Mineral Oil <1.9 m3 1.5 Meter 4.6 Meter 7.6 Meter 7.6 Meter
Above 112.5 KVA with Class 155 separated from a fire-resistant barrier not less than 1.83 m (6
Insulation ft) horizontally and 3.7 m (12 ft) vertically
Over 35KV Installed indoors Vault (Having liquid confinement area and a pressure-relief
vent for absorbing any gases generated by arcing inside the tank, the pressure-
relief vent shall be connected to a chimney or flue that will carry such gases to
an environmentally safe area
Above 112.5 KVA Installed in a transformer room of fire-resistant construction.
Above 112.5 KVA (Class separated from a fire-resistant barrier not less than 1.83 m (6 ft) horizontally
155 Insulation) and 3.7 m (12 ft) vertically
Installed indoors Vault (With construction of reinforced concrete that is not less than
Up to 112.5 KVA
100 mm (4 in.) thick.
Up to 10 KVA & Up to Vault shall not be required if suitable arrangements are made to prevent a
600V transformer oil fire from igniting
Up to 75 KVA & Up to Vault shall not be required if where the surroundingStructure is classified as fire-
600V resistant construction.
Furnace transformers
Installed without a vault in a building or room of fire resistant construction
(Up to 75 kVA)