GP SERIES-VRLA Battery

Applications Specification
Nominal Voltage 12V
All purpose
Approx Weight Approx 28.5 kg (62.8lbs)
Uninterruptable Power Supply (UPS)
Terminal T11/T10
Electric Power System (EPS)
Container Material ABS
Emergency backup power supply
Emergency light Internal Resistance Approx 4.8mΩ
Railway signal Discharge : -15 50℃ (5 122℉)
Operating Temp.Range Charge : 0 40℃ (32 104℉)
Aircraft signal
Storage : -15 40℃ (5 104℉)
Alarm and security system
Nominal Operating Temp. Range 25 3℃ (7 7 5℉ )
Electronic apparatus and equipment
Cycle Use Initial Charging Current less than30.0A.Voltage
Communication power supply
14.4V~15.0V at 25 ℃(77 ℉)Temp. Coefficient -30mV/℃
DC power supply
Auto controlsystem Standby Use No limit on Initial Charging Current Voltage
13.5V~13.8V at 25 ℃(77 ℉)Temp. Coefficient -20mV/℃
40℃ (104 ℉) 103%
Capacity affected by
25℃ ( 77 ℉ ) 100%
Temperature
0℃ ( 32 ℉ ) 86%
GP series batterys may be stored for up to 6 months at
Self Discharge 25℃(77℉) and then a freshening charge is required.
For higher temperatures the time interval will be shorter.

Dimensions
T11 Terminal

Cycle Life in Relation to Depth of Discharge


Discharge Characteristics
12V 6V 4V 2V
Testing condition
Battery Battery Battery Battery Discharging: current 0 . 17 C ( FV 1 . 7 V/ cell);
T e m p e ra tur e :2 5 C( 7 7 F )
0 0
V V V V
Charging: current 0 . 25 C m ax, voltage 2 . 45 V/ cell;
13.0 6.5 4.33 2.16
Charging volume: 125 % of di scharged cap acity.

12.0 6.0 4.00 2.00


120

11.0 5.5 3.66 1.84


100
0.1C 0.0525C
0.205C
10.0 5.0 3.33 1.68 0.4C
80
1C 0.6C
9.0 4.5 3.00 1.52
60

8.0 4.0 2.67 1.36


40
2C
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20
20
Min H

Discharge Time 0
0 200 400 600 800 1000 1200

Number of Cycles