 gas, it acquires very high dielectric
strength. This gas good heat transfer property because of low gaseous viscosity.
SF6 is 100 times more effective in arc quenching media than air circuit breaker.
It is used for both medium and high voltage electrical power system from 33KV
to 800KV.
Types of SF6 Circuit Breaker
Single interrupter SF6 circuit breaker applied up to 220
Two interrupter SF6 circuit breaker applied up to 400
Four interrupter SF6 circuit breaker applied up to 715V
Vacuum Circuit Breaker
A Vacuum circuit breaker is a circuit which vacuum is used to extinct the arc. It
has dielectric recovery character, excellent interruption and can interrupt the
high frequency current which results from arc instability, superimposed on the
line frequency current.
In the principle of operation of VCB will have two contacts called electrodes
will remain closed under normal operating conditions. Suppose when a fault
occurs in any part of the system, then the trip coil of the circuit breaker gets
energized and finally contact gets separated.
The moment contacts of the breaker are opened in vacuum, i.e. 10-7 to 10-5
Torr an arc is produced between the contacts by the ionization of metal vapors
of contacts. Here the arc quickly gets extinguished, this happens because the
electrons, metallic vapors and ions produced during arc, condense quickly on
the surface of the CB contacts, resulting in quick recovery of dielectric strength.
Oil Circuit Breaker
In this type of circuit breaker oil is used, but mineral oil is preferable. It acts
better insulating property than air. The moving contact and fixed contact are
immerged inside the insulating oil. When the separation of current takes place,
then carrier contacts in the oil, the arc in circuit breaker is initialized at the
moment of separation of contacts, and because of this arc in the oil is vaporized
and decomposed in hydrogen gas and finally creates a hydrogen bubble around
the arc.
This highly compressed gas bubble around and arc prevents re-striking of the
arc after current reaches zero crossing of the cycle. The OCB is the oldest type
of circuit breakers.
Different types of Oil Circuit Breaker
Bulk oil circuit breaker
Minimum oil circuit breaker
PROTECTION RELAYS
There are different function of protection relays, Each one of these relays are
able to deal with certain type of faults. Every equipment needs different type of
protection relays. As example, Distance relays are suitable for transmission
lines, and differential relays for power transformers and bus bars.
Over Current Protection
Over current protection is practical application of magnitude relays since it
picks up when the magnitude of current exceeds some value (setting value ).
There are four types of over current relays
Instantaneous Over Current Relay Instantaneous over current. Relays which
operation criteria is only current magnitude (without time delay) . This type is
applied to the outgoing feeders.
Definite Time Over Current Relay
In this type, Two conditions must be satisfied for operation (tripping), Current
must exceed the setting value and the fault must be continuous at least for a
time equal to time setting of the relay. Modern relays may contain more than
one stage of protection each stage includes each own current and time setting.
Definite time over current relay is the most applied type of over current. It is
used as :
1- Backup protection of distance relay of transmission line with time delay
equal to fourth stage of distance relay which is 2.5 second in 220 kV lines,
and 1.5 second in 66 kV lines
2- 2- Backup protection to differential relay of power transformer with time
delay equal to 2.0 second in 220/66 kV transformers, and 1.1 second in the
66/11 kV transformers
3- 3- Main protection to outgoing feeders and bus couplers with adjustable
time delay setting.
Inverse Time Over Current Relay
In this tape of relays, operating time is inversely changed with current. So,
high currents will operate over current relay faster than lower ones. Different
currents of inverse time type are defined as standard inverse, very inverse ,
extremely inverse all these types
Distance Relay or Impedance Relay Working Principle
There is one type of relay which functions depending upon the distance of fault
in the line. More specifically, the relay operates depending upon the impedance
between the point of fault and the point where relay is installed. These relays
are known as distance relay or impedance relay.
Working Principle of Distance or Impedance Relay
The working principle of distance relay or impedance relay is very simple.
There is one voltage element from potential transformer and a current element
fed from current transformer of the system. The deflecting torque is produced
by secondary current of CT and restoring torque is produced by voltage of
potential transformer.
In normal operating condition, restoring torque is more than deflecting torque.
Hence relay will not operate. But in faulty condition, the current becomes quite
large whereas voltage becomes less. Consequently, deflecting torque becomes
more than restoring torque and dynamic parts of the relay starts moving which
ultimately close the No contact of relay. Hence clearly operation or working
principle of distance relay depends upon the ratio of system voltage and
current. As the ratio of voltage to current is nothing but impedance so a
distance relay is also known as impedance relay. The operation of such relay
depends upon the predetermined value of voltage to current ratio. This ratio is
nothing but impedance. The relay will only operate when this voltage to current
ratio becomes less than its predetermined value. Hence, it can be said that the
relay will only operate when the impedance of the line becomes less than
predetermined impedance (voltage/current). As the impedance of a
transmission line is directly proportional to its length, it can easily be
concluded that a distance relay can only operate if fault is occurred within a
predetermined distance or length of line.
Differential Relays
Different relay is that relay which checks the different between the input and
output currents for a power system current. The difference between the currents
may be in magnitude or in phase angle or in both. For healthy operation,
magnitude and angle differences must be zero. If there is a difference and that
difference exceeds some value (setting value) the relay will operate and
associated circuit breaker will trip .
Buchholz Relays
A Buchholz relay is a protection device for monitoring the gas and oil
movements in oil immersed transformers. It is used on practically all power
transformers with the exception of small distribution sizes. In practice it has
proved to be the only protective device that can clear certain types of faults. The
Buchholz relay relies on the principle that during fault conditions, gas is
generated inside the transformer tank from the insulating oil.
The internal mechanism of a Buchholz relay mainly comprises two floats and is
illustrated in figure. During normal operation, the relay is completely filled with
oil keeping the floats in their top limit or rest position. The contact mechanisms
in the relays respond to:
Slight faults causing a slow evolution of gas in the transformer (e.g.
overheating)
Serious faults creating an immediate surge of oil (e.g. short circuits etc.)
Oil leakage
61850 SERVICES:
Control (normal/enhanced, select before operate)
Buffered and Unbuffered report
Logging
GOOSE (Generic Object-Oriented Substation): is a controlled model
mechanism, in which any format of data is grouped (data packet) into
a set and transmitted within 4 milliseconds. This technology enables
fast inter device communication. The events reported by GOOSE are
soft configured in the master file.
Equipment report to the IED in case any fault occurs, which is
communicated to HM, the HMI in turn sends GOOSE message to the
equipment node to take the action as required, hence there is no hard wiring and
al the above required communication happens through the software
configuration itself, hence termed as object oriented.
Substitution
Setting Group
Sampled Value
File transfer
Time synchronization.
TIME SYNCHRONIZATION:
It is very important, but in the conventional stations, where in an engineer
records the reading, especially in the huge stations, time synchronized readings
of all the equipment is not possible.
Hence to achieve time synchronization, the nodes within the network are
synchronized with GPS. The GPS receiver is present for the purpose, which is
connected to the Ethernet.
In the substation automation, the following application requires
synchronization:
Transmission of Ethernet protocols like GOOSE
Real time data acquisition from IED’s, RTU’S and MU’s
Real time process control of the field equipment
Fault analysis and performance study.
BACKIOS: It is a control unit placed in the yard itself, to reduce the number of
hardwires running to the control room. Simple control panel architecture is
present and only the lan cable is carried to the control room, where the HMI is
present.
NETWORKING
IP Addressing & Subnetting
IP Addressing
Subnetting
VLSM
CIDR
IP Addresses
An IP address is an address used to uniquely identify a device on an IP
network.
The address is made up of 32 binary bits which can be divisible into a
network portion and host portion with the help of a subnet mask.
32 binary bits are broken into four octets (1 octet = 8 bits).
Dotted decimal format (for example, 172.16.81.100).
IP Address Classes
Class A: The first octet is the network portion. Octets 2, 3, and 4 are for
subnets/hosts.
Class B: The first two octets are the network portion. Octets 3 and 4 are
for subnets/hosts.
Class C: The first three octets are the network portion. Octet 4 is for
subnets/hosts.
Private Address Range
Class A :10.0.0.0 - 10.255.255.255
Class B: 172.16.0.0 - 172.31.255.255
Class C: 192.168.0.0 - 192.168.255.255
Network Masks
Distinguishes which portion of the address identifies the network and
which portion of the address identifies the node.
Default masks:
Class A: 255.0.0.0
Class B: 255.255.0.0
Class C: 255.255.255.0
Subnetting
Creates multiple logical networks that exist within a single Class A, B, or
C network.
If you do not subnet, you will only be able to use one network from your
Class A, B, or C network, which is unrealistic
Each data link on a network must have a unique network ID, with every
node on that link being a member of the same network
Benefits of Subnetting
Reduced network traffic
Optimized network performance
Simplified management
Facilitated spanning of large geographical distances
IP Subnet-Zero
This command allows you to use the first and last subnet in your network
design.
For example, the Class C mask of 192 provides subnets 64 and 128, but
with the IP subnet-zero command, you now get to use subnets 0, 64, 128,
and 192.
How to create subnets
Determine the number of required network IDs:
One for each subnet
One for each wide area network connection.
Determine the number of required host IDs per subnet:
One for each TCP/IP host
One for each router interface.
Based on the above requirements, create the following:
One subnet mask for your entire network
A unique subnet ID for each physical segment
A range of host IDs for each subnet.
CIDR
Classless Interdomain Routing
Improve address space utilization
Routing scalability in the Internet
For example, if an ISP owns network 172.16.0.0/16, then the ISP can
offer 172.16.1.0/24, 172.16.2.0/24,and so on to customers. Yet, when
advertising to other providers, the ISP only needs to advertise
172.16.0.0/16
RENEWABLE ENERGY IN INDIA
India is one of the countries with the largest production of energy from
renewable sources. In the electricity sector, renewable energy account for 34.6%
of the total installed power capacity. Large hydro installed capacity was 45.399
GW as of 30 June 2019, contributing to 13% of the total power capacity.[1] The
remaining renewable energy sources accounted for 22% of the total installed
power capacity (80467 GW) as of 30 June 2019.
Wind power capacity was 36,625 MW as of 31 March 2019, making India the
fourth-largest wind power producer in the world. The country has a strong
manufacturing base in wind power with 20 manufactures of 53 different wind
turbine models of international quality up to 3 MW in size with exports to
Europe, the United States and other countries. Wind or Solar PV paired with
four-hour battery storage systems is already cost competitive, without subsidy,
as a source of dispatchable generation compared with new coal and new gas
plants in India.
The government target of installing 20 GW of solar power by 2022 was
achieved four years ahead of schedule in January 2018, through both solar
parks as well as roof-top solar panels. India has set a new target of achieving
100 GW of solar power by 2022. Four of the top seven largest solar parks
worldwide are in India including the second largest solar park in the world
at Kurnool, Andhra Pradesh, with a capacity of 1000 MW. The world's largest
solar power plant Bhadla Solar Park is being constructed in Rajasthan with a
capacity of 2255 MW and is expected to be completed by the end of 2018.
Biomass power from biomass combustion, biomass
gasification and bagasse cogeneration reached 9.1 GW installed capacity as of
31 March 2019. Family type biogas plants reached 3.98 million .
Renewable energy in India comes under the purview of the Ministry of New
and Renewable Energy (MNRE). India was the first country in the world to set
up a ministry of non-conventional energy resources, in the early 1980s. Solar
Energy Corporation of India is responsible for the development of solar energy
industry in India. Hydroelectricity is administered separately by the Ministry of
Power and not included in MNRE targets.
India is running one of the largest and most ambitious renewable capacity
expansion programs in the world. Newer renewable electricity sources are
projected to grow massively by nearer term 2022 targets, including a more than
doubling of India's large wind power capacity and an almost 15 fold increase in
solar power from April 2016 levels. These targets would place India among the
world leaders in renewable energy use and place India at the centre of its
"Sunshine Countries" International Solar Alliance project promoting the growth
and development of solar power internationally to over 120 countries. India set
a target of achieving 40% of its total electricity generation from non-fossil fuel
sources by 2030, as stated in its Intended Nationally Determined
Contributions statement in the Paris Agreement. A blueprint draft published
by Central Electricity Authority projects that 57% of the total electricity
capacity will be from renewable sources by 2027. In the 2027 forecasts, India
aims to have a renewable energy installed capacity of 275 GW, in addition to 72
GW of hydro-energy, 15 GW of nuclear energy and nearly 100 GW from “other
zero emission” sources.
Renewable energy overview and targets
The 2022 electrical power targets include achieving 227GW (earlier 175 GW)
of energy from renewable sources - nearly 113 GW through so
lar power, 66 GW from wind power, 10 GW from biomass power, 5GW
from small hydro and 31GW from floating solar and offshore wind power. The
bidding process for the further additional 115 GW or thereabouts to meet these
targets of installed capacity from January 2018 levels will be completed by the
end of 2019-2020. The government has announced that no new coal-based
capacity addition is required beyond the 50 GW under different stages of
construction likely to come online between 2017 and 2022.
Unlike most countries, until 2019 India did not count large hydro power
towards renewable energy targets as hydropower was under the older Ministry
of Power of Ministry of New and Renewable Energy. This system was changed
in 2019 and the power from large hydropower plants is since also accounted for.
This was done to help the sale of the power from the large Hydropower plants,
as this reclassification has made such plants able to sell their power under the
Renewable Energy Purchase Obligation. Under the Renewable Energy Purchase
Obligation, the DISCOMs (Distribution Company) of the various states have to
source a certain percentage of their power from Renewable Energy Sources
under two categories Solar and Non-Solar. The power from the large
Hydropower plants now classifies under the Non-Solar Renewable Energy
Category.
Installed grid interactive renewable power capacity (excluding large
hydropower) as of 30 June 2019 (RES MNRE)
Grid connected installed capacity from all sources as of 30 June 2019
SOURCE TOTAL INSTALLED 2022 TARGET(MW)
CAPACITY(MW)
Wind power 36368 60000
Solar power 29549 1000000
Biomass power 9806 10000
Waste to power 138 10000
Small Hydropower 4604 5000
Total 80467 175000
SOURCE INSTALLED SHARE
CAPACITY(MW)
COAL 194489.50 54.17%
Large Hydro 45399.22 12.64%
Other Renewables 80467.22 22.41%
Gas 24937.22 6.9%
Diesel 637.63 0.24%
Nuclear 6780.00 1.97%
Total 358970.78 100.00%