Beruflich Dokumente
Kultur Dokumente
RCD testings:
- Faulty RCD’s
- Values are high comparatively to 40 mS; comments should be “tripping value is greater than
40mSec.
Cable trays:
Inspection of DB’s
- ETP plant inverter issue & “wiring drawing” is not applicable; but mentioned as gap.
- Boiler House DB ELEC-PDB-072 issues: color codings scheme; cable lugs missing; exposed end of
cable w/o insulation.
- NPS production area Elec-LPDB-92 : 1. Unused opening 2. Cable dressing.
- Elec-lpdb-133 ointment packing light : 1. SLD need to update 2. Cable lugs missing 3. Un-used
opening
- Spansules power DB m/c 6 elec-lpdb-116 : 1. Unused opening 2. Physical barrier not present 3.
SLD missing 4. Ammeter found faulty 5. Dusty
- Chc lights elec-lpdb-102 : 1. Lugs ; un-used opening 3. Rusting 4. Sld need an update.
- Otic DB machines Elec-PDB-124 : 1. Unused opening 2. Rusting 3. Lugs 4. Selector switch of
ammeter/voltmeter is faulty. 5. RDB earthing not proper.
- Production area offices elec-pdb-093 : 1. Tape on busbar 2. Indication light 3. Cable dressing 4.
Lugs issue 5. Db cleaning req.
- Injectable washing area DB Elec-LPDB-122 ( to get this deleted) as area is discontinued.
- Packaging b area -1 ldb-087 : 1. Lugs 2. Excessive tapes 3. Rusting on neautral & earth
- Analytical Lab : 1. No tag on DB 2. Separator sheet missing although present. 3. SLD missing
- Analytical lab UPS power DB Elec-PDB-100 : 1. Earthing issue 2. Taping issue 3. Un used sealing
4. Voltmeter malfunctioned.
- Analytical lab near UPS power DB : elec-pdb-099 1. Cable phase 2. Lugs 3. Un used opening 4.
Physical barrier 5. SLD found un satisfactory 6. Equipment tagging 7. No tag on DB
- Staff canteen light power Elec-Lpdb-048 1. Sharp bending point
- Officers mess panel: 1. Extra wires with taping 2. Loose earth wire.
- Sewerage pumps elec-pdb-054 : 1. Multiple cable enters in same gland 2. 02 cable gland found
missing 3. Rust 4. Yellow & black wire used as earth. 5. Cable color scheme standard issue.
- Officers mess kitchen elec-lpdb-047 1. SLD missing 2. DB completely not earthed 3. Several
joints 4. Color scheme of cables.
- Kitchen exhaust fan DB 1. No tag 2. Cable phase identification 3. SLD 4. No Gas kit.
- Contractors Office DB elec-PDB-194 1. Cable phase 2. Glands 3. Physical barrier 4. SLD 5.
- GMs office Ahu 44 elec-pdb-161 : 1. Multiple cables 2. CT not fixed 3. Cable dressing 4. Rust 5.
- Microlab elec-PDB-152 1. DB not earthed 2. Contactor w/o connections earth bar no
terminations.
- Hub office GMs elec-lpdb-204
- AHU 40 UTL-01-HVAC-112 (sterile Ahu) need to remove
- Elec-pdb-006 1. Earth issues 2. ELI issues 3. Taping 4. Looping
- Elec-ldb-118 injectable DB need to remove