Sie sind auf Seite 1von 6

HIGH ENERGY LIGHTNING IMPULSE STRESS ON MO ARRESTERS

AND THEIR DEGRADATION


B. Weise C. Heinrich L. Klingbeil W. Kalkner
weise@ihs.ee.tu-berlin.de christian.heinrich@ffm7.siemens.de klingbeil@ihs.ee.tu-berlin.de kalkner@ihs.ee.tu-berlin.de
Technical Universitiy of Siemens AG Technical Universitiy of Berlin Technical Universitiy of
Berlin Germany Germany Berlin
Germany Germany

Abstract: The paper describes the degradation of which the surge arresters were stressed, or the different
metal oxide surge arrester blocks stressed with measuring methods used.
lightning impulse currents having high energy content Based on the observation, that the peak value is the
and peak values up to the nominal discharge current main influential parameter, a theory has been developed
of the arresters. All experiments were done with that describes the electrical degradation as a change of the
arrester blocks destined for high voltage applications. microstructure of the MO bulk material caused by
The main purpose of this study is to examine the migration of ions [7].
influence of the energy content on the degradation of Condition for the migration of ions is the presence of
MO arresters. The results are compared to other a very high electric field strength. Therefore a high peak
studies performed with different current impulse value of the current is necessary to cause degradation.
waveforms. The existing theory about the degradation Impulses with peak values below a certain limit do not
caused by lightning current impulses, describing the cause degradation independent of their energy content.
degradation as a change of the microstructure of Because of that, long duration current impulses (square-
MO arresters, can be supported by the presented wave pulses), which have relatively low amplitudes, don’t
results. Additionally an opportunity to predict one cause degradation, in spite of their great energy content.
certain kind of destruction of MO arresters is given. For impulse currents having peak values high enough
to cause degradation, the theory of the ion-migration
Keywords: MO arrester, impulse degradation, high predicts an influence of the impulse duration. The longer
energy content, long duration, voltage-current- the force of the electric field can act on the ions, the
characteristic, puncture, ion-migration greater the degradation will be. As the energy content of
MAX 5 !!!!!!!!!!!!!!!!!!!!!!!!!! an impulse increases with it’s duration, the energy content
must have additional influence on the degradation.
1. INTRODUCTION The present paper describes the degradation of MO
surge arrester blocks stressed with lightning impulse
Several studies showed, that metal oxide (MO) surge currents having high energy content and peak values near
arresters can degrade during their service life under the nominal discharge currents of the arresters, that means
extreme circumstances. One cause for this is lightning much higher than in long duration current impulse tests.
impulse current stress. A lot of previous examinations The main purpose of this study is to examine the
revealed, that the degradation is dependent on the peak influence of the energy content on the degradation of MO
value of the impulse current (or current density arresters, when simultaneously a high peak value is
respectively) [2, 3, 4, 6, 7, 8]. When the peak value is existing. Clarifying this fact will either support or
above a certain limit the degradation increases with the disprove the theory of ion-migration.
current peak. Other parameters of the current may The examinations were carried out in laboratory. The
influence the degradation additionally. In some studies generated waveform is comparable to the 10/350-µs-
also the energy content is revealed to have influence [2, impulse, which is a standardized waveform for simulating
8], in other studies not the energy but the initial steepness lightning electromagnetic impulses [12]. This impulse is
of the impulse is influential [3, 4]. It should be mentioned getting a standard for testing surge protective devices
here, that all parameters seem to have influence on the destined for protection of low voltage supply systems [14]
degradation only when they exceed a certain limit. A and of equipment in structures [13].
possible reason for the different results of the studies can The presented experiments were carried out with
be the different waveforms of the impulse currents, with MO arrester blocks destined for high voltage applications.
Despite of the fact that MO arresters in real high voltage front is caused by the inductance, which must be big in
networks barely will be stressed by such high energy order to provide the long tail of the impulse.
impulses due to the protection by earth wires, the
knowledge of the degradation under high energy lightning 8-kA-impulse 11-kA-impulse
impulse stress is helpful for a better understanding of the peak value i 8,0 kA ± 0,4 kA 11,0 kA ± 0,3 kA
degradation processes. This can give the chance to front time T1 80 µs 98 µs ± 3 %
improve diagnostic methods and the material of the time of half crest on 350 µs ± 5 % 240...460 µs
arresters further. the wave tail T2
max. steepness di/dt 120 A/µs 135 A/µs
2. TEST PROCEDURE energy content W 16 kJ 20...30 kJ
specific energy 18 kJ/Ω 40...50 kJ/Ω
Lightning impulse current waveforms are standardized
ò i dt
2
for testing MO surge arresters for high voltage W R=
applications. These waveforms are 1/20 µs, 4/10 µs,
8/20 µs, and 30...100/60...200 µs [11]. Previous studies
Table 1: Parameters of the generated lightning impulse
were carried out with impulses of these waveforms or
currents
even shorter impulses. For testing the energy absorption
capability longer impulses are needed. For that square-
Single MO surge arrester blocks with a nominal
wave pulses with high energy content but a quite low
discharge current of 10 kA destined for high voltage
current peak, much lower than the nominal discharge
applications were examined. The residual voltage of these
current of the arresters, are used.
arrester blocks is 6,7 kV (10 kA, 8/20) and the peak value
In the presented study a surge current generator with a
of the continuous operating voltage is ÛC = 3,1 kV. The
crowbar sparkgap was used to create long lightning
diameter of one block has 69 mm.
impulse currents. The principle of such a generator is
To measure the degradation caused by impulse stress
shown in figure 1 [9, 10]. It consists of a conventional
the voltage-current-(V-I)-characteristics of the arrester
surge current generator with an additional crowbar
blocks between 0 and 10 mA leakage current at AC
sparkgap. The capacitance CS and the inductance L form
(50 Hz, AC-characteristic) and DC (DC-characteristic)
an oscillating circuit. At the start time sparkgap 1 fires
were measured as well as the power loss. For estimating
and a damped oscillating current begins to flow. At the
the DC-characteristic both polarities were measured.
first peak of the oscillating current the crowbar sparkgap
From the AC-current the resistive component was
is triggered by a secondary Marx generator. At this instant
extracted using the digital reference method [6].
of time, t = tC , the current commutates from the
The V-I-characteristics were measured before and
oscillation to an exponential decay. The tail of the current
after stressing the arresters with lightning impulses. After
impulse is provided only by the magnetic energy stored in
impulse stress the arrester blocks were cooled down for a
the coil L. The duration of the tail is determined by the
certain length of time, until they got room temperature.
decay time constant τ = L/R(U) and is therefore set by the
They were inspected visually before measuring the
inductance L and the (non-linear) resistance R(U) of the
characteristic. Between impulse stress and measurement
device under test. This principle allows to generate
no voltage was applied to the arresters. All measurements
current impulses of longer duration and higher amplitude
were carried out in laboratory under the same
than it would be possible with a conventional lightning
environmental conditions at room temperature.
impulse current generator.
The degradation was determined by comparing these
s p a rk g a p 1 V-I-characteristics. This allows the evaluation of the
R L
1 degradation for the whole range of the leakage current
s ta r t s w itc h im p u ls e and voltage respectively. In this way a behaviour of the
c u rre n t degradation in dependence of the voltage could be
M a rx g e n e ra to r c ro w b a r
c h a r g in g C S s u r g e v o lta g e a s s p a rk g a p d e v ic e
determined. The change of the current, ∆i, was calculated
v o lta g e
tr ig g e r im p u ls e u n d e r with equation (1).
te s t
U 0 R æ i after impulse stress ö
∆i[ %] = çç − 1÷÷ ⋅ 100
S h u n t
(1)
c u rre n t th ro u g h è i before first impulse stress ø
c a p a c ito r m e a s u re m e n t o f th e
im p u ls e c u r r e n t An increase of ∆i means an increase of the absolute
Fig. 1: Principle of a surge current generator with a value of the current. To make comparison more easy the
crowbar sparkgap negative current is plotted over the absolute value of the
voltage (e. g. Fig. 4).
All tests were carried out with impulse currents having For investigating the influence of each single
amplitudes of 8 kA (8-kA-impulses) and 11 kA (11-kA- parameter on the degradation, it is necessary to vary only
impulses) respectively. The parameters of the impulse one parameter of the impulse while leaving all others
currents are given in table 1. The slowness of the impulse constant. This is usually impossible due to the
interdependence of the parameters. For example, the the positive1. At higher voltages the leakage current
energy content increases with increasing peak value of decreases. In the positive characteristic the point, where
impulses having the same waveform. the increase of the current changes into a decrease, is
During the presented investigations a trick was used to approximately the peak value of the COV. In the negative
change the energy content remaining all other parameters characteristic this point is a higher value of the voltage
constant. The length of the wave tail is determined by the (Fig. 3 to 6).
instant tC, at which the crowbar sparkgap fires. If the Figure 3 and 4 show the degradation caused by stress
crowbar sparkgap fires at the peak of the current, the with 8-kA-impulses. The first impulse causes the biggest
energy content is at the most. This is striven for normally. degradation, while the degradation by subsequent
If it fires later, the wave tail becomes shorter and the impulses is lower. Stress with the first 8-kA-impulse leads
energy content is lower (Fig. 2). The front of the current to an increase of less than 5 % at the positive DC-
impulse is not influenced. By the variation of the instant characteristic and between 5 and 10 % at the negative
tC the energy content can be changed without changing DC-characteristic in the range up to the COV.
any other parameter that could have influence on the Measurements of the power loss and the resistive
degradation. The variation of the energy content was used component of the ac-current show the same qualitative
stressing the arrester blocks with 11-kA-impulses. results. Because of the influence of both polarities the
The generated 11-kA-impulses contain front times of changes of the AC-characteristic lie between the changes
98 µs. The maximum steepness of 135 A/µs is almost the of the positive and negative DC-characteristics. The same
same as the one of the 8-kA-impulses. The time of half results were obtained by measuring the power loss.
crest on the wave tail varies from 240 µs to 460 µs. This Therefore, only the degradation of the DC-characteristic
leads to an energy consumption of 20...30 kJ. The specific is presented in this study. The DC-characteristics allow
energy absorbed by the arrester is 40...50 kJ/Ω (Table 1). the investigation of the physical properties of arrester
blocks and their degradation. For arresters in service the
i( t) changes of the AC-characteristics (or power loss
respectively) are determining for service behaviour.
1 0 0 % Although the measured degradation caused by 8-kA-
impulses is quite small, it is greater than degradation
caused by shorter impulses (8/20) with comparable peak
5 0 % values would be. The described behaviour of the
degradation is similar to the one observed in previous
studies made with shorter impulses [6]. The fact, that the
1 0 %
t first impulse causes a higher degradation than subsequent
tC tC ' impulses, is in agreement with some previous studies [4,
T 2' 6]. A decrease of leakage current caused by the first
impulse described in other studies can be in accord, too,
T 2
when the current was measured at voltages above the
continuous operating voltage [2, 8].
Fig. 2: Influence of the instant tC of firing the crowbar
sparkgap on the parameters of the impulse

3. TEST RESULTS
Degradation could be observed for all tested arresters.
In some rare cases damages of the arrester blocks
occured.
3.1 Degradation
The behaviour of the measured degradation is
described in the following. For voltages up to the peak
value of the continuous operating voltage (COV) the Fig. 3: Degradation of the positive DC-characteristic,
leakage current increases slightly. (In the diagrams caused by 8-kA-impulses
showing the DC-characteristic the voltage which equals
the peak value of the COV is marked by ÛC.) The
negative part of the V-I-characteristic degrades more than

1
The positive part is the part where the current flows in the same
direction as the impulse current, in the negative part the current flows
in the opposite direction.
3.2 Damages
All tested MO arresters have survived at least one
high energy lightning impulse without any problem. After
the first impulse none of the arrester blocks failed by
cracking or flashover. Subsequent impulses in some cases
lead to a damage of an arrester block. The damage gets
visible at first with little black spots (Fig. 7), which are
the beginnings of little holes called punctures [1]. These
punctures grow, when the arrester is stressed with
subsequent impulses. After stress with several impulses
they can cause cracking of the arrester block, what means
a total destruction of the block. Never flashover was a
Fig. 4: Degradation of the negative DC-characteristic, problem. The observed failure mode (puncture) is typical
caused by 8-kA-impulses for long impulses (longer than 100 µs and with a current
density of 1 kA/cm² or less) [5].
Like expected, impulses with peak values of 11 kA The probability of destruction increases with the
cause higher degradation than 8-kA-impulses. Impulses number of current impulses, with current peak, and with
with an energy content of 20 kJ cause an increase of the the absorbed energy. An influence of the same parameters
negative leakage current between 5 and 15 % (first on the destruction of arresters is described also in other
impulse) (Fig. 5). Impulses with 30 kJ cause an even studies. The occuring failure modes may be different
greater degradation of the negative leakage current however (e. g. flashover [4]).
between 10 and 20 % (Fig. 6). Qualitatively the In the current study the damage by punctures of any
degradation is equal to degradation caused by 8-kA- arrester in test was always indicated by a quite high
impulses. increase of leakage current at voltages above the
continuous operating voltage after the preliminary
impulse. This increase easily may have 50 % and more,
that means much more than the “normal“ degradation
would be (Fig. 8 and 9, notice the scale).

Fig. 5: Degradation of the negative DC-characteristic,


caused by 11-kA-impulses having energy
contents of 20 kJ
Fig. 7: Puncture caused by 11-kA-impulses
(scale in mm)

Fig. 6: Degradation of the negative DC-characteristic,


caused by 11-kA-impulses having energy
contents of 30 kJ Fig. 8: Degradation of the positive DC-characteristic
indicating puncture
parameters having influence on the degradation, the
presented study supports the existing theory
describing an ion-migration as the cause of the change
of the microstructure of MO arresters and in this
manner of the impulse degradation.
6.) During the tests a damage (puncture) of an arrester
block was always indicated by a quite high increase of
the current at voltages above the continuous operating
voltage after the preliminary impulse. This gave the
opportunity to predict a destruction. It may be
possible to use this effect for a diagnostic method. But
such diagnostic measurements would have to be
carried out off-line in order to apply voltages higher
Fig. 9: Degradation of the negative DC-characteristic than the COV. Therefore a practical use is uncertain.
indicating puncture
5. REFERENCES
[1] M. Bartkowiak, M. G. Comber, G. D. Mahan, “Failure
4. CONCLUSIONS Modes and Energy Absorption of ZnO Varistors“,
1.) The degradation caused by lightning impulse currents IEEE Trans. Power Delivery, 1998
having a high energy content is qualitatively similar to [2] R. Brocke, Th. Gölsch, F. Noack, F. Schmidt,
the degradation caused by normal (4/10, 8/20) P. Zahlmann, “Parameter Changes of Low-Voltage
lightning impulse currents. The negative V-I- Varistors due to Pulse Stresses“, 11th EMC, paper no.
characteristic degrades more than the positive. The 3A3, Zürich, 1995
first impulse causes the greatest degradation. This is in [3] K. Dengler, K. Feser, W. Köhler, B. Richter, “Pulse
accord with previous studies. It indicates that at stress Degradation of MO-Arresters“, 9th ISH, paper no.
with very long impulses the same ageing phenomena 7498, Graz, 1995
are effective as at stress with short (4/10, 8/20) [4] K. Dengler, W. Köhler, K. Feser, B. Richter,
impulses. W. Schmidt, “Einfluß von Hochstromimpulsen auf das
2.) Reason for the greater degradation caused by stress Impulsalterungsverhalten von MO-Ableitern”, EMV
with 11-kA-impulses in comparison with 8-kA- ’98, pages 83-89, VDE-Verlag, 1998
impulses can be the higher peak value and/or the [5] K. Eda, “Destruction mechanism of ZnO varistors due
higher energy absorbed by the arrester. Influence of to high currents“, J. Appl. Phys., vol. 56, no. 10, pages
the peak value is in accord with several previous 2948-2955, 1984
studies. [6] C. Heinrich, “Degradation und Diagnose von
3.) The results of the presented study suggest that the Metalloxid-Ableitern in Hochspannungsnetzen”,
energy content (or the current duration respectively) Diss., Technical University of Berlin, Shaker Verlag,
has additional influence on the degradation. This is Aachen, 1998
confirmed by the fact, that surge arresters stressed [7] C. Heinrich, G. Schöner, V. Hinrichsen, W. Kalkner,
with 11-kA-impulses of high energy content (30 kJ) “Degradation at the Grain Boundary of Metal Oxide
degrade stronger than the ones stressed with 11-kA- Surge Varistors caused by Impulse Stress“, 24th ICLP,
impulses of lower energy content (20 kJ). The energy Birmingham, 1998
content was the only relevant parameter that had [8] F. Noack, F. Schmidt, “Untersuchungen zur Alterung
changed. (As far as only lightning impulses are von Niederspannungsvaristoren durch
concerned, energy content and current duration are Impulsbelastungen“, Elektrie, 50 (4/5/6/7/8), Berlin,
equivalent.) 1996
4.) No statement can be given concerning the influence of [9] W. Zischank, “Schutzfunkenstrecken zur
the parameter steepness. The steepness of all Überspannungsbegrenzung bei direkten
generated impulse currents was almost the same. As Blitzeinschlägen”, Diss., Hochschule der Bundeswehr
the front of the generated impulses was rather slow, it München, 1983
is suggested that the initial steepness of these impulses [10] W. Zischank, “Eine Crowbar-Funkenstrecke in
has no or less influence. The differences of the einem kapazitiven Stoßstromgenerator zur
measured degradations must be caused by other Simulation direkter Blitzströme“, 17th ICLP, Den
parameters. Haag, 1983
5.) The peak values of the generated impulse currents [11] IEC 60099-4, “Surge arresters - Metal oxide surge
were in the range of the nominal discharge current of arresters without gaps for a. c. systems”, 1991
the tested arrester blocks. This was high enough to [12] IEC 61312-1, “Protection against lightning
cause degradation. As peak value and energy content electromagnetic impulse - Part 1: General
(or current duration respectively) were determined as principles“, 1995
[13] IEC 81/120/CDV, “IEC 61312-3: Protection against Wechselstromnetzen mit Nennspannungen zwischen
lightning electromagnetic impulse (LEMP) - Part 3: 100 V und 1000 V, Änderung 1“ (Surge arresters for
Requirements of surge protective devices (SPDs)“, use in a. c. supply systems with rated voltages
1998 ranging from 100 V to 1000 V, Amendment 1),
[14] DIN VDE 0675-6/A1 (Entwurf/Draft), 1996
“Überspannungsableiter zur Verwendung in

Das könnte Ihnen auch gefallen