Beruflich Dokumente
Kultur Dokumente
Abstract— During the normal condition of the power Power Swing Block (PSB) function is used to detect fault
system, power flows through the line in nominal frequency. during power swing. In other word PSB differentiate
Sometimes the disturbances occur due to sudden load change between power swing and fault [4]. During the loss of
or due to any fault in the transmission line. So during the synchronism of power network the generating station must
recovery of the system electromechanical oscillation is there in be separated at predetermined locations to avoid damage of
the power system network which results in power swing, this power networks and to maintain power system stability. The
encourages undesirable tripping or cascade tripping of line Out-of-Step Trip (OST) function is used to differentiate
causes the power system blackouts. To avoid this situation like stable and unstable power swing and initiates the area
blackouts, Here current differential protection scheme and the
separation at the predetermined locations.
phasor difference analysis between two bus power system is
analyzed to detect the fault during out-of-step condition By applying the PSB and OST function we can detect the
accurately. power oscillation or out-of-step conditions. The very general
method of detecting fault in transmission line is to measure
Keywords— Fast fourier transform, Power swing block, the rate of change of apparent impedance seen by the relay
Out of step trip , Phasor measurement unit (PMU) location. In this conventional method, the technique decide
the zone time in which the impedance passing through the
operating zone of distance relay [3]-[6]. A preset value of
I. INTRODUCTION time is defined which decide whether the power swing is
All over the world the power system functions operate at stable or unstable. Due to any reason if load impedance
its nominal frequency. At this steady state condition the enters the circle zone of distance relay the start time is
active power flow and the reactive power flow in the calculated by the timer setting and it decide the fault or
transmission line should be normal. If any transients or power swing by the end time. If the time is greater value then
stability imbalance occurs in the power system network we a unstable power swing or fault condition is there and relay
should remove the reason of system imbalance as soon as trips [7]-[9].
possible. The main reasons of system imbalance are sudden Here a current differential protection [10] and load angle
change in load, any type of fault occur, line switching, difference between two substations is used to detect the fault
generator disconnection and loss of loads occurred in the during the power oscillation or out-of-step [11] conditions.
system. During the clearance of fault, some electro- In differential current protection scheme [12] the
mechanical oscillation occurs. This results in power flow instantaneous current data’s are obtained from PMU’s are
oscillation in the transmission line. Technically during this taken. This technique is used in 2-bus system to get fast and
period variation of the rotor angle occurs [1]. On the basis of accurate [13] result. This technique is verified through
variation of rotor angle there are two types of power swing. PSCAD software.
If the fluctuation die down then we call it as stable power
swing and if oscillation increases gradually then it is called
as unstable power swing. And this results in loss of II.PROPOSED METHOD
synchronism of two area system known as out-of-step A novel method to detect stable and unstable power
condition [2]. swing is to current differential protection in which the
positive sequence PMU data of the instantaneous current is
Generally distance relay in transmission line is used to taken as the major parameter to find the fault during power
avoid unusually tripping of relay which results in severe swing. To get the positive sequence current in both line Fast
blackouts. In distance relay load impedance plays a major Fourier Transform (FFT) concept is used.
role to identify weather it is a fault or power swing [3].
During power swing if the load impedance come in between
the operating zone of distance relay then the relay trips
unnecessarily, which is undesirable operation of relay which
may results in cascading outage and power blackouts. A
1
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
0.4
0.2
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Fig.4:- Phase angle of two bus system
0.4
I(t)
0.2
III.SIMULATION RESULT BY USING PHASOR DIFFERENCE
0 As you know the fault and power swing are same in
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 nature as current increases and voltage decreases. So in fig.5
TIME(sec.)
the two bus system model first the fault occur. Then after this
Fig.2:-Sending end and Receiving end current component another fault is occurred inline 2 intentionally which results
without fault in power oscillation in the power network due to rotor angle
variation of two bus system. So by taking the phasor
difference between the two system, we can get the clear
1 appearance of the fault or unbalance power swing during out
of step conditions.
0.5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0.4
I(t)
0.2
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
TIME(sec.)
Fig.3:- Sending end and Receiving end current component Fig.5:-Single line diagram of modeled 2-bus system
with fault
2
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
50
0
Va
-50 The fault data of the 2-bus system is given below;
0.3 0.4 0.5 0.6 0.7 0.8 0.9
50 Fault-1
0
Time = 0.4
Vb
-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9 Fault resistance=1.0
50
0 Fault duration =0.05
Vc-50 Transmission length =300km
0.3 0.4 0.5 0.6 0.7 0.8 0.9
TIME(sec.)
0.6
0.4 50
0
0.2 Va-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9
50
0 0
0 0.2 0.4 0.6 0.8 1.0
TIME(sec.) Vb-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9
Fig.8:-Phase difference waveform of 3-phase fault 50
0
Vc-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9
TIME(sec.)
3
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]
2
0
Ia-2
0.3 0.4 0.5 0.6 0.7 0.8 0.9
2
0 V.APPENDIX
Ib -2
0.3 0.4 0.5 0.6 0.7 0.8 0.9
2 Generator Data:
Rated Power 600MVA
0
Ic Voltage 22kV
-2 Frequency 50Hz
0.3 0.4 0.5 0.6 0.7 0.8 0.9
TIME(sec.) Inertia Constant 4.4MW/MVA
Fig.10:-Current waveform of 3-phase fault
Transformer Data:
Rated Power 600MVA
Voltage Ratio 22/400Kv
3
Frequency 50Hz.
2
PHASE DIFFERENCE
1 VI .CONCLUSION
4
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]