Sie sind auf Seite 1von 5

International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

Out-of-Step Technique Based Symmetrical fault


Analysis
Srikanta Mohapatra ,Subodh Kumar Mohanty, Tapas Kumar Patel
School of Electrical Engineering, KIIT University, Bhubaneswar-751024 (ORISSA)
E-mail: 1srikantfel@kiit.ac.in , 3patel.tapaskumar64@gmail.com,

Abstract— During the normal condition of the power Power Swing Block (PSB) function is used to detect fault
system, power flows through the line in nominal frequency. during power swing. In other word PSB differentiate
Sometimes the disturbances occur due to sudden load change between power swing and fault [4]. During the loss of
or due to any fault in the transmission line. So during the synchronism of power network the generating station must
recovery of the system electromechanical oscillation is there in be separated at predetermined locations to avoid damage of
the power system network which results in power swing, this power networks and to maintain power system stability. The
encourages undesirable tripping or cascade tripping of line Out-of-Step Trip (OST) function is used to differentiate
causes the power system blackouts. To avoid this situation like stable and unstable power swing and initiates the area
blackouts, Here current differential protection scheme and the
separation at the predetermined locations.
phasor difference analysis between two bus power system is
analyzed to detect the fault during out-of-step condition By applying the PSB and OST function we can detect the
accurately. power oscillation or out-of-step conditions. The very general
method of detecting fault in transmission line is to measure
Keywords— Fast fourier transform, Power swing block, the rate of change of apparent impedance seen by the relay
Out of step trip , Phasor measurement unit (PMU) location. In this conventional method, the technique decide
the zone time in which the impedance passing through the
operating zone of distance relay [3]-[6]. A preset value of
I. INTRODUCTION time is defined which decide whether the power swing is
All over the world the power system functions operate at stable or unstable. Due to any reason if load impedance
its nominal frequency. At this steady state condition the enters the circle zone of distance relay the start time is
active power flow and the reactive power flow in the calculated by the timer setting and it decide the fault or
transmission line should be normal. If any transients or power swing by the end time. If the time is greater value then
stability imbalance occurs in the power system network we a unstable power swing or fault condition is there and relay
should remove the reason of system imbalance as soon as trips [7]-[9].
possible. The main reasons of system imbalance are sudden Here a current differential protection [10] and load angle
change in load, any type of fault occur, line switching, difference between two substations is used to detect the fault
generator disconnection and loss of loads occurred in the during the power oscillation or out-of-step [11] conditions.
system. During the clearance of fault, some electro- In differential current protection scheme [12] the
mechanical oscillation occurs. This results in power flow instantaneous current data’s are obtained from PMU’s are
oscillation in the transmission line. Technically during this taken. This technique is used in 2-bus system to get fast and
period variation of the rotor angle occurs [1]. On the basis of accurate [13] result. This technique is verified through
variation of rotor angle there are two types of power swing. PSCAD software.
If the fluctuation die down then we call it as stable power
swing and if oscillation increases gradually then it is called
as unstable power swing. And this results in loss of II.PROPOSED METHOD
synchronism of two area system known as out-of-step A novel method to detect stable and unstable power
condition [2]. swing is to current differential protection in which the
positive sequence PMU data of the instantaneous current is
Generally distance relay in transmission line is used to taken as the major parameter to find the fault during power
avoid unusually tripping of relay which results in severe swing. To get the positive sequence current in both line Fast
blackouts. In distance relay load impedance plays a major Fourier Transform (FFT) concept is used.
role to identify weather it is a fault or power swing [3].
During power swing if the load impedance come in between
the operating zone of distance relay then the relay trips
unnecessarily, which is undesirable operation of relay which
may results in cascading outage and power blackouts. A

978-1-5090-5682-8 /17/$31.00 ©2017 IEEE

1
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

enters the operating zone of the distance relay.Fig-2 and Fig-


3 gives the idea about the normal condition and the faulty
condition respectively. Here the phasor difference of two bus
system is taken as the important parameter to detect fault
during power swing.
The phase difference of the two bus voltage shown in fig-
4 is used as the main parameter to detect the fault during the
power oscillation.
Fig.1:- Line current in two bus system
V1∠δ 1 V2 ∠δ 2
As per above fig.1,the current difference is taken as the
central parameter to detect the fault in the power system
network weather it is symmetrical fault or asymmetrical fault
during the power oscillation.

0.4

0.2

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Fig.4:- Phase angle of two bus system
0.4
I(t)

0.2
III.SIMULATION RESULT BY USING PHASOR DIFFERENCE
0 As you know the fault and power swing are same in
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 nature as current increases and voltage decreases. So in fig.5
TIME(sec.)
the two bus system model first the fault occur. Then after this
Fig.2:-Sending end and Receiving end current component another fault is occurred inline 2 intentionally which results
without fault in power oscillation in the power network due to rotor angle
variation of two bus system. So by taking the phasor
difference between the two system, we can get the clear
1 appearance of the fault or unbalance power swing during out
of step conditions.
0.5

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0.4
I(t)

0.2

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
TIME(sec.)
Fig.3:- Sending end and Receiving end current component Fig.5:-Single line diagram of modeled 2-bus system
with fault

In line AB the fault is occurred at 0.4second for the


Unstable power oscillation in the transmission line is duration of 0.05 second. So all the power are transmitted
undesirable operation for a power system network. We through the line CD and results in power imbalance. Another
cannot control this phenomena but we can avoid it by fault is occurred at 0.8sec for the duration of 0.05 second.
detecting the power swing and fault during out of step Hence this fault occurred during the power swing and by
conditions. The loss of synchronism between power system using the phasor analysis of positive sequence component of
affects the transmission line relays and system in various the phase difference of the two bus system, we can detect the
ways. During the out-of-step (OOS) event, a distance relay fault and avoid the unwanted operation of relay. The
may detect the OOS as a phase fault if the load impedance waveform of voltage and currents are as below;

2
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

50
0
Va
-50 The fault data of the 2-bus system is given below;
0.3 0.4 0.5 0.6 0.7 0.8 0.9
50 Fault-1
0
Time = 0.4
Vb
-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9 Fault resistance=1.0
50
0 Fault duration =0.05
Vc-50 Transmission length =300km
0.3 0.4 0.5 0.6 0.7 0.8 0.9
TIME(sec.)

Fig.6:-Voltage waveform of 3-phase fault Fault-2


Time =0.8second
2 Fault resistance=1.0
0 Fault duration =0.05 second
Ia
-2 Transmission length =300km
0.3 0.4 0.5 0.6 0.7 0.8 0.9
2
0 IV.SIMULATION RESULT BY USING CURRENT
Ib-2 DIFFERENTIAL PROTECTION
0.3 0.4 0.5 0.6 0.7 0.8 0.9
2
0
The current differential protection is used here to detect
Ic -2
the fault during out of step conditions or power swing. Here
0.3 0.4 0.5 0.6 0.7 0.8 0.9 we are taking the difference of the positive sequence of
TIME(sec.) instantaneous current which is obtained from the Phasor
Fig.7:-Current waveform of 3-phase fault Measurement Unit (PMU). Here intentionally by creating
two in line-1 and line-2 respectively, we will create a power
swing. Then the Fault during power swing is detected by
using the current differential potential skill.
In fig.6 and fig.7, the voltage and current parameter is given,
but the clear view of fault during power swing is not At t =0.4 second first fault occurs for 0.05 sec, then after
obtained here. So phase difference technique comes into removal of this fault another fault is occur at t=0.8second for
picture. ite interval of 0.05 second and this phenomena results in
power swing.Fig-9 and fig-10 shows the voltage and current
0.8 waveform, where the fault detection is not so easy. Then we
are detecting the fault during out of step condition by using
current differential protection. The results are shown below:-
PHASE DIFFERENCE

0.6

0.4 50
0
0.2 Va-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9
50
0 0
0 0.2 0.4 0.6 0.8 1.0
TIME(sec.) Vb-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9
Fig.8:-Phase difference waveform of 3-phase fault 50
0
Vc-50
0.3 0.4 0.5 0.6 0.7 0.8 0.9
TIME(sec.)

Fig.9:-Voltage waveform of 3-phase fault

3
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

Transmission length =500km

2
0
Ia-2
0.3 0.4 0.5 0.6 0.7 0.8 0.9
2
0 V.APPENDIX
Ib -2
0.3 0.4 0.5 0.6 0.7 0.8 0.9
2 Generator Data:
Rated Power 600MVA
0
Ic Voltage 22kV
-2 Frequency 50Hz
0.3 0.4 0.5 0.6 0.7 0.8 0.9
TIME(sec.) Inertia Constant 4.4MW/MVA
Fig.10:-Current waveform of 3-phase fault
Transformer Data:
Rated Power 600MVA
Voltage Ratio 22/400Kv
3
Frequency 50Hz.
2
PHASE DIFFERENCE

1 VI .CONCLUSION

0 The fault during power oscillation and during out-of-step


(OOS) conditions should be detected to maintain the power
-1
system stability of the network. In this situation the rotor
-2 phase angle difference exceed 180 degree, hence it is called
as out of phase condition or unbalanced power swing. So by
-3 using phasor difference technique and current differential
0 0.2 0.4 0.6 0.8 1.0
TIME(sec.) protection algorithm, we can clearly got the fault during the
power oscillation condition by using PSCAD software.
Fig.11:-Current differential waveform of 3-phase fault

The comparison in fig-8 and fig-11 gives the better


understanding to find the fault during power swing. The
current differential scheme is preferred on phase differential VII. REFERENCES
technique.
[1] Kundu, Pratim, and Ashok Kumar Pradhan. "Wide Area
The fault data of the 2-bus system is given beow; backup protection using weighted apparent impedance." Power,
Communication and Information Technology Conference
Fault-1 (PCITC), 2015 IEEE. IEEE, 2015.
Time = 0.4 second
[2] Kundu, Pratim, and Ashok Kumar Pradhan. "Online
Fault resistance=10.0 identification of protection element failure using wide area
Fault duration =0.05second measurements." IET Generation, Transmission & Distribution 9.2
(2014): 115-123.
Transmission length =500km
[3] Rao, J. Ganeswara, and A. K. Pradhan. "Application of
synchrophasor data for fault detection during power
Fault-2 swing." Energy, Automation, and Signal (ICEAS), 2011
International Conference on. IEEE, 2012.
Time =0.8second
Fault resistance=10.0 [4] Tziouvaras, Demetrios A., and Daqing Hou. "Out-of-step
protection fundamentals and advancements." Protective Relay
Fault duration =0.05 second Engineers, 2004 57th Annual Conference for. IEEE, 2004.

4
International Conference on Innovations in Power and Advanced Computing Technologies [i-PACT2017]

[5] Vaidyanathan, Rajani, and S. A. Soman. "Distance relay


coordination considering power swings." Proc. Int. Conf. Power
Syst. Commun. Syst. Infrastructures for Future. 2002.

[6] Kundu, Pratim, and Ashok Kumar Pradhan. "Enhanced


Protection Security Using the System Integrity Protection Scheme
(SIPS)." IEEE Transactions on Power Delivery 31.1 (2016): 228-
235.

[7] Karegar, H. Kazemi, and B. Mohamedi. "A new method for


fault detection during power swing in distance
protection." Electrical Engineering/Electronics, Computer,
Telecommunications and Information Technology, 2009. ECTI-
CON 2009. 6th International Conference on. Vol. 1. IEEE, 2009.

[8] Khoradshadi-Zadeh, H. "Evaluation and performance


comparison of power swing detection algorithms." Power
Engineering Society General Meeting, 2005. IEEE. IEEE, 2005.

[9] Esmaeilian, Ahad, et al. "Evaluation and performance


comparison of power swing detection algorithms in presence of
series compensation on transmission lines." Environment and
Electrical Engineering (EEEIC), 2011 10th International
Conference on. IEEE, 2011.

[10] Subodh Kumar Mohanty, Paresh Kumar Nayak, "A


comparative study of DFT and Moving Window Averaging
Technique of Current Differential Protection on Transmission Line"
International Conference on Advanced Computing and
Communication System(ICACCS),IEEE,2016.

[11] Ghosh, Aritra, et al. "Modified multi-carrier based Pulse


Width Modulation technique to obtain optimal switching and even
power distribution for multilevel inverter." Computation of Power,
Energy Information and Commuincation (ICCPEIC), 2016
International Conference on. IEEE, 2016.

[12] Dubey, Rahul, et al. "A novel out-of-step detection algorithm


using angle of power signal." Power and Energy Systems (ICPS),
2011 International Conference on. IEEE, 2011.

[13] Altay, Ozkan, EkremGursoy, and OzcanKalenderli. "Single


end travelling wave fault location on transmission systems using
wavelet analysis." High Voltage Engineering and Application
(ICHVE), 2014 International Conference on. IEEE, 2014.

Das könnte Ihnen auch gefallen